Wago 787 Series Catalog Page

Volume 4, Section 5 | WAGO Power Supplies
Redundancy Module; 24 VDC / 25 A
787 Series
+
1
IN
+
2
5
Redundancy Module; Input voltage: 2 x 9 … 54 VDC; Input current: 2x 12.5 A; Output voltage: 9 … 54 VDC; Output current: 25 A
Item No. Pack. Unit
787-783 1
H
D
W
OUT
Input
Nominal input voltage U Input voltage range 2 x 9 … 54 VDC Nominal mains frequency range 0Hz Input current I
Output
Nominal output voltage U Output voltage range 9 … 54 VDC (U Voltage drop ≤ 0.8 V (input/output) Nominal output current I Output power (max.) 1350W Nominal output power 600W
Signaling and Communication
Signaling 1 x IN1 LED (green); 1 x IN2 LED (green);
+
Ecienc
y/Power Losses
Power loss P
Eciency ≥ 96 %
Safety and Protection/Environmental Requirements
Isolation voltage (connectors – housing) 500VDC Protection class/protection type III / IP20 (per EN 60529) Short-circuit-protected No Parallel operation/series operation Yes/no MTBF > 10 million h (per IEC 61709) Surrounding air temperature (operation) −25 … +70 °C Relative humidity ≤ 95 % (no condensation permissible)
Derating −2.66 %/K (+55 °C < Tamb ≤ +70 °C)
Pollution degree 2
Connection Data
Connection technology Push-in CAGE CLAMP®
Input/output (solid/ne-stranded/AWG) 0.5 … 6 mm² / 0.5 … 6 mm² / 20 … 10 AWG
Geometric Data/Mechanical Data/Material Data
Width x height x depth (mm) 50 x 130 x 92; depth from upper-edge of DIN-rail Mounting type DIN-35 rail (EN 60715) Weight 470 g
Standards and Specications
Approvals/standards/specications CE; UL 508
l
i nom
i
o nom
o nom
2 x 24VDC
≤ 12.5 A (per path)
24 VDC
− Voltage drop)
i
25 A
1 x OUT LED (green)
≤ 19 W (nominal load)
Features:
• Redundancy module with two inputs for decoupling two power supplies
• For redundant and fail-safe power supply
With LED for input voltage monitoring on site
490
WAGO Electronic Interface
Loading...