Wachendorff UA964802 User guide

Universalanzeige UA964802
User Manual
Version 1.0
Table of contents
1 Safety guide lines ...................................................................................................................6
2 Model ide ntification ..............................................................................................................6
3 Technical Data ........................................................................................................................7
3.1 Genera l data ..................................................................................................................7
4 Hardware data ........................................................................................................................7
4.1 Software d ata ................................................................................................................8
5 Dimensions a nd Installation ...............................................................................................9
6 Electrica l wirings ....................................................................................................................9
6.1 Wiring diagram .......................................................................................................... 10
7 Display and Ke y Functions .................................................................................................14
8 Controller Func tions ........................................................................................................... 16
8.1 Memory Card (opt ional) .......................................................................................... 16
8.2 Mo difying alarm thresholds ................................................................................... 16
8.3 Latch on functio n .......................................................................................................17
8.4 Digital input fu nctions ............................................................................................. 18
8.5 Peak values ...................................................................................................................19
8.6 Totalizer function........................................................................................................19
8.7 Sum function .............................................................................................................. 20
8.8 Customizable line ar input ....................................................................................... 20
8.9 Alarm Interve ntion Modes ...................................................................................... 21
8.10 Data logger ................................................................................................................. 23
9 Serial commu nication ....................................................................................................... 24
10 Configuration ....................................................................................................................... 28
10.1 Modifying co nfiguration parameters .................................................................. 28
10.2 Loading default val ues.............................................................................................28
11 Table of configu ration parameters ................................................................................ 29
11.1 Analogue input .......................................................................................................... 29
11.2 V/I custom .................................................................................................................... 33
11.3 Ala rm 1 ......................................................................................................................... 37
11.4 Ala rm 2 .........................................................................................................................39
11.5 Display .......................................................................................................................... 41
11.6 Di gital input 1 ............................................................................................................. 42
11.7 Di gital input 2 ............................................................................................................. 43
11.8 Graphic .........................................................................................................................43
11.9 Ana logue output in mA ........................................................................................... 44
11.10 Analogue output i n Volt .......................................................................................... 45
11.11 Comunication port .................................................................................................... 46
Introduction
Thanks for choosing a Pixsys device. UA964802 is an indicator/panel meter for acquisition and retransmission of processes, also with fast transient. It is provided with relay outputs for alarm purpose, analogue outputs for retransmission of process/setpoints and programmable digital inputs. Available in standard format 96x48mm, the device can be configured both for horizontal and vertical mounting. Distinctive feature is the intuitive multilingual interface and a graphical OLED display (monochrome yellow) Visualization options include bargraph and process trend with programmable sampling time. Software features include mathematical functions related to process value like Totalizer and Sum. Serial connectivity relies on RS485 and Modbus-RTU protocol.
.
128x64 pixel
1 Safety guide lines
Read carefully the safety guidelines and programming instructions contained in this manual before using/connecting the device. Disconnect power supply before proceeding to hardware settings or electrical wirings. Only qualified personnel should be allowed to use the device and/or service it and in accordance to technical data and environmental conditions listed in this manual. Do not dispose electric tools together with household waste material. In observance European Directive 2002/96/EC on waste electrical and electronic equipment and its implementation in accordance with national law, electric tools that have reached the end of their life must be collected separately and returned to an environmentally compatible recycling facility.
2 Model identification
Model 24.. 230 Vac/Vdc +/-15% 50/60 Hz – 8 VA
UA964 802
6 - UA964802 - User man ual
2 relays 2 A + 1 out V + 1 out mA + 2D.I. + RS485 + OLED + Rfid
3 Technical Data
3.1 General data
Display 2.42” monochrome (yellow) OLED graphical display Operating temperature Sealing IP54 front panel (with gasket) - IP20 box and terminals Material Box: polycarbonate V0 Weight Approx. 165 g
Temperature 0 -40 °C - Humidity 35..95 uR%
4 Hardware data
Power supply
Analogue input
Relay outputs 2 Relays
Analogue output
Extended power supply
24..230 Vac/Vdc ±15% 50/60 HzConsumption: 8 VA.
AN1 Configurable via software. Thermocouple type K, S, R, J, T, E, N, B. Automatic compensation of cold junction from 0..50 °C. Thermoresistance: PT100, PT500, PT1000, Ni100, PTC1K, NTC10K (β 3435K ). Input V/I (linear): 0-10 V, 0-20, 4-20 mA, 0 -60 mV. Potentiometer input: 6 K Ω, 150 KΩ.
1 tension Linear 0..10 Volt. 1 current Configurable as output
0..20mA or 4..20mA.
Tolerance (25 °C) +/-0.2% ±1 digit (F.s.) for thermocouple, thermoresi­stance and V / mA. Cold junction accuracy 0.1 °C/°C.
Impedance: 0-10 V: Ri>110 KΩ 0-20 mA: Ri<5 Ω 4-20 mA: Ri<5 Ω 0-60 mV: Ri>1 MΩ
Contacts 2 A - 250 V~. Resistive charge.
All 16bit +/-0.2% (F.s.)
User manual - UA96 4802 - 7
4.1 Software data
Regulation algorithms
Alarm mode
Sum Function
Totalizer Function
Trend visualization Analogue retransmission Digital transmission
Latch-on function
Data logging function Text menus English/Italian/Deutsch/French/Spanish
8 - UA964802 - User man ual
ON/OFF with hysteresis
Absolute / Threshold, Band with instantaneous/delayed/ retentive ac tion/by digital input activation, Sensor failure / Activation by serial line By digital input or by keyboard it is possible to sum different process measurements over time Visualisation of instant process value and total value since last reset Trend visualisation up to 59 samples, with selectable time basis 1 to 3600s
Process values / Setpoints
Process values / Setpoint / Parameters via RS485
Semi-automatic set ting of limits/ calibration values for analogue input
Selectable time basis 1s to 3600s, tot. memor y 2.5k words
5 Dimensions and Installation
Suggested thickness
5
48 mm
10
2÷15 mm
Memory Card
Memory Card USB
(optional)
USB
Frontal panel cut-out
45 x 91 mm
6 Electrical wirings
Although t his controller has b een designed to re sist noises in an ind ustrial environment, please notice the following safety guidelines:
• Separate control lines from the power wires.
• Avoid the proximity of remote control switches, electromagnetic meters,
powerful engines.
• Avoid the proximity of power groups, especially those with phase control. For permanently connected equipment:
• s upply wiring must b e ≥18 Awg with cables suitab le for temperatur es > 70 ° C;
• for requirements about any external switch or circuit-breaker see EN 61010-1
par. 6.11.3.1 and about external overcurrent protection devices see EN 61010-1 par. 9.6.2; the switch or circuit-breaker must be near the equipment.
User manual - UA96 4802 - 9
6.1 Wiring diagram
Q2
1
2A 23 0V R es i s ti ve
2
1/8 HP Q1
3
2A 23 0V R es i s ti ve
4
1/8 HP
5
S U PP L Y 24 .. . 230 V A C /DC
6
6.1.a Power supply
SUPPLY
24..230V AC/DC
5
Switching supply with ex tended range 24…230 Vac/dc ±15% 50/60Hz – 8 VA (galvanic isolated)
6
AO 1
0/4 .. .2 0m A
AO 2
0. .. 10 V
+24 V dc
P T1 00 -N I1 00
-
TC
0V
+
+
R S 48 5
-
-
V/I
+
P TC NT C
13
7
+
-
8
14
-
+
159
1610
DI .1
1711
DI .2
18
12
6.1.b AN1 analogue imput
For thermocouples K, S, R, J, T, E, N, B.
• Comply with polarity.
13
AI1 TC
10 - UA964802 - User m anual
• For possible extensions, use a compensated wire and terminals suitable for the thermocouples used (comp ensated ).
14
• When shielded cable is used, it should be grounded at one side only.
PT/Ni100
Shield/Schermo
For thermoresistances PT100, NI100.
PTC/NTC
Shield/Schermo
Shield/Schermo
• For the three-wire connection use wires with the same
AI1
Red/Rosso
Red/Rosso
AI1
V/I
+24Vdc
• For the two-wire connection short-circuit terminals 14 an d 15.
14
• When shielded cable is used, it should be grounded at one side only.
15
13
15
13
14
10
13
White/Bianco
Red/Rosso
14
15
Red/Rosso
For thermoresistances NTC, PTC, PT50 0, PT1000 and linear potentiometers.
When shielded cable is used, it should be grounded at one side only to avoid ground loop currents.
For linear signals V / mA .
• Comply with polarity.
• When shielded cable is used, it should be grounded at one side only.
section.
13
White/Bianco
6.1.c Example of connection for linear input Volt and mA
PRESSURE TRANSMITTER / SENSORE DI PRESSIONE
P :0...100mbar
Pmax :3bar
T :0..70°C
OUT : 4...20mA
IN :9...33V DC
For linear signals 0/4..20 mA with three-wire sensor.
10
C
Comply with polarity:
4..20mA
B
13
A= Sensor output (+) B= Sensor ground (-)
A
14
C= Sensor power supply (+24 Vdc / 35mA)
User manual - UA96 4802 - 11
PRESSURE TRANSMITTER /
10
C
SENSORE DI PRESSIONE
Shield/Schermo
SENSORE DI PRESSIONE
P :0...100mbar
Pmax :3bar
T :0..70°C
OUT : 4...20mA
IN :9...33V DC
B
13
4...20mA
A
14
External supply / Alimentazione esterna
For linear signals 0/4..20 mA with external power of sensor.
Comply with polarity: A= Sensor output (+) B= Sensor ground (-)
4..20mA
OUT : 4...20mA
IN :9...33V DC
P :0...100mbar
Pmax :3bar
T :0..70°C
PRESSURE TRANSMITTER /
For linear signals 0/4..20 mA with two-wire sensor. Comply with polarity:
A
14
A= Sensor output C= Sensor power supply (+24 Vdc / 35mA)
6.1.d Serial input
RS485
16
RS485 Modbus RTU communication
17
18
6.1.e Relay Q1 output
3
2A
230V
1/8Hp
Capacity:
Q1
2 A / 250 V~ for resistive loads. NB: see picture below
4
6.1.f Relay Q2 output
1
2A
230V
1/8Hp
12 - UA964802 - Use r manual
Capacity:
Q2
2A/250 V~ for resistive loads. NB: see picture below
2
6.1.g mA / Volt output
+24Vdc
AO1
0/4..20mA
AO2
0..10V
7
8
8
9
6.1.h Digital Input 1
10
11
DI1
(PnP)
Electrical endurance Q1 / Q2.
2 A, 250 Vac, resistive load, 10 20/2 A, 250 Vac, cosφ = 0.3, 10
5
operations.
5
operations.
Pin s 7-8: linear output in mA configurable using parameters as retransmission of process or alarm setpoints (s ee pa r. 112 -116).
Pins 8-9: linear output in Volt configurable using parameters as retransmission of process or alarm setpoints (ve di par. 119-123).
PNP digital input Digital input according to parameter 95
Short-circuit pins 10 and 11 to activate the digital input 1
User manual - UA96 4802 - 13
6.1.i Digital input 2
+24Vdc
DI2
(PnP)
10
PNP digital input Digital input according to parameter 100
Short-circuit pins 10 and 12 to activate the digital
12
input 2
7 Display and Key Functions
7.1 Keys
Process Graphic Peak values
Keys are multifunction: in correspondence of each key its meaning is displayed. If no description is showed, press a key to visualize it. Some menus will be only displayed, when activated.
7. 2 Display
It visualizes the process, the setpoints and all configuration parameters. The programming/ operation interface with text menus in 5 languages makes the navigation intuitive.
English
Italiano Deutsch Français Español
14 - UA964802 - Use r manual
Sel
At first starting, display shows the language
selection.
25.6
Q1 COM
Q2
°C
This page displays the process, the relays status and the serial communication (if available).
4.998
4.998
Q1
25.6
Q1
Bar
°C
Q2
Q2
Bar
Q1
This page displays the process, the relays status and a graph representing the process trend.
This page displays the process and its
Q2
graphic representation as bargraph.
User manual - UA96 4802 - 15
8 Controller Functions
8.1 Memory Card (optional)
Parameters and setpoint values can be duplicated from one controller to another using the Memory card. Insert memory card when the controller is off. On activation, after startup, the display visualizes “Load data” and “Esc” in correspondence of the relative keys (only if the correct values are saved in the memory card). Pressing “Load data” the controller loads the new values. Pressing “Esc” the device keeps the old values.
Updating Memory Card. To update the memo ry card values, fo llow the procedure de scribed on
first mod e, pressing “Esc” so as n ot to load the para meters on control ler. Enter configuration and change at least one parameter. Exit configuration. Changes are stored automatically.
8.2 Modifying alarm thresholds
Selecting one or more absolute/ band alarms, it is possible to modify the intervention thresholds directly by the user menu, without entering configuration.
AL . 1
AL . 2
0006.0
100.0
Sel
°C
°C
Press “Setpoint ” to enter the thresholds
modification.
For the modification procedure refer to the following table:
Press Display Do
Press n e m to modify the
“Sel”
1
16 - UA964802 - User m anual
Selects the setpoint to be modified.
value. Pressing possible to modify digit per digit.
it is
Press Display Do
2
“Sel”
“Sel”
3
Selects the nex t setpoint (if active), otherwise go to point 3.
n
and m disappear Press “Esc” to exit procedure.
See point 1.
8.3 Latch on function
For the use with input Potentiometers max.6 kohm and Pot.max.150 kohm and with linear i nput (0..10 V, 0..60 mV, 0/4..20 mA), it is possibl e to associate the star t value of the scale (par. 4 Lower limit V/I) to the minimum position of the sensor and the value of end scale (par. 5 Upper limit V/I) to the maximum position of the sensor.
Latch on
0.000
Input
0.006 mA
For the calibration procedure refer to the following table:
Press Display Do
n
3
1
m
2
“0” Set the vir tual zero value. Press “Esc” to exit procedure.
4
Bar
0
Esc
To use the LATCH ON function: enter
configuration, select Setting on par. 8 Latch on and press “Sel ” (UA964802 shows the
page in the picture).
Set the value to maximum.
Set the value on minimum.
To exit standard procedure press “Esc”. For zero set tings place the sensor on the zero point Place the sensor on minimum operating value (associated with Lower limit V/I). Place the sensor on maximum operating value (associated with Upper limit V/I).
User manual - UA96 4802 - 17
Max
Min Zero
8.4 Digital input functions
On the UA964802 model, digital inputs can be enabled by confi guring the par. 95 Digital input 1 and the par. 100 Digital Input 2.
Run: allows the action of relays and linear output.
Hold: locks the conversion.
Tare zero (AI): selects to zero the process value (tare function).
Alarm reset: if one or more alarms are selected with manual reset and alarm conditions are no longer present, closing the digital input it is possible to restore the alarm output.
Totalizer reset: if the totalizer function is active, using the digital input it is possible to reset the counter.
Peak s reset: min. peak/max. peak/peak-to-peak values are reset.
Sum total: if the sum f unction is active, using the digital input it is possible to increase the “sum” counter as indicated by the process value.
Sum reset: if the su m function is acti ve, using the digital inp ut it is possible to reset the “su m” counte r.
Confi g. lock: if th e digital input i s active it is not p ossible to enter co nfi guration or to modif y the setpoints.
Selecting Digital input 1 or Digital input 2 on the alarm parameters, the related relays will activate togheter with the digital inp ut; functions sel ected on parameters 95 and 100 will continue to work . To store value in eeprom, see parameter 11 S to re.
18 - UA964802 - User m anual
8.5 Peak values
Maximum
25.6 kg
Minimum
15.7 kg
Peak-Peak
9.9 kg
Rst
Esc
The UA964802 is provided with a page for the visualization of peak values: max. peak, min. peak and peak-to-peak of analogue input. Keeping pressed “Rst” it is possible to reset the visualized values.
8.6 Totalizer function
The totalizer function, which can be enable by par. 9 Totalizer, performs an instant me asurement of the pro cess and sums it on a time bas is to the previously totalized value.
Process
1178.9
Total izer
2301.4
Ex.: if a sensor 4..20mA with F.s. 9000m select Hour on par. 9 Totalizer. The device will increase the totalized value considering the m To store value in eeprom, see parameter 11 S to re.
Rst
m3/h
Esc
3
flowing each second (2.5m3).
On the dedicated page it is possible to see the instant process value and the totalized value: keeping pressed “Rst” it is possible to reset this value.
3
/hour is connected, it is necessary to
User manual - UA96 4802 - 19
8.7 Sum function
The sum function, which can be enabled by par. 10 Sum function, allows to increase a counter adding the process value on command. It is an application typical for weighing systems and allows to know the total weighed value.
Process
100.07
Sum
4703.29 kg
Rst
kg
+ Tar Esc
Press “Sum Func tion” to enter the function page. Pressing “+” the Process value is added to the counter. It is possible to reset the total value keeping pressed “Rst ” and to fix “tare zero” of the process pressing “ Tar” .
Functions t are, sum and reset can b e managed also by dig ital input if enabl ed on par. 95 Digital Input 1 and par. 100 Digital Input 2. To store value in eeprom, see parameter 11 S to re.
8.8 Customizable linear input
Selecting 16 step s on par. 17 V/I custom and connecting a linear sensor it is possible to customize the linear input for a max. of 16 steps. On parameters xx-Input value it is necessary to enter the value of the input to which the value selected on the corresponding parameter xx-Custom value will be related. Example: sensor 0 -10V. 01-Input value => 0.000V 01-Custom value=>0mBar 02-Input value => 2.000V 02-Custom value=>100mBar 03-Input value => 5.000V 03-Custom value=>500mBar 04-Input value => 10.000V 04-Custom value=>1000mBar
At each value in vo lt (input) it is relate d a value in mBar (custom ized): if the senso r supplies 2V the device visualizes 100mBar, if it supplies 5V the device visualizes 500mBa r. For interme diate tension values th e value in mBar is calc ulated linearly
between the entered values containing it: 1V = 50mBar, 3.5V=300mBar and
7V=700 mBar.
20 - UA964802 - User ma nual
8.9 Alarm Intervention Modes
Alarm Spv
Pv
O
On On
O
Hysteresis
par. > 0
Time
Alarm
output
Pv
Dev. Spv
Dev. Spv
8.9.a Absolute alarm (absolute selection)
1
Hysteresis par. < 0
Alarm Spv
2
Time
On On
O
O
8.9.b Band alarm (band selection)
1
On On On
O O
Alarm output
Dev. Spv
Hysteresis par. > 0
Dev. Spv
Time
Alarm output
Absolute alarm and hysteresis value greater than “0” (Par. 58 hysteresis > 0). N.B. The example refers to alarm 1; the function can also be enabled for alarms 2
Absolute alarm and hysteresis value less than “0” (Par. 58 hysteresis < 0). N.B. The example refers to alarm 1; the function can also be enabled for alarms 2.
Band alarm and hysteresis value greater than “0” (Par. 58 hysteresis > 0). N.B. The example refers to alarm 1; the function can also be enabled for alarms 2.
User manual - UA96 4802 - 21
Pv
Dev. Spv
2
On On On
O O
Alarm Spv
Hysteresis par. < 0
Band alarm and hysteresis value less
Dev. Spv
than “0” (Par. 58 hysteresis < 0). N.B. The example refers to alarm 1;
Hysteresis
the function can also be enabled for alarms 2.
Time
Alarm output
8.9.c Digital input alarm (sel. “Digital input 1” or “Digital input 2”)
Alarm related to digital input: the relay activates with digital input active.
8.9.d Loop Break Alarm (selection“L.B.A.”)
Sensor alarm breakage: the relay activates in case of sensor breakage or sensor out of range.
8.9.e Remote control alarm (selection “remote Ctrl ”)
The relay activates writing 1 on word modbus 1015 for the alarm 1 and on word modbus 1016 for the alarm 2. Writing 0 the relay deactivates.
22 - UA964802 - User ma nual
8.10 Data logger
UA964802 implements a basic Data logger function which can be enabled by par. 109 Data logger. Right after startup, the device starts storing the process data on EEPROM memory, the sampling time has to be selected on par. 108 Graphic time. Data can be read via Modbus starting from address 5001 (see next paragraph) or via wirel ess reading the RFid mem ory directly from address 0 x600 (1536). The first data give a reference about the type of saved process values: refer to the following table for the description of the saved data.
0x600 153 6 Data logger: firmware version 0x6 01 1537 Data logger: sensor type 0x602 1538 Data logger: decimal point 0x603 1539 Data logger: measure unit 0x604 1540 Data logger: sampling time in seconds
1541 Data logger: end memory flag. 0 indicates
0x605
0x 610 15 52 First saved value of analogue input 0x611 15 53 Second saved value of analogue input
... ... ...
0xFFF 4 095 Last saved value of analogue input
The reading of value 0x8000 (-32768) indicates the end of the saved data: subsequent read data are not valid.
that memor y still available. 1 indicates that the memor y is exhausted and the device resumed saving data from address 5017
User manual - UA96 4802 - 23
9 Serial communication
UA964802 equipped with RS485 can receive and broadcast data via serial communication using MODBUS RTU protocol. The device can be configured only as a Slave. This function enables the control of multiple controllers connected to a supervisory system. Each controller responds to a master query only if the query contains the same address as that in the parameter par. 126
Slave address
The permitted addresses range from 1 to 254 and there must not be controllers with the same address on the same line. Address 255 can be used by the master to communicate with all the connected equipme nt (broadcast mod e), while with 0 a ll the devices receive th e command, but no response is expected. UA964802 can introduce a delay (in milliseconds) in the response to the master request. This delay must be set on parameter 129 Serial Delay memory (100000 writing cycles).
NB: changes made to Words that are different from those reported in the following table can lead to malfunction.
Baud-rate
Format
24 - UA964802 - User ma nual
.
Each parameter change is saved by the controller on EEPROM
.
Modbus RTU protocol features
Selection on par. 127 Baud Rate:
1.200 baud 28.800 baud
2.400 baud 38.400 baud
4.800 baud 57.600 baud
9.600 baud 115.200 baud
19.20 0 bau d Selection on par. 128 Serial format: 8, N, 1 (8 bit, no parity, 1 stop) 8, E, 1 (8 bit, even parity, 1 stop) 8, O, 1 (8 bit, odd parity, 1 stop) 8, N, 2 (8 bit, no parity, 2 stop) 8, E, 2(8 bit, even parity, 2 stop) 8, O, 2 (8 bit, odd parity, 2 stop)
Modbus RTU protocol features
Supported functions
WORD READING (max 20 word) (0x03, 0x04) SINGLE WORD WRITING (0x06) MULTIPLE WORDS WRITING (max 20 word) (0x10)
Looking at the table here below it is possible to find all available addresses and functions:
RO Read Only R/W Read / Write WO Write Only
Modbus
Description
Address
0 Device type RO EEPROM
Read
Only
Reset value
1 Software version RO EEPROM 5 Slave address R/W EEPROM 6 Boot version RO EEPROM
Process (degrees.tenths for temperature sensors;
1000
digit for linear sensors) Min. peak (degrees.tenths for temperature
1001
sensors; digit for linear sensors) Max. peak (degrees.tenths for temperature
1002
sensors; digit for linear sensors) Peak-to-peak (degrees.tenths for temperature
1003
sensors; digit for linear sensorsati)
RO 0
RO 0
RO 0
RO 0
100 4 Totalizer value (H) RO EEPROM 1005 Totalizer value (L) RO EEPROM 1006 Sum value (H) RO EEPROM 1007 Sum value (L) RO EEPROM 1008 Cold junction temperature (degrees.tenths) RO EEPROM
Relays status (0 = Off, 1 = On):
1009
Bit 0 = Relay Q1
RO 0
Bit 1 = Relay Q2
User manual - UA96 4802 - 25
Modbus
Description
Address
Digital inputs status (0 = Off, 1 = Active):
1010
Bit 0 = D. I.1
Read
Only
RO ­Bit 1 = D.I.2 Keys status (0 = released, 1 = pressed): Bit 0 =
1011
Bit 1 = Bit 2 =
RO 0
Bit 3 = Error flags Bit 0 = Cold junc tion error Bit 1 = Process error (sensor) Bit 2 = Eeprom writing error
1012
Bit 3 = Eeprom reading error
RO 0
Bit 4 = Missing calibration data error Bit 5 = Generic error Bit 6 = Hardware error Alarms status (0 = None, 1 = Active)
1013
Bit 0 = Alarm 1
RO 0 Bit 1 = Alarm 2 Manual reset: write 0 to reset all alarms. In reading (0 = Not resettable, 1 = Resettable)
1014
Bit 0 = Alarm 1
R/W 0
Bit 1 = Alarm 2
1015 Alarm 1 status (remote control) R/W 0 1016 Alarm 2 status (remote control) R/W 0 1017 mA analogue output value (remote control) R/W 0 1018 Volt analogue output value (remote control) R/W 0
Run by serial
1019
0 = Inhibited outputs
R/W 1 1 = Active outputs
26 - UA964802 - User man ual
Reset value
Modbus
Description
Address
Hold by serial
1020
0 = Active analogue input
Read
Only
R/W 0
Reset value
1 = Analogue input in Hold
1021 Tare zero AI (write 1) R/W 0 1022 Totalizer reset (write 1) R/W 0 1023 Peaks reset (write 1) R/W 0
1024 Sum total (write 1) R/W 0 1025 Total sum reset (write 1) R/W 0 2001 Parameter 1 R/W EEPROM 2002 Parameter 2 R/W EEPROM 2150 Parameter 150 R/W EEPROM 4001 Parameter 1* R/W EEPROM 4002 Parameter 2* R/W EEPROM 4150 Parameter 150* R/W EEPROM
* Paramet ers modified usin g serial address 4 001 to 4150, will be stored o n eeprom only af ter 10s
since last writ ing of one paramete r.
User manual - UA96 4802 - 27
10 Configuration
10.1 Modifying configuration parameters
For configuration parameters see par. 11
Press Display Do
1
“Configuration”
n
and
2
3
“Sel” to confirm
n
and
4
“Sel” to enter the parameter
5
group
“Sel” to enter the parameter
6
modification
Shows 0000 with the 1st digit selected. Changes the selected digit
m
and moves to the next one using Shows the names of the parameter groups. Scroll up / down the
m
parameter groups.
Shows the parameters of the selec ted group.
Shows all parameter possible selections or the parameter numeric value.
.
Enter password 1234
Press n and m to select parameter to be modified.
Press n and m to modify parameter. For numeric parameters, pressing it is possible to modif y digit-to-digit. Press “Sel” to confirm modification. Press “<” to exit without modify.
10.2 Loading default values
Enter password 9999 to restore factory settings of the device.
28 - UA964802 - User ma nual
11 Table of configuration parameters
The following table includes all parameters. Some of them will not be visible on the models which are not provided with relevant Hardware data.
11.1 Analogue input
Parameters to configure the analogue input.
1 Sensor type
Analogue input configuration/sensor selection Thermocouple K (Default) -260 °C..1360 °C Thermocouple S -40 °C ..1760 °C Thermocouple R -40 °C..1760 °C Thermocouple J -200 °C..1200 °C Thermocouple T -260 °C..400 °C Thermocouple E -260 °C..1000 °C Thermocouple N -260 °C..1280 °C Thermocouple B +80 °C..1820 °C Pt100 -200 °C..600 °C Ni100 -60 °C..180 °C NTC 10kOhm -40 °C ..125 °C PTC 1kOhm -50 °C..150 °C Pt500 -100 °C..600 °C Pt1000 -100 °C..600 °C
0. .10 V
0..20 mA
4..20 mA
0..60 mV Pot. max. 6 kOhm Pot. max. 150 kOhm
User manual - UA96 4802 - 29
2 Decimal Point
Selects type of the visualized decimal point 0 No decimals. Default
0.0 1 Decimal
0.00 2 Decimals
0.000 3 Decimals
3 Measure unit
Selects the visualized measure unit °C (Default) °F K V mV A mA Bar mBar psi Pa mm cm dm m km in
kg q t oz lb m/s m/m m/h l/s l/m l/h
3
m
3
m
3
m rpm %rh ph
/s /m /h
N
kN
%
L
gal
mmHg
atm
mH2O
Nm
kNm
kgf
kgp
kip
lbf
ozf
pcs
g
4 Lower limit V/I
Range AN1 lower limit only for linear input. Ex: with input 4..20 mA this parameter takes value associated to 4 mA
-32767 + 32767 [digit
30 - UA964802 - User ma nual
1
], Default: 0.
5 Upper limit V/I
Range AN1 upper limit only for linear input. Ex: with input 4..20 mA this parameter takes value associated to 20 mA
-32767 + 32767 [digit
1
], Default: 1000.
6 Offset calibration
Value added / subtracted to the process visualization (usually correcting the value of environmental temperature)
-1000..+1000 [digit
-100.0..+100.0 (degrees.tenths for temperature sensors). Default 0.0.
1
] for linear sensors and potentiometers.
7 Gain calibration
Percentage value that is multiplied for the process value (allows to calibrated the working point)
-100. 0%..+100 .0%, Default: 0.0 ex: to corre ct the range from 0..1000°C showing 0..1010°C, set the par. to -1.0.
8 Latch On
Automatic setting of limits for linear inputs and potentiometers. (see par. 8.3) Disabled (Default) Enabled Setting
9 Totalizer
Visualizes the total fluid volume considering the sensor signal as unit/time value (ex. if the connected sensor has an output 4..20mA with F.s. 2000m³/ hour, the param eter 9 Totalizer has to be selec ted as Hour and the display will visualize th e total fluid volume fro m the last RESET/START signal). (see par. 8.6) Disabled Display visualizes the process (Default) Second Display visualizes the flow in unit/s Minute Display visualizes the flow in unit/min Hour Display visualizes the flow in unit/hour
User manual - UA96 4802 - 31
10 Sum function
Enables the sum function and its dedicated page. Allows to sum the process value to a variable. Disabled (Default) Enabled
(see par. 8.7)
11 Store
Enables to store in eeprom the values of peak, totalizer, sum function and tare zero. If disabled, at starting the above-mentioned values star t from 0. The storing is done automatically every 5 minutes. Disabled (Default) Enabled
12 Filter samples
ADC Filter: number of input sensor readings to calculate the mean that defines process value. NB: when readings increase, control loop speed slows down.
1..15 means Default: 10.
13 Sampling frequency
Sampling frequency of analogue / digital converter. NB: Increasing the conversion speed will slow down reading stability (ex: for fast transients, as pressure, it is advisable to increase sampling frequency) 242 Hz 4.2ms (Maximum speed conversion) 123 Hz 8.2ms 62 Hz 16.1ms 50 Hz 20ms 39 Hz 25.6ms
33.2 Hz 30.1ms
19.6 Hz 51ms
16.7 Hz (Default) 59.9ms Ideal for filtering noises 50 / 60 Hz
12.5 Hz 80ms
32 - UA964802 - User ma nual
10 Hz 100m s
8.33 Hz 120ms
6.25 Hz 160ms
4.17 Hz 240ms (Minimum speed conversion)
11. 2 V/ I custom
Parameters to configure the customizable linear input. (see p ar. 8.8)
17 V/I custom
Selects the linearization type for the analogue input if selected as linear. Lower and upper limits. The input will be linearized by parameters 4 and 5 (Default)
16 sp ezza te. The input will be linearized by parameter 18-49
18 01-Input value
Defines the input value to which the 1st customized value is assigned
0..20000 Default: 0.
19 01-Custom value
Defines the 1st customized value assigned to the input
-32767..32767 [Dig it
20 02-Input value
Defines the input value to which the 2nd customized value is assigned
0..20000 Default: 2000.
21 02-Custom value
Defines the 2nd customized value assigned to the input
-32767..32767 [Dig it
22 03-Input value
Defines the input value to which the 3rd customized value is assigned
0..20000 Default: 0.
1
] Default: 0.
1
] Default: 1000.
User manual - UA96 4802 - 33
23 03-Custom value
Defines the 3rd customized value assigned to the input
-32767..32767 [Dig it
1
] Default: 0.
24 04-Input value
Defines the input value to which the 4th customized value is assigned
0..20000 Default: 0.
25 04-Custom value
Defines the 4th customized value assigned to the input
-32767..32767 [Dig it
1
] Default: 0.
26 05-Input value
Defines the input value to which the 5th customized value is assigned
0..20000 Default: 0.
27 05-Custom value
Defines the 5th customized value assigned to the input
-32767..32767 [Dig it
1
] Default: 0.
28 06-Input value
Defines the input value to which the 6th customized value is assigned
0..20000 Default: 0.
29 06-Custom value
Defines the 6th customized value assigned to the input
-32767..32767 [Dig it
1
] Default: 0.
30 07-Input value
Defines the input value to which the 7th customized value is assigned
0..20000 Default: 0.
34 - UA964802 - User m anual
31 07-Custom value
Defines the 7th customized value assigned to the input
-32767..32767 [Dig it
1
] Default: 0.
32 08-Input value
Defines the input value to which the 8th customized value is assigned
0..20000 Default: 0.
33 08-Custom value
Defines the 8th customized value assigned to the input
-32767..32767 [Dig it
1
] Default: 0.
34 09-Input value
Defines the input value to which the 9th customized value is assigned
0..20000 Default: 0.
35 09-Custom value
Defines the 9th customized value assigned to the input
-32767..32767 [Dig it
1
] Default: 0.
36 10-Input value
Defines the input value to which the 10th customized value is assigned
0..20000 Default: 0.
37 10-Custom value
Defines the 10th customized value assigned to the input
-32767..32767 [Dig it
1
] Default: 0.
38 11-Input value
Defines the input value to which the 11th customized value is assigned
0..20000 Default: 0.
User manual - UA96 4802 - 35
39 11-Custom value
Defines the 11th customized value assigned to the input
-32767..32767 [Dig it
1
] Default: 0.
40 12-Input value
Defines the input value to which the 12th customized value is assigned
0..20000 Default: 0.
41 12-Custom value
Defines the 12th customized value assigned to the input
-32767..32767 [Dig it
1
] Default: 0.
42 13-Input value
Defines the input value to which the 13th customized value is assigned
0..20000 Default: 0.
43 13-Custom value
Defines the 13th customized value assigned to the input
-32767..32767 [Dig it
1
] Default: 0.
44 14-Input value
Defines the input value to which the 14th customized value is assigned
0..20000 Default: 0.
45 14-Custom value
Defines the 14th customized value assigned to the input
-32767..32767 [Dig it
1
] Default: 0.
46 15-Input value
Defines the input value to which the 15th customized value is assigned
0..20000 Default: 0.
36 - UA964802 - User ma nual
47 15-Custom value
Defines the 15th customized value assigned to the input
-32767..32767 [Dig it
1
] Default: 0.
48 16-Input value
Defines the input value to which the 16th customized value is assigned
0..20000 Default: 0.
49 16-Custom value
Defines the 16th customized value assigned to the input
-32767..32767 [Dig it
1
] Default: 0.
11. 3 Alarm 1
Parameters to configure the Alarm 1. (see par. 8.9)
54 Alarm type
Alarm 1 selection Disabled (Default) Absolute alarm Band alarm Digital input 1 Digital input 2 Sensor failure Remote control by Modbus
55 Contact type
Selects the alarm 1 output contact and intervention type Normally open (Default) Normally closed N.O.-Disabled Power on N.C.-Disabled Power on
User manual - UA96 4802 - 37
56 Alarm threshold
Selects the alarm 1 setpoint
-32767..+32767 [Digit1] (degrees .tenths for temperat ure sensors), Default: 0.0.
57 Deviation threshold
Selects the deviation from alarm 1 setpoint for the band alarm
0..+32767 [Digit
1
] (degrees.tenths for temperature sensors), Default: 0.0.
58 Hysteresis
Alarm 1 hysteresis
-1000..+1000 [Digit1] (degrees.tenths for temperature sensors), Default: 0.0.
59 Reset type
Alarm 1 contact reset t ype Automatic: (Default) Manual: Manual reset by keyboard Manual stored: Keeps relay status also af ter an eventual power failure
60 Error contact
State of contac t for alarm 1 output in case of error Open (Default) Closed
62 Actuation delay
Alarm 1 delay.
-3600..+3600 seconds. Default: 0 Negative: delay in alarm output phase. Positive: delay in alarm entr y phase.
63 Lower limit
Lower limit for alarm 1 setpoint.
-32767..+32767 [Digit1] (degrees.tenths for temperature sensors). Default: 0.
38 - UA964802 - User ma nual
64 Upper limit
Upper limit for alarm 1 setpoint
-32767..+32767 [Digit
1000.
1
] (degrees.tenths for temperature sensors). Default:
65 Protection
Alarm 1 set protection. Does not allow user to modify setpoint Free Modification allowed (Default) Lock Protected Hide Protected and not visualized
11. 4 Alarm 2
Parameters to configure the Alarm 2
69 Alarm type
Alarm 2 selection Disabled (Default) Absolute alarm Band alarm Digital input 1
70 Contact type
Selects the alarm 2 output contact and intervention type Normally open (Default) Normally closed N.O.-Disabled Power on N.C.-Disabled Power on
71 Alarm threshold
Selects the alarm 2 setpoint
-32767..+32767 [Digit1] (degrees .tenths for temperat ure sensors), Default: 0.0.
Digital input 2 Sensor failure Remote control by Modbus
User manual - UA96 4802 - 39
72 Deviation threshold
Selects the deviation from alarm 2 setpoint for the band alarm
0..+32767 [Digit
1
] (degrees.tenths for temperature sensors), Default: 0.0.
73 Hysteresis
Alarm 2 hysteresis
-1000..+1000 [Digit1] (degrees.tenths for temperature sensors), Default: 0.0.
74 Reset type
Alarm 2 contact reset t ype Automatic: (Default) Manual: Manual reset by keyboard Manual stored: Keeps relay status also af ter an eventual power failure
75 Error contact
State of contac t for alarm 2 output in case of error Open (Default) Closed
77 Actuation delay
Alarm 2 delay.
-3600..+3600 seconds. Default: 0 Negative: delay in alarm output phase. Positive: delay in alarm entr y phase.
78 Lower limit
Lower limit for alarm 2 setpoint.
-32767..+32767 [Digit1] (degrees.tenths for temperature sensors). Default: 0.
79 Upper limit
Upper limit for alarm 2 setpoint
-32767..+32767 [Digit
1
] (degrees.tenths for temperature sensors). Default:
1000.
40 - UA964802 - User m anual
80 Protection
Alarm 2 set protection. Does not allow user to modify setpoint Free Modification allowed (Default) Lock Protected Hide Protected and not visualized
11. 5 Display
84 Language
Selects the language English (Default) Italiano
86 Contrast
Selects the contrast value for the display 0%..100%, Default: 80%.
87 Reverse
Enables the display reverse visualiz ation Disabled (Default) Enabled
88 Screen timeout
Determines the time af ter which the display switches to standby mode when no key has been pressed, reducing brightness so as not to be an inconvenience in environments with little lighting and to extend the display’s life time. Always on (Default) 15 seconds 30 seconds 1 minute
Deutsch Français
2 minutes 5 minutes 10 minutes
Español
30 minutes
1 hour
User manual - UA96 4802 - 41
89 Display direction
Selects the display visualization direction. Horizontal (Default) Vert ical
90 Starting page
Selects the page visualized at starting after the initial splash screen Process (Default) Graphic Peak values Tot aliz er Sum function
11. 6 Digital input 1
Parameters to configure the digital input 1.
95 Digital input function
Selects the digital input 1 function. (see par. 8.4) Disabled (Default) Run Hold Tare zero (AI) (impulse functioning) Alarm reset Totalizer reset (impulse functioning) Peaks reset Sum total (impulse functioning) Sum reset (impulse functioning) Config. lock
96 Contact type
Selects the digital input 1 inactive contact. Normally open (Default) Executes function with closed contact Normally closed Executes function with open contact
42 - UA964802 - User ma nual
11. 7 Digital input 2
Parameters to configure the digital input 2. (see par. 8.4)
100 Input function
Selects the digital input 2 function Disabled (Default) Run Hold Tare zero (AI) (impulse functioning) Alarm reset Totalizer reset (impulse functioning) Peaks reset Sum total (impulse functioning) Sum reset (impulse functioning) Config. lock
101 Contact type
Selects the digital input 2 inactive contact. Normally open (Default) Executes function with closed contact Normally closed Executes function with open contact
11. 8 Graphic
Parameters to configure the trend and bar graph management.
105 Graphic type
Selects the type of graph to be visualized on the relevant page. Trend (Default) Bar graph
106 Lower limit
Trend or bar graph lower limit.
-32767 + 32767 [Digit
1
], Default: 0.
User manual - UA96 4802 - 43
107 Upper limit
Trend or bar graph upper limit.
-32767 + 32767 [Digit
1
], Default: 1000.
108 Trend time
Selects the trend sampling time.
1..3600 seconds, Default: 60s.
109 Data logger
Enables the over time registration of the process in eeprom The sampling time is equal to the trend upgrading time. Disabled (Default) Enabled
110 Data logger time
Selects the data logger sampling time.
1..3600 seconds, Default: 60s.
11. 9 Analogue output in mA
Parameters to configure the analogue output in mA
112 Retransmission
Enables analogue output Disabled (Default) Process Alarm 1 Alarm 2 Remote control by Modbus
113 Signal type
Selects the signal for the analogue output in mA
0..20 mA
4..20 mA (Default)
44 - UA964802 - Use r manual
(see par. 8.10)
114 Lower limit
Analogue output mA lower limit range
-32767..+32767 [ Digi t
1
] (degrees .tenths for temperat ure sensors), Default: 0
115 Upper limit
Analogue output mA upper limit range
-32767..+32767 [Digit
1
] (degrees.tenths for temperature sensors) Default:
1000
116 Error value
Selects the value of the analogue output in mA in case of error 0 mA (Default) 4 mA 20 mA
11.10 Analogue output in Volt
Parameters to configure the analogue output in Volt
119 Retransmission
Enables analogue output Disabled (Default) Process Alarm 1 Alarm 2 Remote control by Modbus
120 Signal type
Selects the signal for the analogue output in Volt
0..10 V (Default)
121 Lower limit
Analogue output Volt lower limit range
-32767..+32767 [ Digi t
1
] (degrees .tenths for temperat ure sensors), Default: 0
User manual - UA96 4802 - 45
122 Upper limit
Analogue output Volt upper limit range
-32767..+32767 [Digit
1
] (degrees.tenths for temperature sensors) Default:
1000
123 Error value
Selects the value of the analogue output in Volt in case of error 0 V (Default) 10 V
11.11 Comunication port
Parameters to configure the serial communication port. (see par. 9)
126 Slave address
Selects the slave address for serial communication
1.. 254. Default: 24 0
127 Baud rate
Selects the baud rate for serial communication
1.200 b aud
2.400 baud
4.800 baud
9.600 baud
19.200 baud (Default)
28.800 baud
39.40 0 baud
57.600 baud 115 .20 0 ba ud
1
The decimal point visualization depends on the “Sensor type” and “Decimal point” selection.
46 - UA964802 - User m anual
128 ComPort setting
Selects the format for the serial communication 8,N,1 8bit, No parity, 1 Stop bit (Default) 8,E,1 8bit, Even parity, 1 Stop bit 8,O,1 8bit, Odd parity, 1 Stop bit 8,N,2 8bit, No parity, 2 Stop bit 8,E,2 8bit, Even parity, 2 Stop bit 8,O,2 8bit, Odd parity, 2 Stop bit
129 Serial delay
Selects the serial delay
0..100 milliseconds. Default: 10
Notes / Updates
User manual - UA96 4802 - 47
Table of configuration parameters
1 Sensor type 29 2 Decimal Point 30 3 Measure unit 30 4 Lower limit V/I 30 5 Upper limit V/I 31 6 Offset calibration 31 7 Gain calibration 31 8 Latch On 31 9 Totalizer 31 10 Sum function 32 11 Store 32 12 Filter samples 32 13 Sampling frequency 32 17 V/I custom 33 18 01-Input value 33 19 01-Custom value 33 20 02-Input value 33 21 02-Custom value 33 22 03-Input value 33 23 03-Custom value 34 24 04-Input value 34 25 04- Custom value 34 26 05-Input value 34 27 05-Custom value 34 28 06-Input value 34 29 06- Custom value 34 30 07-Input value 34 31 07-Custom value 35 32 08-Input value 35 33 08-Custom value 35 34 09-Input value 35 35 09-Custom value 35 36 10-Input value 35
48 - UA964802 - User m anual
37 10-Custom value 35 38 11-Input value 35 39 11-Custom value 36 40 12-Input value 36 41 12-Custom value 36 42 13-Input value 36 43 13-Custom value 36 44 14-Input value 36 45 14-Custom value 36 46 15-Input value 36 47 15-Custom value 37 48 16-Input value 37 49 16-Custom value 37 54 Alarm type 37 55 Contact t ype 37 56 Alarm threshold 38 57 Deviation threshold 38 58 Hysteresis 38 59 Reset type 38 60 Error contact 38 62 Actuation delay 38 63 Lower limit 38 64 Upper limit 39 65 Protection 39 69 Alarm type 39 70 Contact t ype 39 71 Alarm threshold 39 72 Deviation threshold 40 73 Hysteresis 40 74 Reset type 40 75 Error contact 40 77 Actuation delay 40 78 Lower limit 40 79 Upper limit 40
User manual - UA96 4802 - 49
80 Protection 41 84 Language 41 86 Contrast 41 87 Reverse 41 88 Screen timeout 41 89 Display direction 42 90 Starting page 42 95 Digital input function 42 96 Contact t ype 42 100 Input function 43 101 Contact type 43 105 Graphic type 43 106 Lower limit 43 107 Upper limit 44 108 Trend time 44 109 Data logger 44 110 Data logger time 44 112 Retransmission 44 113 Signal type 44 114 Lower limit 45 115 Upper limit 45 116 Error value 45 119 Retransmission 45 120 Signal type 45 121 Lower limit 45 122 Upper limit 46 123 Error value 46 126 Slave address 46 127 Baud rate 46 128 ComPort setting 47 129 Serial delay 47
50 - UA964802 - User ma nual
User manual - UA96 4802 - 51
Wachendorff Prozesstechnik GmbH & Co. KG
Industriestrasse • 65366 Geisenheim
Tel.: +49 (0) 67 22 / 99 65 - 20 Fax: +49 (0) 67 22 / 99 65 - 78 E-Mail: wp@wachendorff.de www.wachendorff-prozesstechnik.de
© Copyright by Wachendor ff Prozesstechnik GmbH & Co. KG
Loading...