AC Input voltage (V)
Load (%)
DC Input voltage (V)
Load (%)
Temperature (°C)
Load (%)
Operating and Assembly Instructions, Rev. 1.1
9970-0966/0787-1721
-
-
Please keep!
L
N
PE
EPSITRON® ECO Power 787-1721
Switched-Mode Power Supply
Fig. 1: 787-1721 Switched-Mode Power Supply Unit
1. Safety Information and Application Notes
Congratulations on your purchase of this high-quality product. When used as intended in the described scope of application, it will
provide years of reliable service. As with every technical product, however, risk of personal injury or material damage can arise with
improper use, inappropriate removal of necessary covers or incorrect installation or operation. Follow these operating instructions and
proceed according to the accepted technology standards. All work relating to installation, startup and operation, as well as maintenance, must be performed by qualified specialists (IEC 60364, VDE 0105).
1.1 Packaging
Please inspect the equipment promptly for transport damages such as deformation and loose parts. Please report damages to the
transport company immediately, even if the outer packaging is undamaged.
1.2 Storage
Admissible storage temperature: -25 °C to +70 °C
Admissible air humidity: 10% to 95% relative air humidity; no condensation
For long-term storage: At storage temperature +25°C, equipment with built-in condensers
must be attached to the system voltage for at least 5 minutes every 2 years.
1.3 Instructions for Installation and Operation
Protect equipment from inappropriate stress. Particularly during transport and handling, ensure that no parts are bent and that electrical
spacing remains constant. Avoid touching the electrical components and contacts. Keep sufficient distance from adjacent parts so as to
avoid interfering with the cooling! During operation, the equipment (pursuant to the degree of protection) can have hot surfaces. Never
assemble and wire the equipment when the power is connected. Observe the product description and the technical information in our
main catalog, as well as the labels on the equipment and on the type plate. Perform the installation according to the local conditions,
applicable regulations (e.g., VDE 0100), national accident prevention specifications (e.g., UVV-VBG4 or BGV A2) and accepted
technical regulations. This electrical equipment is intended to be installed in electrical systems or machines and fulfills requirements of
the low voltage directive (2006/95/EG). When installing in machines, normal operation must not commence until it is determined the
machine complies with the requirements of the machinery directive (2006/42/EG); EN 60204 shall be observed. Commencement of
normal operation is only allowed under compliance of the EMC directive (2004/108/EG). The manufacturer of the system or machine
is responsible to ensure compliance with the limit values required by EMC legislation.
1.4 Maintenance and Assembly
Electrical equipment does not typically require special maintenance; however, depending on the degree of protection, it must be protected from dust accumulation, moisture, radiation and aggressive chemicals. Repairs shall only be undertaken within the scope of the
measures outlined in these operating instructions. If an equipment failure does occur, please send the equipment to us to be repaired.
Please provide the following information: type of failure, attendant circumstances (operating conditions, wiring), assumptions about the
cause of failure, previous uncommon occurrences, etc.
1.5 Disposal
Please observe current regulations and dispose of equipment according to material composition; e.g., electronic scrap (circuit boards),
plastic, sheet metal, copper, etc.
1.6 Modifications
The product documentation has been prepared and checked with great care. However, no guarantee can be made regarding
completeness and absence of failure. Any transfer of specifications to the respective application should be checked. The technical data
describes the product characteristics but does not guarantee them. We reserve the right to make changes that further the technical
progress.
2. Application Area
This equipment is a primary switched-mode power supply unit. It is a mounting component used to supply energy to industrial electric
and electronic users of information technology, automation, plant construction, process engineering, control engineering and building
automation. Without additional measures, this equipment shall not be used:
- in places with a high concentration of ionizing radiation
- in places with difficult operating conditions;
e.g. dust formation, caustic vapors or gases, Strong electric or magnetic fields
- in facilities which require special monitoring;
e.g. elevators, electrical equipment in particularly dangerous places
An “additional measure“ can be installing this equipment in a cabinet or a box.
3. Special Conditions for Safe Use
This power supply unit shall only be operated in dry conditions and shall be mounted on a DIN 35 rail (acc. to EN 60715).
The power supply unit is intended to be installed within a tool-accessible IP54 enclosure.
The power supply unit shall be used in an environment of not more than pollution degree 2.
Use copper conductors, only, rated to at least 105°C. A minimum 2.5 mm² earthing conductor must be used.
Output side ( - ) shall be earthed due to EN 62368-1 and EN 60204-1.
Provision shall be made to prevent the rated voltage being exceeded by transient disturbances of more than 140% of the peak rated
voltage.
Acc. to EN 60335-1, disconnection from the mains supply must be possible after installation. Therefore a switch for all poles shall be
incorporated in the fixed wiring in accordance with the wiring rules.
Refer to derating curves for load and ambient conditions (chapter 11). Ambient temperature range T
The cooling of this power supply unit shall not be impaired. For consistent heat dissipation, mount horizontally (air inlet below, outlet
above). Other mounting positions: At user‘s risk. In that case, please do not exceed max. 50% power output and max. +45°C ambient
temperature T
Depending on the operating mode, audible noise may develop.
According to EN 60335-1, the appliance is not to be used by persons (including children) with reduced physical, sensory or mental
capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction. Children being supervised not
to play with the appliance. Cleaning and user mainenance shall not be made by children without supervision.
4.1 Assembly (on DIN rail)
The hook on the reverse side connects the power supply unit to the uppershank of the DIN 35 rail (see Fig. 2a). The power supply unit then snaps in
place by pressing it down in the direction of the rail and by simultaneously
pulling the latch on the underside.
4.2 Disassembly (from DIN rail)
By pulling the latch on the underside, the rail support release is activated. By
tilting the power supply unit forward, it can come unhinged from the rail (see
Fig. 2b).
4.3 Other mounting options
The DIN rail mounting adaptor can be fastened on the side of the power
supply, too. Please use the screws delivered with the DIN rail adaptor, only
(see Fig. 2c).
The power supply unit can also be fastenend with screws (M4) to a mounting
plate. Please use screw mount adaptor (see Fig. 2d).
. The minimum distances to adjacent parts need to be obeyed.
amb
Fig. 2a: Assembly Fig. 2b: Disassembly
Fig. 2c: Side mounting Fig. 2d: Screw mounting
WAGO Kontakttechnik GmbH & Co. KG
Hansastr. 27, 32423 Minden, Germany
www.wago.com
+
+
L
N
PE
: -20°C ≤ T
amb
≤ +60°C.
amb
DC+
DC+
DC-
DC-
GB
5.1 Connections
Check the appropriate operating voltage before connecting the equipment (see type plate).
5.2 Terminal Strips
Connecting the supply lines is performed on the input and output sides via securely soldered WAGO 236 Series Terminal Strips with
CAGE CLAMP
On the input side, the black clamping points are intended for the L, N and PE connections.
On the output side, four blue clamping points are available: two for “+“ and two for “-“ (see Fig.1).
Output side ( - ) can be earthed due to EN 62368-1 and EN 60204-1.
5.3 Connecting Cables
The WAGO 236 Series Terminal Strips with CAGE CLAMP
AWG 12 (solid or fine-stranded). With respect to conductor cross-section dimensions, note the possible output current with a measurement of approx. 1.6 x I
6. LED
A green LED [DC OK] serves as an output voltage indicator (U
7. Setting up the output voltage
The frontal trim-pot [Adjust] can be used to externally set up the output voltage of DC 10 V to 14 V (see Fig. 1).
8. Parallel Connection (on the output side)
In parallel operation, set the output voltage of the devices which are to be connected in parallel to precisely the same value, if possible.
Additionally, the wire resistance from the power supply unit to the load must be nearly identical. Only devices of the same type shall be
used for connecting in parallel.
Notes:
Please use external rail-mounted terminal blocks when connecting in parallel. A parallel connection directly on the output side of the
terminal strips of the device is not allowed. When decoupling the outputs in parallel mode, the use of diodes in the positive path is
recommended. These diodes must be configured for the device‘s maximum output current.
9. Inrush Current
If several devices are supplied on the input side using the same electric current, higher inrush currents can result. In this case, the use of
auxiliary relays, which cause a time delay in start-up, is recommended (see Fig. 4).
The number of devices connected to a circuit using the same electric current arises from the amount of leakage current. Acc. to
EN 62368-1, this shall not exceed a maximum of 3.5 mA.
L
N
Fig. 4: Time delay in start-up of power supply units Fig. 5: Output characteristics
10. Overload or Short Circuit
The equipment‘s output is electronically protected from overload and short circuits. If the output current I
l
out,nom
In case of short circuit (I
The device will turn on the output voltage periodically and test the output circuit for short circuit.
After eliminating the overload or short circuit, the power supply unit automatically supplies the output voltage as indicated.
11. Derating
The maximal load is dependent on the ambient air temperature and the input voltage.
Equipment evaluated with the following rated values:
U
in,nom
If equipment is used outside these ratings, additional derating has to be considered:
A derating of -3.0 %/K shall be taken into account for ambient temperature T
An additional derating of -2 %/V shall be taken into account for input voltages U
100
Fig. 6: Temperature derating curve Fig. 7: Input voltage derating curve
12. Standards and Approvals
Electrical safety and EMC (electromagnetic compatibility) is provided through the equipment configuration in accordance with the cited
standards. The equipment conforms to the legal stipulations and standards for conformity and bears the and the TÜV mark.
®
connection technology. The clamping points can be opened with a tool (e.g. WAGO 210-657 or 210-658).
®
connection technology are suited for single conductors of up to 2.5 mm² ,
.
out,nom
> DC 9 V), (see Fig. 1).
out
K1S
K2K1
L
+
787-17xx
N
K2
L
K3
K3
787-17xx
N
L
787-17xx
N
R
L1
–
+
RL2
–
+
RL3
–
DC 12V
(see Fig. 5), the SMPS will be in overload. The output voltage will be reduced.
> 1.4 x I
out
AC 110 ... 240 V, P
80
60
55
40
20
-20 -10 03040506070
out,nom
45
), the green LED [DC O.K.] will turn off, and output voltage U
out, nom
96 W, T
+45°C and U
amb
100
80
60
40
20
90 100 110 230
AC 100 ... 240 V, P
in,nom
amb
> +45°C (see Fig. 6).
U
out
Constant
Power
Mode
0 105%100% 160%140%
is greater than 1.05 to 1.4 x
out
will be turned off.
out
76.8 W, T
out,nom
< AC 100 V (see Fig. 7).
in
264
amb
100
80
60
40
20
125 140
+45°C.
Electrical safety acc. to EN 62368-1: 2014 + A11: 2017 and EN 60335-1: 2012
EMC Emission of interference acc. to EN 61204-3: 2000
EMC Immunity to interference acc. to EN 61204-3: 2000
13. Technical Data
Input (AC IN)
Rated input voltage U
Input voltage range: AC 90 V to 264 V (see Fig. 7),
: AC 100 V to 240 V; DC 140 V to 340 V
in,nom
DC 125 V to 375 V
(external fuse necessary for DC supply)
Frequency: 50 Hz to 60 Hz
Frequency range: 47 Hz to 63 Hz
Input current Iin: < 3.0 A (at AC 100 V and nominal load)
Peak input current: < 18 A (at AC 230 V)
Discharge current: < 3.5 mA (at AC 230V)
Power factor: > 0.45 (at AC 230 V and nominal load)
Mains failure hold-up time: > 10 ms (at AC 230 V)
Output (DC OUT)
Rated output voltage U
Output voltage range: DC 10 V to 14 V; adjustable
: DC 12 V (default setting), SELV
out,nom
Adjustment accuracy: 1%
Residual ripple: < 150 mVpp
Nominal Load Pout,nom: 96 W (AC 110-240 V); 76.8 W (AC 100-240 V)
Output current I
6.4 A (at AC 100-240 V and DC 12 V)
: 8.0 A (at AC 110-240 V and DC 12 V)
out,nom
Efficiency/power losses
Efficiency: typ. 80% (at AC 230 V and nominal load)
Power loss: typ. 20 W (at AC 230 V, DC 12 V, 8 A)
Fuse protection
Internal protection: 3.15 A / 250 V
Recommended backup fusing: Wire breaking 6 A or 10 A, B characteristic
Transient overvoltage protection: Varistor
Connection
Connection technology: CAGE CLAMP
Type of wire: Solid or stranded wire
®
(WAGO Series 236)
Cross section: 0.08 mm² to 2.5 mm² / AWG 28 to12 (Series 236)
Stripped lengths: 5 to 6 mm / 0.20 to 0.24 in (Series 236)
Input side: 3-pole, black, for L, N and PE (Series 236)
Output side: 4-pole, blue, for 2x + und 2x – (Series 236)
Dimensions and weight
Dimensions (mm) W x H x L 60 x 130 x 99 (Length L from upper-edge of DIN 35 rail)
Weight: 0.55 kg
I
out
I
out,nom
Environmental requirements
Storage temperature: -25°C to +70°C
Ambient temperature range T
Relative humidity (without condensation): 10 % to 95 %
: -20°C ≤ T
amb
≤ +60°C
amb
Climatic class: 3K3 (acc. to EN 60721)
Load Derating: Equipment evaluated with the following rated values:
U
U
If equipment is used outside these ratings, additional derating
(see chapter 11) has to be considered:
-3.0 %/K for +45°C < T
-2.0 %/V for U
Pollution degree: 2 (acc. to EN 50178)
Temperature coefficient: < +/- 0.05%/K for -10°C ≤ T
MTBF: > 100'000 h (acc. to MIL-HDBK-217)
AC 110 ... 240 V, P
in,nom
AC 100 ... 240 V, P
in,nom
< AC 100 V
in
out,nom
out,nom
≤ +60°C
amb
≤ +50°C
amb
96 W, T
76.8 W, T
+45°C and
amb
+45°C
amb
Cooling
During operation, some inner components can heat up to more than +100°C. The enclosure surface can heat up to more
than +60°C, minimum distance from adjacent parts in case of natural convection and ambient air temperature +60°C, U
AC 230 V, P
left/right: 15 mm
out
52.8 W:
in
above/below: 70 mm
Safety and protection
Protection class: prepared for protection class I
Degree of protection: IP20 acc. to EN 60529
Overload protection: Reduction of output voltage (see chapter 10) if l
Short-circuit protected: yes
> 1.05 to 1.4 x l
out
out,nom
Idling-proof: yes
375
Feedback voltage: max. 20 V
Parallel operation: yes, max. 2 power supply units for increased power (see chapter 8)
Serial operation: yes, max. 4 power supply units
Vibration stress: 0.7 g (acc. to EN 60068-2-6)
Shock stress: 15 g (acc. to EN 60068-2-27)
Isolation voltages: AC 1.5 kV for input side and PE
AC 3.0 kV for input and output sides
AC 0.5 kV for output side and PE
SELV: acc. to EN 60335-1
Subject to design changes