- NOTICE This Manual is prepared for the use of trained Vulcan Service
Technicians and should not be used by those not properly qualified.
If you have attended a Vulcan Service School for this product, you
may be qualified to perform all the procedures described in this
manual.
This manual is not intended to be all encompassing. If you have not
attended a Vulcan Service School for this product, you should read,
in its entirety, the repair procedure you wish to perform to
determine if you have the necessary tools, instruments and skills
required to perform the procedure. Procedures for which you do not
have the necessary tools, instruments and skills should be
performed by a trained Vulcan Service Technician.
Reproduction or other use of this Manual, without the express
written consent of Vulcan, is prohibited.
For additional information on Vulcan-Hart or to locate an authorized parts and
service provider in your area, visit our website at www.vulcanhart.com.
A product of VULCAN-HARTLOUISVILLE, KY 40201-0696
F25154 (February 2004)
VHX SERIES STEAMERS
TABLE OF CONTENTS
GENERAL ................................................................................4
Installation, Operation and Cleaning ........................................................4
Refer to the Installation and Operation Manual for
specific instructions.
INTRODUCTION
Steam Cooking
Convection cooking in pressure-less steaming
compartments will steam cook fresh foods or will
steam defrost and cook frozen foods providing the
maximum color, flavor and nutritional value with the
least expenditure of energy and labor. The pressureless steaming compartments on the VHX series,
allows the operator to open and close the door
anytime during a cooking cycle. The steam supply
will shut off when the door is opened, then re-start
when the door is closed.
Model Designations
Cooking Compartments Control Panel
Compartment Pan Capacity
MODEL
VHX24E
VHX24E5
NUMBER OF PANS
PER COMPARTMENT
24.0
32.5
61.0
34.0
52.5
Boiler Control Panel
PAN
DEPTH
(INCHES)
101.0
Pan Size 12" x 20"
F25154 (February 2004)Page 4 of 48
VHX SERIES STEAMERS - GENERAL
Boiler Code Descriptions
Vulcan-Hart incorporates redundant controls in
compliance with the CSD-1 controls and safety
devices for boiler construction on the high efficiency
steamer models. A description of the code is listed
below.
CSD-1 Construction - Redundant controls in the
electrical safety circuits that, if tripped, must
manually be reset after the condition causing the trip
subsides. The controls provide low water level cut-off
protection (LLCO), auxiliary low water level cut-off
protection (Aux LLCO), and high pressure protection
for the boiler. Additionally, the low water and high
pressure safety circuits have individual indicator
lights that will illuminate for a visual verification of the
shutdown mode.
CSD-1 construction requires operator intervention in
the event of a shutdown. The indicator lights show
the operator which safety system was shutdown.
WATER CONDITIONING
Furnishing the boiler with treated water to reduce
scale formation is advised. Scale formation will
reduce steam output, cause premature component
failure, and shorten equipment life. Most water
supplies contain scale producing minerals such as
calcium and magnesium. As steam is generated, the
minerals remain and dissolve into the water. As the
concentration of these minerals increases past a
certain point, they precipitate from the water and
coat the inside of the boiler, heating elements, and
water level sensors. Because of the high
temperature of these surfaces, the precipitated
minerals bake onto them and become very difficult to
remove.
This may cause several problems:
1.Reduced heat transfer efficiency.
2.Premature heating element failures.
3.False readings from water level sensors.
These problems are common to any steam
equipment manufacturer, regardless of design, but
can be minimized by furnishing the boiler with
treated water.
Other factors affecting steam generation are iron
content, amount of chlorination and dissolved gases.
The desired water properties can best be achieved
by using a properly maintained water treatment
system.
The water level probes in the boiler use ions in the
water to detect the water level. Do not use fully
demineralized or de-ionized water since it is non
conductive and the water level can not be
detected.
The use of strainers will not remove minerals from
the water.
Water supplies vary from state to state and from
locations within a state. Therefore, a watertreatment specialist should be consulted before
the installation of any steam generating equipment.
Steamers that operate over a long period of time
without the benefit of a water treatment system,
which have developed a heavy scale build-up,
should be cleaned before using the system.
SPECIFICATIONS
Boiler Pressure
Operating - 10 to 12 psi
Maximum - 15 psi
Water Supply
The fact that a water supply is potable is no
guarantee that it is suitable for steam generation.
The supply connection to the steam generator
should be treated water and must be within the
guidelines listed below. For drain water cooling only,
an untreated water supply connection should be
used.
Supply connectioncold water
Supply pressure should be20-60 psig
Hardness*less than 60 ppm
Silica less than 13 ppm
Total Chloride less than 4 ppm
PH Range7 to 8
1. Amperage values in the table are
nominal. Tolerance is +5/-10%.
2. Voltage values are @ 60HZ.
3. 24KW 3 phase is standard for both
models. If a 24KW single phase
connection is needed, the machine is
field convertible at the terminal block.
See heating element circuit diagram
AI1388.
1 PHASE3 PHASE
208V 240V 208V 240V 480V
TOOLS
Standard
!
Standard set of hand tools.
!
VOM with AC current tester.
NOTE: Any quality VOM with a sensitivity of at
least 20,000 ohms per volt can be used.
Special
!
The recommended deliming chemical for the
water treatment system in use, for deliming of
the boiler.
Loctite 242 thread sealant or equivalent
P/N 520228. Used on the top and bottom
cooking compartment door screws.
!
3/8 x 16 tap. Used for cleaning out threads on
front boiler flange.
F25154 (February 2004)Page 6 of 48
VHX SERIES STEAMERS - REMOVAL AND REPLACEMENT OF PARTS
REMOVAL AND REPLACEMENT OF PARTS
PRESSURE SWITCH CONTROL
BOX COMPONENTS
WARNING: DISCONNECT THE
ELECTRICAL POWER TO THE
MACHINE AND FOLLOW LOCKOUT /
TAGOUT PROCEDURES.
CAUTION: Certain components in this system are subject to damage by electrostatic discharge during
field repairs. A field service grounding kit is available to prevent damage. The field service grounding kit
must be used anytime a control board is handled.
1.Open the cabinet base door.
2.Remove cover from pressure switch control box.
3.Disconnect lead wires from component being replaced.
4.To remove:
A.Cycling pressure switch.
1)Disconnect compression fittings in the pressure supply line leading to the switch.
2)Remove mounting nuts from pressure switch mounting panel.
3)Disconnect conduit from box.
F25154 (February 2004)Page 7 of 48
VHX SERIES STEAMERS - REMOVAL AND REPLACEMENT OF PARTS
4)Disconnect lead wires from other
components as necessary then
remove pressure switch mounting
panel.
MAIN CONTROL BOX
COMPONENTS
WARNING: DISCONNECT THE
ELECTRICAL POWER TO THE
MACHINE AND FOLLOW LOCKOUT /
TAGOUT PROCEDURES.
CAUTION: Certain components in this system
are subject to damage by electrostatic discharge
during field repairs. A field service grounding kit
is available to prevent damage. The field service
grounding kit must be used anytime a control
board is handled.
1.Open the cabinet base door.
2.Remove heating element cover then main
control
box cover.
5)Remove screws securing switch to
panel.
B.High limit pressure switch.
1)Disconnect compression fittings from
switch then remove from box.
C.Boiler fill or cold water condenser valve.
1)Turn water supply off and disconnect
compression fittings from valve.
2)Remove valve bracket mounting
screws.
D.Main or auxiliary water level control board
1)Compress locking tab on the board
mounting standoffs and remove
control board.
5.Reverse procedure to install.
NOTE: Before installing the cycling pressure switch,
use pressure scale on the switch to preset the
approximate cut-out (off) and cut-in (on) set points.
A.Adjust the installed pressure switch
(cycling or high limit) as outlined in
SERVICE PROCEDURES AND
ADJUSTMENTS.
3.Disconnect lead wires from component being
replaced.
6.Check for proper operation.
F25154 (February 2004)Page 8 of 48
4.To remove:
A.Contactors.
1)Release catch at the base of
B.Relays.
VHX SERIES STEAMERS - REMOVAL AND REPLACEMENT OF PARTS
WATER LEVEL GAUGE
ASSEMBLY
WARNING: DISCONNECT THE
ELECTRICAL POWER TO THE
MACHINE AND FOLLOW LOCKOUT /
TAGOUT PROCEDURES.
1.Remove right side panel.
NOTE: If right side panel is not accessible, open the
cabinet door and remove control panel to access
from front.
2.Loosen packing nuts on glass tube until threads
disengage then slide nut toward center of tube.
contactor and remove from DIN rail.
1)Remove from socket.
C.Relay Board.
1)Compress locking tab on the board
mounting standoffs and remove
control board.
5.Reverse procedure to install and check for
proper operation.
NOTE:
installed, the gap between the front lip of cover and
main control box must be maintained for adequate
ventilation. Do not seal the gap.
When the main control box cover is properly
LEFT SIDE VIEW SHOWN
3.Slide glass tube up until it clears the bottom
fitting, tilt out at the bottom and slide glass tube
down to remove.
NOTE: Clean glass tube if cloudy or replace if chips
or cracks are noticed.
4.Remove packing nuts from glass tube.
A.A single rubber washer is installed inside
each packing nut. Clean debris from
washer and inspect the rubber for cracks
or hardening.
1)If rubber washer needs replacing,
install a replacement rubber washer in
each packing nut.
NOTE: When installing, ensure friction
washer (flat) is installed inside the packing
nut before rubber washer.
5.To Install:
A.Slide packing nuts onto glass tube and
position each nut approximately 1" from
open end on tube.
F25154 (February 2004)Page 9 of 48
VHX SERIES STEAMERS - REMOVAL AND REPLACEMENT OF PARTS
B.Insert one end of glass tube into top gauge
fitting then align opposite end of tube with
bottom gauge fitting.
C.Lower the glass tube into bottom gauge
fitting then center the tube between top &
bottom gauge fittings.
D.Hold glass tube in place and hand tighten
the bottom packing nut then top.
E.Tighten each packing nut and additional
1/2 turn.
CAUTION: Do not over tighten packing nuts or
damage to glass tube may occur.
6.Re-connect power to the machine.
7.Turn power switch on and allow boiler to fill.
A.Press reset switch to begin heating (green
ready light on).
8.Check gauge glass for water and steam leaks.
A.If necessary, slowly tighten packing nuts
until leak stops.
9.Install right side panel or front control panel (if
removed).
HEATING ELEMENTS
WARNING: DISCONNECT THE
ELECTRICAL POWER TO THE
MACHINE AND FOLLOW LOCKOUT /
TAGOUT PROCEDURES.
1.Turn power switch off and allow boiler to
blowdown/drain.
2.Open the cabinet base door.
3.Remove heating element cover then main
control box cover.
4.Disconnect lead wires from heating element at
the contactor terminals.
5.Remove mounting nuts from heating element
and remove the element from boiler.
6.Clean the mating surface on mounting plate
then install a replacement gasket and heating
element.
7.Reverse procedure to install and check for
NOTE: When installing heating element, route the
lead wires between the contactors.
F25154 (February 2004)Page 10 of 48
proper operation.
VHX SERIES STEAMERS - REMOVAL AND REPLACEMENT OF PARTS
HEATING ELEMENT MOUNTING
PLATE
WARNING: DISCONNECT THE
ELECTRICAL POWER TO THE
MACHINE AND FOLLOW LOCKOUT /
TAGOUT PROCEDURES.
1.Remove heating elements as outlined under
HEATING ELEMENTS.
Loosen mounting hardware securing control
2.
panel to frame and lower the panel.
6.
Loosen both conduit locking nuts (1 1/2" & 3/8")
in main control box.
7.Loosen conduit nut (1 1/2") on elbow connected
to main control box.
8.Remove mounting bolts for main control box.
A.Lift main control box to remove from the
frame and position it to the left side.
9.Remove heating element mounting plate.
3.
On models with cooking compartments
disconnect power cord from power switch box
(rear of control panel).
4.
Disconnect pressure gauge tube
tee.
5.
Disconnect lead wire from Aux LLCO probe.
from fitting at
only,
10. To install:
A.
Clean the mating surfaces on heating
element mounting plate and boiler.
B.Install new gasket on boiler side of
mounting flange.
F25154 (February 2004)Page 11 of 48
VHX SERIES STEAMERS - REMOVAL AND REPLACEMENT OF PARTS
C.Position heating element mounting plate
with mounting studs for the element cover
at the top.
NOTE: When installing heating element
mounting plate
bolts as indicated to ensure the mounting plate
is flush with boiler flange and gasket is evenly
compressed. If bolt is not threading properly by
hand, clean out the threads with a 3/8 x 16 tap.
D.Align mounting holes then press and hold
heating element mounting plate against the
gasket. Install two bolts at the top and two
bolts at the bottom. Hand Tighten Only.
E.Starting with the bottom bolts, tighten each
bolt a few turns at a time and alternate
between the bottom and top bolts.
F.Install two bolts at the left and two bolts at
the right on the heating element mounting
plate. Tighten each bolt a few turns at a
time and alternate between the left and
right bolts.
G.Install the four remaining bolts. Tighten
each bolt a few turns at a time and
alternate between the four remaining bolts.
, install and tighten the mounting
RIGHT SIDE VIEW SHOWN
8.Remove gauge glass as outlined under
WATER LEVEL GAUGE ASSEMBLY.
9.Disconnect water level probe lead wires.
10. Remove coil from blowdown/drain valve.
11. Disconnect boiler fill and cold water condenser
valve water lines and remove lines.
11. To complete heating element mounting plate
installation, reverse procedure from main
control box removal.
BOILER ASSEMBLY
WARNING: DISCONNECT THE
ELECTRICAL POWER TO THE
MACHINE AND FOLLOW LOCKOUT /
TAGOUT PROCEDURES.
NOTE: To perform this procedure, the steamer must
be accessible from all sides.
1.Turn power switch off and allow boiler to
blowdown/drain.
2.Turn water supply off.
3.Remove left and right side panels.
4.Raise steamer from the bottom right side by
approximately three inches to drain the
remaining water from boiler. Lower steamer
when boiler is empty.
5.Remove heating element mounting plate as
outlined under HEATING ELEMENT
MOUNTING PLATE.
6.Disconnect pressure gauge tube from gauge.
7.Disconnect air equalization tube and remove.
LEFT SIDE VIEW SHOWN
12. Remove cover from pressure switch control box
and loosen conduit locking nut.
13. Remove mounting screws for pressure switch
control box.
14. Disconnect pressure relief valve drain line at
the valve.
15. Disconnect water level probe housing air
equalization tube and remove tube.
16. Disconnect water level probe housing drain line
from condenser drain box.
17. Disconnect boiler drain line from condenser
drain box.
F25154 (February 2004)Page 12 of 48
VHX SERIES STEAMERS - REMOVAL AND REPLACEMENT OF PARTS
LEFT SIDE VIEW SHOWN
18. Separate union at boiler drain.
19. On models with cooking compartments:
A.Remove the left and right access panels
between the cooking compartments and
boiler base.
B.Disconnect flexible steam supply line from
boiler tee to cooking compartments and
remove the line.
C.Disconnect both drain lines from cooking
compartments to condenser drain box and
remove the lines.
20. On models
disconnect steam supply line from boiler tee.
21. Loosen conduit nut on field connection box and
slide nut down onto conduit.
22. Remove cover from field terminal box and
disconnect lead wires from terminal block.
with steam generator base only,
LEFT SIDE VIEW SHOWN
23. Remove main control box and pressure switch
control box from boiler base.
24. Remove bolts securing boiler to base frame
then slide boiler forward to remove.
25. Remove all plumbing components from boiler
and install on replacement boiler.
26. Install replacement boiler but hand tighten
mounting bolts only.
27. To complete boiler installation, reverse
procedure from main control box and pressure
switch control box removal.
28. When all connections to boiler are made,
tighten boiler mounting bolts to secure boiler to
base frame.
29. Check for proper operation.
DESCALER (Cathodic Protector)
NOTE: The descalers are accessible only through
the heating element mounting plate opening in boiler.
1.Remove heating element mounting plate as
outlined under HEATING ELEMENT
MOUNTING PLATE.
2.Remove the two descalers hanging from the
front horizontal support rod.
F25154 (February 2004)Page 13 of 48
3.To install:
VHX SERIES STEAMERS - REMOVAL AND REPLACEMENT OF PARTS
5.Adjust the door as outlined in DOOR SEALING
ADJUSTMENT under COOKING
COMPARTMENT.
NOTE: Do not over tighten gasket plate screws as
this will compress the gasket excessively and
interfere with proper door sealing.
NOTE: Damage to the gasket sealing surface, such
as nicks or cuts, will cause steam leakage.
A.On the two replacement descalers, stretch
the coiled wire (cathode) at the top to
elongate the wire then form an open loop.
B.Hang the descalers on the front horizontal
support rod; one to the left of the heating
elements and one to the right.
C.Position the descalers so the core (anode)
is below the minimum water level in the
boiler and hanging freely.
NOTE: To function properly, the descalers must
not contact the interior surfaces of the boiler or
the heating elements.
COOKING COMPARTMENT
DOOR(S)
Removal
1.Remove top cover.
2.Open the door.
3.Pull hinge rod up.
4.Reverse the procedure to install, making sure
the door bushings are in place.
Handle
1.Open the door.
2.Remove screws from the top and bottom of the
door.
3.Pull the inner door panel out from the door
housing with the gasket plate and gasket still
attached.
Gasket
1.Open the door.
2.Remove screws from the gasket plate.
3.Pull the gasket plate out from the door housing
and remove the gasket.
4.Position the new gasket on the gasket plate and
reverse the procedure to install.
F25154 (February 2004)Page 14 of 48
VHX SERIES STEAMERS - REMOVAL AND REPLACEMENT OF PARTS
3.Pull the inner door panel out from the door
housing with the gasket plate and gasket still
attached.
4.Remove the screws from the side edge of the
door that secure the latch mechanism and
remove the latch from the door.
4.Remove the nuts and spacers from the handle
screws and remove the handle from the door.
NOTE: When installing the spacers, the smaller
diameter fits into the slot in the door and the latch
lever must rest on top of the handle latch screw.
NOTE: When installing, the latch lever must rest on
top of the handle latch screw.
5.Reverse procedure to install.
NOTE: When installing screws at the top and bottom
of door, apply thread sealant.
5.Reverse procedure to install.
NOTE: When installing screws at the top and bottom
of door, apply thread sealant.
Latch Assembly
1.Open the door.
2.Remove screws from the top and bottom of the
door.
F25154 (February 2004)Page 15 of 48
Loading...
+ 33 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.