(continued) Page 4
ELECTRICAL
RACEWAY: An electrical raceway is furnished with each refrigerator
for running the fan, anti-condensate, lighting, and control
circuits fro? c
applies, of Iv*
cizad&
ecto case without using conduit. This
when the front panel is properly
secured into position.
This is approved by the Underwriters
Laboratories and may or may not comply with local codes.
MODEL
EVAPORATOR FAN
AMPS. @ 115 VOLTS
ANTI-CONDENSATE
AMPS. @ 115 VOLTS
DEFROST
AMPS.
MlA-8 .
6
None
MlA-12 .
9
.
70 None
MlAG-8 .
6
JF t 70 None
MlAG-12 .
9
11
.
None
FAN MOTORS: The fan motors employed are permanently oiled for the life
of the motor and require no periodic maintenance. These
are to be wired according to the enclosed wiring diagram.
Case fans run continuously; they do reverse during the
defrost cycle when using "AIR DEFROST". The case fan blade
will turn counterclockwise when looking into the refrigerator.
The case fan blade must have it's rib facing up
for proper operation. A label on the blade will also advise you if they are properly installed.
ANTI-CONDENSATE
HEATERS: These heaters are placed in the fixture to eliminate sweat
from forming on certain areas of the fixture. The crosssection of fixture shows location of the heaters.
REFRIGERATION
EXPANSION VALVE: The expansion valve furnished with your refrigeratior has
been carefully sized and set for maximum coil efficiency.
This bulb is located on the outlet of the coil. This location
MUST NOT BE CHANGED. Due to local conditions, adjustment
of the thermostatic expansion valve may be necessary after
+‘a minimum of 6 hours operation.
Do not adjust the expansion
valve at this point until you have checked the inlet strainer.
If adjustment is necessary,
adjust valve to give frost line
to ferrule hole where suctio'n line exits the refrigerator.
Adjust expansion valve l/4 turn and wait for 30 minutes
before making final check.
REFRIGERATION
LINES: On Warren/Sherer meat merchandisers, the liquid and suction
lines are located to the right of case center in the bottom
area. The suction line is 5/8"OD for Ml, and the liquid
line is 3/8"OD. The tubing faces forward so that an elbow
may be used, or if multiplexing a tee can be used.
Be sure
all refrigerant lines lie as close to the refriserator bottom
as possible so as not Q-obstruct-the return-air section of
the refrigerator.