Wagner & Co CIRCO 5 Technical Information/installation Manual

Page 1
TECHNICAL INFORMATION / INSTALLATION MANUAL
W agner& C
o
CIRCO5SolarCirculationUnit
Fast Installation
through pre-mounted parts and compression fittings for the connection to the solar circuit
High Energy Efficiency
All around insulation and speed controlled circulation pump (in combination with all SUNGO solar controllers)
Controlled heat flow
by two temperature resistant non return ball valves
Safe deaeration
by integrated air venting pipe
Variable Installation
wall mounting or fitted directly to the storage cylinder
the reliable pump station for efficient circulation of the heating fluid in combination with SUNGO controls
CIRCO 5 Solar Circulation Unit
Function Control
through flow meter and thermometers
Figure 1 CIRCO 5 solar circulation unit (SUNGO is an optional extra)
Solar Thermal / Solar Circuit EN-CIRCO-5-MA-0701-11217300 1
Page 2
2 EN-CIRCO-5-MA-0701-11217300
1. General Safety Guidelines
The following safety advice is deemed to protect against dangers that can arise from improper handling of the de
­vice, whether knowingly or unknowingly. We distinguish between general advice which is given on this page and specialadvicewhichcan be found inthe texts of the instructions. Watch for the symbols!
Qualification of the installer
Setting up, installation and commissioning of the CIRCO 5 solar circulation unit must be carried out by a qualified in
­staller. Please notethat in caseof a fault report the guarantee ben
­efits can only be claimed if the correct commissioning has been certified by a qualified person in the commissioning protocol.
Use and application
Function
The CIRCO 5 solar circulation unit is suitable for solar hot water systems and solar heating systems together with an
­tifreeze solar as recommended.
Limitations of use
Use is limited to the hydraulic layout of the schematic drawings supplied by Wagner and Co.
Some solar installationsfor spaceheating and the appli-
cation of vacuum tube collectors do require special means of overheating protection, like the installation of an auxiliary vessel or alternative positioningof the safety components.
The CIRCO 5 solar circulation unit can be mounted to a
wall or directly to the storage cylinder.
The CIRCO 5 solar circulation unitmust not be mounted
outside.
Norms and guidelines
EC conformity declaration The CIRCO 5 solar circulation unit has been designed and constructed in accordance with EU regulations.
Please regard national and EU regulations and guide
-
lines for installation work.
Danger to Persons Live-threatening electrical shocks, burns, bruising and other health hazards are possible during installation. Please ensure that you pay attention to guidelines that are indicated with this symbol in the documentation.
Caution Danger to Property This symbol indicates that damagemaybe done to compo
­nents of the solar circuit or the function of the same may be impaired seriously. Please makesure that you follow the in
­stallation procedure step by step as instructed.
Indicator for Additional Information This symbol points to practical advice, tricks of the trade which will make the installation and operation of the solar circuit easier.
Page 3
EN-CIRCO-5-MA-0701-11217300 3
2. Technical Information
List of parts supplied
The CIRCO 5 solar circulation unit is supplied pre-assem
­bled. SUNGO control and CIRCO expansion kit are not part of the unit. You can find additional accessories on the last page.
Maximum number of collectors to be installed
Coll.­Type
Serial-/Parallel connections * Serial connections
18 Ø 22 Ø 28 Ø 18 Ø 22 Ø 28 Ø
EURO 2 x 3 3 x 3 4 x 3 4 4 4
Parallel connections
LBM 67 4 5 6 1 2 2
LBM 100 2 3 4 1 2 2
* Number of fields each with 3 collectors connected in series
Table 1 Maximum number of collectors that can be installed depend
­ing on the collector type, way of connection and size of piping. Single length ofsolar circuitup to 20m; heat carrier:frostprotection/water40/ 60 % per.Volume,Volume flow = 35l/m²/hConnection and connection hoses at collectors are taken into account.
Size of expansion vessel
Fluid
litre
Coll. area
Vessel volume in litres for system height in metres
2,5 5 7,5 10 12,5 15
18 5 1212 12121818
20 7,5 18 18 18 18 18 24
23 10 24 24 24 24 24 24
24 12,5 24 24 24 24 24 24
27 15 35 35 35 35 35 35
32 20 35 35 35 50 50 50
Table 2 Size of expansion vessel depending on thefluid content of the entire system,collector areaandheightabove vessel (distancevessel to upper edge of collectors). Dimensioning scenario: system exposed to full sun light but inactive. These values are only valid up to about 0.5 litres per m² collector volume.
0
0,5
1,5 2,0
0
0 1,0 2,0 3,0
[
m/h
]
3
[m/s]
H [m]
economy
1,0
6
7
5
4
2
1
3
v
maximum
Figure 2 Pump characteristics curves
CIRCO 5 solar circulation unit
Order No. 150 201 14
Insulation EPP (λ = 0.039 W/mK),
in three parts with snap-lock
Mounting plate Steel, galvanised
Max. operating pressure 6 bar
Max. operating temperature 120 °C
Circulation pump ST 25/6 (230V, 50 Hz)
Wattage 3 pump levels, 44/62/81 Watt
Max. pumping height 600 mbar
Max. pumping volume 3.5 m³/h
Controller Suitable for SUNGOS/SL/SXL
Non-return valves 2 x Heat-resistant metal
Temperature indicator 2 Integrated Thermometers
Flow meter Flow meter resistant to dirt
clotting
Safety unit Safety valve 6 bar DN 15 in
accordance with EN 12977, manometer
Filler units 2 Filler and drain valves
with caps
Expansion vessel connection ¾" male
Security valve exhaust connection
¾" female
Solar circuit connections Compression Fittings
18 and 22 mm
Centres distance of solar circuit connections
125 mm
Installation options Suitable for wall and cylinder
installation (see accessories)
Dimensions (HxWxD) 420x260x190mm
Weight 6.7 kg
Figure 3 Front and side view, measurements in mm
420
190
184
60
125
Page 4
4 EN-CIRCO-5-MA-0701-11217300
3. Installation
3
4
5
1
4
4
2
6
7
10
11
3
9
8
12
13
14
15
16
D
spring clips
Figure 4 The parts of the CIRCO 5 solar circulation unit (numbering fits to numbers in brackets at description of assembling steps), items with No. 7, 8, 9, 10, 12 and 14 are not part of the circulation unit.
ball valve with integrated thermometer and non-return valve
air-release pipe
safety valve
compression fitting
compression fitting
mano­meter
filler and drain valve
circulation pump
flow meter with filler and drain valve
Page 5
EN-CIRCO-5-MA-0701-11217300 5
3.1 Installation Preparations
The entire layout of flow and return pipes should be clear before mountingthe CIRCO 5 solar circulation unit (125 mm centres)! In this contextplease also observethe operation instruc
-
tions "Commissioning the System"
If the solar system is installed for heating or if vacuum tubes are used you must pay attention to the technical documentation “Heat Protection”.
These tools are required for the installation of the CIRCO 5 solar circulation unit: Power drill,masonry bits, pipe wrench, stilton etc. (figure 5).
3.2 Wall Mounting
Use spirit level to place the wall mounting bracket (1), see figure 4, into the correct position, mark the three holes, drill and fix with plugs and screws supplied.
Place the two pieces of assembly (2+6) into the correct holders of the wall mounting bracket and affix with the two spring clips (3).
Place the two halves of the back insulation (4) with the recesses over the wall mounting bracket and push to
-
gether.
Connect the safety group (5) with the included ¾" gas-
ket to the free exit of the return unit (6) using an open wrench SW30. Make sure of proper clamping during the tightening of the compression fittings to prevent damage or loosen­ing of other parts of the assembly.
Use the included wall anchors and screws to connect
wall-mount (7) forthe expansion vessel(8) to therightof the safety group. Observe length of the ¾" corrugated tube (9). There are special wall mounting kits for 35 litre and 50 litre vessels.
Connect theflexible hose with the expansion vessel and the pumpstation using supplied ¾ “gaskets.It isrecom
-
mended to fit in a specialcap checkvalve betweenflexi
-
ble hose and vessel.
Connect exhaust pipe (10) to the safety unit and put empty container in place to collect any spills from the pipe.
The connections to the solar circuit (11) (distance of pipes see figure 3) are made by compression fittings 18 or 22 mm (figure 6) . Cut, burr pipes and push into fittings as far as possible, then tighten nuts.Using the 18 mm compression fitting a cracking sound will be heard, which is a sign of proper tightening. Continue until fully tight. Do not solder 18 mm compression fitting. Here too, special care must be taken to ensure proper clamping to prevent damage orloosening of otherparts of the assembly.
Rinse solar pump station and solar circuit and check for leaks. For this procedure a filler valve is fitted to the safety unit (5) and the flow meter below the pump.
Install electrical wiring, switching and sensor circuits (12). Fix cables with cable ties to the prepared sections (notches and long holes) to the wall mounting bracket and ensurethat there areno forces on the connectors of the control unit and that thereis no contact with hot pip
­ing. If required feeding holes can be enlarged with a sharp knife. Always disconnect mains when working with electrical equipment!
Remove frame (13) from the pump station in order to in-
stall the SUNGO control.
Open SUNGO control (14) and affix with the four screws
(15) supplied to the wall mounting bracket.You will find
all required installation and operating instructions in the manuals for SUNGO S, SUNGO SL and SUNGO SXL.
Put front insulation (16) into place.
compression fitting
for 22 mm
compression fitting
for 18 mm
snapping
point
Figure 5 Tools requiredforthe installation of theCIRCO5 solar circula
-
tion unit
Figure 6 Compression fittings 18 and 22mm
Page 6
6 EN-CIRCO-5-MA-0701-11217300
3.3 Mounting to Cylinder
The adjustable mounting kits can be used with all Wagner solar cylinders with 1¼" flat tightening connections, if the vertical distance of these is between 400 and 640 mm. In order to prevent later obstructions of the pipe work in the area of the cylinder it is necessary to make proper lay
-
out plans before commencing.
Connect pipes to cylinder using supplied gaskets.
Adjust the height adjustment until both pipes are reach
­ing the same level and have a distance of 125mm. Tighten adjustment nut.
Trim off the insulation of the adjustable pipe and place pump station on top.
Level the unit and affix to the cylinder.
Connect remaining pipe work.
In order to prevent forces to the cylinder fixing because of pull from pipe work, pipe fixtures should be used at a near wall or at the ceiling.
The expansion vesselmust not be hung from thepump sta
-
tion. Apply wall or floor mounting, depending on type of vessel.
Always ensure proper clamping when tightening 32, 41
and 46 mm nuts in order to prevent loosening of other joints or damage to the unit.
Figure 7 The adjustable cylinder mounting kit consisting of: Adjustable returnpipefittedwith filler anddrain valve, includinginsula
­tion and fittings: 1¼" nut and 22 mm sleeve for compression joint. Flow pipe including insulation and fittings: 1¼" nut and 22 mm sleeve for compression joint.
125
450 mm
suitable for 450 mm to 649 mm
D=22mmfor compression fitting
adjustable pipe
fixing nut
filler and drain valve
insulation
1¼“ nut
Page 7
EN-CIRCO-5-MA-0701-11217300 7
4. Operating Advice
The Flow Meter
The flow meter indicates flow if the pump is switched on. The exact value can be read from the display. It is possible to adjust the flow by turning the adjustment screw with a 4mm Allen key during pump operation. If the screw is turned fully clockwise, flow will stop completely. Flow is cut off, when set screw is turned right to stop posi
-
tion.
litre/minute
4mm
example
8 litre/minute
2
4
6
8
10
12
14
Figure 8 Flow meter of the CIRCO 5 solar circulation unit with adjust
-
ment option
The Return-Flow Stoppers
When the circulation pumps are turned of, unwanted heat distribution in the solar circuit is prevented by non-return ball valves. They only open into the flow direction and by pump pressure. The ball-valve handles can beused to turn them off.
During operation
Filling the system
Emptying the system
“Flow on” Ball valve handle vertical Non-return valve in operation
“Flow off” Ball valve handle vertical Non-return valve in operation
+
+
Figure 9 Operational position
“Flow on” Ball valve handle 45° Flow open, non-return valve off
“Flow off” Ball valve handle horizonta
l
Flow closed
+
+
Figure 10 Filling the system
“Flow on” Ball valve handle 45° flow open, non-return valve off
“Flow off” Ball valve handle 45° Flow open, non-return valve off
+
+
Figure 11 Emptying the System
Page 8
Subject to modifications, errors excepted. · ©Wagner & Co, 2007 · www.wagner-solar.com
8 WAGNER & CO · Zimmermannstraße 12 · D-35091 Cölbe/Marburg ·
+49 6421 80 07-0 · Fax 8007-22
5. Accessories
Accessories Description Order No.
Kit for solar circuit Accessories for the solar circuit pipe work:
2 filler and drain valves and 2 earth connector clips 190 210 22
Air release kit (not normally required because of included air vent pipe)
Automatic air release kit Consisting of 2 automatic air release valves and heat resistant ball valves (up to 200° C), connection 3/8"
190 210 11
Manual air release set Consisting of 2 Manual Air Release Valves 3/8" and Key 190 210 10
CIRCO – expansion vessel kit
Expansion vessel for the CIRCO 5 solar circulation unit, operating pressure max. 10 bar, stainless steel connection hose, connection ¾" female with gasket 12 l-volume, incl. wall mounting bracket, pre-pressurised : 1.5 bar 18 l-volume, incl. wall mounting bracket, pre-pressurised : 1.5 bar 24 l-volume, incl. wall mounting bracket, pre-pressurised : 1.5 bar 35 l-volume, with brackets for wall and floor fixing, pre-pressurised: 2.5 bar
150 300 70 150 300 77 150 300 98 150 300 99
Cap check valve for expansion vessel
Check valve 3/4" with filler and drain valve and with cap against maloperation. 819 200 27
Cylinder mounting kit for CIRCO 5
Non-adjustable pipe work 1¼" male flat tightening, insulated, adjustable return pipe for cylinder connections with 400 to 640 mm vertical distance, with 22 mm sleeves to connect to compression fittings of CIRCO 5
150 301 21