Series 47
4-Channel Relay, Alarm Panel Control
Solid State Reliability
0-50K Ohm/cm Sensitivity
Alarm Contacts for Audible and Visual Alarms
4 Channel Relay
Removable Terminal Strips
Inverse or Direct Acting Field Selectable
U.L. Listed
Series 47 controls offer complete alarm panel control in a single package. Powered
output contacts allow quick connection of lights and audible alarms. Test and silence
functions are built in. Unit also carries one SPDT master alarm contact for remote
alarm activation.
Approved for Class I, II, III, Division 1, Groups C, D, E, F, G hazardous atmospheres,
Series 47 controls supply four channels which can be used with conductivity liquid
level sensors or dry contact sensors.
This device functions as an alarm or single point control. Field adjustable for direct
or inverse operation, it can operate separate visual alarms with a common audible
alarm channel. Silence and test terminals are standard. For additional lights, alarms or
WARRICK CONDUCTIVITY SENSORS
outputs, auxiliary contacts must be ordered.
Alarm Specifications
Contact Design SPDT 1 N.O. & 1 N.C.
Master Alarm Contact Rating
(30VDC, 120/240VAC) 5 amp Resistive, 1/10 hp
Indicator Contacts Powered 120 VAC 25mA
Indicator Contacts for
Audible Alarm Powered 120 VAC 5A
Auxiliary Contacts (optional) SPDT 120 VAC 10A (not powered)
Sensitivity 0-50K ohm maximum specific resistance
Primary Voltage 120 VAC (+10%/-15%) 50/60 Hz
Secondary Voltage 12 VAC @ 6mA RMS
Temperature -40°F to +150°F (-40°C to +65°C)
Approvals U.L. 913 File # E44570
INTRINSICALLY SAFE CONTROLS
Series 47
Applications
• Hazardous Atmospheres • Input for Computer
• Monitoring and Control • Input for Phone Dialer
• Storage Tank Alarm Panels
Dimensions
4.62˝ (11.73cm)
3.00˝ (7.62cm)
6.75˝ (17.15cm)
7.37˝ (18.72cm)
3.00˝ (7.62cm)
1.76˝
(4.47cm)
Wiring
Notes:
1. Terminals 7, 8 & 9 are single-pole double-throw dry contacts
designed for remote alarms.
2. Terminals 8 & 9 close on fault.
3. Terminals 7 & 8 open on fault.
4. Contacts clear when the silence pushbutton is depressed or when
the fault condition is cleared.
How to Order
Use the Bold characters from the chart below to
construct a product code.
Series
47
Sensitivity (ohms)
C – 26K
Supply Voltage
1 – 120 VAC
Auxiliary Contacts
A – Auxiliary Contacts
Number of Probe Channels
3A1 – One
See Our Interstitial Tank Monitoring Products
on page A-22.
D – 50K E – 100K
B – No Auxiliary Contacts
2A2 – Two 1A3 – Three 0A4 – Four
XXXXXX47