Resolution (over entire range) 0.1 °C
Conversion time (typ. ≤) 320 ms
Measuring error (25 °C) < ± 6 K (volt. input < ± 2 K, cold junct. < ± 4 K)
Temperature coefficient < ± 0.2 K/K
Sensor types Thermoelement K; konfigurierbar: L, J, E, T, N, U, B, R, S, mV
Temperature range sensorabhängig
Cold junction compensation at each pair of terminal blocks
System supply voltage DC5V;via data contacts
Current consumption, system supply (5 V) 65 mA
Isolation 500 V system/supply
Connection data
Connection technology: In-/Outputs
8 x CAGE CLAMP
®
Connection type (1) Inputs/Outputs
Solid conductor 0.08 … 2.5mm²/ 28 … 14AWG
Fine-stranded conductor 0.08 … 2.5mm²/ 28 … 14AWG
Strip length 8 … 9mm/ 0.31 … 0.35inch
Geometrical Data
Width 12mm/ 0.472inch
Height 69.8mm/ 2.748inch
Height from upper-edge of DIN-35 rail 62.6mm/ 2.465inch
Depth 100mm/ 3.937inch
Mechanical data
Type of mounting DIN-35 rail
Material Data
Color light gray
Housing material Polycarbonate, polyamide 6.6
Fire load 1.243 MJ
Weight 38.323 g
Conformity marking 1
Environmental Requirements
Surrounding air (operating) temperature 0 … 55°C
Surrounding air (storage) temperature -40 … 85°C
Protection class IP20
Degree of pollution (5) 2 per IEC 61131-2