Volume 4, Section 5 | WAGO Power Supplies
RedundancyModule;
24VDC/25A
787 Series
1 |
+ |
+ |
|
− |
|
||
|
|
||
|
IN |
OUT |
|
2 |
+ |
|
|
− |
− |
||
|
5
RedundancyModule;Inputvoltage:2x9…54VDC; Inputcurrent:2x12.5A;Outputvoltage:
9…54VDC;Outputcurrent:25A
|
Item No. |
Pack. Unit |
|
787-783 |
1 |
|
|
|
<![endif]>H
D |
W |
|
Features:
•Redundancy module with two inputs for decoupling two power supplies
•For redundant and fail-safe power supply
•WithLEDforinputvoltagemonitoringonsite
Input |
2x24VDC |
Nominal input voltage Ui nom |
|
Input voltage range |
2x9…54VDC |
Nominal mains frequency range |
0Hz |
Input current Ii |
≤12.5A(perpath) |
Output |
|
Nominal output voltage Uo nom |
24VDC |
Output voltage range |
9…54VDC(Ui −Voltagedrop) |
Voltage drop |
≤0.8V(input/output) |
Nominal output current Io nom |
25 A |
Output power (max.) |
1350W |
Nominal output power |
600W |
Signaling and Communication |
1xIN1LED(green);1xIN2LED(green); |
Signaling |
|
Efficiency/PowerLosses |
1xOUTLED(green) |
|
|
Power loss Pl |
≤19W(nominalload) |
Efficiency |
≥96% |
SafetyandProtection/EnvironmentalRequirements |
500VDC |
Isolation voltage (connectors – housing) |
|
Protection class/protection type |
III / IP20 (per EN 60529) |
Short-circuit-protected |
No |
Parallel operation/series operation |
Yes/no |
MTBF |
> 10 million h (per IEC 61709) |
Surrounding air temperature (operation) |
−25…+70°C |
Relative humidity |
≤95%(nocondensationpermissible) |
Derating |
−2.66%/K(+55°C<Tamb≤+70°C) |
Pollution degree |
2 |
Connection Data |
Push-in CAGE CLAMP® |
Connection technology |
|
Input/output(solid/fine-stranded/AWG) |
0.5…6mm²/0.5…6mm²/20…10AWG |
GeometricData/MechanicalData/MaterialData |
50x130x92;depthfromupper-edgeofDIN-rail |
Width x height x depth (mm) |
|
Mounting type |
DIN-35rail(EN60715) |
Weight |
470 g |
StandardsandSpecifications |
CE; UL 508 |
Approvals/standards/specifications |
490 |
WAGO Electronic Interface |
|
|