WarmFlow COMBI 70, COMBI 90, KABIN PACK COMBI 90 Installation & Servicing Instructions Manual

INSTALLATION & SERVICING
MANUAL FOR
70/90
COMBI BOILER
&
70/90
KABIN PAK COMBI
LEAVE THESE INSTRUCTIONS WITH THE END USER
CERT. No. FM 29884
BS 5750 PART 2 ISO 9002
ISSUE 4 MAR ’03
SERVICING
To ensure continued reliable operation and
fuel economy it is recommended that the
boiler is serviced annually.
Warmflow Engineering Service division
provides an excellent back-up service,
operating a team of Oftec trained engineers
who can meet all the servicing,
commissioning and breakdown
requirements for your appliance.
Simply telephone
TEL: (028) 9262 0852
FAX: (028) 9262 0869
E-MAIL: service@warmflow.co.uk
COMMISSIONING
*THIS APPLIANCE MUST
BE COMMISSIONED
*Failure to commission this appliance may invalidate warranty
After commissioning ensure that the pre-paid warranty
registration card is filled in and returned.
BEFORE FITTING THIS BOILER THE
INSTALLER MUST CHECK:
1. What the maximum hot water demand is likely to be placed on the boiler. Not every installation is suitable for a Combi boiler. Systems requiring very high hot water flow rates may be better suited with an unvented cylinder.
2. That the mains are capable of supplying up to 24 litre/min with a minimum dynamic pressure of 1.8 bar at the boiler. This is to ensure that the boiler can achieve its maximum output.
3. The hardness of the mains water supply. Systems with hard water must be fitted with a suitable chemical scale preventer (eg Fernox Quantomat or Combimate alternatively contact Warmflow for further details).
4. That the flow from any one hot water outlet does not exceed the maximum recommended. This applies particularly to baths which are usually fitted with larger taps and larger bore supply pipes. It may be necessary to restrict the flow to these taps by reducing the bore of the supply pipework or by fitting a restrictor into the pipework.
5. That any outlet when opened does not starve all the other outlets of hot water. If more than one outlet is open at the same time then the total flow from all the outlets should not exceed the maximum flow rate of the boiler.
6. That any showers being supplied hot water by the boiler are compatible with this type of appliance.
It should be noted that the boiler has been factory fitted with an 18 litre/min flow restrictor.
The manufacturers guarantees are void if the appliance is not installed and commissioned in accordance with the recommendations made herein.
Page 1
Contents Page
1.0 User Instructions ................................................................................................................. 3
1.1 Introduction .................................................................................................................4
1.2 General Requirements ................................................................................................ 4
1.3 Components................................................................................................................ 5
2.0 Technical Details.................................................................................................................. 7
2.1 Sequence of Operation Flow Chart............................................................................. 7
2.2 Baffles ......................................................................................................................... 8
2.3 General Requirements ................................................................................................ 8
2.4 Dimensions ................................................................................................................. 9
2.5 Combi Flue Options .................................................................................................. 10
2.6 Technical Data .......................................................................................................... 13
3.0 Electricity Supply............................................................................................................... 14
3.1 RDB Burner Control Box ........................................................................................... 14
3.2 Fitting a Room Thermostat ....................................................................................... 14
3.3 Combi Wiring Details ................................................................................................ 15
3.4 Kabin Pak Combi Wiring Details ............................................................................... 17
3.5 Frost Thermostats ..................................................................................................... 19
3.6 Timers for Standard Combi ....................................................................................... 20
3.7 Timers for Kabin Pak Combis ................................................................................... 22
4.0 Oil Supply ...........................................................................................................................23
4.1 One Pipe System ...................................................................................................... 23
4.2 Two Pipe System ...................................................................................................... 24
4.3 De-aerator System .................................................................................................... 24
4.4 One Pipe Lift ............................................................................................................. 25
5.0 Flues .................................................................................................................................. 26
5.1 Conventional Flues ................................................................................................... 26
5.2 Low Level Discharge/Low Level Balanced Flues Terminal Position ......................... 26
6.0 Air Supply for Combustion and Ventilation.....................................................................28
6.1 Open Flue Boilers ..................................................................................................... 28
6.2 Balanced Flue Boilers ............................................................................................... 28
6.3 Installation of Flues ................................................................................................... 29
7.0 Thermostat Control Knob Peg Setting............................................................................. 31
8.0 Installation .......................................................................................................................... 32
8.1 Hearth .......................................................................................................................32
8.2 Service Access.......................................................................................................... 32
8.3 Heating System......................................................................................................... 32
8.4 Domestic Hot Water .................................................................................................. 34
8.5 Removal of Flow Restrictor ....................................................................................... 34
8.6 Fitting a Vertical Flue Adaptor ................................................................................... 35
8.7 Installation of Air Intake Duct .................................................................................... 35
9.0 Burners ...............................................................................................................................36
9.1 RDB Burner............................................................................................................... 36
9.2 Oil Supply.................................................................................................................. 36
9.3 Electrical Connections .............................................................................................. 37
9.4 Electrode Setting....................................................................................................... 37
9.5 Burner Start-up Cycle ............................................................................................... 37
10.0 Commissioning and Servicing ......................................................................................... 38
10.1 Commissioning ......................................................................................................... 38
10.2 Servicing ...................................................................................................................38
11.0 Horstmann 626 Electronic Programmer ..........................................................................39
12.0 Fault Finding ...................................................................................................................... 44
12.1 Central Heating ......................................................................................................... 44
12.2 Domestic Hot Water .................................................................................................. 45
12.3 Burner ....................................................................................................................... 46
13.0 Spares ................................................................................................................................. 47
13.1 Riello RDB Burner..................................................................................................... 47
13.2 Pipe Spares .............................................................................................................. 48
13.3 Short Parts List ......................................................................................................... 49
Page 2
1.0 User Instructions
1.0.1 Boiler Control Thermostat
The boiler control thermostat is located on the front of the boiler facia panel and may be adjusted from 52°C to 85°C. The recommended minimum thermostat setting is 65°C. Below this ‘cold water corrosion’ is likely to occur thus reducing the life of the heat exchanger and is not covered by the manufacturer’s warranty. When using hot water only it is recommended that the boiler control thermostat is switched to the off position.
1.0.2 Mains Indicator
The green mains light will be lit when there is power to the control panel.
1.0.3 H/L Reset
The yellow H/L reset lamp will be lit when the high limit thermostat has tripped at its set temperature of 110°C. This cuts off power to the burner and may indicate that there is a fault in the heating system. The high limit thermostat has a manual reset button located underneath the control panel in line with the control thermostat. Once the temperature has fallen and the reset button has been pressed the boiler should restart. If the high limit thermostat continues to trip contact your service engineer/technician.
1.0.4 Lock Out
The red lock out lamp will be lit when the burner has failed and can be reset by pressing the illuminated red reset button on the burner control box. If there is power and the thermostat is calling for heat and the burner has been reset it will go through its start up cycle. If the burner again fails to fire this would indicate a burner fault or oil supply problem (oil supply problems are not covered by manufacturers warranty).
1.0.5 Tank Control Thermostat
Located on the right hand side of the control panel the tank control thermostat controls the temperature in the thermal store. The temperature is adjustable up to a maximum of 80°C. A peg has been fitted to the rear of the knob to prevent the temperature being set too high. To change the setting see page 31.
1.0.6 Tank Limit Thermostat
Located inside the control panel the tank limit thermostat is a thermal resetting device controlling the on/off operation of the burner in hot water mode.
1.0.7 Hot Water and Central Heating On/Off Switch
Both hot water and central heating operations can be controlled via these switches. However it should be noted that when both switches are in the ‘on’ position hot water will have priority. In addition whenever a timer or programmer is connected to the boiler one or more of these switches may be bypassed.
1.0.8 Pressure Gauge
The pressure gauge fitted to the front of the control panel measures system pressure. The pressure should be set at 1 bar when the boiler is cold. As the boiler heats up, the pressure will rise but should not exceed 3 bar.
1.0.9 Servicing
It is recommended that the boiler is serviced annually by an OFTEC registered engineer.
Page 3
1.1 Introduction Note: All our domestic appliances have been independently tested and accredited
as exceeding the minimum SEDBUK efficiency levels required for its type, in compliance with the Building Regulations Approved Document L1 2001 for England and Wales and the Building Standards (Scotland) Regulations 2001 Part J.
The Warmflow oil fired ‘Combi’ boiler and Kabin Pak Combi are suitable for sealed central heating systems and can provide at mains pressure domestic hot water without the use of a cylinder.
The Warmflow oil fired combis are designed to burn Class C2 (28 sec redwood) kerosine or Class D (35 sec redwood) gas oil. However to comply with building regulations only kerosine may be burned when using the low level balanced flue or low level conventional flue.
As standard the appliance is fitted with a system expansion vessel, circulating pumps, filling loop, pressure gauge and safety valve. An optional 7-day electronic programmer is also available.
The pressure jet oil burner is covered by the manufacturer’s parts and labour warranty valid for one year (from the boiler date stamp). The boiler and heat store are covered by a manufacturer’s warranty of 5 years (from the boiler date stamp) but does not include burner, labour, handling or shipping. Details of any extended warranties are contained within the installation pack.
Optional extended guarantees, for the appliance covering parts and labour of up to 5 years initially are also available (although not applicable to the Republic of Ireland).
The manufacturer’s guarantees are void if the appliance is not installed and commissioned in accordance with the recommendations made herein.
1.2 General Requirements
The installation of the boiler must be in accordance with the following regulations.
BS5410 : PART 1 : 1997 Code of practice for oil firing. BS5449 : PART 1 : 1997 Forced circulation hot water systems. BS7593 : 1992 Treatment of water in domestic hot water central heating systems.
Current Building Regulations: Part J England and Wales
Part F Scotland Part L Northern Ireland
Current IEE Regulations:
BS7074 : PART 1 : Application Selection & Installation of Expansion Vessels
The heating system should be installed by a competent installer in accordance with the recommendations laid down by HVCA, OFTEC and a sound engineering practice.
In order to comply with GB building regulations OFTEC forms CD10 for installations and CD11 for commissioning should be left with the customer.
Page 4
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
1.3 Components
1.3.1 Combi Assembly
1. Automatic Air Vents
2. Boiler Heat Exchanger
3. Boiler Control and Limit Stat
4. 12 Litre Esxpansion vessel
5. Boiler Data Plate
6. RDB Burner
7. Boiler Drain Valve
8. Pressure Relief Valve
9. Strainer
10. Filling Loop
11.Tank Control and Limit Stat
12. Flow Switch
13. Mixer Valve
14. Plate Heat Exchanger
15. CH Pump Head
16. DHW Pump Head
17. Pump Gate Valves (x3)
18. Tank Drain Valve
1.3.2 Combi Control Panel
BLANKING
PLATE
CH ON/OFF SWITCH
TANK CONTROL
THERMOSTAT
MAINS ON LAMP (GREEN)
HIGH LIMIT TRIPPED LAMP (YELLOW)
BURNER LOCKOUT LAMP (RED)
SYSTEM
PRESSURE
GAUGE
DHW
PUMP
BOILER
CONTROL
THERMOSTAT
CH
PUMP
HIGH LIMIT THERMOSTAT RESET (UNDERNEATH)
Page 5
1
2
3
4
5
6
7
8
9
10
11 12 13 16 17 18
20
19
22
21
24
23
14 15
1.3.3 Kabin Combi Assembly
1. Flue Terminal Guard
2. Low Level Flue
3. Service Access Hatch
4. Control Panel Cover
5. Controls
6. Pressure Vessel
7. Control Panel Flap Lock
8. Control Panel Flap
9. Door Panel
10. Burner Reset
11. Burner Reset Button
12. Burner
13. Return Connection
14. DHW Pump
15. CH Pump
16. Cable on Oil Line Grommets
Note: To convert the Kabin Pak for use with a conventional flue use the Kabin Pak adaptor
(KPA).
1.3.4 Kabin Pak Combi Control Panel
17. Air Intake Grill
18. Pipe Access Hole
19. Plate Heat Exchanger
20. Mixing Valve
21. Side Panel
22. Pipe Entry Grommets
23. Auto Air Vent
24. Pressure Relief Valve
Mains On (Green)
High Limit (Yellow)
Burner Lockout (Red)
CH Pump
DHW Pump
Boiler Control
Thermostat
DHW ON/OFF
Switch
CH ON/OFF
Switch
High Limit
Thermostat Reset
Tank Control
Thermostat
System
Pressure Gauge
Page 6
2.0 Technical Details
2.1 Sequence of Operation Flow Chart
YES
NO
YES
DHW
Tank Stat
Satisfied
Flow
Switch
Closed
Timer
Calling For
Heat
Power
On
DHW
Pump Only
Runs
HW
Limit Stat
Tr ipped
Burner
Fires
Burner
Stops
CH
Selected
Burner
Fires
CH Pump
Only Runs
Boiler
Stat
Satisfied
Boiler
Limit Stat
Tr ipped
YES
NO
YES
YES
NO
NO
YES
NO
YES
NO
NO
NO
YES
YES
HW
Selected
YES
NO
Room
Stat
Satisfied
NO
YES
Press Reset
Button
YES
NO
Boiler
Limit Stat
Tr ipped
Press Reset
Button
The boiler will have a DHW priority when both domestic hot water (DHW) and central heating (CH) are selected. So if the flow switch is closed or the heat store has not been satisfied the entire output of the boiler is directed to DHW before the boiler will switch over to CH. When fully cold it can take up to 20 minutes for the heat store to be satisfied.
After a draw-off of 120L at 24L/min, with an average temperature rise of 32°C, the thermal store has a recovery time of approximately 7 mins.
Note: If HW has not been selected no hot water can be
produced even if the heat store is up to temperature.
Page 7
2.2 Baffles
FRONT
Before firing make sure the baffles have not been dislodged in transit and are correctly positioned. To achieve maximum efficiency push the baffles in the direction of the arrows as shown.
2.3 General Requirements
1. The Warmflow Combi is supplied with all the necessary components for a sealed heating
system. However, on some larger systems with a total water content greater than approx 150L, an expansion vessel, in addition to the integral 12L vessel supplied, may be required.
2. The pressure relief discharge shall be positioned away from any electrical components.
No other valves should be positioned between the relief valve and the discharge, and the discharge pipe should not be used for any other purposes. The discharge pipe must be plumbed to an external drain in a position where the discharge can been seen but cannot cause any injury or damage.
3. Where there is a catastrophic loss of water from the system the boiler thermostats
may fail to operate which would result in serious damage to the appliance. To prevent this it is recommended that a low pressure cut out switch set at 0.2 bar is fitted to the system and wired in series with the boiler limit thermostat.
4. The boiler should be stored in a dry environment. No heavy objects should be placed
on top of the boiler. Where possible the boiler should be moved on its pallet or trucked from its rear. Manhandling the boiler by its casings will result in damage and must be avoided.
Page 8
1
8045
8000
8130
1620
1310
460
820
REAR VIEW
2 3 4
5
6
2.4 Dimensions
2.4.1 Combi Dimensions
2.4.2 Combi Boiler Connections
All dimensions are given in mm.
1. Cold Mains (15mm)
2. Heating Flow (22mm)
3. Domestic Hot Water (22mm)
4. Pressure Relief Discharge (15mm)
5. Spare Connection (1” BSP)
6. Central Heating Return (1” BSP)
MODEL
70/90
J
127
A
865B595C595D90E59F554G750H125
K
127L203
J
H
K
C
E
G F
D
B
L
A
Page 9
2.4.3 Kabin Pak Combi Dimensions
MODEL
70/90
J
371
A
892B732C636D373E188F191G376H172
102
712 MAX
225 MAX
175 MIN
490 MIN
Ø125
2.5 Combi Flue Options (not applicable to the Kabin Pak Combi)
Note: Low level flue options are rear or left hand outlet only.
2.5.1 ‘Easy Fit’ Telescopic Low Level Balanced Flue (BF-R)
The horizontal dimension can be increased up to an additional 1200mm using a combination of long extension pieces (E600 = 600mm) and short extension pieces (E300 = 300mm).
E
B C
FGJH
D
A
Page 10
2.5.2 ‘Easy Fit’ High Level Balanced Flue (HLBF)
The HLBF is available in 4 fixed horizontal lengths which are:
Option 1 – 455mm
Option 2 – 655mm
Option 3 – 585mm
Option 4 – 785mm
2.5.4 Standard Low Level Conventional Flue (LLF)
The factory supplied elbow may be extended up to 1m horizontally and 1.5m vertically by welding on additional pipe or by using vitreous enamelled flue pipe.
2.5.3 ‘Easy Fit’ Telescopic Low Level Conventional Flue (LLF-R)
102
792 MAX
155 MIN
540 MIN
Ø125
225 MAX
575
155 MIN
102
155x155
225 MAX
225 MAX
175 MIN
1128
SEE OPTIONS
160x160
Page 11
2.5.5 Easy Fit Telescopic High Level Balanced Flue (HLBF-R)
2.5.6 Easy Fit Vertical Balanced Flue (VBF)
EXTENSION KITS
AS REQUIRED
(PACKS C OR D)
PACK E OR F PACK E OR F
A
175 MIN 225 MAX
1570 MIN
2070 MAX
PACK A
PACK H PITCHED ROOF FLASHING (22" – 45" ADJUSTABLE)
PACK B VBF TERMINAL SECTION
EXTENSION KITS (PACK C OR D) AS REQUIRED MAX 2 NO PACK D
PACK A
675mm MIN
675mm MIN
PACK G FLAT ROOF FLASHING
PACK B VBF TERMINAL SECTION
MIN
435
560
735
MAX
610
860
910
A + E
A + F
A + C + E
FLUE PACKS
DIM A
ALL MODELS
MIN
860
1035
1160
1385
1510
MAX
1160
1210
1510
1560
1860
A + C + F
A + C + C + E
A + C + C + F
A + D + E
A + D + F
FLUE PACKS
DIM A
50/70, 70/90 & 90/120 MODELS ONLY
MIN
1340
1640
1940
2290
2590
2890
3240
MAX
1840
2140
2440
2740
3040
3340
3740
A + B
A + B + C
A + B + C + C
A + B + D
A + B + D + C
A + B + D + C + C
A + B + D + D
FLUE PACKS
FLUE HEIGHT
ALL MODELS
Note: When using a VBF or HLBF-R on a 120/150 or 150/200 model ensure that the
boiler is fitted with a RDB3 burner.
AVAILABLE FROM SPRING 2003
Page 12
2.6 Technical Data
Model
Nominal heat KW
Input Btu/hr
Nominal heat KW
Output Btu/hr
Efficiency at max output (net) %
Burner
Head
Flue mm
Size in
Max CO
2
%
Smoke
FGT at max output °C
Water resistance at 20°C T mbar
Approx fuel l/h
Flow rate gals/h
Nozzle make
(kerosine) size
Pump bar
Pressure psi
Nozzle make
(gas oil) size
Pump bar
Pressure psi
Dry weight kg
Primary water content L
Min inlet dynamic pressure bar
for max hot water flow psi
Max DHW flow rate achievable
(refer to page 1)
Factory set DHW flow rate
Min DHW flow rate
DHW temp rise °C
Pressure Relief
Heating flow
Heating return
DHW outlet
Cold water mains inlet (refer to page 1)
Ingress Protection
70/90 Combi
29.3
100,000
26.4
90,000
90
RDB 1
LD3
100 or 127
4 or 5
11.5-12.0
0-1
235
12.0
3.15
0.69
DANFOSS 60°S
0.75
8
116
DANFOSS 60°S
0.6
12
175
155
70
1.8
26
Unrestricted
24 l/min (5.3 gals/min) recommended
18 l/min (4.0 gals/min)
2.5 l/min (0.55 gals/min)
32°C @ 24 L/min for 120L draw off
3 bar (43.5 psi)
22 mm
1” BSP
22 mm
Unrestricted 15 mm bore (minimum)
IPX0
70/90 Kabin Pak Combi
29.3
100,000
26.4
90,000
90
RDB 1
LD3
Integral
Low Level
11.5-12.0
0-1
235
12.0
3.15
0.69
DANFOSS 60°S
0.75
8
116
DANFOSS 60°S
0.6
12
175
155
70
1.8
26
Unrestricted
24 l/min (5.3 gals/min) recommended
18 l/min (4.0 gals/min)
2.5 l/min (0.55 gals/min)
32°C @ 24 L/min for 120L draw off
3 bar (43.5 psi)
22 mm
22 mm Comp.
22 mm
Unrestricted 15 mm bore (minimum)
IP45
Page 13
3.0 Electricity Supply
220 - 240V. 1PH, 50 Hz
The boiler/burner and other external electrical equipment should be wired via a fused double pole isolating switch which should be fitted with a 5 amp fuse.
In order to ensure the safety of the Kabin Pak Combi Warmflow recommends that power to the appliance is supplied through a suitable CE approved RCD trip switch.
The appliance must be effectively earthed and all external wiring should comply with current IEE Regulations. It is the responsibility of the installer to ensure that the appliance has been properly earthed.
3.1 RDB Burner Control Box
CONTROL BOX
535SE/LD
M
M
Oil Valve
Photoresistance
Black White Blue
Motor
Capacitor
Lock Out
Live
Neutral
Earth
Fan
Housing
3.2 Fitting a Room Thermostat
Remove the purple wire from no 5 and no 28 on the PCB and wire the thermostat as shown. The room thermostat should be located where it is not subjected to extraneous heat gains, direct sunlight or draughts.
ROOM THERMOSTAT
282726
PCB
N
5
29 30
Page 14
3.3 Combi Wiring Details
3.3.1 Wiring Diagram
P– Purple
O– Orange
Y– Yellow
R– Red
W– White
BR – Brown
BL – Blue
B– Black
G/Y – Green/Yellow
Page 15
3.3.2 Combi Wiring Schematic
BREAK INTO THE WHITE
WIRE BETWEEN NO 16 ON
THE PCB AND THE LIMIT
STAT AND CONNECT IN THE
PRESSURE SWITCH WITH A
WIRING BLOCK AS SHOWN
Page 16
3.4 Kabin Pak Combi Wiring Details
3.4.1 Kabin Pak Combi Wiring Diagram
P– Purple
O– Orange
Y– Yellow
R– Red
W– White
BR – Brown
BL – Blue
B– Black
G/Y – Green/Yellow
GY – Grey
Page 17
3.4.2 Kabin Pak Combi Wiring Schematic
BREAK INTO THE WHITE
WIRE BETWEEN NO 16 ON
THE PCB AND THE LIMIT
STAT AND CONNECT IN THE
PRESSURE SWITCH WITH A
WIRING BLOCK AS SHOWN
Page 18
3.5 Frost Thermostats
3.5.1 Combi Boilers
The switched live from the frost thermostat (the frost thermostat must be supplied by a permanent live) should be connected to number 5 on the boiler terminal block. In order to protect the fabric of the building as well as the boiler and pipework, the thermostat should be located in the coldest part of the house but where it can respond to any temperature rise.
3.5.2 Kabin Pak Combi Boilers
As the boiler is supplied with a factory fitted frost thermostat all that is required is for a permanent live to be supplied to the control panel.
FROST THERMOSTAT
PERMANENT
LIVE
543 6
Page 19
3.6 Timers for Standard Combi
Note: Single channel timers or programmers are not recommended.
3.6.1 Installation of a remote two channel programmer (option 1)
Remove the purple wire connecting 5 and 28 and the white wire connecting 3 and 19.
Connect the programmer as shown via a fused isolator.
This bypasses the central heating and hot water on/off switch.
If the connection to terminal 12 is not made the mains on lamp is also bypassed.
A separate live supply to the boiler is not required. However a neutral and earth must be supplied to the boiler.
3.6.2 Installation of a remote two channel programmer (option 2)
Remove the purple, white and brown wires connecting the central heating and hot water on/off switches to the 6 pin male plug.
Connect the programmer as shown.
The mains is supplied via a fused isolator to the boiler 3 pin mains plug.
OFFOFFENL
COM
ON
22 21 20 19
PCB CONTROLLER
ON
COM
CH HW
26 25 24 2328 27
12 11
EARTH
POST
OFFOFFENL
COM
ON ON
COM
CH HW
1
2
3
4
5
6
EARTH
POST
Page 20
3.6.3 Installation of W armflow Optional Programmer (not applicable to the Kabin Pak
Combi)
1. Disconnect the electrical supply.
2. Remove top casing (4 studs) and control box cover (1 screw).
3. Remove 2 screws securing blanking plate/programmer bracket. Remove bracket and
blanking plate from the control panel.
4. Disconnect the blanking plate from bracket (2 screws).
5. Feed programmer harness through the hole in the bracket. The programmer is secured
to the bracket with 2 screws.
6. Disconnect the 6 pin plug from the CH and HW on/off plugs.
7. Connect the programmer 6 pin plug into the socket.
8. Locate the programmer into the hole in the facia and secure the bracket to the control
panel (2 screws).
9. Set the time switch on the rear of the programmer to ‘G’ or ‘P’ (see programmer
instructions).
10. Replace the control panel cover and reconnect electrical supply.
11. Operational instructions are included in this handbook. (Section 11, Page 27)
CONTROL PANEL
BLANKING PLATE
OPITIONAL
PROGRAMMER
BLANKING PLATE/
PROGRAMMER
BRACKET
Page 21
3.7 Timers for Kabin Pak Combis
Note: Single channel timers or programmers are not recommended.
3.7.1 Installation of a Remote Two Channel Programmer
ONOFF
COM
ENL
CH
ONOFF
COM
HW
5 3
RCD
LNE
BOILER MAINS PLUG
ISOLATOR TO BE
FITTED WITHIN
BOILER CASING
THE HW AND CH SELECTOR
SWITCHES ON THE BOILER
CONTROL PANEL SHOULD BE
LEFT IN THE OFF POSITION
BUT CAN BE USED AS
SERVICING SWITCHES TO
TURN THE BOILER ON EVEN
WHEN THE CLOCK IS OFF
Page 22
4.0 Oil Supply
1. Oil Tank
Steel tanks constructed to BS 799 Part 5 1987 should be painted on the outside only and mounted on piers to prevent corrosion. Plastic oil tanks are also available and can be suitable for installation at ground level. However, oil should never be stored in translucent plastic containers.
The tank outlet should be at a height to provide sufficient clearance to allow for proper maintenance of any isolation valve oil filter or water separator fitted.
2. The pipe from the oil tank to the burner should be run in copper, steel or aluminium
pipework. Galvanised pipe and fittings should not be used. The pipework should terminate close to the boiler and be fitted with an isolating valve and filter. It is also recommended that a remote sensing fire valve should be fitted to the oil line preferably before the oil line enters the building (BS5410 : PART 1). Where a fire valve is fitted to a Kabin Pak Combi the valve body must be situated at least one metre away from this appliance.
Depending on the position of the tank a two pipe system may be required. One and two pipe oil systems are shown below. As an alternative to a two pipe system a Tigerloop or other approved de-aerator. may be used.
4.1 One Pipe System
0.5 10 20
1 20 40
1.5 40 80
2
60
100
I.D.
8 mm
I.D.
10 mm
Head H
(m)
Total Maximum Pipe Length (m)
Note: Plastic oil level gauges may shrink when
exposed to kerosene thus allowing the ingress of water. Pump failures due to water contamination are not covered under the warranty.
WATER
SEPARATOR
20mm PER METRE SLOPE
Page 23
0.5 35
100
0.5 30
100
1
25
100
1.5 20 90
I.D.
8 mm
I.D.
10 mm
Lift H
(m)
Total Maximum Pipe Length (m)
2 15 70
3 8
30
3.5 6
20
4.2 Two Pipe System
4.3 De-aerator System
For maximum pipe length and lift contact de-aerator manufacturer.
DE-AERATOR MAY BE ABOVE OR BELOW BURNER AND MUST BE POSITIONED OUTSIDE
NON-
RETURN
VALV E
FILTER MAY BE POSITIONED OUTSIDE
DE-AERATOR Must be upright
FIRE VALVE SENSOR
FIRE VALVE
FILTER
SHUT OFF VALVE
‘T’ & TAP FOR DRAIN
PLASTIC TANK SHOWN
STEEL TANK ALSO SUITABLE
20mm PER METRE SLOPE
WATER
SEPARATOR
APPROVED SITE GAUGE
APPROVED SITE GAUGE
Page 24
4.4 One Pipe Lift
20mm PER METRE SLOPEAPPROVED
SITE GAUGE
WATER
SEPARATOR
Note: The pump vacuum should
not exceed a maximum of 0.4 bar. Above this gas is released from the oil thus leading to burner lock out.
Total Maximum Pipe Length (m)
0.5
35
100
0.5
30
100
1
25
100
1.5
20
90
2
15
70
3
8
30
3.5
6
20
Lift H
(m)
ID 8mm
ID 10mm
Page 25
5.0 Flues
5.1 Conventional Flues
The flue should be designed in accordance with the local bye-laws and the Clean Air Act. Draught stabilisers are not recommended for oil fired boilers. Sharp bends or horizontal runs should be avoided and the flue should terminate 2 feet (600 mm) above the ridge of the dwelling. Terminals which restrict the discharge or allow ingress of water should be avoided.
It is recommenced that when connecting to an existing masonry chimney a flexible stainless steel liner of the correct diameter should be used. The annular space must be sealed top and bottom and filled with insulation.
5.2 Low Level Convert/Low Level Balanced Flues T erminal Positions and Kabin Pak Flues
Attention should be given to the position of the flue discharge; we recommend the following guidelines be adopted.
1. The flue should not discharge beneath opening windows or within 2 metres of other accesses to the building.
2. The flue should not discharge near internal/external corners of the building where turbulent wind conditions could occur.
3. A terminal guard should be fitted at all times.
4. The terminal should not discharge over property boundaries.
5. Discharge into narrow passageways should be avoided.
6. The actual siting of the flue should be determined by the installer after consultation with the householder.
7. In positioning this flue the wind direction should be considered.
Installation in exposed positions is not recommended.
Page 26
Terminal Position Min Distance
A Below gutters, soil pipes or drain pipes 1000 B From a door, window or air vent 600 C Above ground, flat roof or balcony level 600 D Below eaves or balconies 1000 E From an internal or external corner 600 F From a terminal facing the terminal 600 G From a surface facing the terminal 600 HVertically from a terminal on the same wall 1500 I Horizontally from the terminal on the same wall 600 J Directly below an opening, air brick, window, etc. 600 K From a vertical drain pipe or soil pipe 1000
These are minimum dimensions and are only quoted as a guideline but they will
satisfy the requirements of all UK Building regulations.
Where the flue terminal is within 1 metre of any plastic material, such material
should be shielded from the effects of the combustion products of the flue.
Page 27
6.0 Air Supply for Combustion and Ventilation (see BS 5410)
6.1 Open Flue Boilers
When the boiler is sited in a cellar where the only access for combustion and ventilation air is at high level then the combustion air should be ducted to low level.
Combustion Air Supply
Boiler in Room
Boiler in Compartment
6.2 Balanced Flue Boilers in a Compartment
Air Supply for Ventilation
No Combustion Air Inlet required to Room
Page 28
6.3 Installation of Flues
OPTIONAL EXTENSION PIECES
Easy Fit Vertical
Balanced
Flue (VBF)
Easy Fit High
Level Balanced
Flue (HLBF)
Standard Low
Level Conventional
Flue (LLF)
Easy Fit Low Level
Conventional Flue
(LLF-R)
Easy Fit
Balanced Flue
(BF-R)
Easy Fit High
Level Balanced
Flue (HLBF-R)
RIELLO RDB BURNER
AIR INTAKE COVER
AIR INTAKE ADAPTER SPIGOT & GASKET
BOILER LID
CONVENTIONAL FLUE RING
HORIZONTAL FLUE ADAPTOR
FLUE TERMINAL
TOP PANEL
TEST HOLE PLUG
FLUE GASKET
OPTIONAL FLUE DRESSING RING
TOP PANEL BLANKING PLATE
Page 29
6.3.1 Installation of a Balanced Flue (BF-R, HLBF-R & VBF)
1. Make a suitable sized hole in the wall or ceiling for the flue kit. Add the dimensions given on pages 6 (Dimension G) and 8 (Flue Vertical Dimension). The cavities around the opening must be sealed and protected by a non-combustable sleeve.
2. Remove the top panel (kitchen and utility models) and the combustion chamber lid.
3. Remove the flue ring from the top of the boiler (3 screws) ensuring that any remaining silicone sealant has been cleaned away.
4. Carefully fit the inner and out seals to the flue adaptor.
Note: After fitting the seals to the flue smear them with soap or any suitable lubricant
which does not react with the silicone rubber.
5. Place the gasket correctly on the boiler and locate the flue adaptor over this, fixing it in position using the nuts and bolts provided. For BF-R side outlet options on white case boilers it will be necessary to manoeuvre the adaptor through the side panel before fixing it to the boiler after the blanking plate has been removed. Push boiler into position against the wall.
6. If fitting extension pieces ensure the seals are correctly fitted and lubricated before pushing through the wall and attaching to the flue adaptor.
Note: Any combination of short (300mm) and long (600mm) extension pieces for the
BF-R can be used up to a maximum additional length of 1200mm.
7. Slide the flue terminal into position with a twisting movement ensuring that it protrudes through the wall by a minimum of 175mm and a maximum of 225mm or through the roof by a minimum of 665mm.
8. Seal the gap between the flue and the wall both inside and out after which the protective basket must be fitted to the wall over the flue terminal.
9. After removing the air inlet cover fit the air intake adaptor spigot and gasket to the burner. Connect one end of the air duct to the flue and the other end to the air intake spigot on the burner. Both ends should be securely fastened with the jubilee clips.
10. The boiler is now ready to be connected to the plumbing, oil supply and mains electricity.
11. The baseplate of the Goldbird and Whitebird has been designed to allow the oil pipe and electric cable to pass unnoticed inside the unit from the rear of the installation. Alternatively the grommeted holes either side, towards the front of the baseplate, can be used.
12. A test hole for commissioning purposes has been provided on the boiler lid.
Page 30
6.3.2 Installation of Telescopic Low Level Conventional Flue
Installation instructions as per the balanced flue except there is only an inner seal, the burner does not require modification and there is no flexible hose to be fitted. In addition the low level flue should only protrude through the wall by a minimum of 155mm and a maximum of 225mm.
6.3.3 Installation of Standard Low Level Flue (LLF)
After cutting a hole in the wall place the flue in the hole. The flue must be a minimum of 155mm through the wall. Fit the steel elbow into the pressed ring on the boiler and the end of the flue kit. The elbow should then be sealed into both rings using high temperature silicone sealant or fire cement which may also be used in conjunction with glass fibre rope.
6.3.4 Installation of High Level Balanced Flue (HLBF)
Installation instructions as per the balanced flue except there are no seals involved as the flue is not telescopic. There are no extension pieces available for these units.
Note: When filling a HLBF to a Combi a new top panel with a larger cut out for the flue
is required.
7.0 Thermostat Control Knob Peg Setting
Tank
DECREASE
TEMPERATURE
SETTING
INCREASE
TEMPERATURE
SETTING
REAR VIEW
Page 31
8.0 Installation
The boiler installation must be in compliance with BS 5410 Part 1 1997 and the Building Regulations.
8.1 Hearth
The boiler hearth temperature is between 50
O
C and 85OC and should be stood on a rigid, non-porous, non-combustible base, which is not softened by warmth to comply with the Building Regulations.
8.2 Service Access
8.2.1 Combi
24" (600 mm) Clearance should be provided above and in front of the boiler to allow for routine servicing. If placed under a worktop ensure that the worktop is easily removed.
8.2.2 Kabin Pak Combi
The Kabin Pak Combi has been designed to allow fitting into a corner. However a minimum clearance of 600mm should be provided to the front and right hand side of the Kabin Pak to allow access for servicing.
8.3 Heating System
The heating system should be installed to HVCA current codes of practice.
Before installing the boiler the new or existing system should be thoroughly flushed to clear all sludge or other foreign matter such as solder, steel wool and copper fillings. We recommend that the system is cleaned out in accordance with BS 5449 and BS 7593:1992 using a suitable non-corrosive commission cleanser.
It is further recommended that a suitable corrosion inhibitor is added to the heating system, which will not damage the synthetic rubber membrane of the expansion vessel.
8.3.1 Air Vents
An automatic air vent complete with is own check valve is fitted to the top of the heat store and boiler heat exchanger. However it is recommended that another air vent is fitted at the highest point in the system.
8.3.2 Drain Cock
Drain cock(s) should be fitted to the lowest points in the system to enable the system to be fully drained. A drain cock has also been fitted to the heat store and boiler heat exchanger.
Page 32
8.3.4 Boiler Connections
All connections to the appliance should be made with compression fittings.
8.3.5 Additional Requirements for a Kabin Pak Combi
1. Although the Kabin Pak is manufactured from galvanised sheet it is recommended that after a period of weathering (approx 4-8 weeks) that the Kabin Pak is painted with a suitable primer and finish coat to prevent corrosion.
2. When using the Kabin Pak with the integral low level flue only 28 second redwood number 1 (kerosine) may be used in order to comply with building regulations. Suitable flue terminal positions are shown on page 27.
3. The boiler must be provided with a suitable well drained hard standing area to prevent the formation of pools of water in order to eliminate any risk to the service engineer or end user.
4. The boiler must not be serviced or the panels removed where there is a risk of the ingress off water.
5. Although the Kabin Pak has been weatherproofed to IP45 it should not be subjected to a jet of water from a hose or power washer.
8.3.6 Expansion Vessel
A 12 litre expansion vessel charged to 0.5 bar is supplied with the boiler. This can
accommodate a maximum system volume of approximately 150 litres. If this volume is exceeded an additional vessel will be required. Refer to BS 7074: Part 1 or BS
5449 for details of sizing. The values given in the table are for total system values which includes the primary water capacity. See page 4.
8.3.7 System Filling
As standard, a filling point complete with a filling loop has been included within the appliance. The temporary hose must be disconnected after filling. A system pressure when cold of 1 bar is recommended.
Water loss from the system as indicated by a reduction in pressure on the pressure gauge may be made up through the filling loop.
After filling, vent all air from the system. Ensure the caps on the automatic air vents are loose and bleed both circulating pumps.
VESSEL VOLUMES
0.5 2.1 4.2 6.3 8.3 10.5 12.5 14.6 16.7 18.7 20.8 22.9 25.0
1.0 2.7 5.4 8.2 10.9 13.6 16.3 19.1 21.8 24.5 27.2 30.0 32.7
1.5 3.9 7.8 11.7 15.6 19.5 23.4 27.3 31.2 35.1 39.0 42.9 46.8 25 50 75 100 125 150 175 200 225 250 275 300
INITIAL CHARGE
TOTAL
SYSTEM
VOLUME
Page 33
8.4 Domestic Hot Water
The mains water supply pressure must be less than 5 bar. If this pressure is exceeded a pressure reducing valve must be fitted. The final 600 mm of the mains supply pipe to the appliance must be in copper. The flow rate of water from individual taps is dependant on the number of outlets being operated together, as well as the length and size of pipework in the system and the mains supply pressure flow regulators.
Whenever a pressure reducing valve or any other device containing a non-return valve is fitted to the mains water supply pipe entering the boiler, it is recommended that a mini expansion vessel, suitable for use on potable water, is fitted between the device and the closed tap.
Although many of the DHW components are designed to resist lime scale formation, in areas of hard water it may still be necessary to fit an inline chemical water softener. For further information contact Warmflow and your local water company.
To ensure economic use, the pipe runs between the boiler and the taps should be as short as possible and insulated to reduce heat loss. For boilers that have to be sited remotely from the main point of use, there is likely to be very long pipe runs which can lead to excessive water usage and poor fuel efficiency. It is recommended that a pumped hot water return is used in order to improve HW reaction times. Contact Warmflow for details.
Note: An 18L/min flow restrictor has been factory fitted but can be easily removed if
required.
8.5 Removal of Flow Restrictor
FLOW SWITCH
FLOW RESTRICTOR
WASHER
Page 34
8.6 Fitting a Vertical Flue Adaptor
1. Remove the 2 self tappers connecting the flue main body to the Kabin Pak and lift off. It may be necessary to break the seal between the flue main body and the top of the flue pipe.
2. Ensure that the gap between the existing flue pipe and the top of the Kabin Pak is properly sealed with high temperature silicone sealant.
3. Once the flue main body has been removed fit the Kabin Pak adaptor (KPA) into position and secure with the 2 self tapping screws. A 5” conventional flue can now be attached.
8.7 Installation of Air Intake Duct
1. Cut a 4” hole through the wall, minimum 300mm above the ground.
2. Cut plastic vent tube to suit wall thickness and insert into the hole in the wall.
3. Remove plastic air inlet cover on the burner. Attach the air intake gasket and adapter to the burner using the screws supplied.
4. Attach one end of the flexible duct to the burner air intake adapter using 1 no 3” jubilee clip as supplied.
5. Feed the flexible duct through the plastic vent tube to the outside of wall and fix to the air intake duct using the remaining jubilee clip, cut the flexible duct to a suitable length ensuring adequate length for rotation of burner during removal.
6. Once the flexible duct is attached to the air intake duct, insert into the vent tube and fix it to the wall using appropriate fixings. Ensure the perforated side of the air intake duct is facing downwards.
Air Intake Duct
Jubilee Clip
Flexible Duct
Plastic Vent Pipe
Jubilee Clip
Page 35
9.0 Burners
9.1 RDB Burner
The burner is fitted with the correct nozzle and the pressure set. All that is further required before commissioning, is to connect the oil and electricity supply.
1. Pump 5. Air damper adjustment screw
2. Control box 6. Air tube connection (supplied with BF kit)
3. Reset button with lock-out lamp 7. Pump pressure adjustment screw
4. Flange with insulating gasket 8. Pressure gauge port
9.2 Oil Supply
The burner is supplied for use with a one pipe system. For use on a two pipe system, it is necessary to remove the return port plug and fit a small by-pass plug as shown.
1. Suction port
2. To nozzle
3. Pressure gauge port/air bleed
4. Pump pressure adjustment
5. Vacuum port
6. To hydraulic ram
7. Return port
8. By-pass plug
Page 36
Attention Before assembling or removing the nozzle,
loosen the screw (A) and move the electrodes away from the nozzle.
9.3 Electrical Connections
The boiler control equipment and the burner are provided ex works, it is only necessary to connect a 230V 50Hz supply in accordance with the electrical drawings.
9.4 Electrode Setting
9.5 Burner Start-up Cycle
~ 12s
Thermostat
Motor
Ignition transformer
Valve
Flame
Lock-out lamp
~ 12s
Normal Lock-out due to failure to light
~ 5s
Page 37
10.0 Commissioning and Servicing
10.1 Commissioning
Note:IT IS RECOMMENDED THAT AN OFTEC TRAINED AND REGISTERED TECHNICIAN
SHOULD BE USED.
IT IS THE RESPONSIBILITY OF THE INST ALLER TO ENSURE THAT THE BOILER IS PROPERLY COMMISSIONED. SEE BS 5410. FAILURE TO DO SO MAY INVALIDATE THE WARRANTY.
Combustion tests must be carried out using a Combustion Analyser. The pump pressure can be checked by fitting a manifold and a pressure gauge to the oil pump.
Before firing ensure that all the baffles are in place as they may have been displaced during transit as shown in on page 8. Set the boiler control to 80°C switch on, ensuring all controls are calling for heat. Typical burner settings and test data are shown in section 2.2.
Check the smoke reading, CO
2
content and flue gas temperature with the boiler up to temperature. Testing while the boiler is still relatively cold gives inaccurate results and leads to incorrect adjustments being made.
Where a balanced flue has been fitted ensure the air duct connecting the flue and burner has been properly connected before commissioning. On the Kabin Pak Combi refit the front door panel before doing a flue gas analysis.
To comply with GB building regulations OFTEC form CD11 should be completed and a copy left with the householder.
10.2 Servicing
10.2.1 General Requirements
It is recommended that the appliance is serviced annually by an OFTEC registered service technician in accordance with the recommendations laid out in OFTEC’s technical information book 2 – ‘Pressure Jet Appliances – Commissioning Requirements for Technicians’.
Additionally when servicing special attention should be paid to the condition of the oil nozzle, flexible oil line, fuel filter and lid and base insulation all of which will need to be replaced on a regular basis.
Note: Second year or other extended warranties will be invalidated if the appliance is
not serviced annually.
10.2.2 Kabin Pak Combis
1. The boiler must be provided with a suitable well drained hard standing area to prevent the formation of pools of water in order to eliminate any risk to the service engineer or end user.
2. The boiler must not be serviced or the panels removed where there is a risk of the ingress of water.
Page 38
P
123456LN
HEATING SUPPLYWATER
G
HORSTMANN TIMERS & CONTROLS Ltd: NEWBRIDGE ROAD, BATH.
626 OEM - WARMFLOW 220-250V 50Hz 5(2)A T.55
11.0 Horstmann 626 Electronic Programmer (not applicable to Kabin Pak Combi)
User Instructions
Note: Ensure selection switch on the rear of the
programmer is at the correct setting ‘G’ for HW only or HW and CH. ‘P’ for independent HW and CH.
The programmer is factory set at its mid-position.
The 626 Boiler Mounted Programmer is an electronic, 7 day central heating and hot water control; extremely reliable and easy to operate. Properly programmed it will help you save energy and create a comfortable environment in your home.
The 626 Electronic Programmer has the following features:
•3 ON and 3 OFF periods every 24 hours with a choice of different programmes for each day of the week.
Override programme options of AUTO, ALL DAY, 24 HOUR and OFF.
•A choice of HOT WATER and CENTRAL HEATING.
•A central heating ADVANCE button allowing an instant switch from ON to OFF, or from OFF to ON, without affecting normal settings.
Most of the control buttons on your programmer are dual purpose buttons.
They can be used as SET buttons for inputting time of day, ON/OFF times, etc, or as SELECT buttons for using the advance facility and choosing override programme options.
The diagram below can be used to identify the SET buttons, indicators and symbols referred to in the following sections of these instructions.
1. Set indicator.
2. Set positions.
3. Time-of-Day.
4. Day-of-Week indicator.
5. ON/OFF switch period symbol.
6. SET button.
7. Minus(-) adjust button.
8. Plus(+) adjust button.
9. ENTER button.
10. COPY button.
Page 39
Setting the Time of Day
Press the SET button so that the SET indicator is pointing to the CLOCK position on the front of the programmer. The DAY OF THE WEEK indicator will now flash.
Use the PLUS(+) or MINUS(-) buttons to move the DAY OF THE WEEK Indicator to the current day of the week. Numbers relating to the days of the week are printed along the top of the programmer display, i.e. 1 = Monday, 2 = Tuesday, etc.
Press the ENTER button. The TIME OF DAY will now flash.
Now use the (+) or (-) buttons to alter the display to the correct time of day, making sure that the AM/PM SYMBOL is also correct (see figure 4).
Note: By pressing and releasing the (+) and (-) buttons you advance
or retard the time in 1 minute steps. If you keep the button depressed the display will fast cycle and the time can be changed more rapidly.
Press the ENTER button and then use the SET button to return the SET indicator to the RUN POSITION.
Setting the ‘ON’ and ‘OFF’ Times
Note: The minimum ON/OFF time that can be set is TEN MINUTES.
The programmer already has a factory pre-set programme of ON/OFF times in its memory. These are based on the most commonly used settings and are as follows.
Monday to Friday:
1st ON: 7.00am 1st OFF: 10.00am 2nd ON: 12.00pm 2nd OFF: 12.00pm 3rd ON: 5.00pm 3rd OFF: 11.00pm
If these settings do not meet your own requirements then they can be easily changed as follows:
Press the SET button so that the SET indicator is in the position shown. The display will indicate ‘DAY’ and the DAY OF THE WEEK indiactor will now flash.
Use the (+) and (-) buttons to move the indicator to the day of the week you wish to change the times for. Press ENTER.
The display will now show ‘1 ON’ and the first ON time for that day will flash.
Saturday/Sunday:
1st ON: 7.30am 1st OFF: 11.30am 2nd ON: 12.00pm 2nd OFF: 12.00pm 3rd ON: 5.00pm 3rd OFF: 11.00pm
Page 40
Adjust the flashing time as required by using the (+) AND (-) BUTTONS THEN PRESS ENTER.
The display will now show ‘1 OFF’ and the first programmed OFF time for the day will flash.
This can be altered in the same way as the ‘1 ON’.
Follow the same procedure for the 2nd and 3rd ON/OFF times remembering to press ENTER after each change to the programme. If you do not wish to alter a particular time then simply press ENTER and the display will move on to the next ON/OFF time leaving the previous one unchanged.
When the 3rd OFF time has been entered the programmer will display the word COPY and the DAY OF THE WEEK indicator will flash (see figure 8).
You can now copy the ON/OFF times you have just input for one day onto any other days that you wish them to apply. This saves you having to separately programme days with identical switching times.
Use the (+) and (-) buttons to mov the DAY OF THE WEEK indicator to the next day that you wish the times to apply and press the COPY button, the display will indicate ‘IN’.
Continue in this way until the programme has been copied to all the days that you wish it to apply to.
When you have finished copying simply press ENTER. The word COPY will be replaced with ‘DAY’ and the DAY OF THE WEEK indicator will flash.
You can now programme those days that require different times to the ones that you have just copied by following the same procedure as described at the start of this section, parts (ii) to (v).
Note:Your programmer allows you to have up to three ON/OFF periods each day. If you do
not want to use all of these, a switch period can be cancelled by programming the ON operation the same time as the OFF operation, eg, 2nd ON at 12.00pm and 2nd OFF at 12.00pm.
The next diagram can be used to identify the SELECT buttons and indicators referred to in the following sections of this leaflet.
Page 41
1. Hot water ON indicator.
2. Central heating ON indicator.
3. Advance button.
4. Hot water programme select button.
5. Central heating programme select button.
6. Programme positions.
7. Central heating programme indicator.
8. Hot water programme.
Programme Selection
The following programmes can be selected for either HOT WATER by itself, CENTRAL HEATING by itself or HOT WATER and HEATING together.
AUTO
When AUTO is selected the programmer will switch ON and OFF according to the switching times held in the memory, i.e. up to three ON/OFF periods per day.
ALL DAY
When ALL DAY is selected the programmer will switch the system on at the 1st ON TIME and OFF at the 3rd OFF TIME.
24 HOUR
When 24 HOUR is selected the system remains on continuously, ignoring all time settings.
OFF
When OFF is selected the programmer clock continues to operate but the system remains off.
To select a programme for hot water press the HW PROGRAMME SELECT button until the HW (HOT WATER) PROGRAMME indicator is pointing to the required programme, eg AUTO.
To select a central heating programme follow the same procedure using the CH PROGRAME SELECT button.
Note: When HOT WATER or HEATING is switched to ON the relevant indicator light will be
illuminated.
Page 42
Using the Advance
The ADVANCE facility allows you to bring forward the next ON or OFF period without having to alter the programmed ON/ OFF times.
Press the ADVANCE button once and release. The word ADVANCE will appear in the display.
If the programmer was originally ON it will now switch OFF and stay OFF until the next programmed ON time.
The opposite will apply if the programmer was originally OFF.
In both cases the unit will then revert to the normal programme times.
If you wish to cancel the advance simply press the ADVANCE button again and the word ADVANCE will disappear from the display.
Note: The ADVANCE facility has no effect when the CH PROGRAMME indicator is in either
the 24 HOUR or OFF position.
Electronic equipment can, in exceptional circumstances be affected by electrical interference.
If your programmers’ display or switching programme becomes frozen or scrambled, or you wish to revert to the factory pre-set programme you can RESET your programmer by pressing the MINUS(-) adjust button and the ENTER/HW SELECT button together.
After using the RESET procedure you will need to re-programme the day and time of day plus any changes you wish to make to the factory pre-set programme.
Reserve Battery
Your programmer is fitted with a NON-RECHARGEABLE LONG LIFE battery which will maintain the programmed ON/OFF settings for a period in excess of two years.
This is more than sufficient to cover all the expected power interruptions during the life of the unit.
Heating Systems
Information for use with various systems is available on request from Warmflow on (028) 9262 1515.
Page 43
12.0 Fault Finding
12.1 Central Heating
NO
Switch on power,
set selectors for
CH on and DHW
off.
Set all controls to
call for heat.
Does the burner
fire?
Is lockout lamp on
burner or panel
lit?
Is high limit
thermostat lamp
lit?
Is there continuity across the boiler
stat connections
17 and 18 on the
PCB?
Is there continuity
across the
connections 28
and 30 on the
PCB?
Check power
from clock or
switch, check
wiring fuses and
mains supply.
Refer to burner
fault finding.
Press reset
button, replace if
necessary.
Check wiring, replace boiler
thermostat.
Check relay and
PCB, replace.
Do radiators get
hot?
Does boiler cycle on its thermostat?
Check all valves
are open and
pump is working,
check pressure,
check all air is
vented.
Check boiler
thermostat,
replace if
necessary.
HEATING IS
WORKING
NORMALLY
YES
YES
NO
NO
NO
NO
YES
YES
YES NO
YES
YES
NO
Page 44
12.2 Domestic Hot Water
Switch on power, set
selectors to CH off and
DHW on.
Is DHW pump working?
Is there continuity
across connection 20
and 21 on the PCB?
Check wiring, replace
tank thermostat.
Is there continuity
across 25 and 27?
Check wiring, replace
relay, replace PCB.
Check wiring, replace
pump.
Does burner fire? Do radiators get hot?
Check plumbing,
replace non-return
valve.
Refer to burner fault
finding.
Is lockout lamp on
burner or pump lit?
Does tank get hot?
Vent all air from system
pumps, ensure all
valves are open.
Press reset button,
replace limit thermostat.
Is high limit thermostat
lamp lit.
Does boiler shut down
when tank reaches
temperature?
Replace tank stat,
replace relay.
Check wiring, replace
tank limit stat.
Is there continuinity
across 23 and 22?
With tap closed, switch
the CH switch to on.
Check wiring, replace
relay, replace PCB.
Is there continuinity
across 22 and 16?
Do radiators get hot? Check CH fault finding.
Check power from
clock or switch, check
wiring, check fuses.
Does CH pump stop
when tap is opened?
Check flow switch,
check relay.
Is hot water produced
when tap is opened.
BOILER IS WORKING
NORMALLY
NO NO
NO
YES
NO
NO
NO
YES
YES
YES
NO
NO
NO
NO
YES
YES
NO
YES
YES
YES
YES
YES
Check mixer valve,
check plate heat
exchanger for blockage,
ensure all air is vented
from boiler.
YES
YES
NO
NO
NO
YES
Page 45
Does burner motor start?
YES
NO
START
Switch on electricity supply. Set all boiler controls and external controls to call for heat.
Burner operating satisfactorily.
Press reset button. Check for pump seizure. Faulty capacitor or faulty motor.
Check for correct fitting of photocell, or change photocell. Check there is oil in tank, all oil pipe valves are open, oil pipe and pump are purged of air. Check oil pump drive and oil pump. Check oil pump solenoid opens. Check wiring to solenoid coil. Check for kinks in flexible oil pipe. Check nozzle for blockage. Check fire valve.
Check pump solenoid is operating correctly. Check correct nozzle is fitted. Check pump pressure and air shutter setting. Check correct fuel is used. Check flue for blockage or inadequate draught.
Is flame stable?
Is flame established?
Is burner lockout lamp lit?
12.3 Burner
YES
NO
NO
YES
YES
NO
YES
NO
Is oil delivered to combustion chamber?
Clean reset or change electrodes, check ignition transformer and leads, check nozzle for damage or carbon build up.
Check motor wiring fuse, boiler control and limit thermostat. Check power supply.
Page 46
13.0 Spares
13.1 Riello RDB Burner
NO CODE 3748757 DESCRIPTION 16 3008654 Pump
17 3007162 ‘O’ Ring 18 3008653 Filter ‘O’ Ring 19 3003602 Connector 20 3005720 Flexible 21 3008644 Tube 22 3008876 Pressure Gauge 23 3000443 Joint 24 3008648 Coil 25 3008650 Motor 25 3002836 Motor 26 3008649 Protection 27 3008652 Control Box 535 RSE/LD 28 3008877 Lead Coil 29 3008879 Cover 30 3008878 Kit Seal
NO CODE 3748757 DESCRIPTION 1 3005787 Gasket
2 3006384 Flange 3 3008769 Cup-shaped Head 4 3007513 Electrode Assembly 5 3006552 Electrode Bracket 6 3008642 Nozzle Holder 7 3008643 Collar 8 3008794 High Voltage Lead 9 3008647 Air Damper Assembly 10 3008645 Fan 11 3008646 PE Cell 12 3007479 Capacitor 4
µF
12 3002837 Capacitor 4
1
/2µF 13 3007582 Needle Valve 14 3008651 Regulator 15 3000439 Pump Seal
Note: The 41/2µF capacitor is only suitable for use with the 3002837 motor and the 4µF capacitor is only suitable for use with the 3008650 motor.
Page 47
13.2 Pipe Spares
CH Pump to Boiler Flexible Pipe 2056
Plate Heat Exchanger to Boiler
Flexible Pipe 2057
Boiler to Pressure Vessel
Flexible Pipe 2056
Flow Switch to Strainer
Pipe 1999
From CH Pump
Pipe 1996
Plate Heat Exchanger to Boiler
Pipe 1997
Plate Heat Exchanger to Flow Switch
Pipe 1992
Hw Pump to Pipe Support
Pipe 1993
Plate Heat Exchanger to Mixer Valve
Pipe 1994
From Mixer Valve
Pipe 1995
All Combis All Combis All Combis
Std Combis Std Combis
All Combis All Combis All Combis
All Combis Std Combis
Flow Switch to Strainer
Pipe 2490
From Mixer Valve
Pipe 2491
From CH Pump
Pipe 2492
Kabin Pak Combis Kabin Pak Combis Kabin Pak Combis
Page 48
13.3 Short Parts List
Part Description Code
Flow Switch 1476
Tank & Boiler Control Thermostat 2131
Boiler Limit Thermostat 281
Tank Limit Thermostat 2126
Plate Heat Exchanger 599
Twin Head Grundfoss Pump 2130
Grundfoss 15/60 Pump (for replacement head) 602
3 Pole Relay 1827
Auto Air Vent C/W Check Valve 614
Pressure Relief Valve 2132
Filling Loop 2133
Pressure Gauge C/W Capillary 2169
Mixer Valve 1621
Low Pressure Switch 2270
Burner Reset Button Membrane R7627
PCB Controller MK4 2419
Frost Thermostat 2508
Conventional Flue Adaptor KPA
Air Intake Duct AID
12 Litre Pressure Vessel 2128
When ordering replacement casing panels it should be noted that due to the painting process there may be some variation in colour.
This manual is accurate at the date of printing but will be superseded and should be disregarded if specifications
and/or appearances are changed in the interests of continued product improvement.
Code 991
FOR PARTS, SERVICE &
WARRANTY CONTACT
FOR TECHNICAL ASSIST ANCE
CONTACT WARMFLOW ON
TEL: (028) 9262 1515
E-MAIL: technical@warmflow .co.uk
TEL: (028) 9262 1515
FAX: (028) 9262 2827
N IRELAND
service@warmflow.co.uk
TEL: (DUBLIN) 8416158
REP OF IRELAND
FAX: (DUBLIN) 8416614
TEL: (0161) 205 4202
ENGLAND,
FAX: (0161) 205 4818
SCOTLAND & WALES
Lisburn
Lissue Industrial Estate, Moira Road,
Lisburn, Co Antrim, N Ireland, BT28 2RF
Tel: (028) 9262 1515 Fax: (028) 9262 0869
E-mail: sales@warmflow.co.uk
Manchester
144 Bradford Road,
Manchester, M40 7AS
Tel: (0161) 205 4202
Fax: (0161) 205 4818
E-mail: sales@warmflow.co.uk
Dublin
Balbriggan Industrial Estate,
Dublin
Tel: (01) 841 6158
Fax: (01) 841 6614
Loading...