Warrick a Brand of Gems Sensors Series 67 Multi-Function Control Catalog Page

Series 67 Multi-Function Control Duplex Pump System Control
Inverse or Direct Acting, Field SelectableSolid State ReliabilityCompact SizeFour Independent Channels – 2 Single, 2 DifferentialField Adjustable, Sensitivity and Mode SelectionLED Channel IndicatorsBuilt-in Silence/Acknowledge CircuitU.L. “Intrinsically Safe”
Warrick’s Series 67 four channel level control is an ideal solution to liquid level problems in hazardous applications for the sewage, waste water, chemical and groundwater remediation industries.
Connected to floats or conductance probes this versatile control provides simplex or duplex pump/solenoid valve control; automatic or manual alternation; high and/or low level alarms with silence/acknowledge capabilities.
The Series 67 can be used in hazardous applications as an intrinsically safe interface to non-powered contacts and sensors such as push button operators, limit, temperature, pressure and vacuum switches.
Designed for hazardous applications, its low cost, integrated features and compact size also make it ideal for non-hazardous applications.
MULTI-FUNCTION CONTROLS
Applications
• Hazardous Atmospheres
• Multiple Functions
• Simplex or Duplex
• High/Low Level Alarms
• Auto or Manual Alternation
Dimensions
Series 67
• Pump/Solenoid Valves
• Sewage Lift Stations
• Wastewater Treatment
• Chemical Plants
• Groundwater Remediation
Specifications
Contact Design Standard N.O., N.C. (form C); Optional N.O., N.C. Contact Rating
(30VDC, 120/240VAC) 10 amp (style C); 5 amp (style A) Primary Voltage 120 VAC, 50/60 Hz Secondary Voltage 12 VAC @ 6mA RMS Sensitivity 4.7K - 100K ohms maximum specific resistance, factory set Temperature -40°F to +150°F (-40°C to +65°C) Approvals U.L. 913 File # E44570
How to Order
Use the Bold characters from the chart below to construct a product code.
XXXXX67
Series
67
Sensitivity
Supply Voltage
1 – 120 VAC
Contact Design
A – 1 Form A & B
(N.O. & N.C. isolated) for each channel
Enclosure
0 – None
D.C. Probe Circuit Option
A – No option
*Eliminates short cycles
D – 50K E – 100K
C – 1 Form C
(N.O., N.C., Common) for each channel
1 – NEMA 1
D – D.C. Probe Circuit*
4 – NEMA 4
WARRICK CONDUCTIVITY SENSORS
Wiring
*Form A & B contacts available
See Our Interstitial Tank Monitoring Products on page A-22.