Wagner & Co SUNGO SL Operating Instructions Manual

Page 1
OPERATING INSTRUCTIONS, Version SW1203/3.00/ HW3.0
W agner& C
o
Solar Controller SUNGO SL
W agner& C
o
The benefits at a glance
-
ance values and system status with clearly visible sym
-
bols for easy readability.
Easy and safe operation via four buttons for vertical and horizontal scrolling through the menus.
Extensive diagnostics for monitoring system functions, eg. sensor cutoff and monitoring of temperature differ
-
ence “T too high”
Integrated security functions such as collector cooling, storage tank cooling, system protection and vacuum tube collector function.
Solar charging of 1 and 2 tank systems
Choice of thermostat function or return temperature in
-
crease
Balance/reset values
5 temperature inputs PT1000
1 output, speed-controlled
The sensor T5 (solar return) and an external volume measuring device provide energy measurements
in
kWh.
NEW – now also SECUSOL system ready!
Contents
1. Technical Description ................. 2
2. General Safety Guidelines ............... 4
2.1 Installer’sQualifications ................ 4
2.2 OperatingRequirements ............... 4
2.3 Installationand OperatingInformation ....... 4
3. Installation........................ 4
3.1 Installationof the Housing............... 4
3.2 ConnectingWires ................... 5
4. Operation ........................ 6
4.1 Displayand Buttons .................. 6
4.2 InformationMenu ................... 8
4.3 SettingsMenu...................... 9
4.4 ManualOperationMenu ...............10
4.5 SpecialFunctionsMenu ................10
4.6 Service– System Messages ..............11
4.7 Service– Sensor Control ................11
5. Application Examples .................11
5.1 StandardSingleTankSystem .............11
5.2 StandardDualTankSystem ..............12
5.3 SECUSOLSystem....................12
Figure 1 Solar Controller SUNGO SL.
Solar Thermal / Solar Circuit EN-SUNGO-SL_BA-0809-1122P300 · 1316BED008-30B-E 1
Page 2
2 EN-SUNGO-SL_BA-0809-1122P300
1. Technical Description
Solar Controller SUNGO SL
Material
100 % recyclable ABS-housing for wall mounting
Dimensions (LxHxWinmm) 173x138x51
Protection type IP40 according to VDE 0470
Rate of radio interference N according to VDE 0875
Operating voltage
230 Volt AC; 50 Hz;
-10% to +15%
Diameter of cable max. for 230 V connections
2.5 mm² unifilar or finely stranded
Temperature sensor / Temperature range
Pt1000; 1000 W at 0 °C; Range: -30 °C to +225 °C
Sensor load
The cable of the sensor must be installed with no tension. The sensor must not be loaded mechanically when the temperature of the collector is more than 60 °C.
Test voltage
4 kV 1 min according to VDE 0631
Switching voltage Output parameters of switches
230 Volt AC 1A / ca. 230 VA for cos ϕ = 0.7-1.0 for each output
Internal mains protection
Microfuse5x20mm; 2 A/T
Operating temperature (internal) / storage temperature
0° to +50 °C /
-10° to +65 °C
Weight ca. 360 g
Solar Charging
The solar circuit pump is switched on and off by means of a temperature difference control. The sensors T1 (collector) und T2 (tank, bottom) are requiredas control elements. The on/off conditions and the temperature limitation can be variably set in the settings menu. Note: The temperature limitation always affects sensor T2 (tank, bottom).
Speed Control
The solar circuit pump can be controlled via speed control (in this case impulse packet control). This means that indi
­vidual sine half-waves in the alternate current are switched on or off depending on the temperature difference. There
­fore the speed can be altered within a range of 30-100% which results in longer system run times. The minimum speed can be custom set.
Sensor T3 (tank, top)
Sensor T3 (tank,top) has different functions.By default it is the measuring sensor for the top of the tank. In that case it has no switch function and is not monitored by the diag
­nostics system. With the return temperature increase function activated it functions as ahot sensor (source).Withthe thermostat heat
­ing with additional sensor function activated it functions as an additionalsensor.In both casesthis sensor is used in the hotareaofthetankandaffectsswitchingoutputA2.
If used in this way the sensor function is monitored as nor
-
mal by the diagnostics system.
Balance Values
In addition to the actual values of the sensors T1 (collector) and T2 (tank, bottom) the display also shows balance val
­ues which represent the smallest and biggest temperature values for each sensor. After reset the actual temperature value is displayed.
Manual Operation
Allows switching inputs andoutputs on or off manually. On exiting themanual operation menu,the software returns to automatic operation. The manual operation menu can be used for amaximum of 8 hours. After that the softwareauto
­matically switches back to automatic operation and to the information menu.
Manual Lag Function
In order tocheck the temperature valuesin the information menu even when the outputs are set manually, a time lag has to be selected in the manual lag function in the manual operation menu. On exiting the manual operation menu, this time span passes once and then is set back to zero. In this mode a blinking symbol for the manual operation is shown in the information menu.
Collector Cooling
The tank is loaded up to the preset temperature limitation which affects sensor T2(tank,bottom).If the preset temper­ature limitation is exceeded output A1 (solar circuit pump) switches off. If the temperature of T1 (collector) then rises above theselectable standardvalue of 110 °C the solar cir­cuit pump is switched on in order to cool the collector. It switches off again when the temperature at the collector sensor has decreased by 10 K. This type of intermittent operation of the solarcircuit pump means that the collector is never or only rarely in an idle state. If the preset tank temperature limitation is exceeded by 5 Kthecollector cooling functionissuppressed.Thesys
­tem shuts down completely.
Storage Tank Cooling
Storage TankCoolingmeans that ifnecessary the tanktem
­peraturecan be reduced downtoa preset lowest switching off value (setting for vacations). When the collector cooling function is activated storage tank cooling will also become active. In order for storage tank cooling to become active the fol
­lowing 3 conditions must be met:
1. Temperature T2 (tank, bottom) must be higher than or equal to the preset tank temperature limitation plus 2 K.
2. Temperature T2 (tank, bottom) must be higher than the preset switching off value for storage tank cooling.
3. Temperature T1 (collector) must be lower than tempera
­ture T2 (tank, bottom) minus 10 K.
In order forstorage tank coolingto switch offone of the fol
­lowing 2 conditions must be met:
1. Temperature T2 (tank, bottom) is lower than the switch
­ing off value for storage tank cooling.
2.Temperature T1(collector) must be higher than tempera
­ture T2 (tank, bottom) minus 2 K.
Page 3
EN-SUNGO-SL_BA-0809-1122P300 3
Vacuum Tube Collector Function
The vacuum tubecollector function allows operation of the solar heating system even if sensor T1 (collector) is in
-
stalled in the connecting pipe of the collector. If the tem
-
perature increase at sensor T1 exceeds the preset switch
­ing on value for the collector temperature increase (standard: 1K) the solar circuitpumpis switched on forthe duration of a preset lag time (standard: 15 s). During this time the switching on difference and the solar charge between sensor T1 (collector) and sensor T 2 (tank, bottom) has to be activated, otherwise the solar circuit pump will switch off again. The rise intemperature at sensorT1 (collector) ismeasured again immediately after the last runtime of the pump.
System Messages
The system messages for interrupted or shorted-out sen
­sors are represented by symbols on the display.For better recognition of the system messages
the display illumina
­tion switches on and off every second as long as the error prevails and no key entry is made.
Triac
The Triac is anelectronic on/off switchfor the 230Voutputs of the SUNGO Controller. Function: A triac switch consists of 2 diodes which can be switched anti-parallel (= antiparallel thyristors). The thyristors switch through the positive or negative sine half­wave as long as a switching on difference exists. The triac switch switches off when the temperature falls below the switching-off difference.
System Protection
In order to protect the system components (solar circuit pump, 2 or 3 way valves etc.) in the solar heating circuit from extremely high temperatures the solar charge is stopped completely if a temperature limit at the collector sensor is exceeded, even if this was permitted on account of a temperature difference between sensor T1 (collector) and sensor T2 (tank, bottom). The standard temperature value for activating the system protection function is 135 °C. However, this value can be variably set within a range of 115° to 200 °C.
Dual Tank Operation
The SUNGO SL is capableof controlling a dual tank system by using output A2 for switching between tanks with the help of a 3 way valve.Change the menuitem 0–1to0–2in order to control a dual tank system. Note: If the dual tank option is selected menu item 10 can no longer be activated.
Preference
The SUNGO SL always uses tank 1 as a preference for the dual tank option. This cannot be changed.
Thermostat
The thermostat function for switching on can be set at a range between 0° to 130 °C with a variable difference be
­tween 1 to 40 K for switching off.Choose between the op
­tions heating and cooling. With the heating option activated output A2 switches on if the current temperature T4 fallsbelow the preset switching on level. Output A2 switches off if the current temperature
T4 is higher than the switch-on level plus the switch-off dif
­ference. With the heating option an additional sensor T3 can be ac
­tivated. If this is the case A2 is only switched on if tempera
­ture T3 ishigher than theswitching on level plus the switch
­ing off difference plus the additional difference for T3. With the cooling option activated output A2 switches on if the current temperature T4 falls below the preset switch level. Output A2 switches off if the current temperature T4 is lower than the switch level minus the switching off difference. There are 3 independent time windows available for the thermostat. If no time window is activated time window 1 has to be set to 0:00 and 23:59.
Return Flow Boost
This is a freely adjustable temperature differencefor simple heating support which leads the heating return-flow T4 (drain) to the heating boiler, either directly or via the solar tank, depending on the preset temperature difference to the tank sensorT3 (source) , by switching the3 way valve on output A2. Note: In addition to the switching phase (black) on output A2, the switching head also requires a constant phase (brown).
SECUSOL Function
The solar heating systemisoperated on a drainback princi
­ple. This means if the solar circuit pump is not activated there is no solar fluid in the collectors and risers. See SECUSOL instructions for further details.
Measuring the Yield
For measurements of the solar yield in kWh.The heat yield is measured with a volume flow metre connected to input T7, an additional sensor T5 (return) and the existing sensor T1 (collector).
Page 4
4 EN-SUNGO-SL_BA-0809-1122P300
2. General Safety Guidelines
The following safetyadvice is designedto protect youfrom dangers that can arise from improper handling of devices, whether intentional or otherwise. A distinction is made be
­tween general advice presented here and specific advice presented throughout the guidelines.
DANGER for danger to the person Improper electrical installation of the device can lead to potentially fatal electric shocks as well as other health hazards.
CAUTION for danger to property This symbol indicates dangers that can result in damage to the components or the function of the control.
NOTE for additional information This symbol indicates practical advice and tricks of the trade which will be useful for installing and operating the control.
2.1 Installer’s Qualifications
Setting up and commissioning of the SUNGO SL must be carried out by a qualified installer.
All national andlocal safety regulationsneed to be com
-
plied with.
Please note that in case of a complaint the guarantee is only valid if correct commissioning has been certified in a commissioning report.
2.2 Operating Requirements
Application
Controlling solar thermal systems through the selection of applicable control patterns and additional functions to adaptthe control forthe required operation of the hy
-
draulic system.
The control must only be operated in dry rooms.
The control can be integrated into the solar circulation unit or mounted on the wall.
Limitations of use
If usedina non-solar thermalapplicationthe functionality of thecontrol hastobe checked before commissioning.If in doubt contact the control service of Wagner & Co.
If these operating requirements are not observed any claims under the warranty will not be accepted.
2.3 Installation and Operating Information
Any installation and wiring work has to be carried out in an idle state as during operation the voltage on the out
-
side of the triacs is 230 V.
Mains power mustbe connected to thecontrolfrom out
­side the solar station via an external ON/OFF Switch. This is also required to activate the special functions menu through switching the mains power ON/OFF.
Operating temperatures above 50 °C are not permitted for the control.
LCD display panels are designed in such a way that a specific reading position isrequired.When installing the control, be careful to place the display so that it is at eye level or slightly higher. This way you can ensure optimal display contrast.
The base of the control is divided into a safety low volt
­age section and a 230 V section by a crosspiece. Make sure that you do not confuse these sections during the installation process.
The default operating mode is the automatic mode.
Manual operation is used only for functional testing of the different hydraulic components (pump, 2/3 way valve). In this operating mode maximum temperatures or sensor functions are not monitored.
Do notoperatethesystemif the control,the wiring or the
connected 230 V mains are visibly damaged.
The control is fitted with a mains microfuse.
Collectors and hydraulic pipework can get extremely
hot during sunny periods. There is a risk of scalding when fitting the collector temperature sensor.
3. Installation
3.1 Installation of the case
Opening the case
No tools are required to open the control case. The lid folds overon top of the lower half. Youcan dislodge and lift up the lid by pulling gently on the side clips.
When fully opened the lid will not move so that you can take care of mounting and wiring comfortably.
Wall mounting
Use the supplied drillingtemplatetodrill the fixing holes for the controller.
Mount the control to the wall.
Do not overtighten the screws to avoid damage to the lower part of the housing.
Page 5
EN-SUNGO-SL_BA-0809-1122P300 5
Installation in the Solar Circulation Unit
With the screws mount the SUNGOSL on the wall holder of the solar circulation unit.
Break out the cable feeds which are located on the base housing next to the crosspiece.
Strip the 230 V cables in a way that the insulated single cables start directly at the feed to the base housing.
Hold cable clamps steady when screwing tight in order to minimisepressure on the circuit board. Thereis a dan
-
ger of the terminals to be torn off!
Finally connect to mains power.
When the controlis switched onthe voltage on thetriacs housing is 230 V AC.
3.2 Connecting Wires
Layout of the SUNGO SL Connections
All electrical connections are made to the circuit board at the bottom of the control. The sensor connections (safety low voltage)are located onthe right hand side andthe 230 V mains connections and the switching outputs A1 and A2 on the left hand side.
General connection rules
If flexiblewires are used andthe control iswall mounted, a strain relief must be fixed within or outside of the con
-
trol.
In this case you must crimp the wire ends.
If requiredPG9 screws canbe fixed atthe feed-throughs
in case of wall mounting.
230 V mains connection
Mains power is connected from outside the control via an ON/OFF Switch. This switch is not required if mains power is with a pro
­tective plug to a socket.
The control is suitable for mains operation at approx. 230 V/50 Hz.
All earth wires are connected to the PE terminals.
The neutral terminals (N) are connected electrically.
Switching output A1 is a 230 V normally open contact which is activated via speed-control. Switching output A2 is purely a normally open contact.
Connecting the temperature sensors
The wires of the temperature sensors can be extended: Up to 15 m length, 2 x 0.5 mm² cable can be used, be
­yond 15 m and up to 50 m 2 x 0.75 mm² is necessary. Shielded cables should be used for long connections to the collector. Do not connect the shielding at the sensor end,just trim and isolate.
The polarity of the temperature sensors is irrelevant and they can be connected either way.
The sensor wires mustbeinstalled separately from 230V mains cables.
Lightning Protector Module
The SUNGO SL is fitted with spike protection on all sensor terminals. Generally, further protection of the tank sensors is not required. Sensor T1 (collector) should be fitted with the sensor
con-
nection box SP2 with an overvoltage protection.
FUSE 5X20
T1 T2 T3 T4 T5
M
MMM
PE-PE A2
A1 L1
PE-PE N N N
M
ControllerIC
Triac
Plug for Display
Trafo
Potential Earth
Switching output
Solar circuit pump
Mains L1
Collector sensor, T1
Tank sensor, bottom,T2
Tank sensor, top /
Additional thermostat sensor /
return flow boost (source)
Thermostat /
return flow boost (sink), T4
Heat meter (yield), return flow sensor, T5
T7
M
“Volume flow meter” for yield measurement, T7
Figure 2 SUNGO SL circuit board components.
Page 6
6 EN-SUNGO-SL_BA-0809-1122P300
4. Operation
4.1 Display and Buttons
!
dT min max start stop
R
R
ok?
88888
°C %
KWh
x
Manual operation menu
Special functions menu
Balance or start / stop values
Units
Tank temp., top/ thermostat additional senso
r
Temperature thermostat/ return flow boost (sink)
Time slot thermostat
Tank temp., mid section/ return flow boost (source)
Confirm and save symbol
System error
Settings menu
Information menu
Temperature difference
Numerical display for temp. or sensor errors
Collector temperature
Symbol for reset value
Tank temp., bottom
Pump ON/ Pump OFF
Output A1 Output A2
Page 7
EN-SUNGO-SL_BA-0809-1122P300 7
dT max
__K
dT min
__K
__°C
T max
dT
__K
dT
__K
__°C
T start
__
d max
d min
__
__K
dT
4
4
1
__:__
__°C
T max
__°C
__K
__K
T min
dT max
dT min
I
I
2
2
2
3
3
__:__
__:__
__:__
__:__
__:__
__:__
R
R
R
R
stop
start
stop
start
stop
start
2
2
2
__°C
T min
Horizontal operating level
Vertical operating level
Set values
Settings menu as an example
Ý
Decrease
value
Ý
Increase
value
Activate
save function
ÝÝ
Activate
value
Save
value
Switching off diff. T3 - T4,
return temperature increase
Switching on diff. T3 - T4,
return temperature increase
Min temp. level,
return temperature increase
Temp. limitation,
return temperature increase
Stop time window 3, thermostat
Start time window 3, thermostat
Stop time window 2, thermostat
Start time window 2, xx thermostat
Stop time window 1, thermostat
Start time window 1, thermostat
Temperature limitation tank, bottom
Switching on difference T1 - T2, solar
Switching off difference T1 - T2, solar
Min. temp. source
Design temp. diff. speed control, solar
Min. speed, solar circuit pump
Max. speed solar circuit pump (SECUSOL)
Charge time solar heating system (SECUSOL)
Current time
Switching on temperature, thermostat
Switching off temperature, thermostat
Difference additional sensor T3, thermostat
Page 8
8 EN-SUNGO-SL_BA-0809-1122P300
4.2 Information Menu
Information menu
Menu item Description Display
Collector temperature; Current value °C
Collector temperature; Balance; minimum, resettable °C
Collector temperature; Balance; maximum, resettable °C
Tank temperature, bottom; Current value °C
Tank temperature, bottom; Balance; minimum, resettable °C
Tank temperature, bottom; Balance; maximum, resettable °C
Tank temperature, top; Current value °C
Operating hours, total; Balance h
R operating hours since last reset; Balance, display, resettable h
Tank temperature 1 or 2, bottom; (if 2 tank system is selected) Current value
°C
Tank temperature 1 or 2, bottom; (if 2 tank system is selected) Balance; minimum, resettable
°C
Tank temperature 1 or 2, bottom; (if 2 tank system is selected) Balance; maximum, resettable
°C
Operating hours tank 1 or 2, total; (if 2 tank system is selected) Balance
h
R operating hours tank 1 or 2 since last reset; (if 2 tank system is selected) Balance; display, resettable
h
Thermostat or return temperature increase (drain); Current value °C
Heat counter, return; (flow value corresponds to collector temperature) Current value
°C
Heat counter, total yield; Balance kWh
R heat counter since last reset; Balance, display, resettable kWh
Heat counter tank 1 or 2, total; Balance kWh
R heat counter, tank 1 or 2 since last reset; Balance, display, resettable
kWh
Pump symbol idle: Operating symbol Temperature difference (collector, tank) is smaller than required to activate the solar circuit pump. The solar circuit pump is off.
Rotating pump symbol: Operating symbol Temperature difference (collector, tank) is sufficient to activate the solar circuit pump. The solar circuit pump is running.
min
__°C
__°C
__°C
__°C
__°C
__°C
__°C
__°C
__°C
__°C
__h
__kWh
__kWh
__kWh
__kWh
__h
__h
min
min
max
max
max
__h
R
1 2
__°C
1 2
1 2
1 2
1 2
1 2
1 2
R
R
R
R
__°C
Page 9
EN-SUNGO-SL_BA-0809-1122P300 9
4.3 Settings Menu
Settings menu
Menu item Description Range Default setting
Temperature limitation tank, bottom 15 – 90 °C 85 °C
Switching on difference between collector and tank 3 – 40 K 5 K
Switching off difference between collector and tank 2 – 35 K 3 K
Min. temp. above which the switching difference is analyzed 5 – 90 °C 10 °C
Temperature limitation tank 1 or 2, bottom 15 – 90 °C 85 °C
Switching on difference between collector and tank 1 or 2 3 – 40 K 10 K
Switching off difference between collector and tank 1 or 2 2 – 35 K 3 K
Design temperature difference the speed control adjusts to 2 – 50 K 10 K
Minimum speed of the solar circuit pump 10% increments
30–100% 30%
Maximum speed of the solar circuit pump
Only with SECUSOL!
30–100% 100%
Charge time (s) of the solar heating system with speed 100 %; in 10 s increments
Only with SECUSOL!
20 – 360 s 60 s
Set current time (keep button pressed for faster run-through) 0:00-23:59 0:00
Switching on temperature thermostat
1
0° – 130 °C 30 °C
Switching off difference thermostat
1
1–40K 5K
Additional sensor difference for tank, top, can be selected in heating function.
1
3–20K 10K
Start time slot 1, thermostat
1
0:00-23:59 0:00
Stop time slot 1, thermostat
1
0:00-23:59 23:59
Start time slot 2, thermostat
1
0:00-23:59 0:00
Stop time slot 2, thermostat
1
0:00-23:59 0:00
Start time slot 3, thermostat
1
0:00-23:59 0:00
Stop time slot 3, thermostat
1
0:00-23:59 0:00
Temperature limitation return temperature increase
2
15°–90°C 85°C
Minimum temperature from which the switching on difference is read
2
15°–90°C 20°C
Switching on difference return temperature increase between temperature measure location T3 and T4
2
3–40K 4K
Switching off difference return temperature increase between temperature measure location T3 and T4
2
2–35K 2K
1
Only available if heating or cooling thermostat is used.
2
Only available if return temperature increase is used.
dT max
dT min
T max
__K
__K
__°C
dT max
dT min
dT
__:__
__:__
__:__
__:__
__:__
__:__
__:__
T max
d max
T start
T max
dT
dT max
T min
__°C
dT min
d min
1
1 2
1 2
1 2
__K
__K
__K
__K
start
stop
stop
stop
start
start
__K
__K
__K
__°C
__
__°C
__°C
__
__
dT
I
I
2
2
3
3
__°C
T min
2
R
2
R
2
R
2
R
Page 10
10 EN-SUNGO-SL_BA-0809-1122P300
4.4 Manual Operation Menu
Manual operation menu
Menu item Description Range Default setting
Off = 0/On = 1
Switching the solar circuit pump on or off manually (A1)
0–1 0
Off = 0/On = 1
Switching output A2 on or off manually (RLA or thermostat)
0–1 0
Activation of manual operation lag time in automatic mode 0 – 600 min 0 min
4.5 Special Functions Menu
During the first minute after switching on the control
activate the special functionsmenu byselecting it so thatparameterscanbe altered.Themenustays active for 1minuteaf
-
ter exiting it. On exiting themenuthe parameters can onlybeviewed but notchangedagain.Place the control intheidle position once again if you need to alter any functions.
Special functions menu
Menu item
Application Description Range Default
setting
0 System choice
0 – 1: Standard single tank system 0 – 2: Standard dual tank system 0 – 3: SECUSOL system (see SECUSOL instructions for further info)
1–3 1
1
System Protection
Off = 0/On = 1
Activation of system protection. Cannot be activated with SECUSOL!
0or1 1
2 System protection start temperature 115 – 200 °C 135 °C
3
Collector Cooling
Off = 0/On = 1
Activation of collector cooling. Cannot be activated with SECUSOL!
0or1 1
4 Collector cooling start temperature 100 – 150 °C 110 °C
5
Storage tank Cooling
Off = 0/On = 1
Activation of tank cooling. Only possible with collector cooling. Cannot be activated with SECUSOL!
0or1 0
6 Switching off temperature 30 – 90 °C 60 °C
7
Measuring the Yield
Off = 0/On = 1
Activation of yield measurement
0or1 0
8
Frost protection type 8-1: DC20 for standard systems 8-2: DC40 for vacuum tube collectors (ready mix)
1or2 1
9
Glycol fraction in %. 0% = No Glycol (pure water) 100 % = Pure Glycol (no water) Note: Glycol fraction for solar circuit can only be selected with DC20!
0–100% 40%
10
Function selection
10 – 0: Additional functions off 10 – 1: Thermostat, heating 10 – 2: Thermostat, heating with additional sensor T3 (tank, top) 10 – 3: Thermostat, cooling 10 – 4: return temperature increase
0–4 0
11
Vacuum Tube collector function
Off = 0/On = 1
Activation of vacuum tube collector function
0or1 0
12 Run time of solar circuit pump from reaching the switching on value 1 – 60 s 15 s
13 Switching on value for temperature increase at sensor T1 (collector) 1.0 – 5.0 K 1.0 K
The special functions menus should only be edited by expert personnel. Incorrect settings may adversely affect the solar heating system.
T stop
__
Page 11
EN-SUNGO-SL_BA-0809-1122P300 11
4.6 Service – System Messages
System information with display
Display Description Remedy
System messages
All system messages are displayed with a blinking caution symbol. In case of sensor errors the sensor in question is also marked with short circuit or interruption symbol.
Interruption
The sensor on the display or the pipe is interrupted.
Test the resistance value of the sensors and compare with the tables.
Check all connections to the sensor.
Short circuit
There is a short circuit on the sensor on the display, the cable or the output on the control.
dT too high
A value of 20 K is added to the switch-on difference between T1 and T2. The message is displayed if after 30 minutes the total difference has not been reduced.
Check wiring to the pump
Check system for air and vent if required
Check sensors and sensor wiring, replace sensors if required
4.7 Service – Sensor Control
Resistance values for Pt1000 sensors in relation to the temperature
-10°C 0°C 10°C 20°C 30°C 40°C 50°C 60°C 70°C 80°C 90°C 100°C 110°C
961 1000 1039 1078 1117 1155 1194 1232 1271 1309 1347 1385 1423
The working condition of the sensor can be checked with this table and an Ohm meter.
5. Application examples
5.1 Standard Single Tank System
!
Blinking
!
Blinking
!
Blinking
°C
!
Blinking
°C
Ttw
T4
T1
T3
T2
A
AB
B
Vr
P2
P3
TERMO
P1P1
CIRCO
T4A1T1
A2
T2T3
T7
T5
T1
Measuring the yield
Solar return-flow
Collector field
Cold water
Hot water
Version 1 – TERMO Combi Cylinder
Heating circuit
Oil or gas boiler
P1: Solar circuit pump P2: Heating circuit pump P3: Tank chargingpump Vr: Switch-over valvefor return temperature increase
T1: Collectorsensor T2: Tank sensor, bottom T3: Tank sensor, middle T4: Sensorheating return-flow T5: Yield measurement,return flow sensor T7: Yield measurement,volume flow metre
Collector field
Figure 3 Standard single tank system controlled by SUNGO SL.
Page 12
Figure 4 Standard dual tank system controlled by SUNGO SL.
5.2 Standard Dual Tank System
P3
P2
BWM
T1
T2
T3
Ttw
P1
A1
T1
SECUSOL
Ta
T7
T5
T1
T3
T2
Heating circuit
Hot water
Cold water
Measuring the yield
Solar return-flow
Collector field (EURO C22)
Oil or gas boiler
T1: Collectorsensor T2: Tank sensor, bottom T3: Tank 1 sensor,top (optional) T5: Yieldmeasurement, return flow sensor T7: Yieldmeasurement, volume flow metre
P1: Solar circuit pump P2: Heating circuit pump P3: Tank charging pump
Ttw: Hot water sensor (heatingcontrol) BWM: Thermostatic mixing valve
Collectorfield
5.3 SECUSOL System
P1
P3
P2
P1
CIRCO
Vu
T3 T2 T1T4
A1
A2
M
ECOplus
T1
T5
T7
AB
A
B
T4
T2
T1
T3
Ttw
Collector field
Heating circuit
Oil or gas boiler
Hot water
Cold water
Solar return-flow
Collector field
Measuring the yield
P1: Solar circuit pump P2: Heating circuit pump P3: Tank chargingpump Vu: Switch-over valve, tank charging
T1: Collector sensor T2: Tank1 sensor, bottom T3: Tank1 sensor, top T4: Tank2 sensor, bottom T5: Yield measurement,return flow sensor T7: Yield measurement,volume flow metre
Figure 5 SECUSOL system controlled by SUNGO SL.
Subject to modifications, errors excepted. · ©Wagner & Co, 2008 · www.wagner-solar.com
12 WAGNER & CO · Zimmermannstraße 12 · D-35091 Cölbe/Marburg ·
+49 6421 80 07-0 · Fax 8007-22
Loading...