Wall Bracket Centrifugal Upblast Exhaust Maintenance Manual

Document 483966
Wall Bracket
Centrifugal Upblast Exhaust, Sizes 060-300
Installation, Operation and Maintenance Manual
Please read and save these instructions for future reference. Read carefully before attempting to assemble, install, operate or maintain the product described. Protect yourself and others by observing all safety information. Failure to comply with these instructions will result in voiding of the product warranty and may result in personal injury and/or property damage.
Item #1
Hardware List
Item #2
Item
Number
1
Qty. Fan Size Description
8 060-200
14 220-300
1/4 - 20 x 0.75” L Hex Bolt, Stainless Steel
Part
Number
415573
8 060-200
2
14 220-300
1/4 - 20 U Style Spring Nut, Black Phosphate Coated Steel
415244
Recommendations for Installation
Wall brackets have pre-punched 5/16 inch holes for mounting the bracket to the wall. Hole diameter may need to be increased depending on the anchor fasteners chosen by the installer. Quantity of fan-to-wall bracket fasteners vary by wall bracket size. Refer to ‘Included Hardware’ table above.
A
B
C
F
D
E
Concrete Anchoring
A. Concrete - 4 inch minimum wall
thickness. Minimum of 2,500 psi.
B. Expansion Wedge Anchors
- Min. of 3/8inch diameter
- Min. of 2inch engagement
- Use a washer under each nut
Timber Anchoring
C. Wood Timber - minimum nominal
thickness of 4 inch.
D. Lag Bolt
- Min. of 5/16 inch diameter
- Min. 2 inch of thread engagement
- Use a washer under each bolt head
Steel Anchoring
E. Structural Steel
- 1/8 inch thick or 12 ga min.
F. Self-Drilling Screw
- Min. size of #12
- Min. 1/2 inch of thread hangout
- Use a washer under each screw head.
Wall Bracket 1
Wall Opening Size
X
Caulk entire perimeter of wall bracket
Unit Size
060-070 17 12.5
080-130 19 14.5
099-160 22 17.5
140-160 26 21.5
180-200 30 25.5
220-240 34 29.5
300 40 35.5
Fan Curb Cap Size
(in.)
Maximum Wall Opening - X
Installation
(in.)
1. Cut an appropriate sized hole in the wall based on the ‘Wall Opening Size’ table above.
2. Locate the wall bracket in the desired installation position and check for potential unit clearance issues.
3. Using the anchoring guidelines on page 1, fasten the wall bracket to the wall. If mounting a size 240 or 300, ensure the sides of the wall bracket with the four U-nuts are on the top and bottom.
4. Caulk the perimeter of the wall bracket to ensure a watertight seal. See Figure 1. Shims or additional sealant methods may be needed for an uneven wall surface.
Figure 1
6. Lift the fan into place and orient the breather tube and drain/grease trough in a downward position as shown in Figure 2.
NOTE
Do NOT support the unit by the hoodband during installation.
Hoodband
Breather
Tube
Figure 2
7. Secure fan to the wall bracket using the supplied 1/4 - 20 hex bolts. You may need to use a drift, small screwdriver, or the supplied bolts to properly position the U-nuts.
8. Complete fan installation using the instruction manual provided with the fan.
Drain/Grease
Trough
5. If the installation requires a backdraft damper, it should be installed in the duct at this time.
483966 • Wall Bracket, Rev. 3, February 20212