WarmlyYours WRM1301 Specifications

Page 1
Floor Heating Application
Electrical Install Kit with Conduit Installation
TOOLS REQUIRED (NOT SUPPLIED)
Hammer
Screw Driver
Wood Chisel
Nails
KIT ITEMS (ROUGH-IN-KIT-03)
4”x4”
Dual Gang Box
1/2” Single Gang
Mud-Ring
Protector
Plate
6’ Flexible
Conduit
2 pcs.
This kit contains enough conduit for protection of line voltage wires and sensor wires.
PLEASE CONSULT YOUR LOCAL CODE AUTHORITY FOR REQUIREMENTS.
1. Have an electrician supply power to the thermostat box location with a dedicated, 20 Amp 120V or 240V circuit (determined by the voltage of the product ordered), controlled by a non-GFCI breaker.
2. Place the 4”x4” dual gang box against a stud, approximately 50 inches above the oor. At this time, it is important to know the thickness of the drywall that will be installed. The box needs to be mounted so that the raised portion of the single-gang mud-ring that will be placed onto the box will be ush with the nal wall surface. Once that depth is determined, hammer two, box-mounting nails through the box into the stud. Break the tabs/knockouts at the applicable location of the box and insert the power supply wires and/or conduit into and through the conduit knock-outs.
ENT Tube
Conduit from Breaker Box
Drive Strap
Anti-Short
Bushing
4 pcs.
2 pcs.
Set Screw
Connector
2 pcs.
3. The sill plate or bottom plate of the wall may need to be notched with a wood chisel directly below the location of the thermostat to allow placement of the conduit for the coldlead and sensor (if required). There should be a conduit for the cold lead and a separate conduit for the sensor if the local code requires low voltage wires be protected by conduit.
Never run the sensor wire in the same conduit as the cold lead!
4. If conduit is required by the local code, install the approved conduit now between the thermostat box and the notch cut into the bottom plate at the base of the wall. Use approved conduit anchors and bushings to protect the cold lead wire and sensor wires as they are fed up the wall and into the thermostat box. The supplied conduit may need to be shortened at this time to t properly. Test the thermostat sensor with a digital ohm meter as described in the installation manual. If the sensor tests good, run the sensor wire up the other conduit and into the thermostat box. Install the oor sensor (if applicable) as shown in the instructions.
5.
1.
4.
3.
2.
Drive Strap
Anti-Short
Bushing
1.
Cold Lead
1.
2.
4.
3.
2.
5. Drive Strap
Black
Anti-Short
Bushing
1.
Sensor Wire
Black
Sensor
Wire
2.
PAGE 1 / 3
Installation Support •(800) 875-5285 • www.WarmlyYours.com
Page 2
Electrical Install Kit with Conduit Installation
5. Once the electric radiant heating system has been installed, test the system with a digital ohm meter as described in the installation manual. If the system tests good, run the cold lead up the conduit and into the thermostat box.
Floor Heating Application
Black
Yellow or Red
Black
Ground
Yellow or Red
Ground
6. Once the wires are run up to the thermostat box, install the cable protector plate so it covers the wires at the bottom plate. This will protect the wires from stray nails.
Drive Strap
Cold Lead
Floor Sensor
Floor Sensor
6/17/99
Protector Plate
SENSOR
Cold Lead
FLOOR HEATING SYSTEM
7. Place the smurf/ENT tube over the sensor wire to protect it from the high voltage wires.
8. Install the single gang mud-ring at this time. Verify that the drywall being used is 1⁄2” thick. If it isn’t, the mudring included in the kit will need to be replaced with a locally sourced mud-ring of the appropriate depth, that corresponds to the thickness of the drywall being used.
PAGE 2 / 3
Installation Support •(800) 875-5285 • www.WarmlyYours.com
Page 3
Floor Heating Application
Electrical Install Kit with Conduit Installation
Drywall
Fill with Mud over Mud-Ring
9. When the drywall is installed, the raised portion of the mud-ring mounted on the square box should be ush with the nished wall's face and ready for mud to be applied into the gap between the drywall and the mud-ring.
10. Make connections to line and load wires at the back of the thermostat. Place sensor wires into and through the top hole of the thermostat’s power base. Attach the sensor wires to the front of the thermostat’s power base.
11. Place the thermostat on the front of the white cover plate and line up all of the holes. Use the included screws to attach the power base and white cover plate to the silver mud-ring. Center and level the thermostat and then tighten the screws to hold the pieces in place. Install thermostat’s faceplate onto the power base.
Black
Red
Red
Black
Sensor
Wire
ENT
Tube
Ground
Black
Yellow(120V)
Red(240V)
Installation Support •(800) 875-5285 • www.WarmlyYours.com
PAGE 3 / 3
Loading...