Warner TCS-200-1, TCS-200-1H Service & Installation Manual

P-2003-2-WE 819-0420
TCS-200-1 and TCS-200-1H
Tension Controls
Service & Installation Instructions
An Altra Industrial Motion Company
Introduction ............................2
Theory of Operation ......................3
Technical Specifications ..................3
Installation
Control Mounting .....................4
External Sensor Mounting...............5
System Wiring ..........................5
System Start-Up and Adjustment ..........11
Voltage Tables .........................19
System Troubleshooting .................20
Component Parts List
Coupling, MCS-605-1 284-8000-003 Roll Pin (Drive) for Sensor Coupling 679-8001-067 TCS-200-1 Tension Control 6910-448-086 TCS-200-1H Tension Control 6910-448-087 Ultrasonic Sensor 4-40in 7600-448-001
List of Illustrations and Figures
Figure 1 Dimensional Data, Mounting ....... 6
Figure 2 Power Connections .............. 7
Figure 3 Brake Connections ..............8
Figure 4 Remote Torque and Roll
Follower Connections ............. 9
Figure 5 Remote Switch, Analog Input and Analog Input Isolation Connections . 10
Tables 1,2,3 Voltage/Current Tables .......... 19
Templates TCS-200-1H Template ........... 21
TCS-200-1 Template ............ 21
Introduction
The Warner Electric Tension Control system is comprised of a tension brake, control module, and optional external sensor input.
This manual has been designed to cover installation, start-up, adjustment, and maintenance of your tension control system and covers the control system only. Further information on brake sizing and selection can be found in catalogs P-1234 or P-771.
Power Source
The TCS-200-1 series Tension Controls operates from a power source of 115 or 230 VAC, 50/60 Hz input. Primary voltage is determined by the customer’s input voltage source. The control is factory set to accept 115 VAC input. Refer to the wiring section for 230 VAC input connections.
Control
The TCS-200-1 series controls are selectable voltage or current controlled power supply designed to power up to a 16 magnet Electro Disc tension brake system, Electromagnetic Particle Brakes, TB series brakes or Advanced Technology tension brakes. This control can be operated manually from the front panel or remotely via an analog voltage input, a current input, a remote pot, or a roll follower. External inputs are also provided for remote brake “off”, “run”, and “stop” functions, as well as front panel control of these functions.
The analog voltage and current inputs are electrically isolated from the main power circuitry of the control when 15-35 VDC supply is provided to maintain full isolation. If isolation is not needed, an on board 15 VDC supply is jumpered to act as a default.
Sensors
When the TCS-200-1 series controls are operated in a remote torque adjust mode, a 1,000 ohm potentiometer is required. This should be a linear type potentiometer with a rating of .5 watts, 10 percent tolerance, and a .5 percent linearity.
For roll follower input applications, a 1,000 ohm potentiometer with a rating of .5 watts, 10 percent tolerance, and .5 percent linearity is required for best performance.
Brakes
All 24 VDC tension brakes that Warner Electric offers, to a maximum of 4.25 amps, can be used with the TCS-200-1 tension control. For all 24 VDC tension brakes that require greater current capability from the control (not to exceed 5.8 amps), use a TCS-200­1H. The brake converts electrical current supplied by the control into torque, which retards material flow, maintaining the desired web tension.
2 Warner Electric • 800-825-9050 P-2003-2 • 819-0420
Theory of Operation
When in operation, the control is powered by a standard 115/230 VAC line. The control has a transformer that converts that voltage to a level suitable for any 24 VDC brake system. The signal is rectified to DC and pulse width modulated (PWM) to the desired brake current via the TENSION ADJUST knob.
The front panel TENSION ADJUST feeds a small voltage to a comparator, which compares this signal to a triangular wave. This is where the PWM pulse is generated. This pulse is then inverted and used to drive a power circuit. The main brakes and a sense brake are then energized by the power circuit at regular intervals. From the sense brake, a growth and decay signal is converted to a voltage that can be added to the signal by setting a jumper on the inside of the cover. This signal, when selected, is used to maintain constant current to the brake. The signal must not be selected when no sense brake is connected.
The control has several options that allow for external/remote tension adjust in addition to the tension adjust pot on the front of the panel. Two such options are the remote pot or a roll follower. Another is the option for an analog input of voltage or current from a PLC or ultrasonic sensor. A special feature of the analog inputs is that they are optically isolated from the rest of the control circuitry if an external power source is used to power the isolated circuits. The isolation is needed when using a PLC or an external power supply for the ultrasonic sensor. An internal power source is also available and jumpered in as default if isolation is not necessary. The tension adjust pot on the front of the panel becomes a span adjust when any of the external control options are connected.
The two indicators on the front of the panel are green for “power on” and red to indicate a short circuit. When a short occurs in the brake, the control disables the power circuits to prevent damage. Turn the switch to “off” to reset the short circuit indicator.
Because this is a basic tension control, no anti-residual circuits, zero adjust circuits, or other complex control circuits (found in other Warner Electric tension control systems) are included in the TCS-200-1 series controls.
Technical Specifications
TCS200-1 and TCS200-1H
Input Power
115/230 VAC 50/60 Hz
Output TCS-200-1
Adjustable 0-24 VDC. Maximum of 4.25 amps continuous. Can be used with any 24 VDC tension brake with or without the need for a sense coil.
Output TCS-200-1H
Adjustable 0-24 VDC. Maximum of 5.8 amps continuous. Can be used with any 24 VDC tension brake with or without the need for a sense coil.
Ambient Temperature
-20° to 125° F (-29° to 51° C)
Fuse
2.5 Amp, 250 VAC, Slow-Blow
Protection
Internal short-circuit protection on driver output stage
Sensor Inputs
• Remote Torque Adjust 1,000
The control also has the capability to duplicate the front panel selector switch at a remote location. Brake “off” mode overrides the tension adjustment and provides for resetting the short circuit indicator. In the “run” mode, output operation is normal and is controlled by any of the front panel or remote tension adjust features discussed above. The brake “stop” mode provides for full output current to the brake.
Warner Electric • 800-825-9050 P-2003-2 • 819-0420 3
• Roll Follower 1,000
• Analog voltage input, 0-10 VDC (Optically isolated when 15-35 VDC supplied from external source)
• Analog current input, 4-20mA (Optically isolated when 15-35 VDC supplied from external source)
Auxiliary Inputs
• Brake Stop – Applies full voltage to the connected brakes. Active high input.
o 1. If you are using a PLC or an
external power supply with this control, you must enable the isolation of the control.
• Brake Run – Voltage to the brake is controlled by any of the sensor inputs and/or the front panel tension adjust. Active high input.
• Brake Off – Removes output current to the brake. Puts the brake at zero current level. Active high input.
Note 1: The remote input signal for these functions requires a minimum contact rating of 20 VDC at .01 amps and a maximum of state leakage current less than 100 micro-amps.
Note 2: The remote switch input overrides the front panel switch.
Front Panel
• Tension Adjust – Provides current adjust to the brake from 0 to 100%. In the remote and analog input mode, provides for maximum output level set to the brake.
• Brake Mode Switch –
Modes: “stop”-brake full on
“run” -normal operation
o 2. The TCS-200-1 cannot operate a single brake
or brakes that require more than 4.25 amps continuous.
o 3. The TCS-200-1H cannot operate a single
brake or brakes that require more than 5.8 amps continuous.
This Installation and Operation Manual has been arranged for the systematic installation and start-up of your tension control system. To achieve the best possible results, we recommend checking off each completed step in the space provided before proceeding to the next step.
Sample
o Attach the TCS-200 control chassis to the
mounting surface and secure with mounting hardware.
Check box after completing each step.
Control Mounting
“off” -brake off
Indicators (Front Panel)
• Green LED indicates AC power has been applied to the control.
• Red LED indicates there is a short on the output. Turn the front panel switch “off” to reset the short circuit.
General
The control chassis must be considered NEMA 1 and should be kept clear of areas where foreign material, dust, grease, or oil might affect control operation.
Potentiometers (supplied by the customer)
• Remote Torque Adjust 1,000 ohms, 10% tolerance, .5% linearity, .5 watts, linear taper
• Roll Follower – 1,000 ohms, 10% tolerance, .5% linearity, .5 watts, linear taper
o 1. Determine a suitable location for the control to
be mounted. Consideration should be given to whether the front panel adjustments will require access by the operator.
o 2. Using the dimensional data supplied in Figure
1a and Figure 1b, drill four mounting holes using a #16 drill if #8 through-bolts are used. For #8 capscrew mounting, use a #29 drill and tap holes for #8 screws. Templates for hole drilling are found on page 21.
o 3. Attach the TCS-200-1 or TCS-200-1H control
chassis to the mounting surface and secure with mounting hardware.
Note: The control chassis has been designed to accommodate two half-inch conduits for wiring when the control is mounted to the machine frame.
4 Warner Electric • 800-825-9050 P-2003-2 • 819-0420
o 4. Attach conduit or seal tight connectors.
The control is now ready to be wired. Refer to the wiring section of this manual for proper system wiring.
Brake Installation
Refer to the brake manual that is appropriate for the brake selected for its installation procedures.
External Sensor Mounting (Optional)
Options for four types of external sensor inputs are available. These consist of either an external torque adjust, roll follower input that provides a signal directly proportional to the diameter of the roll to be processed, analog voltage, or analog current input. Determine which type of external sensor will be used and proceed to the appropriate section of this manual.
Remote Torque Adjust Potentiometer (Optional)
Note: If angular rotation is not adequate, insufficient
output from the control is possible. In this case, a timing belt drive between the roll follower pivot-point and the sensor potentiometer may be necessary to obtain adequate angular rotation.
o 2. Secure the roll follower potentiometer. This
completes the mounting for a roll follower potentiometer. Refer to the wiring section of this manual for proper control wiring.
Analog Input (Optional)
o 1. Select an appropriate mounting location for the
PLC or ultrasonic sensor.
o 2. Mount and secure the PLC or ultrasonic
sensor according to the specifications for those products.
This completes the mounting. Refer to the wiring section of this manual for proper control wiring.
o 1. Select an appropriate mounting location for the
external torque-adjust potentiometer.
Note: In determining this mounting location, take into consideration the routing of the wires necessary to connect the control, access for the operator, and space required by the physical size of the potentiometer.
o 2. Drill a mounting hole based on the bushing
diameter of the potentiometer selected.
o 3. Mount and secure the potentiometer.
This completes the mounting for an external remote torque adjust potentiometer. Refer to the wiring section of this manual for proper control wiring.
Roll Follower Adjust Potentiometer (Optional)
o 1. Mount the roll follower potentiometer and
determine the amount of angular rotation at the potentiometer shaft.
System Wiring
System Wiring Precautions
The following wiring precautions will help you properly wire and install a trouble free system.
o1. Use a proper gauge wire for all wiring.
o2. Insure that wires are cut and stripped so that
no excess bare wire is exposed.
o 3. Segregate AC input power from control
switching and external sensor wiring (if used).
o 4. Do not run AC power lines with DC power,
input sensor wiring, or switching wiring. Noise transients can be easily transferred, causing erratic control operation.
o 5. Use shielded cable when possible for
connecting the TCS-200-1 to external switches, the sensor potentiometer, PLC’s, and ultrasonic sensor.
Warner Electric • 800-825-9050 P-2003-2 • 819-0420 5
o 6. Under no circumstances should auxiliary
accessories be operated from the TCS-200-1 control.
WA RNER ELECTRIC
®
TCS-200-1H
POWER SHORT
TENSION
ADJUSTMENT
BRAKE MODE
.875 DIA. 2 PLCS. FOR 1/2 CONDUIT
3.75
1.25
3.00
C
L
4.00
6.82
6.00
5.75
POWER SHORT
BRAKE MODE
®
6.00
.875 DIA. 2 PLCS. FOR 1/2 CONDUIT
3.75
WA RNER ELECTRIC
TCS-200-1H
C
L
1.00
4.00
5.75
TENSION
ADJUSTMENT
6.82
TCS-200-1H with Heat Sink
Figure 1a
POWER SHORT
WA RNER ELECTRIC
TCS-200-1
TENSION
ADJUSTMENT
6.00
®
BRAKE MODE
1.25
3.00
7.50
.31 Dia.
6 Warner Electric • 800-825-9050 P-2003-2 • 819-0420
CS-200-1 Figure 1b
1.25
3.00
.875 DIA. 2 PLCS.
2.87
o 7. Do not attempt to incorporate
TB2
TB2
GNDGND
external switching schemes between two or more brakes and the TCS-200-1 output. This will damage the control and void the warranty.
o 8. Do not attempt to wire two or more controls in
parallel.
TCS-200-1 Series Controls Wiring
Refer to Figure 2 for actual wiring connections.
o 1. Unlatch the front cover of the TCS-200-1.
o2. Connect one of the jumpers to terminals 5
and 6 of terminal block TB2 and discard the spare jumper.
o 3. Connect the 230 VAC power to terminals 4
& 8 of terminal block TB2. Secure the terminal screws.
o 4. Connect an earth ground wire between
terminal 9 of terminal block TB2 and an unpainted metal surface of the control panel to ensure a good ground connection. Secure the terminal screw. Make sure the panel itself is properly grounded.
Power
Determine if 115 VAC or 230 VAC will be used to power the control and proceed to that section of this manual.
Insure power is off and disconnects open on the control panel before connecting the AC input. Failure to do so can result in damage to equipment and injury or even death to personnel.
115 VAC
Refer to Figure 2a for 115 VAC power input connections.
o 1. Connect the 115 VAC power to terminals 4
& 8 of terminal block TB2 located in the base of the TCS-200-1 enclosure. Secure the terminal screws.
o 2. Connect an earth ground wire between
terminal 9 of terminal block TB2 and an unpainted metal surface of the control panel to ensure a good ground connection. Secure the terminal screw. Make sure the control panel itself is properly grounded.
FACTORY INSTALLED JUMPERS
1
2
3
NEUTRAL
4
5
6
7
8
9
115 VAC
HOT
INSTALL JUMPER
1
2
3
NEUTRAL
4
5
6
7
8
9
230 VAC
HOT
a. 115 AC Power Wiring b: 230 VAC Power Wiring
Figure 2
Note: Do not apply power to the system at this point.
Brake
Determine the type of brake to be used with this control and proceed to that section of this manual.
Insure connections are tightly secured. Intermittent connection will cause the control to shut down and output current to the brake will be removed.
Electro Disc Tension Brake
230 VAC Input
Refer to Figure 2b for 230 VAC power input connection.
o 1. Remove the factory installed jumpers from
terminals 4 & 5 and 6 & 7 of terminal block TB2 located in the base of the TCS-200-1 enclosure.
Warner Electric • 800-825-9050 P-2003-2 • 819-0420 7
Refer to Figure 3a for the Electro Disc Tension Brake wiring connections.
o 1. Connect the red wire from one brake
magnet to terminal 1 of terminal block TB2 of the TCS-200-1. This becomes the sense magnet.
Loading...
+ 15 hidden pages