Memory card slot Push-push mechanism, sealable cover lid
Number of modules per node max. 4
Input and output process image (internal) max. 1000Worte/1000Worte
Input and output process image (MODBUS) max. 1000Worte/1000Worte
Indicators LED (SYS, RUN, I/O, U1 … U7) red/green/orange: Status system,
program, internal data bus, status programmable by user (can be
used via CODESYS library); LED (A, B) green: System power supply
status, field supply
System supply voltage
DC24V(-25 … +30%);via wiring level (CAGE CLAMP connection)
®
Input current typ. at rated load (24 V) 550 mA
Total current for system supply 1700 mA
Field supply voltage DC24V(-25 … +30%);via power jumper contacts
Current carrying capacity of the power jumper contacts 10 A
Number of outgoing power jumper contacts 3
Isolation 500 V system/supply
Connection data
Connection technology: communication/fieldbus Modbus TCP/UDP:2 x RJ-45;Modbus RTU:1 x D-Sub 9 socket;RS-
232 serial interface:1 x D-Sub 9 socket;RS-485 interface:1 x D-Sub
9 socket;Telecontrol protocols:1 x D-sub 9 socket;Telecontrol
protocol IEC 60870-5-104:1 x RJ-45;Telecontrol protocol IEC
61850:1 x RJ-45;Telecontrol protocol DNP3:1 x RJ-45 or D-sub 9
socket
Connection technology: system supply
2 x CAGE CLAMP
®
Connection technology: field supply
6 x CAGE CLAMP
®
Connection type (1) System/field supply
Solid conductor 0.08 … 2.5mm²/ 28 … 14AWG
Fine-stranded conductor 0.08 … 2.5mm²/ 28 … 14AWG
Strip length 8 … 9mm/ 0.31 … 0.35inch
Connection technology: Device configuration 1 x 4-pole male connector
Geometrical Data
Width 78.6mm/ 3.094inch
Height 71.9mm/ 2.831inch
Height from upper-edge of DIN-35 rail 64.7mm/ 2.547inch
Depth 100mm/ 3.937inch
Mechanical data
Weight 231.307 g
Color light gray
Housing material Polycarbonate, polyamide 6.6