11.9 Ana logue output in mA ........................................................................................... 44
11.10 Analogue output i n Volt .......................................................................................... 45
11.11 Comunication port .................................................................................................... 46
Introduction
Thanks for choosing a Pixsys device.
UA964802 is an indicator/panel meter for acquisition and retransmission of
processes, also with fast transient. It is provided with relay outputs for alarm
purpose, analogue outputs for retransmission of process/setpoints and
programmable digital inputs.
Available in standard format 96x48mm, the device can be configured both for
horizontal and vertical mounting.
Distinctive feature is the intuitive multilingual interface and a
graphical OLED display (monochrome yellow)
Visualization options include bargraph and process trend with programmable
sampling time. Software features include mathematical functions related to
process value like Totalizer and Sum.
Serial connectivity relies on RS485 and Modbus-RTU protocol.
.
128x64 pixel
1 Safety guide lines
Read carefully the safety guidelines and programming instructions contained in
this manual before using/connecting the device. Disconnect power supply
before proceeding to hardware settings or electrical wirings.
Only qualified personnel should be allowed to use the device and/or service it
and in accordance to technical data and environmental conditions listed in this
manual. Do not dispose electric tools together with household waste material.
In observance European Directive 2002/96/EC on waste electrical and electronic
equipment and its implementation in accordance with national law, electric
tools that have reached the end of their life must be collected separately and
returned to an environmentally compatible recycling facility.
2 Model identification
Model 24.. 230 Vac/Vdc +/-15% 50/60 Hz – 8 VA
UA964 802
6 - UA964802 - User man ual
2 relays 2 A + 1 out V + 1 out mA + 2D.I. + RS485 +
OLED + Rfid
3 Technical Data
3.1 General data
Display2.42” monochrome (yellow) OLED graphical display
Operating
temperature
SealingIP54 front panel (with gasket) - IP20 box and terminals
MaterialBox: polycarbonate V0
WeightApprox. 165 g
Temperature 0 -40 °C - Humidity 35..95 uR%
4 Hardware data
Power supply
Analogue input
Relay outputs2 Relays
Analogue output
Extended power supply
24..230 Vac/Vdc ±15% 50/60 HzConsumption: 8 VA.
AN1 Configurable via
software.
Thermocouple type K, S,
R, J, T, E, N, B. Automatic
compensation of cold
junction from 0..50 °C.
Thermoresistance: PT100,
PT500, PT1000, Ni100, PTC1K,
NTC10K (β 3435K ).
Input V/I (linear): 0-10 V,
0-20, 4-20 mA, 0 -60 mV.
Potentiometer input: 6 K Ω,
150 KΩ.
1 tension
Linear 0..10 Volt.
1 current
Configurable as output
0..20mA or 4..20mA.
Tolerance (25 °C)
+/-0.2% ±1 digit (F.s.) for
thermocouple, thermoresistance and V / mA.
Cold junction accuracy 0.1
°C/°C.
Trend
visualization
Analogue
retransmission
Digital
transmission
Latch-on function
Data logging
function
Text menusEnglish/Italian/Deutsch/French/Spanish
8 - UA964802 - User man ual
ON/OFF with hysteresis
Absolute / Threshold, Band with instantaneous/delayed/
retentive ac tion/by digital input activation, Sensor failure /
Activation by serial line
By digital input or by keyboard it is possible to sum
different process measurements over time
Visualisation of instant process value and total value since
last reset
Trend visualisation up to 59 samples, with selectable time
basis 1 to 3600s
Process values / Setpoints
Process values / Setpoint / Parameters via RS485
Semi-automatic set ting of limits/ calibration values for
analogue input
Selectable time basis 1s to 3600s, tot. memor y 2.5k words
5 Dimensions and Installation
Suggested thickness
5
48 mm
10
2÷15 mm
Memory Card
Memory Card USB
(optional)
USB
Frontal panel cut-out
45 x 91 mm
6 Electrical wirings
Although t his controller has b een designed to re sist noises in an ind ustrial
environment, please notice the following safety guidelines:
• Separate control lines from the power wires.
• Avoid the proximity of remote control switches, electromagnetic meters,
powerful engines.
• Avoid the proximity of power groups, especially those with phase control.
For permanently connected equipment:
• s upply wiring must b e ≥18 Awg with cables suitab le for temperatur es > 70 ° C;
• for requirements about any external switch or circuit-breaker see EN 61010-1
par. 6.11.3.1 and about external overcurrent protection devices see EN
61010-1 par. 9.6.2; the switch or circuit-breaker must be near the equipment.
User manual - UA96 4802 - 9
6.1 Wiring diagram
Q2
1
2A 23 0V
R es i s ti ve
2
1/8 HP
Q1
3
2A 23 0V
R es i s ti ve
4
1/8 HP
5
S U PP L Y
24 .. . 230 V
A C /DC
6
6.1.a Power supply
SUPPLY
24..230V
AC/DC
5
Switching supply with ex tended range 24…230 Vac/dc
±15% 50/60Hz – 8 VA (galvanic isolated)
6
AO 1
0/4 .. .2 0m A
AO 2
0. .. 10 V
+24 V dc
P T1 00 -N I1 00
-
TC
0V
+
+
R S 48 5
-
-
V/I
+
P TC
NT C
13
7
+
-
8
14
-
+
159
1610
DI .1
1711
DI .2
18
12
6.1.b AN1 analogue imput
For thermocouples K, S, R, J, T, E, N, B.
• Comply with polarity.
13
AI1TC
10 - UA964802 - User m anual
• For possible extensions, use a compensated wire
and terminals suitable for the thermocouples used
(comp ensated ).
14
• When shielded cable is used, it should be grounded at
one side only.
PT/Ni100
Shield/Schermo
For thermoresistances PT100, NI100.
PTC/NTC
Shield/Schermo
Shield/Schermo
• For the three-wire connection use wires with the same
AI1
Red/Rosso
Red/Rosso
AI1
V/I
+24Vdc
• For the two-wire connection short-circuit terminals 14
an d 15.
14
• When shielded cable is used, it should be grounded at
one side only.
15
13
15
13
14
10
13
White/Bianco
Red/Rosso
14
15
Red/Rosso
For thermoresistances NTC, PTC, PT50 0, PT1000 and
linear potentiometers.
When shielded cable is used, it should be grounded at
one side only to avoid ground loop currents.
For linear signals V / mA .
• Comply with polarity.
• When shielded cable is used, it should be grounded at
one side only.
section.
13
White/Bianco
6.1.c Example of connection for linear input Volt and mA
PRESSURE TRANSMITTER /
SENSORE DI PRESSIONE
P :0...100mbar
Pmax :3bar
T :0..70°C
OUT : 4...20mA
IN :9...33V DC
For linear signals 0/4..20 mA with three-wire sensor.
10
C
Comply with polarity:
4..20mA
B
13
A= Sensor output (+)
B= Sensor ground (-)
A
14
C= Sensor power supply (+24 Vdc / 35mA)
User manual - UA96 4802 - 11
PRESSURE TRANSMITTER /
10
C
SENSORE DI PRESSIONE
Shield/Schermo
SENSORE DI PRESSIONE
P :0...100mbar
Pmax :3bar
T :0..70°C
OUT : 4...20mA
IN :9...33V DC
B
13
4...20mA
A
14
External supply /
Alimentazione esterna
For linear signals 0/4..20 mA with external power of
sensor.
2 A / 250 V~ for resistive loads.
NB: see picture below
4
6.1.f Relay Q2 output
1
2A
230V
1/8Hp
12 - UA964802 - Use r manual
Capacity:
Q2
2A/250 V~ for resistive loads.
NB: see picture below
2
6.1.g mA / Volt output
+24Vdc
AO1
0/4..20mA
AO2
0..10V
7
8
8
9
6.1.h Digital Input 1
10
11
DI1
(PnP)
Electrical endurance Q1 / Q2.
2 A, 250 Vac, resistive load, 10
20/2 A, 250 Vac, cosφ = 0.3, 10
5
operations.
5
operations.
Pin s 7-8: linear output in mA configurable using
parameters as retransmission of process or alarm setpoints
(s ee pa r. 112 -116).
Pins 8-9: linear output in Volt configurable using
parameters as retransmission of process or alarm setpoints
(ve di par. 119-123).
PNP digital input
Digital input according to parameter 95
Short-circuit pins 10 and 11 to activate the digital
input 1
User manual - UA96 4802 - 13
6.1.i Digital input 2
+24Vdc
DI2
(PnP)
10
PNP digital input
Digital input according to parameter 100
Short-circuit pins 10 and 12 to activate the digital
12
input 2
7 Display and Key Functions
7.1 Keys
Process
Graphic
Peak values
Keys are multifunction: in correspondence
of each key its meaning is displayed.
If no description is showed, press a key
to visualize it. Some menus will be only
displayed, when activated.
7. 2 Display
It visualizes the process, the setpoints and all configuration parameters. The
programming/ operation interface with text menus in 5 languages makes the
navigation intuitive.
English
Italiano
Deutsch
Français
Español
14 - UA964802 - Use r manual
Sel
‹
At first starting, display shows the language
‹
selection.
25.6
Q1COM
Q2
°C
This page displays the process, the relays
status and the serial communication (if
available).
4.998
4.998
Q1
25.6
Q1
Bar
°C
Q2
Q2
Bar
Q1
This page displays the process, the relays
status and a graph representing the process
trend.
This page displays the process and its
Q2
graphic representation as bargraph.
User manual - UA96 4802 - 15
8 Controller Functions
8.1 Memory Card (optional)
Parameters and setpoint values can be duplicated from one controller to
another using the Memory card.
Insert memory card when the controller is off. On activation, after startup, the
display visualizes “Load data” and “Esc” in correspondence of the relative keys
(only if the correct values are saved in the memory card). Pressing “Load data”
the controller loads the new values. Pressing “Esc” the device keeps the old
values.
Updating Memory Card.
To update the memo ry card values, fo llow the procedure de scribed on
first mod e, pressing “Esc” so as n ot to load the para meters on control ler.
Enter configuration and change at least one parameter. Exit configuration.
Changes are stored automatically.
8.2 Modifying alarm thresholds
Selecting one or more absolute/ band alarms, it is possible to modify
the intervention thresholds directly by the user menu, without entering
configuration.
AL . 1
AL . 2
0006.0
100.0
Sel
‹
°C
°C
Press “Setpoint ” to enter the thresholds
‹
modification.
For the modification procedure refer to the following table:
PressDisplayDo
Press n e m to modify the
“Sel”
1
16 - UA964802 - User m anual
Selects the setpoint to be
modified.
value. Pressing
possible to modify digit per
digit.
it is
Loading...
+ 36 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.