Warner Electric PB-120, PB-170, PB-250, PB-400 User Manual

Primary Brakes
PB-120, PB-170, PB-250, PB-400
P-201 819-0480
Installation Instructions
Contents
Mounting
Surface
Magnet
Pilot
Diameters
PB-120 PB-170 PB-250 PB-400 . . . . .2-9
Electrical Specifications . . . . . . . . . . . . . . . . . . . .5
Drawings and Parts Breakdown or Exploded Views
PB-120 . . . . . . . . . . . . . . . . . . . . . . . . . .10-11
PB-170 . . . . . . . . . . . . . . . . . . . . . . . . . .12-13
PB-250 . . . . . . . . . . . . . . . . . . . . . . . . . .14-15
PB-400 . . . . . . . . . . . . . . . . . . . . . . . . . .16-17
Warranty . . . . . . . . . . . . . . . . . . . . . . .Back Cover
Follow the installation instructions in this manual carefully to ensure safe, reliable operation. All stated or implied manufacturer warranties are void if this product is not installed in accordance with these instructions.
Failure to follow these instructions may result in product damage, equipment damage, and serious or fatal injury to personnel.
Primary Brake PB-120 PB-170 PB-250 PB-400
The illustration drawings, parts lists, and exploded views for these units can be found beginning on page 10.
A. Installing the Conduit Box
To install the conduit box on the size 400 unit, refer to the instructions supplied with conduit box.
PB-170
PB-400
B. Mounting the Magnet
The brake magnet is mounted to a stationary machine member by a flange. Extreme care must be taken in selecting the location for the mounting of the magnet. Proper positioning is very important for the unit to function correctly.
1. A pilot diameter on the mounting surface is essential to hold the magnet within the required tolerances (Figure 1).
Figure 1
Warner Electric • 800-825-9050 P-201 819-0485
2
Figure 2
2. A machined pilot diameter is provided on the magnet mounting flange (refer to illustration drawings page 10-17) to aid in the proper positioning of the magnet.
Figure 3
3. An optional release spring may be used
with the standard armatures and hubs. The release spring forces the armature back against the hub retainer ring when the magnet coil is de-energized.
3. Once the mounting surface has been prepared, the magnet is bolted in place with capscrews and lockwashers. (Figure 2.)
4. After assembly, the magnet must be concentric and square within the required tolerances listed on the illustration drawing.
C. Assembling the Armature and Hub
1. The antibacklash armatures are shipped
assembled and ready to be installed. See Step D.
2. The standard armature and hub must be
assembled before it can be installed. Assemble the armatures so that the shiny surfaces (120 and 170) or backing plate sides (250 and 400) are against the hub retainer ring (Figure 3).
Follow these instructions to assemble the armature and hub when the optional release springs are being used.
Warner Electric • 800-825-9050 P-201 819-0485
3
PB-170
Assemble the splined armature to the hub. The shiny side of the armature should be against the hub retainer ring.
Assemble the release spring into the groove in the hub spline. The curved portion of the spring should be against the armature. (Figure 4)
Figure 4
PB-250
Insert the hub, with snap ring intact, into the arma­ture from the backing plate side. (Figure 5)
PB-400
Insert the release springs into the backing plate holes of the armature. Bow the springs as necessary to insert them into the armature. (Figure 7)
Figure 7
Remove the snap ring from the hub.
Insert the hub, with the setscrew end first, into the armature from the segmented side. Slide the hub
Figure 5
Insert both release springs into the holes of the backing plate. Bow the springs as necessary to
into the armature until the release springs engage the snap ring groove. (Figure 8)
Figure 8
insert them into the armature. (Figure 6)
Figure 6
Figure 9
Warner Electric • 800-825-9050 P-201 819-0485
4
Assemble the snap ring into the groove in the hub, clamping the release spring against the end of the spline. (Figure 9)
4. Secure the assembly in this position by alternately tightening the two setscrews in the hub.
D. Mounting the Armature Assembly
5. The hub will need to be repositioned as wear
1. (250 and 400 units only) Insert a key in the
occurs with time.
keyway of the shaft.
2. Slide the armature assembly onto the shaft.
3. Position the assembly in accordance with the overall axial dimensions given on the illustration drawings. For air gap (.015'').
Electrical Specifications
Unit Size PB 120 PB 170
Voltage – DC 6 24 90 6 24 90
Resistance @ 20°C — Ohms 6.32 104 1386 6.96 111.2 1506
Current — Amperes .949 .230 .065 .861 .215 .060
Watts 5.69 5.52 5.85 5.85 5.16 5.37
Coil Build-up — Milliseconds 12 12 11 17 17 16
Coil Decay — Milliseconds 88 78 76
Unit Size PB 250 PB 400
Voltage – DC 6 24 90 6 24 90
Resistance @ 20°C — Ohms 5 76.4 1079 4.88 73 1087
Current — Amperes 1.2 .314 .084 1.23 .322 .083
Watts 7.2 7.5 7.51 7.39 7.96 7.45
Coil Build-up — Milliseconds 48 48 44 154 154 154
Coil Decay — Milliseconds 15 15 13 62 60 55
Notes: Build-up time equals current to approximately 90% of steady state value and flux to 90%. Decay time equals current to approximately 10% of steady state value and flux to 10%.
Warner Electric • 800-825-9050 P-201 819-0485
5
4
10
8
11
9-1
*7
3
6
5
9
9-1
12
2
1
4
Installation Instructions
Conduit box kit No. 5200-101-010 contains all components needed to assemble a conduit box for PB400 brake.
When properly installed, this conduit box is designed to provide a proper means for field wiring terminations. It conforms to the requirements of Underwriters Laboratories.
Do not connect rigid conduit directly to the conduit box. A minimum of 12” of flexible liquid tight conduit or other suitable flexible wiring with appropriate fittings is required. Flexible wiring is required to prevent side loading of bearing on bearing mounted clutches and possible deformation or breakage of the conduit box or clutch/brake components during assembly.
Step 1
Assemble a customer supplied flexible wiring connector into desired end of conduit box (3). Press protective plug (5) into unused conduit hole.
Components
Thread green washer head hex screw (9) into round hole in base of conduit box. Place terminal ring (9-1) over screw before inserting.
Snap two wire grommets (6) into square holes in conduit box base. The grommet crowns should be toward the outside of the box and the rubber flanges should be on both sides of the conduit box.
Push two terminal spacers (7) through rubber grommets. Number 6 spacers fit in PB400. (See Figure 10)
Parts List for kit 5200-101-010
Item Quantity Part Name
11Bracket
-­21
31Box, Conduit 43Screw, Hex, Washer Head 51Plug, Protective 62Grommet, Wire
*7
2 Spacer No. 8 Thd. 2 Spacer No. 6 Thd.
82Cap terminal
91
Screw, Hex, Washer Head and Sems Conical Washer
Screw, Hex, Washer Head, Green
9-1 3 Terminal, Ring
10 1 Cover 11 2 Screw, No. 8 Brass 12 1 Plug, Protective
*The No. 6 spacers are required on Sizes 375, 400 and 475. All others use No. 8.
Warner Electric • 800-825-9050 P-201 819-0485
6
Figure 10
Loading...
+ 12 hidden pages