Input and output process image (CAN) max. 2000Worte/2000Worte
Indicators LED (SYS, RUN, I/O, CAN, BF, DIA, U1 U4) red/green/orange:
Status system, program, internal data bus, CANopen, PROFIBUS,
PROFIBUS diagnostics, status programmable by user (can be used
via CODESYS library); LED (A, B) green: System power supply status,
field supply
System supply voltage
DC24V(-25 +30%);via wiring level (CAGE CLAMP connection)
®
Input current typ. at rated load (24 V) 550 mA
Total current for system supply 1700 mA
Field supply voltage DC24V(-25 +30%);via power jumper contacts
Current carrying capacity of the power jumper contacts 10 A
Number of outgoing power jumper contacts 3
Isolation 500 V system/supply
Connection data
Connection technology: communication/fieldbus PROFIBUS:1 x D-Sub 9 socket;CANopen:1 x D-Sub 9
connector;Modbus TCP/UDP:2 x RJ-45;Modbus RTU:1 x D-Sub 9
socket;RS-232 serial interface:1 x D-sub 9 socket;RS-485
interface:1 x D-Sub 9 socket
Connection technology: system supply
2 x CAGE CLAMP
®
Connection technology: field supply
6 x CAGE CLAMP
®
Connection type (1) System/field supply
Solid conductor 0.08 2.5mm²/ 28 14AWG
Fine-stranded conductor 0.08 2.5mm²/ 28 14AWG
Strip length 8 9mm/ 0.31 0.35inch
Connection technology: Device configuration 1 x 4-pole male connector
Geometrical Data
Width 112mm/ 4.409inch
Height 71.9mm/ 2.831inch
Height from upper-edge of DIN-35 rail 64.7mm/ 2.547inch
Depth 100mm/ 3.937inch
Mechanical data
Weight 264.2 g
Color light gray
Housing material Polycarbonate, polyamide 6.6
Conformity marking CE
Environmental Requirements
Surrounding air (operating) temperature -20 60°C