VULCAN-HART CORPORATION, 3600 NORTH POINT BOULEVARD, BALTIMORE, MARYLAND 21222, TEL. (301) 284-0660
OPERATING, INSTALLATION AND SERVICE PERSONNEL
Operating information for this equipment has been prepared for use by qualified and/or authorized operating
personnel.
All installation and service on this equipment is to be performed by qualified, certified, licensed and/or
authorized installation or service personnel, with the exception of any marked with a , in front of the part
number.
Service may be obtained by contacting the Factory Service Department, Factory Representative or Local
Service Agency.
DEFINITIONS
QUALIFIED AND/OR AUTHORIZED OPERATING PERSONNEL
Qualified or authorized operating personnel are those who have carefully read the information in this manual
and are familiar with the equipment's functions or have had previous experience with the operation of the
equipment covered in this manual.
QUALIFIED INSTALLATION PERSONNEL
Qualified installation personnel are individuals, a firm, corporation or company which either in person or
through a representative are engaged in, and are responsible for:
1. The installation of gas piping from the outlet side of the gas meter, or the service regulator when the meter
is not provided, and the connection and installation of the gas appliance. Qualified installation personnel
must be experienced in such work, be familiar with all precautions required, and have complied with all
requirements of state or local authorities having jurisdiction. Reference in the United States of America National Fuel Gas code ANSI Z223 1 (Latest Edition) In Canada-Canadian Standard CAN1-B149 1 NAT
GAS (Latest Edition) or CAN1-B149 2 PROPANE (Latest Edition).
2. The installation of electrical wiring from the electric meter, main control box or service outlet to the electric
appliance. Qualified installation personnel must be experienced in such work, be familiar with all
precautions required, and have complied with all requirements of state or local authorities having
jurisdiction. Reference In the United States of America-National Electrical Code ANSI NFPA No 70 (Latest
Edition) In Canada-Canadian Electrical Code Part 1 CSA-C22 1 (Latest Edition).
QUALIFIED SERVICE PERSONNEL
Qualified service personnel are those who are familiar with Vulcan equipment who have been endorsed by
the Vulcan-Hart Corporation. All authorized service personnel are required to be equipped with a complete
set of service parts manuals and stock a minimum amount of parts for Vulcan equipment.
SHIPPING DAMAGE CLAIM PROCEDURE
For your protection, please note that equipment in this shipment was carefully inspected and packed by
skilled personnel before leaving the factory. The transportation company assumes full responsibility for safe
delivery upon acceptance of this shipment.
If shipment arrives damaged:
1. VISIBLE LOSS OR DAMAGE — Be certain this is noted on freight bill or express receipt and signed by
person making delivery.
2. FILE CLAIM FOR DAMAGES IMMEDIATELY — Regardless of extent of damage.
3. CONCEALED LOSS OR DAMAGE — If damage is unnoticed until merchandise is unpacked, notify
transportation company or carrier immediately, and file 'concealed damage" claim with them. This should
be done within (15) days of date of delivery is made to you. Be sure to retain container for inspection.
We cannot assume responsibility for damage or loss incurred in transit. We will, however, be glad to
furnish you with necessary documents to support your claim.
PLEASE RETAIN THIS MANUAL FOR FUTURE REFERENCE
IMPORTANT NOTES FOR ALL VULCAN APPLIANCES
1. These units are produced with the best possible workmanship and material. Proper installation is vital if best performance and
appearance are to be achieved. Installer must follow the installation instructions carefully.
2. Information on the construction and installation of ventilating hoods may be obtained from the "Standard for the installation of
equipment for the removal of smoke and grease laden vapors from commercial cooking equipment,” NFPA No 96 (latest edition)
available from the National Fire Protection Association, Battery March Park, Quincy MA 02269.
3. For an appliance equipped with a flexible electric supply cord, the cord is equipped with a three-prong (grounding) plug. This
grounding plug is for your protection against shock hazard and should be plugged directly into a properly grounded three prong
receptacle. Do not cut or remove the grounding prong from this plug If the appliance is not equipped with a grounding plug, and
electric supply is needed, ground the appliance by using the ground lug provided (refer to the wiring diagram).
(FOR GAS APPLIANCES ONLY)
4. Do not obstruct the air flow into and around the appliance. This air flow is necessary for proper combustion of gases and for
ventilation of the appliance. Provisions for ventilation of incoming air supply for the equipment in the room must be in accordance
with National Fuel Gas Code ANSI Z223.1 (latest edition).
5. Do not obstruct the flow of flue gases from the flue duct (when so equipped) located on the rear (or sides) of the appliance. It is
recommended that the flue gases be ventilated to the outside of the building through a ventilation system installed by qualified
personnel.
6. For an appliance equipped with casters, (1) the installation shall be made with a connector that complies with the Standard for
Connectors for Movable Gas Appliances, ANSI Z21.69 (latest edition), and Addenda, Z21. 69a (latest edition), and a quickdisconnect device that complies with the Standard for Quick-Disconnect Devices for Use With Gas Fuel, ANSI Z21.41 (latest
edition), and Addenda, Z21.41 a (latest edition) and Z21.41 b (latest edition), and (2) adequate means must be provided to limit
the movement of the appliance without depending on the connector and the quick-disconnect device or its associated piping to
limit the appliance movement.
If disconnection of the restraint is necessary, reconnect this restraint after the appliance has been returned to its originally
installed position.
7. The appliance and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing
of that system at test pressures in excess of 1/2 psig (3.45 k Pa).
8. The appliance must be isolated from the gas supply system by closing its individual manual shutoff valve during any pressure
testing of the gas supply system at test pressures equal to or less than 1/2 psig (3.45 k Pa).
CAUTIONS
FOR YOUR SAFETY
DO NOT STORE OR USE GASOLINE OR OTHER FLAMMABLE VAPORS AND LIQUIDS IN
THE VICINITY OF THIS EQUIPMENT OR ANY OTHER APPLIANCE.
1. KEEP THE APPLIANCE FREE AND CLEAR FROM ALL COMBUSTIBLE SUBSTANCES.
2. IN THE EVENT A GAS ODOR IS DETECTED, SHUT UNIT(S) DOWN AT THE MAIN
SHUTOFF VALVE AND CONTACT THE LOCAL GAS COMPANY OR GAS SUPPLIER FOR
SERVICE.
3. POST IN A PROMINENT LOCATION, INSTRUCTIONS TO BE FOLLOWED IN THE EVENT
THE SMELL OF GAS IS DETECTED. THIS INFORMATION MAY BE OBTAINED FROM A
LOCAL GAS SUPPLIER.
WARNINGS . . .
FROM THE TERMINATION OF THE
REFERENCE: ANSI/NFPA
96-1984 4
-
1.2.2.2.
OF THE NATIONAL FIRE
DO NOT SPRAY LIQUIDS OR VAPORS ON OR NEAR
WARNING:
EQUIPMENT UTILIZING ELECTRICITY
APPLIANCE FLUE VENT TO THE
FILTERS OF THE HOOD VENTING
SYSTEM, AN 18 INCH MINIMUM
CLEARANCE MUST BE MAINTAINED.
PROTECTION ASSOCIATION, INC., BATTERYMARCH PARK, QUINCY, MA
02269, AND NATIONAL BUILDING CODE 1976 SEC. 1015.7b (2) OF THE
AMERICAN INSURANCE ASSOCIATION. ENGINEERING AND SAFETY
SERVICE, 85 JOHN STREET, NEW YORK, NY 10038
116696-5
IMPORTANT NOTES
1. Vulcan units are produced with the best possible workmanship and material. Proper installation is vital if best
performance and appearance is to be achieved. Installer must follow the installation instructions carefully.
2. Keep the appliance area free and clear from all combustible substances,
3. For an appliance equipped with a flexible electric supply cord, the cord is equipped with a three prong (grounding)
plug. This grounding plug is for your protection against shock hazard and should be plugged directly into a three
prong receptacle. Do not cut or remove the grounding prong from this plug. If the appliance is not equipped with a
grounding plug, and electric supply is needed, ground the appliance by using the ground lug provided (refer to the
wiring diagram).
4. Retain this manual for future reference.
IMPORTANT
THIS EQUIPMENT IS DESIGN CERTIFIED BY A NATIONALLY
RECOGNIZED TESTING LABORATORY TO THE
APPROPRIATE NATIONAL STANDARDS AS INDICATED ON
THE EQUIPMENT RATING PLATE. ANY MODIFICATION
WITHOUT WRITTEN PERMISSION OF VULCAN-HART
CORPORATION VOIDS CERTIFICATION AND WARRANTY OF
THIS UNIT.
5. CAUTION: Post in a prominent location, instructions to be followed in the event the smell of gas is detected. This
information may be obtained from a local gas supplier.
6. Do not obstruct the air flow into and around the appliance. This air flow is necessary for proper combustion of gases
and for ventilation of the appliance. Provisions for ventilation and incoming air supply for the equipment in the room
must be in accordance with National Fuel Gas Code ANSI-Z223.1-1984.
7. Do not obstruct the flow of flue gases from the flue duct (when so equipped) located on the rear, sides or top of the
appliance. It is recommended that the flue gases be ventilated to the outside of the building through a ventilation
system installed by qualified personnel.
8. All CCFD-2C-KFC fryers are to be installed with a 6" clearance at the sides and rear adjacent to combustible
construction.
NOTE: An 18" minimum clearance must be maintained when placing a fryer next to adjacent to or behind an open top
flame unit.
9. The unit wiring diagram is packed in a clear plastic Ziploc bag placed within the fryer tank and also printed on the last
page of the CCFD-2C-KFC fryer installation, service and parts manual. A wiring diagram decal may be found
mounted on the inside left hand body side, just beyond the door area.
116696-6
INSTALLATION, SERVICE & PARTS MANUAL
FRYCAT™ GAS FRYER MODEL CCFD-2C-KFC INDEX
Your Vulcan fryer is produced with the best possible workmanship Proper usage and maintenance will result in many
years of satisfactory performance.
DESCRIPTION PAGE
The manufacturer suggests that you thoroughly read this entire
manual and carefully follow all of the instructions provided.
DEFINITIONS OF PERSONNEL (Operating, Installation & Service) and
SHIPPING DAMAGE CLAIM PROCEDURES
Warranty Information116696-3
Cautions116696-4 thru -5
Important Notes116696-6
Installation for Units on Casters116696-8
Uncrating Instructions116696-9
Electrical Connection116696-9
Gas Supply Connection116696-9
Installation Procedures to Verify Fryer Operation116696-10
Computer Mounting Installation Procedures116696-10 thru -11
Switch Panel Controls116696-11
Adding Shortening116696-11
Initial Operation Instructions116696-12
Cleaning116696-12
Blower Motor116696-12
Door Switch116696-12
Blower Air Adjustment116696-13
Foam Pre-Filter Cleaning116696-13
Ignitor Modules116696-14
Ignitor Module Reset116696-14
Setting Ignitor Location116696-14
High Limit Control116696-14
Suggestions for Care and Cleaning116696-14
Removal of Control Box Housing116696-15 thru -16
Troubleshooting Guides116696-17 thru -21
Replacements Parts List & Photographs116696-22 thru -32
Replacements Parts List & Exploded View116696-33 thru 35
Wiring Diagram116696-36
Revision Page(Inside Back Cover)
(Inside Front Cover)
SERVICE NOTE:
DO NOT ATTEMPT TO REMOVE SPARK IGNITORS OR BURNERS WITHOUT
CONSULTING VULCAN-HART SERVICE DEPARTMENT.
TELEPHONE: 1-800-638-2474
CAUTION: ELECTRICIAN
CONTINUITY OF ELECTRICAL GROUND TO WHICH THIS APPLIANCE WILL BE
CONNECTED MUST BE CONFIRMED. SEVERE DAMAGE TO ELECTRONIC
COMPONENTS CAN OCCUR AS A RESULT OF INADEQUATE GROUNDING.
116696-7
INSTALLATION FOR UNITS ON CASTERS
NOTE: All units on casters must be installed with a gas connector that complies with the American
National Standard ANSI Z21.69-1979 for movable gas appliances.
UNITS MOUNTED ON CASTERS UTILIZING A FLEX HOSE AND QUICK DISCONNECT GAS
CONNECTION MUST BE INSTALLED WITH RESTRAINING DEVICE AT ALL TIMES. THE
RESTRAINING DEVICE IS TO BE SUPPLIED BY OTHER THAN VULCAN-HART
CORPORATION.
If necessary, appliance strain relief may be disconnected when moving unit for cleaning. However,
caution must be taken that the gas supply has been turned off and disconnected. Reconnect
harness prior to the reconnecting of the gas supply and restoring unit to position and operation.
116696-8
UNCRATING INSTRUCTIONS
DETAIL A
116696
-
9
The following procedure should be followed when uncrating all CCF fryers.
NOTE: Personnel required to perform uncrating proce-
dure (2).
1. Place crated unit in open area near to final installation
locality.
2. Using band cutters, carefully remove (2) outer crating
straps.
3. Unfold cardboard crate top and remove (4) cardboard
cover protector sleeves.
4. Lift cardboard crate shell from unit.
5. Using band cutters, carefully remove (2) inner crating
straps.
6. Remove (2) cardboard protector sleeves from top right
and left hand tank sides.
7. Remove clear plastic protective cover from unit.
ELECTRICAL CONNECTION
Improper grounding and/or polarity will result in lock out
of unit and eventual damage to the ignition systems. The
unit is supplied with a 10 foot long 3 wire supply cord.
This appliance is equipped with a 3 prong (grounding)
8. Carefully lift unit styrofoam support block and wood
crating platform, then gently rest unit onto the floor.
9. Check unit packaging in areas indicated for the
following items:
FRYER TANK
A. Instruction Manual Packet (1).
B. Wiring Diagram Packet (1).
C. Clean-Out Rod (1).
D. Basket Supports (2).
E. Drain Pipe (1).
Items missing from the above packing list may be
obtained by contacting the local area Vulcan parts
depot or the Vulcan-Hart Corporation, Baltimore,
Maryland - Division Parts Department.
10. Discard crating materials.
11. Gently lift unit front and carefully wheel fryer to final
installation location.
plug for your protection against shock hazard and should
be plugged directly into a properly grounded three prong
receptacle. DO NOT cut or remove the grounding prong
from this plug. (DETAIL A)
GAS SUPPLY CONNECTION
For proper functioning of the CCF catalytic fryers, a gas
main feed inlet pressure of at least 5.0" W.C. (Water Column) but not more than 8.75" W.C. must be maintained
for natural gas while the unit is in operation. A gas main
feed inlet pressure of at least 12.0" W.C. but not more
than 13.0"W.C. must be maintained for propane gas
while the unit is in operation.
The pressure regulator setting of the CCFD-2C-KFC fryer
is 3.0"W.C. for natural gas and 9.0" W.C. for propane
gas.
When connecting unit to gas supply, installation
personnel must install this equipment in accordance with
all state and local authorities having jurisdiction. Refer to
inside front cover of manual under qualified personnel,
ITEM NO. 1.
All gas supply connections and any pipe joint compound
used must be resistant to the action of propane gases.
Pipe joints should be tested for leaks with a soap and
water solution before operating unit. (DETAIL A)
INSTALLATION PROCEDURES TO VERIFY
FRYER OPERATION
After making all electrical and gas connections, verify
fryer operation before installing computer as follows:
NOTE: An independent gas shut-off valve is supplied
within the fryer unit location to the rear of the gas
manifold system connecting to the 1/2" inlet gas pipe. This
shut-off valve must be in open position for proper unit
functioning.
1. Clean fryer tank as stated within the K.F.C. C.O.M.
and fill melted shortening to 1/2" below the vat full
mark.
2. Packing fryer vat with solid shortening
A. Remove basket rack supports.
B. Place solid cube of shortening to the rear of the
fryer tank. On split vat models be sure to push
cube down over the center divider in equal
sections.
C. Chop shortening cube up and pack shortening
well all around the heat exchanger tubes and
thermistor probe(s).
D. Replace basket rack supports in correct position
on top of the packed solid shortening.
E. Turn unit on and place unit into fat melt operation.
HAZARD NOTE: Failure to pack solid shortening as
described above may result in vat fire. Caution
should be taken and fryer should not be left
unattended.
3. Close fryer doors.
4. Check left side vat operation first by pushing left side
power switch to "ON" position. Verify fryer operation
and turn left vat side "OFF".
5. Check right side vat operation by pushing right side
power switch to "ON". Verify right side fryer operation.
6. Push left side power switch back "ON" and verify
simultaneous operation of both vats.
7. Allow fryer to operate for two to three minutes.
8. Shut fryer "OFF" and unplug electric supply. This completes fryer operation check out. NOTE: If fryer fails to
operate during any of the above procedures, verify
gas supply, electrical connections and refer to VulcanHart troubleshooting instructions.
COMPUTER MOUNTING INSTALLATION PROCEDURES
After verifying fryer operation, mount the computer panel
separately supplied by Stratford Control Systems, Inc. to
the CCFD-2C-KFC fryer following the instructions below:
1. Remove computer from shipment package.
2. Remove (2) black screws and (2) tinnerman nuts from
the right (RT.) and left (LT.) hand sides of the
computer panel.
3. Place clip section of tinnerman nuts (1 ea.) onto the
RT. & LT. hand fryer control housing frame. (See
Detail B).
DETAIL C
6. Align tinnerman nuts and computer mounting holes.
7. Reinstall black screws to the RT. and LT. hand sides
of the computer panel. Be sure screws are tightly secured. (See Detail D).
DETAIL B
4. Connect (2) sets of wiring harness cables (1 set for
LT. vat and 1 set for RT. vat.) supplied with the fryer
to the plugs provided on the rear of the computer
panel. (See Detail C).
5. Insert computer panel into the rectangular spacing
provided in the control housing frame.
116696-10
DETAIL D
COMPUTER MOUNTING INSTALLATION PROCEDURES
116696
-
11
NOTE: Check (FAST) operating instructions to verify cor-
rect computer installation and operation procedures.
8. Verify computer operation as follows:
A. Close fryer doors and plug in fryer electrical supply
cord.
B. Push right and left vat power switches to "ON".
C. Allow unit to heat up to frying temperature.
NOTE: If computer display reads LO-R or LO-L, the fryer
is in the automatic melt mode and the burner may not
come on immediately. When unit reaches programmed
frying temperature, computer display will indicate cooking
mode as described in the (FAST) computer operation instructions.
D. This completes the computer check-out procedure.
NOTE: If computer does not operate properly, refer
to (FAST) troubleshooting instructions.
SWITCH PANEL CONTROLS CCFD-2C-KFC
1. Power Switch "ON-OFF" - Controls electric supply to
unit.
2. Panel "ON" Light - Light "ON" indicates that electric
supply is functioning.
3. Microprocessor Controlled Cooking Computer -
Preprogramming device which, when activated, controls unit frying modes. (Computer supplied by other
than Vulcan-Hart Corp.) (See Detail E).
4. Heating Light - When "ON" indicates that the temperature controller is calling for gas to the burner.
5. Trouble Light - When "ON" indicates that ignition device has locked out (reset required). NOTE: To reset,
turn power switch "OFF" then "ON".
DETAIL E
ADDING SHORTENING
REFER TO CONFIDENTIAL OPERATION MANUAL.
See also pg. 10 of this manual (Packing fryer vat with solid shortening).
INITIAL OPERATION INSTRUCTIONS
DETAIL F
116696
-12
1. Push power supply rocker switch to "ON" position.
NOTE: Gas line service valve must be in "OPEN"
position and all power supply cords and harness cables
must be connected to the unit power source for
operational functioning. The independent gas shut-off
valve supplied within the unit located to the rear of the
unit manifold system connecting to the 1/2" inlet pipe
must be in the open position for proper unit operation.
NOTE: If the shortening temperature is less than 185°F
the fryer is in the automatic melt mode and the burner
During the first few "ON" pulses, the trouble indicator
light may come on indicating no ignition due to air in the
gas line. If this happens, turn the rocker switch off and
then back on and try again.
For service or extended shutdown, turn service valve to
"CLOSED" position, push unit power supply rocker
switch to "OFF" position and disconnect power supply
cord from main power source.
The above information may also be found on the inside
fryer door panel.
may not come on immediately. In this mode, the burner
pulses "ON" 4 seconds and "OFF" 26 seconds.
New fryer tanks must be cleaned before filling with shortening.
REFER TO KFC CONFIDENTIAL OPERATION MANUAL.
BLOWER MOTOR
CCFD-2C-KFC series fryers are equipped with a factory
installed blower motor. Proper operation of the blower
motor is vital to the fryer performance. The blower motor
is the main source of air flow servicing the burner ignition
system.
DOOR SWTICH
Each CCFD-2C-KFC fryer is equipped with a door safety
switch that will automatically shut the unit down when the
fryer door is opened. However, operating and service
personnel should NOT rely on door switch to shut unit
down while working inside the door panel control area.
WARNING: Do not rely on door switch to shut unit power
down. Push fryer power switch to "OFF" before entering
the inside door panel control area for filtering or servicing.
By-passing the fryer door switch should be done by
service personnel only. (See Detail F).
Loading...
+ 24 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.