VWR International INCU-Line 68R, INCU-Line 150R, INCU-Line 250R Instruction Manual

I
I
I
N
N
N
S
S
S
T
T
T
R
R
R
U
U
U
C
C
C
T
T
T
I
I
I
O
O
O
N
N
N
M
M
M
A
A
A
N
N
N
U
U
U
A
A
A
L
L
L
1.
The unit cannot be installed:
outside,
in damp places or places which can be easily flooded,
near flammable or volatile substances,
near acids or in corrosive environments.
2.
It is forbidden to:
store inflammable or volatile substances inside the unit,
touch live parts of the unit
operate the unit with wet hands,
put water vessels on the unit,
climb or put any objects on the unit,
do not overload the shelves ( the maximum load is described in technical data)
3.
You should:
place samples in such a way to provide proper air circulation in the chamber
open the door for the shortest period of time to reduce temperature fluctuations
defrost the chamber more often if you open the door a lot or store humid samples
if possible, do not store warm samples
secure samples from being blown out by the chamber fan e.g powdery samples
always check that the doors are closed
use only mains with earth to avoid electric shocks,
unplug the power cable holding the protective cover and not the cable itself,
disconnect the unit from the mains before undertaking any repairs or maintenance works,
protect the power cable and the plug from any damage
disconnect the power plug before moving the unit,
disconnect the power plug if the device will not be used for a long period of time,
disconnect the unit and protect it from reconnecting if it has any visual faults.
While carrying the unit, please do not tilt it to one side more than 45° from the upright position, as there is a high probability of the damaging the compressor. If it is necessary to tilt it to one side more than 45°, then after placing it, please wait at least 3 hours before connecting the unit to the mains.
The device is powered by AC 230V/50Hz. Please connect it to a socket with ground in order to avoid electric shocks in case of the unit’s failure.
2
1
4
3
Hmax
H
Hmax
a
u
v w
x
y z
b
u+v+w > 1/3 a
x+y+z > 1/3 b
Hmax = 2/3H
u v w
x y z
H
≅ ≅ ≅
Front view
Top view
Shelf
If water gathers, use a dry cloth to wipe the bottom of the chamber.
13
14
12
7
10
1 2 3
4
5 6 8
9
11
Temperature
Time
Tp
To
Tp – set temperature
To – ambient temperature
Device series
IL
Number of programs
3
Number of segments in each program
6
If the device has been switched off during an active program, it will automatically resume once the device has been switched on again.
Use the main switch to turn off the unit only if you are not going to use it for a longer period of time (e.g. a couple of days) or for maintenance.
Press UP or DOWN to edit the temperature.
The temperature will flicker. Use UP or DOWN to set a new temperature. Press ENTER to confirm.
Use UP or DOWN to set the decimal value and confirm with ENTER .
A new temperature has been set.
You can press ESC at any time to cancel.
In the main window press ESC to enter the MENU.
Enter SETUP using ENTER . Press down and choose PROG.MODE.
Press ENTER . The setting will flicker.
Press and choose >complex<. Confirm with ENTER .
It is impossible to make changes to a currently running program – it needs to be terminated first.
You can press ESC at any time to cancel the adjustment.
In the main window press ESC twice.
Enter PROGRAMMING using ENTER .
Choose the program you want to edit using and .
Press ENTER , then use and to set the number of segments. Confirm with ENTER .
Then you can choose the set temperature for segment 1. Use
and to set a new value, then confirm with ENTER . Set
the decimal value in the same way.
Now you can set the segment time in dd:hh:mm format.
If the program has more than one segment, you can set its pa­rameters here.
Here you can set start delay in hh:mm format if required.
Here you can set if the program should run in cycles:
- it can be OFF, the program will stop after finishing
- infinite cycles – the program will continue to run till it is stopped by the user
- you can define the number of cycles between 2 and 99
After all parameters have been set, you can start the program. Use ENTER to confirm.
In the main window, press .
Using and choose the program you would like to start and press .
In the main window press twice.
Confirm with .
In the main window press ESC twice to enter MENU.
Choose SETUP using .
Press ENTER to enter the menu.
TIME ALARM, TEMP ALARM., POWER ALARM,
More information in 10.1
[hh:mm], first you set up the hour, then the minutes. You change the value using / the up/down buttons and confirm with the ac-
cept button. The program automatically moves to setting the next val­ue.
After selecting a sub-menu the user is able to choose a protocol for each socket separately – Please press the button. Available proto-
cols:
- none (interface off)
- text (protocol for printers with serial port, terminal),
- service (service and text protocol).
- dedicated software
After selecting a protocol with / buttons, the user is able to de­termine its settings.
- Print interval: [mm:ss] determines the interval after which data is sent to the serial port (available in service and text protocols),
- address [1-255] – determines the address of the instrument con­nected to the network
selecting the type of programming the device, there are two options available ‘simple’– simple mode and ‘complex ‘ – complex mode of programming the device. See point 5.4.
There is a possibility to choose controller backlight mode. “Fixed
mode means constant backlight. “Temporary” mode means that the
backlight will go off in approximately one minute from the last bottom touch.
In MENU choose LOGGER
To choose from DATA or EVENTS.
In the menu you can set the interval time of saving temperature in the chamber. Note <00:15> means, that every 15 minutes data of tempera­ture will be registered in internal memory (max 2048 results). If the memory will be fulfilled, the data will be over written.
Erase the data.
Reading the data from logger is possible by using a PC application – Basic Control
Event window opens the internal event logger.
Command ‘view will display events like: start, stop or end of program as well as loss and return of power, alarm of over temperature, door openings.
Sample of displayed events and occur time of the event. After pressing and pushing the date of the event will be displayed.
Erasing the event from the memory (max. numbers of saved events is
110), If the memory will be fulfilled, the data will be over written.
Reading the data from logger is possible by using a PC application – Basic Control.
In the main window press ESC .
Enter STATISTICS using ENTER .
Using and choose the segment which you want to see the statistics of, then press ENTER .
Using and you can see the average, max and min temper­ature recordings.
You can also see how many recordings are available.
If the simple mode is active the statistics of chosen segment is not possible to preview.
Choose RESET and confirm with ENTER to zero the recordings.
Sort of event
Duration
of sound
alarm
Red di-
ode
Duration of break
between sounds
[second]
Terminate of event
Displayed command
Temperature
sensor fault
0.1s
yes
1s
Replacing of tempera-
ture sensor
SENSOR
ERROR
Time alarm
1s
no
1s
Pressing of any button
TIME ALARM
Power alarm
0.1s
no
5s
Pressing EXIT button
POWER
ALARM
Open door alarm
1s
no
1s
Closing door or press-
ing any button
DOOR OPEN
If the parameters: interruption, fall/rise of temp will be turned off (selected off) and the alarm is on, the user will be informed about the time of power failure, and the program will continue.
1.
At temperatures above +8ºC the air automatically defrosts the ice cover, defrosting is self­operating.
2.
In temperatures below +8ºC the evaporator may be covered in ice and the device should be
defrosted manually. In order to do that you need to open the door and turn on the defrost function on the controller (go to the SETUP / DEFROSTING, choose “on”). Defrosting lasts 30 minutes, after this time function will turn off automatically. You can also stop defrosting function in any time (turning it off takes place in the same location as turning on). To start defrosting stop the program first. Defrosting will cause that the temperature inside the unit will oscillate in ca. 30°C
After the defrosting has finished, wipe the chamber precisely.
If the unit works in a temperature below +8°C and the user does not defrost it periodi­cally, it may make the compressor overheat and break down the unit.
3.
The device is equipped with a protection mechanism against damaging the cooling system.
The mechanism makes it impossible to turn on cooling when the temperature exceeds 45ºC. As a result if the device has been programmed to go down with temperature (e.g. from 60ºC to 20ºC) it may take longer for the program to operate until it reaches 45ºC. The tempera-
ture inside the device is lowered naturally by emitting the heat to the surrounding environ­ment.
4.
Always make sure that the door has been closed properly!
Before cleaning the device, it needs to be disconnected from the electrical supply!
1.
The housing and door should be cleaned with caution using a soft cloth dampened with water.
2
Only mild cleaning products should be used to clean the device.
3.
Electrical parts should not get in contact with water or detergent.
When cleaning stainless steel product with dedicated cleaning solution, one should pay attention to the suggestions and recommendations given in the user manual (or in the safety data sheet) of the cleaning solution.
4.
On a regular basis clean with a vacuum cleaner of a duster the cooling unit and condenser (exchanger) which is placed in the rear (or upper) part of the device. Disobeying this pre-
caution may harm the compressor. In such case the warranty repair will not be ac­cepted!
1.
The chamber should be emptied of any samples before cleaning.
2.
Open the door of the device and wait for the frost to melt, take out the shelves and start cleaning the device,
3.
Only water or water with mild detergent should be used.
4.
Having finished cleaning, you should allow the device to dry completely.
5.
During cleaning pay attention not to damage the temperature sensor in the chamber.
1.
Remove all objects from the chamber.
2.
Disconnect the device from the mains.
3.
Clean and dry the chamber.
4.
Leave the door open to avoid bad smell.
5.
Store in temperature between 0°C and 50°C and relative humidity maximum 70%.
1.
There is not an electrical supply failure?
2.
The power cord is plugged in the mains socket properly?
3.
The fuse has not been blown?
4.
The power cord has not been damaged?
1.
What is the temperature outside the device?
2.
Is the door shut tight?
3.
Is the condenser clean?
4.
Is the device placed in direct sunlight?
5.
Is there any heat source near the device?
6.
Are there too many objects inside the device that are not cool enough?
1.
Is the defrosted water outlet not blocked?
1.
Usual condition while working in low temperatures.
1.
Is the device not leaning against furniture or other objects?
2.
Are the pipes at the back in direct contact or are they vibrating?
3.
Is the device leveled properly?
CAUTION: Buzz and noise from decompression coming from the cooling circuit are normal noises.
1. Logo
2. Type of device
3. Catalogue number
4. CE mark
5. Name and address of manufacturer
6. Serial number
Model
Parameter '
INCU-Line 68R
INCU-Line 150R
INCU-Line 250R
air convection
forced
chamber capacity ¹
[l]
68
143
245
door type
glass door
solid + internal glass door
temperature range [ºC]
+3ºC… up to 70ºC
temperature variation (spatial) at 37ºC
+/- 0,3ºC
+/- 0,8ºC
+/- 1,0ºC
temperature fluctuation (time) at 37ºC
+/- 0,1ºC
+/- 0,2ºC
+/- 0,3ºC
controller
microprocessor with external LCD graphic display
interior
stainless steel
housing
powder coated sheet
overal dims
[mm]**
width 570
620
620
height 600
860
1260
depth 680
650
650
internal dims
2
[mm]
width
470
520
520
height
430
660
1060
depth
300
410
410
weight (kg)
41
68
86
shelves fitted/max3
2/2
3/4
4/6
max shelf workload [kg]*
10
10
10
max unit workload [kg]
20
30
50
voltage 50/60 Hz [V]
220-240
nominal powder [W]
250
250
250
warranty
24 months
* - at even surface workload ** - dims of power cable (50 mm) not included 1 - working capacity of chamber can be smaller
2- "fitted” number of shelves fitted, included in price
- "max" number of shelves which can be fitted
Loading...