All HE-A-**-21 Electric Furnaces must use one of two chip codes based on applications
An AHS chip code: forced air space heating applications
WFMU chip code: make-up air applications.
If you have a chip code other than AHS or WFMU, please call factory for assistance.
Application
Forced Air Space Heating:
This model series is outlet warm air sensing only for non-heat pump applications. With a preset warm air
temperature, the electric elements modulate to maintain this preset temperature based on the sensing of
the supply sensor (ST). The CFM requirement will always have to be setup for full electric capacity.
Heat/cool conventional room thermostat applies
Make-Up Air Heating:
Fresh air code requirements and/or appliances which could
create unhealthy negative pressure within the building.
Building usage, people loading
Air environment within building
Fireplace
Larger kitchen vent hoods
Appliances, without sealed combustion
Single vent gas furnace or water heater
Forced exhaust systems - restrooms, bathrooms,
kitchens, etc.
DO NOT DESTROY THIS MANUAL. PLEASE READ CAREFULLY AND KEEP IN A SAFE
PLACE FOR FUTURE REFERENCE BY A SERVICE TECHNICIAN.
Drawings:
NH806, NH807, NH819, NS802, EC001, XX017
02/04/2014 NI804
Table of Contents
Configurator 1
Inlet Cabinets 2
General Comments 3
Application 4
Installation Requirements 6
Mechanical Installation 7
Electrical Installation 9
Setup or Programming 11
Operation Indicators 12
Handheld Analyzer/Laptop Software 13
Troubleshooting 13
Replacement Parts 15
Drawings Included:
NH806
NH807
NS802
EC001
XX017
02/04/2014 NI804
Configurator
HE-T-KW-CW
Type Cabinet Width
H, A, E, N 21 = 21”
(see below) 24 = 24”*
All models – ECM™ blower motor, setup selection of four cooling sizes, 50% continuous air (fan – on
setting). High efficient air circulation at about 50-watt.
H = Full WarmFlo capability with outdoor sensor. This provides warm air outlet temperature dial
selection and supply air ramp up with the decrease of outdoor temperature. This WarmFlo
feature definitely applies to heat pumps, but it is also the top of the line comfort for straight
electric, with air conditioning. The warm air dial suggested setting is 96° or 100° and the front
dial selects the rate of ramp up or temperature increase based upon outdoor. The “C” setting
will provide 114° warm air at 0° or 125° at -20° F outside. The ECM™ blower also ramps up
in speed as there is an increase in supply temperature or decrease in outdoor temperature.
Depending upon setup selection, the moderate heating blower speed could be as low as 60% of
full capacity and full capacity blower is only used below 30° outdoor.
Heat/cool conventional thermostat must be used in non-heat pump applications
Basic heat pump room thermostat must be used in all heat pump applications.
A = WarmFlo element modulation based upon a warm air set point and duct sensor. Heating blower
speed is installation setup per kW size. A higher CFM selection can be made if there is a desire
to “work” WarmFlo harder.
Heat/cool conventional thermostat applies.
E = Non-WarmFlo, 10, 15, or 20 kW built-in strip heat, direct function of roomstat W. Setup
selection determines nominal ECM™ motor speed. A thermostat “E” type function could be
used to jump to full speed.
N = Cabinet only, no electric elements or WarmFlo. This could typically be associated with an inlet
hydronics water coil. Control board includes a relay for pump, initiated with input W. Setup
selection determines heating blower speed. Cooling speeds and air conditioning interface are
the same as mentioned above.
Note: Two-speed and multi-function room thermostat can also be configured with this system by adding
WF-HP2 interface controller.
02/04/2014 1 NI804
Inlet Cabinets
Factory optional cabinets can be configured with this Electric Furnace. Typically these are designed for
upflow applications; however, the heat pump coil cabinet could be used in other positions.
Side Entry, Filter Cabinet
Return air can be ducted into either side, 15-⅜” x
19” cutout hole is provided with one filler plate.
Easy access door for checking and changing filter.
Adjustable rails are provided for standard 4” x 20”
x 20” pleated filter.
Filter examples include Honeywell 203721, BestAir
HW2020, or Grainger
Standard 1” filter (20” x 20”) – field installer could arrive at filter filler bracket for slip-in within the
provided rails.
Comment – The 3M MERV filter airflow resistance needs to be considered in duct design
calculations. Per specification information from 3M the static pressure drop across the 1”, Series
1000, MERV 11 filter is 0.2” SP.
Hydronics Coil and Cabinet
The inlet cabinet includes a water coil with
parameters shown. The return air connection must
be on a side which allows coil draw-through. The
cabinet can be reversed for either left or right side
entry. The inlet for this cabinet is sized for an
externally installed packaged return air filter cabinet
– typical 20” x 20” size.
1. Nominal or rated Btu/h, 50,000
2. Recommended CFM setup, 1100 min.
3. Inlet water 120° at 10 GPM minimum.
4. Expected outlet air temperature, 115°
Reduced CFM and/or inlet water temperature will
reduce Btu/h rating.
®
6B936.
02/04/2014 2 NI804
General Comments
Upflow/Downflow/Horizontal
The arrangement of refrigerant coil, hydronics coil, and built-in electric elements need to follow specific
air direction or airflow rules, but the orientation of this Electric Furnace is not critical.
For upflow and horizontal standard air conditioning applications; the A-coil is mounted at the blower
outlet with field provided plenum or AC manufacturer’s case coil.
All models contain GE ECM™ Series 2.3 blower motors. The special Electro Industries interface board
allows hookup for heat/cool conventional or basic heat pump room thermostat. Blower speed setup and
WarmFlo sensor control are separate for cooling and heating (unique).
The ECM™ motor provided in this unit has many features not available in a standard motor.
- Improved efficiency
- Constant CFM
- Soft start and stop
- Better humidity control
The provided ECM™ motor contains permanently sealed bearings and does not require oiling.
Utility Load Control
Provisions are included for the Utility Receiver to interrupt compressor and WarmFlo or strip heat. No
provisions for dual heat, add EE-5046.
Zone Controller/Dampers
When using models HE-A or HE-H Series there are no adverse electrical heat concerns associated with a
zone damper system. However, there may be an effect on the heat pump compressor due to potential
reduced airflow. The zone dampers themselves must be in the horizontal ducts after the WarmFlo duct
sensor and at least 12” downstream of the WarmFlo sensor.
The zone controller “HVAC equipment” terminal block simply connects to this unit’s control board as if
it was a room thermostat to this unit. If the various zone sizes produce high static pressure and reduced
airflow, the WarmFlo temperature sensing technology will reduce the electric elements automatically.
If the zone damper action has an adverse effect on the heat pump compressor, Electro has zone controller
staging interface for 2-speed heat pump application (WF-HP2, etc.).
Side by Side, with Gas Furnace or Other Dual Heat Arrangements
Add-on dual heat controller HP-5046 can simplify the wiring for dual heat.
For side by side ducting, a motor operated damper is required to isolate the return air between two
blowers. The operation of this motor damper can be controlled from the HP-5046.
Installation Setup
There are specific peg jumpers relating to cooling tons, heating kW, heat pump reversing valve logic, and
thermostat type. These must be properly evaluated and selected to match each installation.
The “setup or programming” section has all the detailed instructions and selection tables.
The WarmFlo controller also has various dial switch selections relating to duct temperature set point,
minimum warm air set point, HP compressor ODT shutoff temperature, and ramp up efficiency dial.
These are standard WarmFlo technology and setup requirements, if you’re not familiar with WarmFlo
controller study the HD320 WarmFlo information document, also in this package.
02/04/2014 3 NI804
NOTICE: When changing any setup jumpers, power down and up. ECM™ motor needs 240V power
and control power removed to reset and reread specific control lines. Open CB number 1 for 10 seconds.
Operation Instructions
The “Operation Indicators” section contains information relating to LED monitor lights, thermostat
sequences, etc.
Installation Checkout
Attached to this manual is a warranty certification and checkout procedure. This must be completed and
returned for warranty coverage. This is the responsibility of the contractor or company which “sold the
job” and is assuming responsibility to the end customer.
Warranty Statement
See the last page of this manual for detailed limited warranty coverage explanation.
Application
General
The configurator, previous page, details several product types. Re-verify nameplate on your received unit
to make sure it properly represents the product type you need for your installation/application.
The setup control board jumpers provide ECM™ blower motor speed flexibility to match the model and
your heat/cool size requirements.
This specific model series, HE-A-**-**
This model series is outlet warm air sensing only. With a preset warm air temperature, the electric
elements modulate to maintain this preset temperature based on the sensing of the supply sensor (ST).
The CFM requirement will always have to be setup for full electric capacity.
Make-Up Air Applications
Located on the WarmFlo board (logic controller) is a 40-pin microcontroller chip. On this chip is a white
sticker which indicates chip version (V2.3*) and chip code. This correct chip code for make-up air
applications is WFMU which has a specific temperature range options for make-up air applications.
Backup or Assist Wood Heating
This WarmFlo Electric Furnace is ideal for accompanying a wood heating system. The WarmFlo
technology and sensors will determine the Btu/h heating requirement of the building. If the wood warm
air is below the requirement, a small portion (or as required) of the electric elements will come on
automatically supplementing the wood heat.
Using a wood boiler with the water coil inlet option is an ideal arrangement.
If using a forced wood system, caution must be used when allowing the wood warm air to enter through
the ECM™ motor blower. The maximum temperature for the ECM™ motor is approximately 120° F.
1. All installation work must be performed by trained, qualified contractors or technicians. Electro
Industries, Inc., sponsors installation and service schools to assist the installer. Visit our web site at electromn.com for upcoming service schools.
WARNING
ALL ELECTRICAL WIRING MUST BE IN ACCORDANCE WITH NATIONAL ELECTRIC CODE
AND LOCAL ELECTRIC CODES, ORDINANCES, AND REGULATIONS.
WARNING
OBSERVE ELECTRIC POLARITY AND WIRING COLORS. FAILURE TO OBSERVE COULD
CAUSE ELECTRIC SHOCK AND/OR DAMAGE TO THE EQUIPMENT.
CAUTION
This unit can only be used for its intended design as described in this manual. Any internal
wiring changes, modifications to the circuit board, modifications or bypass of any controls, or
installation practices not according to the details of this manual will void the product warranty,
the CSA/us certification label, and manufacturer product liability. Electro Industries, Inc.,
cannot be held responsible for field modifications, incorrect installations, and conditions which
may bypass or compromise the built-in safety features and controls.
2. If this is a Dual Heat system, this product relates only to the addition to the furnace ducting system
external to the gas or oil force air furnace. The owner/ installer assumes all responsibility and/or
liability associated with any needed installation of the gas/oil furnace, fuel system, flue, chimney, etc.
Any instructions or comments made within this manual (or factory phone assistance) relating to the
gas/oil furnace are provided as comments of assistance and “helps” only.
CAUTION
This unit shall not be operated (either heating section or blower) until the interior of the
structure is completed and cleaned. This also means all duct work must be complete with
filter, etc. Both manufacturers’ warranties are void if this unit is operated during structure
construction.
CAUTION
Hazards or unsafe practices could result in property damage, product damage, severe personal
injury and/or death.
3. Remember, safety is the installer’s responsibility and the installer must know this product well
enough to instruct the end user on its safe use.
Safety is a matter of common sense - - a matter of thinking before acting. Professional installers have
training and experienced practices for handling electrical, sheet metal, and material handling
processes. Use them.
02/04/2014 6 NI804
Mechanical Installation
Clearances and Accessibility
Zero clearance is allowed on all sides for combustible materials. However, 36” should be allowed at the
front for operation, maintenance, and service.
To reduce the risk of rusting and appearance, do not install the unit directly on the ground or on a floor
that is likely to be wet. In such environments the unit must be elevated by use of a sturdy non-porous
material.
General Ductwork and Airflow Requirement
Design the airflow ductwork to meet the maximum operating airflow (CFM) for the kW and cooling ton
requirements (whichever is larger). This document does not provide installation and design information
for the ductwork external to this product. It is assumed this is being accomplished by a professional and
trained installer understanding ductwork design, airflow/static pressure resistance, and forced air
distribution systems. Key requirements information:
- Heating and cooling blower speed or minimum CFM is setup independently. See the “Blower
Speed Selection” to match the airflow capacity with the ducting design.
- The airflow distribution system shall be designed for a maximum of 0.5” SP. Ideally the design
should be set at 0.3” to 0.4” SP.
- The variable speed, ECM™ motor, is sensitive to inlet static pressure. In order for the motor to
arrive at the setup CFM (motor RPM adjust according to static pressure) the inlet must have a
minimum resistance of about 0.15 to 0.2. If you do not have return air ducting and you’re simply
allowing free return air circulation through a filter at this Electric Furnace inlet, you may need to
have a slight restriction in order for the blower motor to arrive at its setup speed.
- All transitions must have a slope of 30° to 45°. There shall be no 90° bends or surfaces causing
airflow bounce/eddy current.
- The manufacturer strongly recommends the return air entering the bottom (under the blower) of
the cabinet. For smaller kW and smaller cooling (10 kW or 2-ton) it is permissible to bring the
air in on either side of the 32” cabinet.
- Previous Specification Chart shows the minimum CFM associated with the kW. Again this is
setup as detailed in the “Setup or Programming” section.
- The cooling CFM is also selected but is not shown on the Specification Chart. In many cases the
airflow distribution system is probably designed to meet the cooling requirement.
- The room registers and individual 5” or 6 “ runs must also match the total setup or planned CFM
for this installation. Typically a 6” round and a typical room register is rated at 100 CFM.
- All distribution ducts (supply and return) must be sized for the setup or planned total CFM
requirement. The attached duct sizing chart shows various distribution duct sizes relating to their
ability to properly handle the stated CFM.
- Seal connections between this unit and ductwork, all ductwork connections, etc. as required to
reduce or eliminate air leakage. Sealing all connections will also reduce air noise.
Comment: The ECM™ motor efficiently relates to system static pressure. On one hand a minimum of
about 0.2” SP is required for the motor to adjust itself, but above 0.3” it begins to drain high current. For
information, consider (at 240):
1.0” SP – 3.4A
0.8” SP – 2.5A
0.5” SP – 0.9A
0.2” SP – 0.4A
Continuous Air – 0.25A
02/04/2014 7 NI804
Loading...
+ 18 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.