3-1/2˝
3-1/2˝
3˝
3˝
1/4˝
1/4˝
L1 L2
POS- 1 POS- 2
SW- 1
SW- 2 LOAD- 1 LOAD- 2
L1
L1L2L2
SW1
SW2
SW-1 SW-2 LOAD-2LOAD-1
LOAD- 2
LOAD- 1
LOAD- 2
LOAD- 1
SW-1
SW-2
L1 L2
1
2
3456
7
8
RElAY OUTpUT
Series A & AM
Solid State Alternators
Series A has an open circuit board design. Series AM provides convenient plug-in
design, either octal socket or DIN mount. The housing carries no NEMA rating.
Contact Rating 10 amp @ 120 VAC or 24 VAC Resistive
Primary Voltage 120 VAC, 24 VAC (+10%/-15%) 50/60 Hz
Secondary Voltage 20 mA @ 120 VAC, 80 mA @ 24 VAC
Temperature -40°F to +150°F (-40°C to +65°C)
Terminal Style
Series A 1/4˝ spade
Series AM Screw connector
Approvals U.L. 508 Recognized Motor Control
How to Order
Use the Bold characters from the chart below to construct a product code.
A X X X XX
Series
A – Alternator – Open Circuit Board
Supply Voltage
WARRICK CONDUCTIVITY SENSORS
1 – 120 VAC 3 – 24 VAC
Standoff Style
C – Screw Mount
Number of Loads
2 – 2
Power Outage Time Delay
15 – 15 Seconds
Series AM
Applications
• DuplexPumping
• SingleorDualSwitch
Operation
Dimensions
Series A
Series A
• PowerOutageTime
Delay Available on
Open Version
(Series A)
AM X X X
Series
AM – Alternator – Module
Supply Voltage
1 – 120 VAC 3 – 24 VAC
Socket Style
A – Octal B – DIN Mount M – None
Number of Loads
2 – 2
E-1 4
Series AM dimensions are the same as Series DC above.
Wiring
Series A
Note: For ease of wiring, L1 and L2 each have two tabs.
Series AM