Warner Electric AC10 User Manual

AC10 Measuring System
P-2012-2 819-0402
Installation Instructions
Contents
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
AC10 Specifications . . . . . . . . . . . . . . . . . . . . 6
Pushbutton Key Functions . . . . . . . . . . . . . . . 7
Installation
Pre-Installation Inspection. . . . . . . . . . . . . . . . 8
Mechanical Installation . . . . . . . . . . . . . . . . . . 8
Electrical Connections. . . . . . . . . . . . . . . . . . 10
AC10 Setup Procedure . . . . . . . . . . . . . . . . . 13
Programmable Threshold Relay . . . . . . . . . . 15
Reset Tare to Zero . . . . . . . . . . . . . . . . . . . . . 15
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . 16
Failure to follow these instruc­tions may result in product damage, equip­ment damage, and serious or fatal injury to personnel.
Introduction
This manual is intended for use by qualified per­sonnel to assist them in the safe setup and operation of the Warner Electric AC10 Tension Measuring System. Warner Electric has made every effort to insure the accuracy and com­pleteness of the information and recommends that all procedures be read and understood before performing them. Please contact Warner Electric with any questions regarding any infor­mation contained in this manual.
Dimension Drawings
AC10 Tensioncells . . . . . . . . . . . . . . . . . . . . . 18
Model Number Designation. . . . . . . . . . . . . . 18
PSAC10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Warner Electric • 800-825-9050 P-2012-2
2
System Overview
J
3
J4
J6
J5
W
arner Part# 80-165 Rev Serial#
Setup
Rapid
E
xit
Setup
E
nter
J7
J8
J9
J
1
J2
PSAC10 Board
Power Switch
Output #1
Output #2
Control
Analog or Digital
Meter
Drive
Cell #1/Total/Cell #2
Switch
AC-10 Tensioncells
Threshold Alarm
RS-422 Interface
MCS2000-CTDA
MCS2000-CTDA
Control
Analog or Digital
Meter
Drive
The AC10 Tension Measuring System is designed to measure tension on continuous strip process­ing lines and equipment. The system consists of two AC10 Tensioncells, the PSAC10 power supply amplifier board, and two cables for connecting the Tensioncells to the board.
AC10 Tensioncells are mounted in pairs, one at each end of the measuring roll. During operation the Tensioncells continuously measure the mechanical tension force applied to the measuring roll. When the force is applied, the load plate deflects toward or away from the base block depending on the resultant force acting upon the Tensioncell. Deflection toward the base block is defined as the "Compression Mode.” Deflection away from the base block is defined as the "Tension Mode." AC10 Tensioncells work equally well in either mode.
The mechanical deflection of the load plate is converted into an electrical output signal by the
AC Linear Variable Differential Transformer (LVDT). Displacement of the LVDT core caused by variations in web tension results in an output signal to the PSAC10 board directly proportional to the applied tension.
The analog outputs from the Tensioncells are con­verted into digital signals by the microprocessor­based electronics. The signals are conditioned, processed, and summed to produce two individu­ally scaleable, -10 to +10 volt DC analog outputs to a tension indicator, drive or a MCS2000 CTDA control which can be used to monitor or control tension. The percent tension applied to each Tensioncell and the total tension are displayed on the board mounted 16-character liquid crystal display (LCD).
Terminals are also provided for connecting a user supplied On/Off power switch, 1-only 2-only switch, and RS-422 PC interface. A threshold alarm relay connection is also provided.
Note: When using the PSAC10 board, connect the outputs to the MCS2000 CTDA. There is no need to use the MCS2000 CTLC, because the signal is amplified and summed in the PSAC10.
Warner Electric • 800-825-9050 P-2012-2
3
AC10 Tensioncells
Shaft Support Block
Self-Aligning Shaft Support Bushing
Electrical Connector
5/8-1 1 UNC
Mounting
Hole
Load Plate
C-Flexure
Mechanical Stop
LVDT
LVDT Core
Base Block
Locating Tab
AC10 Tensioncells are available in three capaci­ty ranges for non-rotating shaft applications with maximum resultant force plus tare load of 60, 170, or 500 pounds respectively.
The rugged, all-steel construction of the AC10 Tensioncell includes four basic components: the one-piece base block, the patented C-Flexure, the load plate, and the shaft support block. The factory-set mechanical stop provides overload protection up to ten times the maximum rated load capacity of the unit.
Each unit is wall mounted by means of a single bolt located in line with the integral self-aligning, stainless steel shaft support bushing and the
centerline of the roll shaft. This permits the Tensioncell to be rotated and mounted at the required angle around the axis of the measuring roll. The locating tab at the bottom of the unit locks it in position.
The primary conversion element between the mechanical tension force and the electrical out­put signal is an AC Linear Variable Differential Transformer (LVDT). The LVDT electrical ele­ments are encapsulated and sealed against shock, vibration, or tampering. Input and output circuits are isolated from each other and from the Tensioncell body. This permits the Tensioncells to be used in floating ground elec­trical systems.
Warner Electric • 800-825-9050 P-2012-2
4
AC10 Electronics
J3
J4
J6
J5
Warner Part# PSAC10 Serial#
Setup
Rapid
Exit
Setup
Enter
J7
J8
J9
J1
J2
Input Power Selector Switch
Input Power Terminal
Power On Switch Terminal
Output #1 Output #2 Terminal
Cell #1/T otal/Cell#2 Switch Terminal
Tensioncell #1 Terminal
Tensioncell #2 Terminal
16-Character LCD
LCD Brightness Adjustment
Pushbutton Keys
Threshold Relay Terminal
RS-422 Output Terminal
Run Mode LED
Spare
230V
The AC10 microprocessor-based electronics adds ease of setup, versatility, and accuracy of the overall system by eliminating the need for potentiometers to adjust or setup the system. All adjustments and system settings are per­formed by using the pushbutton keys on the board. During setup, alphanumeric prompts are displayed on the 16-character LCD to guide the user through the setup procedure.
Other features of the PSAC10 board include:
Two individually scaleable -10 to +10 volt DC outputs Run Mode LED
Programmable threshold relay Cell#1/Total/Cell#2 switch connection LCD Brightness Adjustment Switch selectable 115/230 volt AC input power
An RS422 Serial Output terminal is also provid­ed for interfacing the AC10 system with a PC to monitor and/or record the percent tension applied to each Tensioncell. Data is transferred in ASCII text format. The RS422 output can be converted to RS-232.
Warner Electric • 800-825-9050 P-2012-2
5
Specifications
AC10 Tensioncells
Dimensions (I x w x h) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.00" x 3.44" x 3.90"
Maximum Load Capacity (tension plus tare)
AC10A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .60 pounds
AC10B . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .170 pounds
AC10C . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .500 pounds
Minimum Tension Load Required for Setup
AC10A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 pounds
AC10B . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10 pounds
AC10C . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30 pounds
Standard Shaft Diameters (1/16" increments) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1/2" to 1-1/2"
Overload Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10 times maximum rated load of unit
Maximum Deflection at Full Load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .0.010"
LVDT
Operating Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .250°F maximum
Excitation Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15 Vrms @5KHz
Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.2 volts AC/inch displacement / volt excitation
Excitation Resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .335 Ohms ±5%
Output Signal Resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .100 Ohms ±5%
Linearity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .0.1% of full scale
Hysteresis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .0.1% of full scale
Repeatability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .0.1% of full scale
Temperature Drift . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .0.02% per °C
PSAC10 Power Supply/Amplifier Board
Dimension (I x w) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8.75" x 6.88"
Maximum height of components above board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.5"
Operating Temperature Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32°F to +160°F (0°C to +70°C)
Input Voltage (switch selectable) . . . . . . . . . . . . . . . . . . . . . . . . . .115/230 VAC, 50-60 Hz, <1.0 Ampere
Output Voltage (two individually scaleable)
Maximum cable distance between Tensioncell and board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .100 feet
(The output load to the board must be 2 kor greater)
Threshold Relay Contact . . . . . . . . . . . . . . . . . . .1A @ 24 VDC, 500mA@ 120 VAC, 250 mA @ 220 VAC
RS-422 Data Rate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .300bps, NP, 8, 1 stop bit
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .-10 to +10 VDC
Warner Electric • 800-825-9050 P-2012-2
6
Pushbutton Key Functions
The six pushbutton keys on the PSAC10 board are used to enter and exit the Setup Mode and to make adjustments during the procedure. This section describes the various key functions and combi­nations that are used while setting up the system.
The UP arrow key is used to toggle between selections. It is also used to incremental-
RAPID
ly increase the output voltage each time the key is pressed. When the UP arrow and RAPID keys are pressed simultaneously, the voltage value will change continuously until the keys are released or the upper limit is reached. (See note below.)
ENTER
SETUP
EXIT
SETUP
RAPID
ENTERSETUP
RAPID
The DOWN arrow key is used to toggle between selections and to incrementally decrease the output voltage each time the key is pressed. When the DOWN arrow and RAPID keys are pressed simultaneously, the voltage value will change continuously until the keys are released or the lower limit is reached. (See note below.)
The ENTER key is used to make selections and store values before proceeding to the next Setup step.
Pressing and releasing these keys simultaneously accesses the Setup Mode. An aster­isk (*) will display next to the right tension value.
Press and release these keys simultaneously to start the Setup procedure when in the Setup Mode.
Press and release this key to exit the Setup Mode at any time. The system will return the settings entered during the last completed setup procedure.
Press and release these keys simultaneously to enter the settings for the Programmable Alarm Output.
SETUP
EXIT
Press and release these keys simultaneously to zero the system.
Note: During setup, the output voltage value will change approximately 5 millivolts each time the Up or Down arrow key is pressed and released. Pressing and releasing the RAPID key and the Up or Down arrow key simultaneously will change the value approximately 200 millivolts. Holding the Rapid key and an arrow key in, will continuously change the value until the keys are released.
Warner Electric • 800-825-9050 P-2012-2
7
Installation
T
E
B
TW
T
RF
L
O
Tensioncell Model Number Designation
AC10B 18 W1
Code
A
B
C
Max. Load
Capacity
(pounds)
60
170
500
Min. Tension
Load for Setup
(pounds)
4
10
30
Example: AC10B18W1 AC10 = Side Mount Tensioncell B = 170 pound capacity 18 = 1-1/8 inch shaft diameter W1 = AC10 with split brushing
Support Bushing (AC10 only)
W1 = Split bushing for clamping W2 = Solid bushing for expansion
08 1/2 09 9/16 10 5/8 11 11/16 12 3/4
13 13/16 14 7/8 15 15/16 16 1 17 1-1/16
18 1-1/8 19 1-3/16 20 1-1/4 21 1-5/16 22 1-3/8
23 1-7/16 24 1-1/2
Shaft Diameter
Pre-Installation Inspection
Before installing the AC10 system:
1. Insure all components are present. A typical system consists of two AC10 Tensioncells, one PSAC10 board, and two 30 foot lengths of cable for connecting the Tensioncells to the board. Refer to Model Number Designation (Chart 1) below to verify load capacity and shaft diameter.
2. Inspect all electrical and mechanical compo­nents for physical damage.
3. Promptly report any damage to the carrier and Warner Electric.
Mechanical Installation – Tensioncells
The maximum rated load capacity must be g
reater than or equal to (RF + TW) where W = Tare Weight. The Web Resultant Force (RF) and Tare Weight are always summed. Refer to the Model Number Designation (Chart 1) below to verify the shaft diameter, and that the maximum rated load capacity of each unit.
Warner Electric also recommends the Resultant Force (RF) be greater than 1/3 the maximum load capacity of the Tensioncells.
Warner Electric side mount AC10 Tensioncells are shipped in pairs designated W1 and W2. The W1 unit has a split stainless steel, self­aligning bushing for clamping the measuring roll. The bushing in the W2 unit is not split to allow for shaft expansion.
AC10 Tensioncells are available in three capaci­ty ranges. The rated load capacity should always be larger than the maximum calculated Tare Weight (W) plus the Resultant Force (RF).
To calculate the Resultant Force:
B
1. E = (180°-
/2) where B = Wrap Angle
2. RF = T x CosineE where T = Web Tension
Warner Electric • 800-825-9050 P-2012-2
8
Chart 1
B
T
E
B
TW
T
RF
L
O
5/8-11 UNC Mounting Bolt
Machine Frame
W1
Locating Tab
Centerline
Shaft Support Block & Screws
W2
efore installing the Tensioncells, refer to machine drawings, or other documentation to determine the mounting angle. If the mounting angle is not specified, mount the Tensioncells so that the Tensioncell load line (OL) bisects the wrap angle and aligns with the Resultant Force (RF).
The Tensioncells are mounted to the machine frame with a 5/8-11 UNC bolt. The bolt is in line with the centerline of the shaft support bushing. This allows the Tensioncells to be rotated around the centerline of the roll so that the Tensioncell load line (OX) aligns with the Resultant Force (RF).
To install the Tensioncells:
1. Drill a 5/8" diameter hole through each side
of the machine frame at the measuring roll location. The holes must be in line with each other and roll centerline to insure that the roll is level.
2. Fasten the Tensioncell to the machine frame
with the 5/8-11 UNC mounting bolt.
3. Rotate the Tensioncell to the proper mount-
ing angle and tighten the mounting bolt.
4. Drill a #6 (.204) hole concentric with the 1/4" h
ole in the locating tab.
5. Remove the Tensioncell to provide clearance to tap the hole for a 1/4-20 thread.
6. Repeat steps 2 through 5 for the Tensioncell for the other end of measuring roll shaft.
7. Loosen, but do not remove, the four screws in the bottom of the shaft support block enough to slide the Tensioncells on the roll shaft.
Note: The mounting angle must be the same for both Tensioncells and the Load Plate for both units must face in the same direction.
8. Position the roll with the Tensioncells in the machine and fasten them to the machine frame with the mounting bolts. Tighten the bolts enough to allow the Tensioncells to be rotated to the desired mounting angle.
9. Rotate the Tensioncells to align the locating tab with the 1/4-20 threaded hole. Lock the Tensioncells in position against the machine frame using a 1/4-20 x 1/2 socket head cap screw.
10. Tighten the mounting bolt on each unit.
11. Align the measuring roll so that there is no mechanical binding or friction.
12. Tighten the four screws in the bottom of each shaft support block.
Note: The mechanical stops are factory set to provide 1000% overload protection.
Warner Electric • 800-825-9050 P-2012-2
9
Electrical Installation
Oscillator
Demodulator
Shield to Pin H
Shield to Pin H
White to Pin G
Brown to Pin A
Pink to Pin E
Yellow to Pin C
Input
Output
P1
S1
S2
A
GH E C
A
H
G
C
D
E
FB
Sig Sig Exc Exc Gnd
Yellow Pink Brown White Shield
Yellow Pink Brown White Shield
Sig Sig Exc Exc Gnd
J2
J1
1
1
2
2
3
3
4
4
5
5
Electrical Connections
(Read the entire electrical installation proce­dure before proceeding.)
The PSAC10 Power Supply/Amplifier board should be securely mounted in a cabinet or enclosure using the mounting holes and standoffs INPUT provided. Refer to the dimension drawing on Page 19 for mounting hole locations.
Two 30 foot cables are provided for connecting the AC10 Tensioncells with the PSAC10 board. A screw-on connector is provided at one end of each cable for connecting to the AC10 Tensioncells.
Note: If the board must be located more than 30 feet away from the Tensioncells, the cable can be extended up to a total of 100 feet using Belden #8723 (or equivalent) in a grounded steel conduit.
Although either Tensioncell in the system can be designated as Tensioncell #1 or #2, the following electrical connections assume the AC10 Tensioncell marked W1 is Tensioncell #1 and the Tensioncell marked W2 is Tensioncell #2.
Notes:
1. The wire color connections listed for J1 and J2 will differ if Belden #8723 (or equivalent) cable is required. lnsure the correct wiring connections are made with respect to the connection made with the Warner Electric supplied cable.
2. The Warner Electric supplied cable/connec­tor assembly is an eight conductor cable. However, only the yellow, pink, brown, and white and shield wires used.
J1 to W1 Tensioncell Terminal Connection with Warner Electric supplied cable
Terminal Label Description Wire Color
J1-1 Sig AC signal from LVDT Yellow
J1-2 Sig AC signal from LVDT Pink
J1-3 Exc Excitation to LVDT Brown
J1-4 Exc Excitation to LVDT White
J1-5 Gnd Shield Shield
Note: Pins B, D & F are not used
Warner Electric • 800-825-9050 P-2012-2
10
Tension signal from transducer 0-700mVAC, 5KHz
Tension signal from transducer 0-700mVAC, 5KHz
Warner Electric Supplied Cable to Transducers
15 V
AC, 5KHz excitation to the transducer
15 VAC, 5KHz excitation to the transducer
J2 to W2 Tensioncell Connection with Warner
Gnd L1 L2
J3
230V
1
2
3
X
X
2-Only
1-Only
Gnd
J5
Cell #2Cell #1
Total
1
2
3
2L1
1L1
2L2
1L2
J4
1
2
3
4
E
lectric supplied cable
Terminal Label Description Wire Color
2-1 Sig AC signal from LVDT Yellow
J J2-2 Sig AC signal from LVDT Pink J2-3 Exc Excitation to LVDT Brown J2-4 Exc Excitation to LVDT White J2-5 Gnd Shield Shield
J3 Input Power (115/230 VAC, 1-PH, 50/60 Hz)
Terminal Label Description Wire Color
J3-1 Gnd Ground Green J3-2 L1 L1 (230V) or Hot (115V) Black J3-3 L2 L2 (230V) or Neutral (115V) White
Terminal Label Description
J4-1 2L1 (Switched) Line 1 J4-2 1L1 (Hot) Line 1 J4-3 2L2 (Switched) Line 2 J4-4 1L2 (Hot) Line 2
J5 Cell#1/Total/Cell#2 Switch Terminal (For Output #2 only)
Make sure voltage select switch is in proper position
Input Power single phase 115 or 230 VAC
The input voltage selector switch must corre­spond to the voltage of the input power source.
J4 AC Power Switch and/or Power Indicator Terminal
J4 provides the terminal connection for an exter­nal AC Power Switch and/or power indicator. The indicator should not draw more than 40 milliamps of current. J4 may also be used to supply AC power to a digital voltmeter by connecting the meter between J4-2L1 and J4-2L2.
J5 provides the connections for an external three-position switch with two normally open contacts. When used in conjunction with a remote meter, the switch allows the user to monitor total tension or the tension applied to either Tensioncell. The meter should be connect­ed to Output #2 at J6, terminals Out2 and Gnd.
With the switch in the normally closed position, Output #2 will indicate the total tension. In the Cell#1 position, Output #2 switches to indicate the tension measured by the W1 Tensioncell. Changing to the Cell#2 position switches Output #2 to indicate the tension applied to the W2 Tensioncell.
Terminal Label Description
J5-1 2-Only (Switched) tension W1 J5-2 1-Only (Switched) tension W2 J5-3 Gnd Ground
Note: If an ON-OFF switch is not used, jumpers must be installed from J4-2L1 to J4-1L1 and from J4-2L2 to J4-1L2 for proper operation.
Warner Electric • 800-825-9050 P-2012-2
11
J6 Analog Outputs Terminal
Out 2
Gnd
Out 1
Gnd
J6
Output #2 ( -10 to +10 VDC)
Common
Output #1 ( -10 to + VDC)
Common
1
2
3
4
Normally Closed
Common
Normally Open
J7
NC
COM
NO
1
2
3
Ground
Data Line -
Data Line +
J8
Gnd
Tx-
Tx+
1
2
3
The J6 terminal provides the connections for the two 10 volt DC outputs. Each output can provide up to 30 milliamp current.
During setup, each output is individually scaleable to meet the requirements needed to calibrate the indicator, drive, or control connect­ed to the board. The board circuitry is designed to allow a switch to be connected at Terminal J5. This switch allows the user to monitor the Output #2 signal with respect to total tension, or the ten­sion applied to either Tensioncell.
The contact may be wired to function in either t
he normally open or normally closed state.
Terminal Label Description
7-1 NC Normally Closed Contact
J
7-2 COM Common
J J7-3 NO Normally Open Contact
Terminal Label Description
J6-1 Out2 Scaleable -10 to +10 VDC Output J6-2 Gnd Common J6-3 Out1 Scaleable -10 to +10 VDC Output J64 Gnd Common
J7 Threshold Relay Terminal
J7 provides the connections for utilizing the AC10 Threshold Relay which is a form "C" dry relay contact, rated at 1 Amp. During setup, the threshold (percentage of total tension) is pro­grammed to operate when the total tension is either above or below the threshold value.
J8 RS232 Output T
erminal
J8 provides the cable connections for interfac­ing the PSAC 10 board with a PC to monitor total tension and tension applied to each Tensioncell. Data is transferred in ASCII text for­mat.
Terminal Label Description
J8-1 Gnd Ground J8-2 Tx- Data Line + J8-3
Tx+ Data Line-
J9 (Spare)
Initial Electrical Checks
Before applying power:
Note: Make sure that the Input Power Selector Switch matches the available input voltage.
Switch 1 2 3 4 5 6 7 8 Position ON ON ON ON OFF ON ON ON
Apply power.
The red Run Mode LED in the lower right hand corner of the board should be flashing.
Warner Electric • 800-825-9050 P-2012-2
12
Verify that the 8-position dip switch is set as follows:
AC10 Setup Procedure
Compression
Te nsion
Important: The input to any external device wired to J6-3 Out1 or J6-1 Out 2 must be 10 VDC or less.
4. Press ENTER when the desired mode is dis­p
layed.
Steps 5 through 8 are performed with only the tare load applied on the Tensioncells.
The following procedure assumes a digital volt­meter will be used when measuring and setting the desired output voltages. If the outputs are connected to a digital or analog indicating device, which will be used during normal opera­tion, these devices may be used during the setup procedure.
Note: The voltage setting for Output #1 at 100% load must be more positive than the voltage setting at 0% load. The same applies to the voltage settings for Output #2.
With power applied to the PSAC10 board, allow the system to "warmup" for 20 minutes or longer before proceeding with the setup proce­dure.
1. Press and release the SETUP and UP­ARROW keys simultaneously. An asterisk (*) will display next to the right tension value.
Note:
To exit the SETUP mode at anytime dur­ing the following procedure, press and release the EXIT key. The system will return to the set­tings entered during the last completed setup
Apply Load 0%
5.
Insure that the Tensioncells are properly installed and the material is removed from the measuring roll.
6. Press ENTER.
.
0% 0% *0%
2. Press and release SETUP & ENTER simulta­neously to start the SETUP procedure.
Note: The Run Mode LED should stop flashing.
Compression Mode
3. Select either the COMPRESSION MODE or
TENSION MODE using the UP or DOWN arrow key to toggle between the two choices.
a. Select the COMPRESSION MODE if the
direction of the tension force is toward the base block.
b. Select TENSION MODE the direction on
the tension force is away from the base block.
Warner Electric • 800-825-9050 P-2012-2
13
7. Adjust Out 1 0%
Out 2
Gnd
Out 1
Gnd
J6
Output #2 ( -10 to +10 VDC)
Common
Output #1 ( -10 to + VDC)
Common
1
2
3
4
Scale
W eb Path
Roll
Rope
W eb Path
Roll
Rope
W eights for Max. Tension
a. Connect a digital voltmeter between J6-3
Out 1 and J6-4 Gnd.
b. Press the UP or DOWN arrow key (and
RAPID key if necessary) until the desired no load output voltage is attained.
c. Press ENTER.
8.
Adjust Out 2 0%
a. Connect a digital voltmeter between J6-1
Out 2 and J6-2 Gnd.
b. Press the UP or DOWN arrow key (and
RAPID key if necessary) until the desired no load output voltage is attained.
c. Press ENTER.
Note: All rolls used in the pull test s
hould be free running rolls.
c. With one end of the rope secured, hang a
weight equal to the full load tension. (50% if selected)
A crane scale may be used to apply the required load.
d. Press ENTER.
10.
Adjust Out 1 100%
a. Connect a digital voltmeter between J6-3
Out 1 and J6-4 Gnd.
b. Press the UP or DOWN arrow key (and
RAPID key if necessary) until the desired full load output voltage is attained.
c. Press ENTER.
Note: Steps 9 through 12 can be performed with 50% or 100% load applied when setting Output #1 and Output #2 voltage. Refer to the table at the right for minimum resultant load required for setup before proceeding.
9. Apply Load 100%
a. Press the UP or DOWN arrow key to tog-
b. Thread a non-stretchable rope over the
Warner Electric • 800-825-9050 P-2012-2
14
gle between 50% or 100%. When desired percentage is displayed.
The illustrations at the right show two pull test methods. These tests are used to apply a load representative of the web tension. The load should be equal to the percentage of the full load selected (50% or 100%).
center of the tension measuring roll simu lating the web path.
Model Max Load Min. Tension
Capacity Load for Setup
(Pounds) (Pounds)
-
ACIDA 60 4
ACIDB 170 10
ACIDC 500 30
Table 2
11.A
djust Out 2 100%
5. Press ENTER to select the desired mode.
a. Connect a digital voltmeter between J6-1
Out 2 and J6-2 Gnd.
b. Press the UP or DOWN arrow key (and
RAPID key if necessary) until the desired output voltage is attained.
c. Press ENTER.
12.
Setup Complete
a. Press ENTER.
Programmable Threshold Relay
The Threshold Relay can be programmed to Close on Higher (if the total tension goes above) or Close on Lower (if the total tension goes below) a preset programmable threshold between 0% and 102% of the total tension. The dry relay contact is rated at 1 amp @ 24VDC, 250mA @ 220 VAC, or 500 mA @ 120 VAC.
Note: The threshold may be set while the web machinery is in operation. Although the LCD will not be showing the tension, Output #1, Output #2, and the serial output will still be responding to tension changes.
If the threshold value or mode is reset with the equipment operating, the new value will take effect immediately.
Reset Tare to Zero
The tare value may be zeroed to compensate for any offsets accumulated during normal oper­ation. Press the SETUP and EXIT keys simulta­neously to reset the tare to zero.
Note: Resetting tare to zero must be done with no tension load applied.
A lamp may be connected between J7-3 NO (or J7-1 NC) and J7-3 COM during setup, start up, and/or normal operation to verify the relay is operating properly.
To set the threshold value:
1. Press the SETUP & RAPID keys simultane-
ously. The display will show a message indi­cating the current value of the threshold. The Run Mode LED will continue to flash.
Threshold 000%
2. Press the UP or DOWN arrow key until the
desired threshold value is displayed.
3. Press ENTER to select the value.
4. Press the UP or DOWN arrow key to toggle
between the CLOSE ON LOWER or CLOSE ON HIGHER prompt.
Close on Lower
Warner Electric • 800-825-9050 P-2012-2
15
Troubleshooting
Test Points TP5, TP6, TP7, TP8, TP9
Enter
J7
J8
J9
LCD Brightness Adjustment
+5VDC
-5VDC
-5VDC
+5VDC
GND
Test Points TP2, TP3, TP4
When properly installed in accordance with the design specification and procedures outlined in this manual, the AC10 Tension Measuring System should require little or no regular main­tenance or service. Certain conditions, however, can impair the accuracy, reliability, and perform­ance of the system. The following are some conditions to consider which may effect the mechanical and/or electrical components of the system.
1. Have the system operating parameters changed?
a. Has the web tension changed?
b. Does the tension plus tare load exceed
the maximum rated load capacity of the unit?
9. Verify the following voltages.
T
P3 to TP7 +10 volts DC
TP4 to TP7 +2.5 volts DC
TP5 to TP7 +15 volts DC
TP6 to TP7 +5volts DC
TP8 to TP7 -5 volts DC
TP9 to TP7 -15 volts DC
10. Are outputs responding to tension changes? Check connections and voltages at J1, J2, and J6.
11. Does the output signal(s) from the board meet the voltage requirements for the device(s) connected to it?
12. Is the Excitation Voltage to the LVDTs cor­rect?
c. Has the Wrap Angle changed?
2. Are the Tensioncells mounted correctly and securely?
3. Is the tension measuring roll properly aligned and does it turn freely?
4. Is the line voltage present and the on-board Input Power Selector Switch in the correct position?
5. Is an external power switch connected and operating correctly? If an external switch is not used, are the jumpers properly installed at J4? See page 11.
6. Are all fuses and/or circuit breakers installed and functional? There are two 250V, 500mA fuses on the board.
7. Is the Run Mode Indicator LED flashing? If not, check if the system is in Setup mode.
8. Is the on-board display lit? Check LCD Brightness Adjustment.
Warner Electric • 800-825-9050 P-2012-2
16
a. Using an AC volt meter with at least
5
Khz band width, measure the voltage between J1-3 Exc and J1-4 Exc. The meter should read 15Vrms ~ 5Khz ± 5%. If excitation voltage is low, turn off power to the board and remove the J1 connector. Turn power back on and recheck. If voltage is correct, check for a short in Tensioncell cable assembly. Repeat test for Cell #2 at J2.
b. With board power off, remove the J1
connector and measure the resistance between the Yellow (J1-1 Sig) and Pink (J1-2 Sig) wire terminals. The resistance reading should be 335 ohms ± 5%. The resistance between White (J1-3 Exc) and Brown (J1-4 Exc) wire terminals should be 100 ohms ± 5%. If readings are incor­rect, disconnect cable at the Tensioncell designated as Cell #1, and check resist­ance between pins C and E, and A and G. Repeat test for Cell #2 at J2.
13. Does the system zero? Press the SETUP and EXIT keys simultaneously.
14. Does repeating Setup procedure help?
15. If problem(s) persists, contact your local Warner Electric Representative or the factory.
Warner Electric • 800-825-9050 P-2012-2
17
See Note
3
.13
2.13
3.44
1.13
5/8-11 UNC .93 Full Th’d for Mounting Bolt
Electrical Connector
2.50
.25 Dia. Hole For Locking Screw
3
.90
1
.13
2.00
.75
3.00
Note: Stainless steel self-aligning bushing provided for 1/2” to 1-1/2” diameter shafts in 1/16” increments.
+
.50
2.00
.25
1.31
1.44
W2 unit shown here. W1 unit is available.
AC10 Tensioncell Dimensional Drawings
(Specifications and dimensions subject to change without notice.)
Tensioncell Model Number Designation
A C 1 0 B 1 6 W 1
Max.Load Min.Tension
Code Capacity Load for Setup Support Bushing (AC10 only)
(pounds) (pounds) W1 = Split bushing for clamping
A 60 4 W2 = Solid bushing for expansion B 170 10 S = System, which includes one “W1” cell, C 500 30 one “W2” cell, two 30 ft cables and a
Examine: AC10B16W1 AC10 = Side Mount Tensioncell 12 3/4 B = 170 pound capacity 16 1 16 = 1 inch shaft diameter 20 1-1/4 W1 = AC10 with split bushing 23 1-7/16
Shaft Diameter
Note: Other shaft diameters are available.
PSAC10 board.
Warner Electric • 800-825-9050 P-2012-2
18
PSAC10 Board Dimensions
1.31
.31
.25
5.75
3.13
J3
J4
6.88
6.25
3.13
Mounting Holes .250 Dia. (7) Places
J6
J5
8.25
Warner Part# PSAC10 Serial#
Setup
Rapid
Exit
Setup
Enter
J7
8.75
J8
J9
J1
J2
Specifications and dimensions subject to change without notice.
Warner Electric • 800-825-9050 P-2012-2
19
Warranty
Warner Electric LLC warrants that it will repair or replace (whichever it deems advisable) any product manufactured and sold by it which proves to be defective in material or workmanship within a period of one (1) year from the date of original purchase for consumer, commercial or industrial use.
This warranty extends only to the original purchaser and is not transferable or assignable without Warner Electric LLC’s prior consent.
Warranty service can be obtained in the U.S.A. by returning any defective product, transportation charges prepaid, to the appropriate Warner Electric LLC factory. Additional warranty information may be obtained by writing the Customer Satisfaction Department, Warner Electric LLC, 449 Gardner Street, South Beloit, Illinois 61080, or by calling 815-389-3771.
A purchase receipt or other proof of original purchase will be required before warranty service is rendered. If found defective under the terms of this warranty, repair or replacement will be made, without charge, together with a refund for transportation costs. If found not to be defective, you will be notied and, with your consent, the item will be repaired or replaced and returned to you at your expense.
This warranty covers normal use and does not cover damage or defect which results from alteration, accident, neglect, or improper installation, operation, or maintenance.
Some states do not allow limitation on how long an implied warranty lasts, so the above limitation may not apply to you.
Warner Electric LLC’s obligation under this warranty is limited to the
repair or replacement of the defective product and in no event shall Warner Electric LLC be liable for consequential, indirect, or incidental damages of any kind incurred by reason of the manufacture, sale or use of any defective product. Warner Electric LLC neither assumes nor authorizes any other person to give any other warranty or to assume any other obligation or liability on its behalf.
WITH RESPECT TO CONSUMER USE OF THE PRODUCT, ANY IMPLIED WARRANTIES WHICH THE CONSUMER MAY HAVE ARE LIMITED IN DURATION TO ONE YEAR FROM THE DATE OF ORIGINAL CONSUMER PURCHASE. WITH RESPECT TO COMMERCIAL AND INDUSTRIAL USES OF THE PRODUCT, THE FOREGOING WARRANTY IS IN LIEU OF AND EXCLUDES ALL OTHER WARRANTIES, WHETHER EXPRESSED OR IMPLIED BY OPERATION OF LAW OR OTHERWISE, INCLUDING, BUT NOT LIMITED TO, ANY IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS.
Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you. This warranty gives you specic legal rights and you may also have other rights which vary from state to state.
Changes in Dimensions and Specifications
All dimensions and specications shown in Warner Electric catalogs are subject to change without notice. Weights do not include weight of boxing for shipment. Certied prints will be furnished without charge on request to Warner Electric.
Warner Electric LLC
31 Industrial Park Road • New Hartford, CT 06057 815-389-3771 • Fax: 815-389-2582 www.warnerelectric.com
P-2012-2 819-0402 7/05 Printed in USA
Loading...