Input and output process image (internal) max. 1000Worte/1000Worte
Input and output process image (MODBUS) max. 1000Worte/1000Worte
Input and output process image (CAN) max. 2000Worte/2000Worte
Indicators LED (SYS, RUN, I/O, U1 … U6) red/green/orange: Status system,
program, internal data bus, CANopen, status programmable by user
(can be used via CODESYS library); LED (A, B) green: System power
supply status, field supply
System supply voltage
DC24V(-25 … +30%);via wiring level (CAGE CLAMP connection)
®
Input current typ. at rated load (24 V) 550 mA
Total current for system supply 1700 mA
Field supply voltage DC24V(-25 … +30%);via power jumper contacts
Current carrying capacity of the power jumper contacts 10 A
Number of outgoing power jumper contacts 3
Isolation 500 V system/supply
Connection data
Connection technology: communication/fieldbus CANopen:1 x D-Sub 9 connector;Modbus TCP/UDP:2 x RJ-45
Connection technology: system supply
2 x CAGE CLAMP
®
Connection technology: field supply
6 x CAGE CLAMP
®
Connection type (1) System/field supply
Solid conductor 0.08 … 2.5mm²/ 28 … 14AWG
Fine-stranded conductor 0.08 … 2.5mm²/ 28 … 14AWG
Strip length 8 … 9mm/ 0.31 … 0.35inch
Connection technology: Device configuration 1 x 4-pole male connector
Geometrical Data
Width 78.6mm/ 3.094inch
Height 71.9mm/ 2.831inch
Height from upper-edge of DIN-35 rail 64.7mm/ 2.547inch
Depth 100mm/ 3.937inch
Mechanical data
Weight 210 g
Color light gray
Housing material Polycarbonate, polyamide 6.6
Conformity marking 1
Environmental Requirements
Surrounding air (operating) temperature -20 … 60°C
Surrounding air (storage) temperature -40 … 85°C