GENERAL
GFI CIRCUIT PROTECTION - To minimize danger from possible sustained electrical arcing due to damaged or improperly
installed heating cable, and to comply with agency certifications and the National Electric Code (Article 427) - Ground Fault
Equipment Protection must be used on each heating cable branch circuit. Arcing may not be stopped by conventional circuit
protection. Contact a qualified electrician for installation if GFI is not available.
WARNING:
ELECTRIC SHOCK AND/OR FIRE HAZARD. If cable is damaged, remove from service. Do not attempt to repair. There are no user
serviceable parts. Replace damaged cable with new assembly.
KEEP INSTRUCTIONS FOR FUTURE REFERENCE.
IMPORTANT NOTES ON CABLE SELECTION
• For any “non-Standard” installations please contact Warmup at (888) 927-6333 (US) or (888) 592-7687 (Canada).
• We assume a minimum ambient temperature of 0°F and a thermal insulation of thick fiberglass wrap or equivalent.
For protection to -20°F minimum ambient use 1” thick fiberglass wrap or equivalent.
• Add 1 foot of heating cable for every valve or spigot in the pipeline - make sure to apply this extra cable at each valve/
spigot when installing.
• If your selected cable length is longer than your pipe length, spiral the cable evenly along the length of pipe.
• NAMSRK has a 5W/lin ft output. Ensure all metal pipes get 5W/lin ft.
• For 2” pipes and each 2” in diameter, double the output.
• Por plastic pipes, consider 25% more heat required.
Code Length in ft Voltage
Power output on pipe at 40°F
(5°C) in W
Power output on pipe at 50°F
(10°C) in W
Power output in ice & snow at 32°F
(0°C) in W
NAMSRK-6FT 6 110-120 36 30 60
NAMSRK-12FT 12 110-120 72 60 120
NAMSRK-18FT 18 110-120 108 90 180
NAMSRK-24FT 24 110-120 144 120 240
NAMSRK-50FT 50 110-120 300 250 500
NAMSRK-75FT 75 110-120 450 375 750
NAMSRK-100FT 100 110-120 600 500 1000
SPECIFICATIONS
Service voltage 110-120V
Normal cable width (in/mm) 0.42 (10.6)
Normal cable thickness (in/mm) 0.23 (5.8)
Cable bus wire gauge (AWG) 16
Cold lead length (in/mm) 30 (762)
Min. Circuit breaker size (Amps) 15
Max. Exposure Temperature 185°F (85°C)
Electrical classification Nonhazardous
Nominal Power Output Chart