WAGO 879-3000, 879-3020 User guide

WAGO Energy Meters (MID)
with Push-in-CAGE CLAMP® and Levers
879-3020 4PS 879-3000 4PU
User manual
Version: 052021V1.1
© 2021 Wago. All rights reserved.
Index
1 Safety instructions ......................................................................................................................................................................... 3
2 Foreword ....................................................................................................................................................................................... 5
3 Certificates .................................................................................................................................................................................... 6
4 Specifications ................................................................................................................................................................................ 7
4.1 Performance criteria ......................................................................................................................................................................... 7
4.2 Basic errors ....................................................................................................................................................................................... 8
4.3 Bluetooth specification ..................................................................................................................................................................... 8
4.4 M-bus communication specification ................................................................................................................................................. 8
4.5 Modbus/RS485 communication specification................................................................................................................................... 8
4.6 Dimensions
4.7 Wire connection
4.8 Connection diagram 879-3000 (4PU)
4.9 Connection diagram 879-3020 (4PS)
5 Installation .................................................................................................................................................................................. 12
6 Operation .................................................................................................................................................................................... 13
6.1 Display part 1 (MID relevant)
6.2 Display part 2 (MID relevant)
6.3 Display part 3 (non MID relevant)
6.4 Settings
6.5 Bluetooth
6.6 Button settings
6.6.1 Password ................................................................................................................................................................................... 16
6.6.2 Tariff .......................................................................................................................................................................................... 16
6.6.3 S0-Impulsausgang...................................................................................................................................................................... 16
6.6.4 Pulse type setting ...................................................................................................................................................................... 17
6.6.5 S0 Pulse width ........................................................................................................................................................................... 17
6.6.6 Modbus ID ................................................................................................................................................................................. 17
6.6.7 Modbus Baudrate ...................................................................................................................................................................... 18
6.6.8 Modbus parity ........................................................................................................................................................................... 18
6.6.9 M-Bus ID .................................................................................................................................................................................... 18
6.6.10 M-Bus baud rate ...................................................................................................................................................................... 18
6.6.11 Backlight .................................................................................................................................................................................. 19
6.6.12 Powerdown counter ................................................................................................................................................................ 19
6.6.13 Trip counter ............................................................................................................................................................................. 19
6.6.14 OBIS codes ............................................................................................................................................................................... 20
6.6.15 Combination Code (adjustable via Modbus, M-bus & Bluetooth) .......................................................................................... 21
7 Troubleshooting .......................................................................................................................................................................... 22
7.1 Errors / Diagnostics display
7.2 Technical support
Appendix 1 – Multi tariff function .................................................................................................................................................. 24
A1.1 How to switch between T1 und T2 A1.2 How to switch between T3 and T4
Appendix 2 - M-Bus ........................................................................................................................................................................ 25
A2.1 Communication via M-Bus A2.2 M-bus register map A2.3 M-Bus write registers
Appendix 3 - Modbus ..................................................................................................................................................................... 28
A3.1 Communication via Modbus A3.2 Modbus register map A3.3 Modbus write register
Appendix 4 - Bluetooth .................................................................................................................................................................. 35
A4.1 Bluetooth app A4.2 Connect the meter A4.3 Device page A4.4
Read meter data ............................................................................................................................................................................ 38
A4.5
Save meter data ............................................................................................................................................................................ 39
A4.6 Change settings
......................................................................................................................................................................................... 9
................................................................................................................................................................................. 9
................................................................................................................................................ 10
................................................................................................................................................. 11
............................................................................................................................................................ 13
........................................................................................................................................................... 13
..................................................................................................................................................... 13
............................................................................................................................................................................................ 14
......................................................................................................................................................................................... 14
................................................................................................................................................................................. 15
.............................................................................................................................................................. 23
............................................................................................................................................................................. 23
.................................................................................................................................................. 24
.................................................................................................................................................. 24
.............................................................................................................................................................. 25
....................................................................................................................................................................... 26
...................................................................................................................................................................... 27
........................................................................................................................................................... 28
..................................................................................................................................................................... 29
..................................................................................................................................................................... 34
................................................................................................................................................................................ 35
.......................................................................................................................................................................... 36
.................................................................................................................................................................................... 37
.............................................................................................................................................................................. 40
Wag - 4PU & 4PS - 3
1 Safety instructions
Information for your own safety
This manual does not contain all of the safety measures for operation of this meter because special operating conditions, local code requirements or local regulations may necessitate further measures. However, it does contain information which must be adhered to for your own personal safety and to avoid material damage. This information is highlighted by a warning triangle with an exclamation mark or a lightning bolt depending on the degree of actual or potential danger:
Qualified personnel
Installation and operation of the device described in this manual may only be performed by qualified personnel. Only people that are authorized to install, connect and use this device, who have the proper knowledge about labeling and grounding electrical equipment and circuits and can do so in accordance with local (safety)regulations, are considered qualified personnel in this manual.
Use for the intended perpose
This device may only be used for the application cases specified in the catalog and the user manual and only in connection with devices and components recommended and approved by Wago.
Proper handling
The prerequisites for perfect, reliable operation of the product are proper transport, storage, installation and connection, as well as proper operation and maintenance. During its operation certain parts of the meter might carry dangerous voltages.
Only use insulated tools suitable for the voltages this meter is used for.
Do not connect while the circuit is connected to a power or current source.
Only place the meter in a dry environment.
The meter is intended to be installed in a Mechanical Environment ‘M1’, with Shock and Vibrations of low
Do not mount the meter in an explosive area or exposed to dust, mildew and/or insects.
Make sure the used wires are suitable for the maximum current of this meter.
Make sure the AC wires are connected correctly before activating the current/voltage to the meter.
Warning
This means that failure to observe the instruction can result in death, serious injury or considerable material damage.
Caution
This means hazard of electric shock and failure to take the necessary safety precautions will result in death, serious injury or considerable material damage.
significan- ce and Electromagnetic Environment ‘E2’, as per 2014/32/EC Directive. The meter is intended for indoor use. The meter shall be installed inside a suitable IP rated enclosure, in accordance with local codes and regulations.
4- 4PU & 4PS - Wago
Do not touch the meter’s connection clamps directly with your bare hands, with metal, blank wire or
other conducting material as you will risk an electric shock that could cause possible injury, serious injury or death.
Make sure the protection covers are replaced after installation.
Maintenance and repair of the meter should only be carried out by qualified personnel.
Never break any seals (if present on this meter) to open the front cover as this might influence the functionality
or accuracy of the meter, and will void all warranty.
Do not drop, or allow physical impact to the meter as there are high precision components inside that may
break and affect the meter measurement negatively.
All clamps should be properly tightened.
Make sure the wires fit properly in the connection clamps.
If the wires are too thin it will cause a bad contact which can spark causing damage to the meter and its
surroundings.
Exclusion of liability
We have checked the contents of this manual and every effort has been made to ensure that the descriptions are as accurate as possible. However, deviations from the description cannot be completely ruled out, so that no liability can be accepted for any errors or omissions in the information given. The data in this manual are checked regularly and the necessary corrections will be included in subsequent editions. If you have any suggestions, please do not hesitate to contact us.
Wago - 4PU & 4PS - 5
2 Foreword
Although we produce the Push-in-CAGE CLAMP® meter according to international standards and our quality inspection is very accurate it’s still possible that this device shows a defect or failure for which we do apologize. Under normal conditions your product should give you years of trouble free operation. In case there is a problem with the energy meter you should contact your distributor immediately. Most of our energy meters are sealed with a special seal. Once this seal is broken there is no possibility to claim any warranty. Therefore NEVER open an energy meter or break the seal of the device. The limited warranty is 5 years after production date, divided into various periods., after production, and only valid for production faults.
6 - 4PU & 4PS - Wago
3 Certificates
Wago - 4PU & 4PS - 7
Artikel/
Product
Leiterquerschnitt/
Conductor cross-section
Bemessungsstrom/
Rated current
Umgebungstemperatur/
Ambient temperature
40 °C
55 °C
70°C
879-3000 879-3020
25 mm²
(Feindrähtiger Leiter/Fine-stranded conductor)
65 A
x
45 A
x
16 mm²
(Feindrähtiger Leiter mit Aderendhülse/
Fine-stranded conductor with insulated ferrule)
65 A
x
55 A
x
35 A
x
16 mm²
(Feindrähtiger Leiter/Fine-stranded conductor)
65 A
x
50 A
x
35 A
x
10 mm²
(Feindrähtiger Leiter mit Aderendhülse/
Fine-stranded conductor with insulated ferrule)
55 A
x
45 A
x
30 A
x
10 mm²
(Feindrähtiger Leiter/Fine-stranded conductor)
55 A
x
40 A
x
30 A
x
6 mm²
(Feindrähtiger Leiter mit Aderendhülse/
Fine-stranded conductor with insulated ferrule)
41 A
x
39 A
x
27 A
x
6 mm²
(Feindrähtiger Leiter/Fine-stranded conductor)
41 A
x
37 A
x
25 A
x
4 mm²
(Feindrähtiger Leiter mit Aderendhülse/
Fine-stranded conductor with insulated ferrule)
32 A
x
27 A
x
17 A
x
4 mm²
(Feindrähtiger Leiter/Fine-stranded conductor)
30 A
x
25 A
x
15 A
x
4 Specifications
Casing PC flame resistant plastic Nominal voltage (Un) 230/400V AC (3~) Operating voltage 3x230/400V ±20% Insulation capabilities:
- AC voltage withstand 4KV for 1 minute
- Impulse voltage withstand 6KV – 1,2μS waveform
Basic current (Ib) 5A Maximum rated current (Imax) 65A Operational current range 0,4%Ib-Imax Overcurrent withstand 30Imax for 0,01s Operational frequency range 45-60Hz Internal power consumption ≤2W/Phase - ≤10VA/Phase (active - reactive) Test output flash rate (RED LED) 10.000 imp/kWh Pulse output rate 10.000/2.000/1.000/100/10/1/0,1/0,01 imp/kWh Pulse width Selectable 2-99ms (depending on pulse output rate setting) Data store The data can be stored for more than 10 years
without power
4.1 Performance criteria
Operating humidity ≤ 75% Storage humidity ≤ 95% International standard EN50470-1/3 Accuracy class B (=1% accuracy) Protection against penetration of dust and water IP51 Insulating encased meter of protective class II Operating temperature range -40°C - +70°C
Do not exceed the following limits for ambient temperature in combination with conductor cross-section and rated current:
8 - 4PU & 4PS - Wago
0,05Ib
Cosφ = 1 ±1,5%
0,1Ib
Cosφ = 0,5L
±1,5%
Cosφ= 0,8C
±1,5%
0,1Ib - Imax
Cosφ = 1
±1,0%
0,2Ib - Imax
Cosφ = 0,5L
±1,0%
Cosφ = 0,8C
±1,0%
4.2 Basic errors
4.3 Bluetooth specification
Protocol BLE 4.2 Frequency range Bluetooth 4.0: 2402 - 2480 MHz (40 CH)
4.4 M-bus communication specification
Bus type 2- wire (M-bus) Baud rate 300, 600, 1200, 2400 (default), 4800 and 9600 Range 1000m Downlink signal Master to slave. Voltage modulation Uplink signal Slave to master. Current modulation Cable JYSTY (nx2x0,8) Protocol EN13757-3 Unit loads 1 Max. number of meters 64 per bus*
4.5 Modbus/RS485 communication specification
Bus type RS485 Protocol MODBUS RTU with 16 bit CRC Baud rate 1200, 2400, 4800, 9600 (default), 19200, 38400, 57600 and 115200 Address range 1-247 user settable Maximum bus load 60 meters per bus* Range 1000m
*Note that the maximum number of meters is dependent on the converter, baudrate (the higher the baudrate, the smaller the number of meters which can be used) and the circumstances under which the meters are installed.
Wago - 4PU & 4PS - 9
Wiring diagram: Solid conductor
Wiring diagram: Fine-stranded conductor
Wiring diagram: Fine-stranded conductor
with insulated ferrule
4.6 Dimensions
Height without protection cover 92 mm Height 140 mm Width 72 mm Depth 63 mm Weight 0,34 Kg (net)
4.7 Wire connection
Connection technology Push-in CAGE CLAMP Actuation type Lever
WAGO serie 2616 Solid conductor 0.75 16 mm² / 18 4 AWG Fine-stranded conductor 0.75 … 25 mm² / 18 … 4 AWG Fine-stranded conductor; with insulated ferrule 0.75 16 mm²
WAGO serie 2604 Solid conductor 0.2 4 mm² / 24 … 12 AWG Fine-stranded conductor 0.2 … 4 mm² / 24 … 12 AWG Fine-stranded conductor; with insulated ferrule 0.25 2.5 mm²
Push-in technology can be used for Solid conductors and fine-stranded conductors with insulated ferrule. Fine-stranded conductors require opening the levers for connection.
®
10 - 4PU & 4PS - Wago
4PU – 3P4W
IN L1: Input Phase L1 - OUT L1: Output Phase L1 IN L2: Input Phase L2 - OUT L2: Output Phase L2 IN L3: Input Phase L3 - OUT L3: Output Phase L3 Klemme/Clamp N: Neutral conductor Klemme/Clamp 4: S0-Output 1 (+) Klemme/Clamp 5: Ground for S0 (-) Klemme/Clamp 6: S0-Output 2 (+) Klemme/Clamp 7: Modbus (A) Klemme/Clamp 8: Ground for Modbus (B) / MBus (-) Klemme/Clamp 9: MBus (+) Klemme/Clamp 10, 11: Tariff switching (230V AC)
4PU – 3P3W Open Delta (Aron)
Please shorting the Clamps N and U2!
IN L1: Input Phase L1 - OUT L1: Output Phase L1 IN L2: Input Phase L2 - OUT L2: Output Phase L2 IN L3: Input Phase L3 - OUT L3: Output Phase L3 Klemme/Clamp N: Not used Klemme/Clamp 4: S0-Output 1 (+) Klemme/Clamp 5: Ground for S0 (-) Klemme/Clamp 6: S0-Output 2 (+) Klemme/Clamp 7: Modbus (A) Klemme/Clamp 8: Ground for Modbus (B) / MBus (-) Klemme/Clamp 9: MBus (+) Klemme/Clamp 10, 11: Tariff switching (230V AC
4PU – 3P3W Delta
IN L1: Input Phase L1 - OUT L1: Output Phase L1 IN L2: Input Phase L2 - OUT L2: Output Phase L2 IN L3: Input Phase L3 - OUT L3: Output Phase L3 Klemme/Clamp N: Not used Klemme/Clamp 4: S0-Output 1 (+) Klemme/Clamp 5: Ground for S0 (-) Klemme/Clamp 6: S0-Output 2 (+) Klemme/Clamp 7: Modbus (A) Klemme/Clamp 8: Ground for Modbus (B) / MBus (-) Klemme/Clamp 9: MBus (+) Klemme/Clamp 10, 11: Tariff switching (230V AC)
4PU 1P2W Single - Phase
IN L1: Input Phase L1 - OUT L1: Output Phase L1 IN L2: Not used - OUT L2: Not used IN L3: Not used - OUT L3: Not used Klemme/Clamp N: Neutral conductor Klemme/Clamp 4: S0-Output 1 (+) Klemme/Clamp 5: Ground for S0 (-) Klemme/Clamp 6: S0-Output 2 (+) Klemme/Clamp 7: Modbus (A) Klemme/Clamp 8: Ground for Modbus (B) / MBus (-) Klemme/Clamp 9: MBus (+) Klemme/Clamp 10, 11: Tariff switching (230V AC)
4.8 Connection diagram 879-3000 (4PU)
Wago - 4PU & 4PS - 11
4PS – 3P4W
IN L1: Input Phase L1 - OUT L1: Output Phase L1 IN L2: Input Phase L2 - OUT L2: Output Phase L2 IN L3: Input Phase L3 - OUT L3: Output Phase L3 Klemme/Clamp N: Neutral conductor Klemme/Clamp 4: S0-Output 1 (+) Klemme/Clamp 5: Ground for S0 (-) Klemme/Clamp 6: S0-Output 2 (+) Klemme/Clamp 7: Modbus (A) Klemme/Clamp 8: Ground for Modbus (B) / MBus (-) Klemme/Clamp 9: MBus (+) Klemme/Clamp 10, 11: Tariff switching (230V AC)
4PS – 3P3W Open Delta (Aron)
Please shorting the Clamps N and U2!
IN L1: Input Phase L1 - OUT L1: Output Phase L1 IN L2: Input Phase L2 - OUT L2: Output Phase L2 IN L3: Input Phase L3 - OUT L3: Output Phase L3 Klemme/Clamp N: Not used Klemme/Clamp 4: S0-Output 1 (+) Klemme/Clamp 5: Ground for S0 (-) Klemme/Clamp 6: S0-Output 2 (+) Klemme/Clamp 7: Modbus (A) Klemme/Clamp 8: Ground for Modbus (B) / MBus (-) Klemme/Clamp 9: MBus (+) Klemme/Clamp 10, 11: Tariff switching (230V AC)
4PS – 3P3W Delta
IN L1: Input Phase L1 - OUT L1: Output Phase L1 IN L2: Input Phase L2 - OUT L2: Output Phase L2 IN L3: Input Phase L3 - OUT L3: Output Phase L3 Klemme/Clamp N: Not used Klemme/Clamp 4: S0-Output 1 (+) Klemme/Clamp 5: Ground for S0 (-) Klemme/Clamp 6: S0-Output 2 (+) Klemme/Clamp 7: Modbus (A) Klemme/Clamp 8: Ground for Modbus (B) / MBus (-) Klemme/Clamp 9: MBus (+) Klemme/Clamp 10, 11: Tariff switching (230V AC)
4PS 1P2W Single - Phase
IN L1: Input Phase L1 - OUT L1: Output Phase L1 IN L2: Not used - OUT L2: Not used IN L3: Not used - OUT L3: Not used Klemme/Clamp N: Neutral conductor Klemme/Clamp 4: S0-Output 1 (+) Klemme/Clamp 5: Ground for S0 (-) Klemme/Clamp 6: S0-Output 2 (+) Klemme/Clamp 7: Modbus (A) Klemme/Clamp 8: Ground for Modbus (B) / MBus (-) Klemme/Clamp 9: MBus (+) Klemme/Clamp 10, 11: Tariff switching (230V AC)
4.9 Connection diagram 879-3020 (4PS)
12 - 4PU & 4PS - Wago
Caution!
Turn off and if possible lock all sources supplying the energy meter and the equipment that is connected to it
before working on it.
Always use a properly rated voltage sensing device to confirm that power is off.
Warning
The installation should be performed by qualified personnel familiar with applicable codes and regulations.
Use insulated tools to install the device.
A fuse, thermal cut-off or single-pole circuit breaker should be fitted on the supply line and not on the neutral line.
5 Installation
The connecting wire, connecting the device to the outside circuit, should be sized in accordance with local regulations for
the maximum amount of the current breaker or other overcurrent protection devices used in the circuit.
An external switch or a circuit-breaker should be installed on the supply wires, which will be used to disconnect the meter
and the device supplying energy. It is recommended that this switch or circuit-breaker is placed near the meter because that is more convenient for the operator. The switch or circuit-breaker should comply with the specifications of the building’s electrical design and all local regulations.
An external fuse or thermal cut-off used as an overcurrent protection device for the meter must be installed on the supply side
wires. It’s recommended that this protection device is also placed near the meter for the convenience of the operator. The overcurrent protection device should comply with the specifications of the building’s electrical design and all local regulations.
This meter can be installed indoor, or outdoor enclosed in a meter box which is sufficiently protected, in
accordance with local codes and regulations.
To prevent tampering, an enclosure with a lock or a similar device can be used.
The meter has to be installed against a fire resistant wall.
The meter has to be installed in a well-ventilated and dry place.
The meter has to be installed in a protective box if the meter is exposed to dust or other contaminants.
The meter can be installed and used after being tested and can be sealed afterwards.
The device can be installed on a 35mm DIN rail.
The meter should be installed on a location where the meter can be read easily.
In case the meter is installed in an area with frequent surges for example due to thunderstorms, welding machines,
inverters etc., the meter is required to be protected with a Surge Protection Device.
The device should be sealed immediately after installing it in order to prevent tampering.
Wago - 4PU & 4PS - 13
6 Operation
6.1 Display part 1 (MID relevant)
Part 1 of the display shows the MID relevant software version number, the meter serial number, the CRC code, the actual tariff and an indication of the MID-relevant measurement units (kWh). Meter serial number and CRC code are scrolling every 10 seoconds. When Bluetooth communication is activated, icon 1 will be shown. When Modbus or M-bus communication is activated, icon 2 will be shown on the display.
6.2 Display part 2 (MID relevant)
Part 2 of the display shows the MID relevant measurement values. OBIS codes are used to identify the corresponding measurement values:
Foreward:
1.8.1: Positive active energy in tariff 1
1.8.2: Positive active energy in tariff 2
1.8.3: Positive active energy in tariff 3
1.8.4: Positive active energy in tariff 4
Reverse:
2.8.1: Negative active energy in tariff 1
2.8.2: Negative active energy in tariff 2
2.8.3: Negative active energy in tariff 3
2.8.4: Negative active energy in tariff 4
Die Tarifwerte werden im Wechsel angezeigt, sodass T1 und T2 zusammen, T3 und T4 zusammen angezeigt werden. Der Zähler hat eine 6+3-stellige kWh-Anzeige. Bei Erreichen von 999999,999 geht dieser Wert zurück auf 000000,000.
6.3 Display part 3 (non MID relevant)
Part 3 of the display shows the non-relevant data like current direction, trip counter, reactive energy, power factor, present quadrant, frequency, active power, apparent power, reactive power, voltage and current.
Scroll through the display pages (Total - L1 - L2 -L3) using the capacitive touch buttons on the frontside of the meter.
14 - 4PU & 4PS - Wago
6.4 Settings
On the front side of the meter are three sensitive buttons, which are marked with a green line in the right corner in the bottom. To enter the settings mode press and hold the middle button for >3 seconds.
The following display will appear:
6.5 Bluetooth
When the arrows point at the Bluetooth symbol, press the middle button to activate Bluetooth:
Now the Bluetooth ist activated in the energy meter and you can scan the QR code on the display or scan the area for bluetooth devices by using the wago mobile phone app.
Wago - 4PU & 4PS - 15
When Bluetooth connection is active, the Bluetooth activation icon will be show on the display:
Go to Appendix 4 - Bluetooth for the wago mobile phone app user guide.
6.6 Button settings
Settings can also be done using the capacitive touch buttons on the front of the meter. Scroll through the options using the left << and right >> button. Confirm the setting using the middle button. Select the following page to go to the settings menu:
Enter the password to get acces to the settings menu (default 0000). Confirm each digit (1-9) using the middle button:
The settings menu will appear after entering the password correctly:
16 - 4PU & 4PS - Wago
Beispiel Verdrahtung der S0-Impulskontakte
6.6.1 Password
The button setting function can be protected by setting a password. This password is also valid for settings via Blue- tooth. The default password is 0000. This password can only be changed using the button function.
6.6.2 Tariff
The default tariff is 1. The tariff can be set to T2, T3 and T4. Tariff 1 and 2 are always displayed in part 1 and 2 of the meters. kWh values in tariff 3 and 4 will be added to the automatic scroll in part 2 of the display.
6.6.3 S0-Impulsausgang
The energy meter is equipped with two pulse outputs (forward & reverse or active & reactive) which are optically isolated from the inside circuit. It generates pulses in proportion to the measured consumption for purpose of remote reading or accuracy testing. The pulse output is a polarity dependent, open-collector transistor output requiring an external voltage source for correct operation. For this external voltage source, the voltage (Ui) should be lower than 27V DC. The maximu m switching current (Imax) is 100mA. To connect the impulse output, connect 5-27V DC to connector 4/6 (collector), and the signal wire (S) to connector 5 (emitter).
Wago - 4PU & 4PS - 17
The default imp/kWh setting for the S0 output is 1.000Imp/kWh. The S0 output setting can be set via push buttons direct on the meter or via bluetooth app to 10.000 / 2.000 / 1.000 (default) / 100 / 10 / 1 / 0,1 / 0,01 Imp/kWh.
6.6.4 Pulse type setting
The default pulse type setting is active & reactive. This means that the two pulse outputs pulse based on the active and reactive energy. The pulse type can be set to forward & reverse, which means that the pulse outputs pulse based on forward and reverse active energy.
6.6.5 S0 Pulse width
The default S0 pulse width is 30ms. The pulse width setting can be modified to 2-99ms (depending on the imp/kWh setting).
6.6.6 Modbus ID
The Modbus ID can be set from 1 to 247, the default Modbus ID is 1.
18 - 4PU & 4PS - Wago
6.6.7 Modbus Baudrate
The default Modbus baud rate setting is 9600. The baud rate setting can be modified to:
115.200 / 56.700 / 38.400 / 19.200 / 9600 (default) / 4800 / 2400 / 1200 / 600 / 300 bps.
6.6.8 Modbus parity
The default Modbus parity setting is even. The parity can be modified to none or odd.
6.6.9 M-Bus ID
The M-Bus ID can be set from 0 to 250, the default M-Bus ID is 0.
6.6.10 M-Bus baud rate
The default M-bus baud rate setting is 2400. The M-Bus baud rate setting can be modified to: 9600 / 4800 / 2400 (default) / 1200 / 600 / 300 bps.
Wago - 4PU & 4PS - 19
6.6.11 Backlight
The meter is equipped with a blue backlight. The backlight can be set to always on, off or button mode.
6.6.12 Powerdown counter
The powerdown counter registers the number of times that the meter has been turned off.
6.6.13 Trip counter
The meter is equipped with a trip counter that can be set to zero by the user. This is the energy calculated based on the combination code setting (see 6.6.15).
20 - 4PU & 4PS - Wago
OBIS code Content
1.8.1 Positive active energy in tari ff 1 (kWh)
1.8.2 Positive active energy in tari ff 2 (kWh)
1.8.3 Positive active energy in tari ff 3 (kWh)
1.8.4 Positive active energy in tari ff 4 (kWh)
2.8.1 Negative active energy in tari ff 1 (kWh)
2.8.2 Negative active energy in tari ff 2 (kWh)
2.8.3 Negative active energy in tari ff 3 (kWh)
2.8.4 Negative active energy in tari ff 4 (kWh)
1.7.0 (forward +) ;
2.7.0 (reverse -)
Total active power
21.7.0 (forward +) ;
22.7.0 (reverse -)
L1 Active power
41.7.0 (forward +) ;
42.7.0 (reverse -)
L2 Active power
61.7.0 (forward +) ;
62.7.0 (reverse -)
L3 Active power
9.7.0 Total apparent power
29.7.0 L1 Apparent power
49.7.0 L2 Apparent power
69.7.0 L3 Apparent power
3.7.0 (forward +) ;
4.7.0 (reverse -)
Total reactive power
23.7.0 (forward +) ;
24.7.0 (reverse -)
L1 Reactive power
43.7.0 (forward +) ;
44.7.0 (reverse -)
L2 Reactive power
63.7.0 (forward +) ;
64.7.0 (reverse -)
L3 Reactive power
11.7.0 Current
31.7.0 L1 Current
51.7.0 L2 Current
71.7.0 L3 Current
32.7.0 L1 Voltage
52.7.0 L2 Voltage
72.7.0 L3 Voltage
6.6.14 OBIS codes
OBIS codes can be used to identify the corresponding measurement values. By default the OBIS codes are turned off.
Following OBIS codes are included in the meter:
Wago - 4PU & 4PS - 21
Code
Total (active) energy
C-01
Nur Bezug / Forward only
C-02
Nur Liefereung / Reverse only
C-03
Bezug + Lieferung / Forward + Reverse
C-04
Lieferung – Bezug / Forward - Reverse
C-05
Bezug – Lieferung / Forward - Reverse*
(saldierende Messung)
Example of flow through the meter
L1
+5 kWh
L2
+5 kWh
L3
-12 kWh
LCD reading and calculation of total energy
Code
C-01
C-02
C-03
C-04
C-05*
Total
10
-12
22
-2
-2
Forward
10
10
10
10
0
Reverse
-12
-12
12
-12
-2
*Meters ordered or set afterwards to C-05 cannot be set to another calculation mode.
6.6.15 Combination Code (adjustable via Modbus, M-bus & Bluetooth)
The meter allows you to display the total energy (usage) shown on the display in accordance to different calculation methods. You can use the following calculation methods for total energy:
22 - 4PU & 4PS - Wago
Caution
During repair and maintenance, do not touch the meter connecting clamps directly with your bare hands, with
metal, blank wire or other conducting material as that will cause an electric shock and possibly cause injury, serious injury or even death.
Turn off and if possible lock all sources supplying the energy meter and the equipment that is connected to it
before opening the protection cover and working on it.
Turn off and lock all power supply to the energy meter and the equipment to which it is installed before opening
the protection cover to prevent the hazard of electric shock.
Warning
Maintenance or repair should only be performed by qualified personnel familiar with applicable codes and
regulations.
Use insulated tools to maintain or repair the meter.
Make sure the protection cover is in place after maintenance or repair.
The case is sealed, failure to observe this instruction can result in damage to the meter.
Problem
Mögliche Ursache
Überprüfung / Lösung
The red consumption LED is not flashing (PULSE LED).
There is no load connected to the meter. The load on the line is very low.
Connect a load to the meter. Check with an Ohm-meter if the load value is very low.
The register doesn’t count.
There is almost no load connected to the meter.
Check if the red consumption LED is flashing.
No pulse output.
The pulse output is not supplied with DC power. The pulse output is not connected correctly.
Check the external voltage source (Ui) is 5-27V DC with a voltage meter. Check if the connection is correct: the 5-27V DC should be connected to the collector connection (pin 4/6) and the signal wire to the emitter connection (pin 5).
If none of the above works, please contact technical support
7 Troubleshooting
Wago – 4PU & 4PS - 23
7.1 Errors / Diagnostics display
All measurement values are stored twice with the accompanying checksums. In case the checksum fails, the backup data is used. If both the normal storage and backup fail, the meter will stop working and indicate error XX:
XX is the hexadecimal data, convert the data to binary to analyze the data. bit0: The data in the main storage area and backup area of the battery is wrong or cannot be operated . bit1: The battery mantissa area cannot be operated. bit2: The battery backup area cannot be operated. bit3: The main battery storage area cannot be operated . bit4: Data error in the battery mantissa area. bit5: Data error in the battery backup area (integer bit). bit6: Data error in the main battery storage area (integer bit).
bit7: EEPROM cannot be fully initialized.
7.2 Technical support
For questions about one of our products please contact our technical support:
Telefon: +49 (0) 571/887 – 44555
Fax: +49 (0) 571/887 – 844555
E-Mail: support@wago.com
Website: www.wago.com/support
24 – 4PU & 4PS - Wago
Appendix 1 – Multi tariff function
A1.1 How to switch between T1 und T2
The meter is equipped with a multi tariff functionality. T1 and T2 can be activated by an external voltage connected to the terminals 10/11.
As soon as a voltage of 230V AC is applied to terminals 10 and 11, the meter switches to tariff 2 and writes the measured values into the the measured values into the registers provided for T2.
4PU:
4PS:
A1.2 How to switch between T3 and T4
T3 and T4 can only be activated by Bluetooth, Modbus, M-bus or using the button function. After activating T3 and/or T4 once, the energy values per tariff (3 / 4) will be displayd in the MID relevant part of the display. This cannot be undone.
Wago - 4PU & 4PS - 25
Appendix 2 - M-Bus
A2.1 Communication via M-Bus
The 4PU and 4PS meters are equipped with an M-bus port, the data can be read out via this port. The communication protocol conforms to the EN13757-3 standard.
The meter can communicate with your PC. In order to read out the meter registers first install and configure the PC software. Use an M-bus level converter to connect the PC and the meter. The cable should be connected to terminals 8 and 9. The default communication address of the meter is 00.
The defaults for M-bus communication are:
Baud rate 2400
8 data bits
Even parity
1 stop bit
4PU: 4PS:
The secondary addressing (253/FD) is preset to the last 8 digits of the serial number printed on the side of the meter. However this can be changed to a more convenient number through IR or M-bus communication.
The baud rate can be changed to values 9600, 4800, 2400, 1200, 600 and 300 baud. Data, parity and stop bit cannot be changed.
For the registers used in the meter and how to interpreted the data, please use the M-bus register map on the next page.
More detailed information on M-Bus can be found:
www.m-bus.com
26 - 4PU & 4PS - Wago
M-bus Command
Contents
M-bus register header DIF
M-bus register VIF
Response/example
Remarks
1. REQ UD2: 10 5B xx
68 xx xx 68 08 xx 72
68 [data length] 68 08 [address] 72 [header]
[datablocks] [checksum] 16
Serial number
Header
46 02 02 19
Manufacturer ID
CD 25 Version
01
Same as the mayor version of the software
Medium
02
Electricity
Acces number
04
Every time the meter is read this number is increased by 1 up to 255, then it becomse 0 again
Status
00
00 = OK 02 = Error
Signature
00 00
Always 00 00
Datenblock
Total forward active energy
04
03
15 CD 5B 07
123456789 Wh
Forward active energy T1
84 10
03
15 CD 5B 07
123456789 Wh
Forward active energy T2
84 20
03
15 CD 5B 07
123456789 Wh
Forward active energy T3
84 30
03
15 CD 5B 07
123456789 Wh
Forward active energy T4
84 80 10
03
15 CD 5B 07
123456789 Wh
Total reverse active energy
04
83 3C
15 CD 5B 07
123456789 Wh
Reverse active energy T1
84 10
83 3C
15 CD 5B 07
123456789 Wh
Reverse active energy T2
84 20
83 3C
15 CD 5B 07
123456789 Wh
Reverse active energy T3
84 30
83 3C
15 CD 5B 07
123456789 Wh
Reverse active energy T4
84 80 10
83 3C
15 CD 5B 07
123456789 Wh
Total kWh (resettable)
04
83 FC 10
15 CD 5B 07
123456789 Wh
Forward reactive energy
04
FB 82 73
15 CD 5B 07
123456,789 kVARh
Reverse reactive energy
04
FB 82 F3 3C
15 CD 5B 07
123456,789 kVARh
L1 voltage
02
FD C7 FC 01
E4 59
230,12 V
L2 voltage
02
FD C7 FC 02
E4 59
230,12 V
L3 voltage
02
FD C7 FC 03
E4 59
230,12 V
L1 current
03
FD D9 FC 01
1B 87 01
100123 mA
L2 current
03
FD D9 FC 02
1B 87 01
100123 mA
L3 current
03
FD D9 FC 03
1B 87 01
100123 mA
Total active power
03
2B
87 D6 12
1234567 W
L1 active power
03
AB FC 01
87 D6 12
1234567 W
L2 active power
03
AB FC 02
87 D6 12
1234567 W
L3 active power
03
AB FC 03
79 29 ED
-1234567 W
Total reactive power
03
FB 14
87 D6 12
1234,567 kVAR
L1 reactive power
03
FB 94 FC 01
87 D6 12
1234,567 kVAR
L2 reactive power
03
FB 94 FC 02
87 D6 12
1234,567 kVAR
L3 reactive power
03
FB 94 FC 03
87 D6 12
1234,567 kVAR
Total apparent power
03
FB 34
87 D6 12
1234,567 kVA
Total power factor
0A
FD 3A
00 01
1,00
Grid frequency
03
FB 2C
37 C7 00
50,999Hz
Tariff
09
7C 01 54
01
T1
CT rate (only for CT version)
0A
FD 3A
05 95 99
9995/5
Checksumme
xx xx
xx 16
A2.2 M-bus register map
27 - 4PU & 4PS - Wago
Contents
Command part 1
Address
Command part 2
New value Response
Remarks
Baudrate
68 03 03 68 53
01 - BB
E5 (new Baud 2400)
B8 = 300; B9 = 600; BA = 1200; BB = 2400; BC = 4800; BD = 9600
Primary address
68 06 06 68 53
01 51 01 7A
01
E5 (new id 01)
000 - 250 write in HEX
Secondary address
68 09 09 68 53
01 51 0C 79
15 01 23 45
E5 (new address 1501 2345)
4 bytes BCD same as read
Tariff mode
68 08 08 68 53
01 51 09 7C 01 54
02 E5 (tariff 2)
T1 = 01 ; T2 = 02 ; T3 = 03 ; T = 04
Combined code
68 07 07 68 53
01 51 09 FD 3A
05 E5 (combined code 05)
01, 02, 03, 04 and 05
S0 rate
68 0A 0A 68 53
01 51 0C FD 3A
00 00 01 00
E5 (S0 rate 100)
10.000 / 2.000 / 1.000 / 100 / 10 / 1 / 0,1 / 0,01
Resettable kWh
68 09 09 68 53
01 51 0C 04
00 00 00 00
E5 Value is ignored, always set to 0
Reset power down counter
68 08 08 68 53
01 51 0A FD 60
00 00 E5 Value is ignored, always reset to 0
SND NKE
10 40
01 - -
E5
Can be send to primary or secondary address and resets all communication values
Selecting slave by secondary addressing
Serial number
Manufacturer ID
Generation version
Medium
68 0B 0B 68 53 FD 52
aa aa aa aa
bb bb cc dd Input 01 00 07 13
CD 25 01 02
Remarks
13070001
-
Major version of the software
Electricity
A2.3 M-Bus write registers
Wago - 4PU & 4PS - 28
Appendix 3 - Modbus
A3.1 Communication via Modbus
The energy meter can communicate with the PC and other Modbus master devices. To read out the meter registers, first install and configure the PC software. Use an RS485 to USB converter to connect the PC and the meter. The cable is connected to terminals 7 and 8.
The following are the factory set Modbus parameters:
Modbus addresse 001
Baud rate 9600
8 data bits
Even parity
1 stop bit
The baud rate can be changed to values 115200, 56700, 38400, 9600, 4800, 2400, 1200, 600 and 300. The parity can be set to none or odd. Data and stopbit cannot be changed.
4PU: 4PS:
When connecting the meter through a serial converter (RS485) for testing, please be aware that because of not implementing the complete Modbus infrastructure, there will be a need to put an additional resistor (120 ohms/ 0,25 watts) across the terminals (7 & 8) on the meter side.
For the registers used in the meter and how to interpreted the data, please use the Modbus register map on the next pages.
More information on Modbus can be found:
Physical: Protocol: http://www.modbus.org/docs/Modbus_Application_Protocol_V1_1b3.pdf
http://www.modbus.org/docs/Modbus_over_serial_line_V1_02.pdf
29 - 4PU & 4PS - Wago
Reg. address
Content
Function code
Length
Unit
Data type
4000
Serial number
03 2 -
HEX
4002
Meter code
03 1 -
HEX
4PU: 1111 - 4PS: 1112 - 2PCT: 1113
4003
Modbus ID
03 1 -
Signed
4004
Baud rate
03 1 -
Signed
1: 300 - 2: 600 - 3: 1200 - 4: 2400 5: 4800 - 6: 9600 - 7: 19200 - 8: 38400
9: 57600 - 10: 115200
4005
Protocol version
03 2 -
Float ABCD
4007
Software version
03 2 -
Float ABCD
4009
Hardware version
03 2 -
Float ABCD
400B
Meter amps
03 1 A
Signed
400C
CT ratio
03 1 A
HEX
400D
S0 output rate
03 2 imp/kWh
Float ABCD
400F
Combination code
03 1 -
Signed
1: forward only - 2: reverse only 3: forward+reverse - 4: import-export
5: import-export (10)
4010
LCD cycle time
03 1 sec.
HEX
4011
Parity setting
03 1 -
Signed
1: even - 2: none - 3: odd
4012
Current direction
03 1 -
ASCII
F: forward - R: reverse
4013
L2 Current direction
03 1 -
ASCII
F: forward - R: reverse
4014
L3 Current direction
03 1 -
ASCII
F: forward - R: reverse
4016
Power down counter
03 1 -
Signed
4017
Present quadrant
03 1 -
Signed
4018
L1 Quadrant
03 1 -
Signed
4019
L2 Quadrant
03 1 -
Signed
401A
L3 Quadrant
03 1 -
Signed
401B
Checksum
03 2 -
HEX
401D
Active status word
03 2 -
HEX
401F
CT ratio
03 2 A
Signed
9995 005 = 9995/5
4021
Pulse width
03 2 ms
Signed
Value between 2-99 ms
4022
Pulse type setting
03 1 -
HEX
1: active & reactive 2: forward & reverse
4023
Checksum 2 (non-relevant)
03 2 -
HEX
4025
Reserved
- 1 -
-
4026
Data type setting
03 1 -
Signed
1: standard - 2: integer
A3.2 Modbus register map
Wago - 4PU & 4PS - 30
4027
Reserved
- 4 -
-
4032
Screen direction
03 1 -
Signed
0: standard - 1: turn 180 degrees
4033
OBIS code ON/OFF
03 1 -
Signed
0: OFF - 1: ON
Reg. address
Content
Function code
Length
Unit
Data type
5000
Voltage*
03 2 V
Float ABCD
5002
L1 Voltage
03 2 V
Float ABCD
5004
L2 Voltage
03 2 V
Float ABCD
5006
L3 Voltage
03 2 V
Float ABCD
5008
Grid frequency
03 2 Hz
Float ABCD
500A
Current*
03 2 A
Float ABCD
500C
L1 Current
03 2 A
Float ABCD
500E
L2 Current
03 2 A
Float ABCD
5010
L3 Current
03 2 A
Float ABCD
5012
Total active power
03 2 kW
Float ABCD
5014
L1 Active power
03 2 kW
Float ABCD
5016
L2 Active power
03 2 kW
Float ABCD
5018
L3 Active power
03 2 kW
Float ABCD
501A
Total reactive power
03 2 kvar
Float ABCD
501C
L1 Reactive power
03 2 kvar
Float ABCD
501E
L2 Reactive power
03 2 kvar
Float ABCD
5020
L3 Reactive power
03 2 kvar
Float ABCD
5022
Total apparent power
03 2 kVA
Float ABCD
5024
L1 Apparent power
03 2 kVA
Float ABCD
5026
L2 Apparent Power
03 2 kVA
Float ABCD
5028
L3 Apparent Power
03 2 kVA
Float ABCD
502A
Power factor
03 2 -
Float ABCD
502C
L1 Power factor
03 2 -
Float ABCD
502E
L2 Power factor
03 2 -
Float ABCD
5030
L3 Power factor
03 2 -
Float ABCD
5032
L1-L2 Voltage
03 2 V
Float ABCD
5034
L1-L3 Voltage
03 2 V
Float ABCD
5036
L2-L3 Voltage
03 2 V
Float ABCD
31 - 4PU & 4PS - Wago
Reg. address
Content
Function code
Length
Unit
Data type
6000
Total active energy
03 2 kWh
Float ABCD
6002
T1 Total active energy
03 2 kWh
Float ABCD
6004
T2 Total active energy
03 2 kWh
Float ABCD
6006
L1 Total active energy
03 2 kWh
Float ABCD
6008
L2 Total active energy
03 2 kWh
Float ABCD
600A
L3 Total active energy
03 2 kWh
Float ABCD
600C
Forward active energy
03 2 kWh
Float ABCD
600E
T1 Forward active energy
03 2 kWh
Float ABCD
6010
T2 Forward active energy
03 2 kWh
Float ABCD
6012
L1 Forward active energy
03 2 kWh
Float ABCD
6014
L2 Forward active energy
03 2 kWh
Float ABCD
6016
L3 Forward active energy
03 2 kWh
Float ABCD
6018
Reverse active energy
03 2 kWh
Float ABCD
601A
T1 Reverse active energy
03 2 kWh
Float ABCD
601C
T2 Reverse Active Energy
03 2 kWh
Float ABCD
601E
L1 Reverse active energy
03 2 kWh
Float ABCD
6020
L2 Reverse active energy
03 2 kWh
Float ABCD
6022
L3 Reverse active energy
03 2 kWh
Float ABCD
6024
Total reactive energy
03 2 kvarh
Float ABCD
6026
T1 Total reactive energy
03 2 kvarh
Float ABCD
6028
T2 Total reactive energy
03 2 kvarh
Float ABCD
602A
L1 Total reactive energy
03 2 kvarh
Float ABCD
602C
L2 Total reactive energy
03 2 kvarh
Float ABCD
602E
L3 Total reactive energy
03 2 kvarh
Float ABCD
6030
Forward reactive energy
03 2 kvarh
Float ABCD
6032
T1 Forward reactive energy
03 2 kvarh
Float ABCD
6034
T2 Forward reactive energy
03 2 kvarh
Float ABCD
6036
L1 Forward reactive energy
03 2 kvarh
Float ABCD
6038
L2 Forward reactive energy
03 2 kvarh
Float ABCD
603A
L3 Forward reactive energy
03 2 kvarh
Float ABCD
603C
Reverse reactive energy
03 2 kvarh
Float ABCD
603E
T1 Reverse reactive energy
03 2 kvarh
Float ABCD
6040
T2 Reverse reactive energy
03 2 kvarh
Float ABCD
Wago - 4PU & 4PS - 32
6042
L1 Reverse reactive energy
03 2 kvarh
Float ABCD
6044
L2 Reverse reactive energy
03 2 kvarh
Float ABCD
6046
L3 Reverse reactive energy
03 2 kvarh
Float ABCD
6048
Tariff
03 1 -
Signed
6049
Resettable day counter
03 2 kWh
Float ABCD
604B
T3 Total active energy
03 2 kWh
Float ABCD
604D
T4 Total active energy
03 2 kWh
Float ABCD
604F
T3 Forward active energy
03 2 kWh
Float ABCD
6051
T4 Forward active energy
03 2 kWh
Float ABCD
6053
T3 Reverse active energy
03 2 kWh
Float ABCD
6055
T4 Reverse Active Energy
03 2 kWh
Float ABCD
6057
T3 Total reactive energy
03 2 kvarh
Float ABCD
6059
T4 Total reactive energy
03 2 kvarh
Float ABCD
605B
T3 Forward reactive energy
03 2 kvarh
Float ABCD
605D
T4 Forward reactive energy
03 2 kvarh
Float ABCD
605F
T3 Reverse reactive energy
03 2 kvarh
Float ABCD
6061
T4 Reverse reactive energy
03 2 kvarh
Float ABCD
6063
Imp. Inductive reactive energy in Q1 (total)
03 2 kWh
Float ABCD
6065
Imp. Inductive reactive energy in Q1 (T1)
03 2 kWh
Float ABCD
6067
Imp. Inductive reactive energy in Q1 (T2)
03 2 kWh
Float ABCD
6069
Imp. Inductive reactive energy in Q1 (T3)
03 2 kWh
Float ABCD
606B
Imp. Inductive reactive energy in Q1 (T4)
03 2 kWh
Float ABCD
606D
Imp. capacitive reactive energy in Q2 (total)
03 2 kWh
Float ABCD
606F
Imp. capacitive reactive energy in Q2 (T1)
03 2 kWh
Float ABCD
6071
Imp. capacitive reactive energy in Q2 (T2)
03 2 kWh
Float ABCD
6073
Imp. capacitive reactive energy in Q2 (T3)
03 2 kWh
Float ABCD
6075
Imp. capacitive reactive energy in Q2 (T4)
03 2 kWh
Float ABCD
6077
Exp. Inductive reactive energy in Q3 (total)
03 2 kWh
Float ABCD
6079
Exp. Inductive reactive energy in Q3 (T1)
03 2 kWh
Float ABCD
607B
Exp. Inductive reactive energy in Q3 (T2)
03 2 kWh
Float ABCD
607D
Exp. Inductive reactive energy in Q3 (T3)
03 2 kWh
Float ABCD
607F
Exp. Inductive reactive energy in Q3 (T4)
03 2 kWh
Float ABCD
6081
Exp. capacitive reactive energy in Q4 (total)
03 2 kWh
Float ABCD
6083
Exp. capacitive reactive energy in Q4 (T1)
03 2 kWh
Float ABCD
33 - 4PU & 4PS - Wago
6085
Exp. capacitive reactive energy in Q4 (T2)
03 2 kWh
Float ABCD
6087
Exp. capacitive reactive energy in Q4 (T3)
03 2 kWh
Float ABCD
6089
Exp. capacitive reactive energy in Q4 (T4)
03 2 kWh
Float ABCD
608B
Resettable day counter L1
03 2 kWh
Float ABCD
608D
Resettable day counter L2
03 2 kWh
Float ABCD
608F
Resettable day counter L3
03 2 kWh
Float ABCD
Wago - 4PU & 4PS - 34
Reg. address
Content
Function code
Length
Unit Data type
4003 Modbus ID
06
1 - Signed
Command: 01 06 4003 000A (new ID: 10)
01~247 - 01 default - 00 broadcast
4004 Baud rate
06
1 - Signed
Command:
01 06 4004 00 06 (new Baudrate: 9600)
1: 300 - 2: 600 - 3: 1200 - 4: 2400
5: 4800 - 6: 9600 - 7: 19200
8: 38400 - 9: 57600 - 10: 115200
400D S0 output rate
10
2
imp/kWh
Float ABCD
Command:
01 10 400D 0002 04 41 20 00 00 (new S0: 10)
10.000 - 2.000 - 1.000 - 100 - 10 - 1 0,1 - 0,01
400F Combination code
06
1 - Signed
Command:
01 06 400F 0004 (new code: 4 F-R)
1: forward only - 2: reverse only
3: forward+reverse
4: import-export
5: import-export (10)
4010 LCD cycle time
06
1
sec. HEX
Command:
01 06 4010 0025 (new time: 25 sec.)
01~30
4011 Parity setting
06
1 - Signed
Command:
01 06 4011 0002 (new parity: none)
01: even - 02: none - 03: odd
4016 Power down counter
06
1 - Signed
Command:
01 06 4016 0000
Reset to 0
6048 Tariff 06
1 - Signed
Command:
01 06 6048 0002 (new tariff: 2)
1: T1 - 2: T2 - 3: T3 - 4: T4
6049 Resettable day counter
10
1
kWh Float ABCD
Command: 01 10 6049 0002 04 0000 0000
Reset to 0
401F
CT ratio
2 - Signed
Command:
01 10 401F 0002 04 9995 0005
Set to 9995/5
4021
Pulse width
06 1 ms
Signed
Command: 01 06 4021 0030 (new setting: 30ms)
2~99 ms
4022
Pulse type
06 1 - Signed
Command: 01 06 4022 0002 (new setting: forward &
reverse)
2 = forward & reverse
4026
Data type setting
06
1 - Signed
Command: 01 06 4026 0002 (new setting: integer)
1=standard, 2=Integer
4032 Screen direction
06
1 0
-
Signed
Command: 01 06 4032 0001 (new setting: turn 180
degrees)
0: standard - 1: turn 180 degrees
4033 OBIS code ON/OFF
06
1 0 =
Signed
Command:
01 06 4033 0001 (new setting: OBIS ON)
0: OFF - 1: ON
A3.3 Modbus write register
35 - 4PU & 4PS - Wago
Appendix 4 - Bluetooth
All Push-in-CAGE CLAMP® meters are able to be read and configured via Bluetooth. The standard used is standard used is
BLE 4.2. You can download the smartphone app for Android and IOS free of charge from the stores.
You can find the smartphone app under the name "WAGO Energy Meter Configurator".
A4.1 Bluetooth app
Activate the Bluetooth on the energy meter according to the steps in 6.5 Bluetooth.
Start the smartphone app.
Wago - 4PU & 4PS - 36
A4.2 Connect the meter
The energy meter can be connected with the Scan Bluetooth or Scan QR function.
1. Scan Bluetooth: The app scans for all Bluetooth measurement devices in the vicinity.
Select the correct serial number for the connection.
2. Scan QR: The app opens the camera of the cell phone to scan the QR code on the meter display.
Once the code is scanned, the meter is connected.
37 - 4PU & 4PS - Wago
A4.3 Device page
The energy meter is now connected to the smartphone app.
The meter type, serial number, software version and checksums are displayed on the device page.
Wago - 4PU & 4PS - 38
A4.4
Read meter data
All energy values are located under "Energy", as well as all instantaneous values are located under "Instantaneous".
Refresh the data using the refresh arrow in the upper right corner.
39 - 4PU & 4PS - Wago
A4.5
Save meter data
Save the data using the memory disk in the upper right corner.
The data can be stored locally on the smartphone or shared through various channels such as email, Bluetooth or other programs.
Wago - 4PU & 4PS - 40
A4.6 Change settings
Settings can be selected individually and/or saved all at once.
Select the settings that you want to change. The changed settings are highlighted in green.
Save the values via the memory disk in the upper right corner. First, a pop-up menu for the password appears. By default, the password is always 0000. The password can only be changed on the meter using the keys. After entering the correct password, the new settings are saved in the meter.
41 - 4PU & 4PS - Wago
WAGO Kontakttechnik GmbH & Co. KG Postfach 2880 – 32385 Minden Head office 0571/887 - 0 Hansastraße 27 – 32423 Minden Sales 0571/887 - 44 222
info@wago.com Order service 0571/887 - 44 333 www.wago.com Fax 0571/887 - 844 169
WAGO is a registered trademark of WAGO Verwaltungsgesellschaft mbH. Copyright - WAGO Kontakttechnik GmbH & Co. KG - All rights reserved. The content and structure of the WAGO websites, catalogs, videos and other WAGO media are subject to copyright. The distribution or modification of the content of these pages and videos is not permitted. Furthermore, the content may not be copied for commercial purposes or made available to third parties. Also subject to copyright are the images and videos that have been made available to WAGO Kontakttechnik GmbH & Co. KG by third parties are also subject to copyright."
Loading...