Vulcan-Hart BVD34FP50F, BVP42FP32F, BVD36FP52F, BVD36FP32F, BVP42FP52F User Manual

...
INSTALLATION INSTRUCTIONS
GAS-FIRED
AND
OWNER’S MANUAL
The Keystone "B" Vent Zero Clearance Gas
Fireplace
B-VENT
GAS FIREPLACE
MODEL SERIES
MILLIVOLT
BVD34FP30(F,L)N-1 BVD36FP32(F,L)N-1
BVP42FP32(F,L)N-1
DIRECT IGNITION
BVP42FP52(F,L)N-1
EFFECTIVE DATE
APRIL 2006
UL FILE NO. MH45034
Installer: Leave these instructions with the consumer.
Consumer: Retain these instructions for future use.
WARNING: If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
-
-
Do not try to light any appliance.
Do not touch any electrical switch; do not use any
● Immediately call your gas supplier from a neighbors
● If you cannot reach your gas supplier, call the fire
-
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
phone in your building.
phone. Follow the gas supplier's instructions.
department. Installation and service must be performed by
a qualified installer, service agency, or the gas supplier.
NOT INTENDED FOR USE AS A PRIMARY HEAT SOURCE. This appliance is tested and approved as either supplemental room heat or as a decorative appliance. It should not be factored as primary heat in residential heating calculations.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certified kit is used.
WARNING: If not installed, operated and maintained in accordance with the manufacturer’s instructions, this product could expose you to substances in fuel or from fuel combustion which can cause death or seri­ous illness.
Page 119400-3-0406
TABLE OF CONTENTS
Section 
Important Safety Information ....................................................................................................3
Safety Information for Users of LP Gas ....................................................................................4
Introduction ..............................................................................................................................5
Specifications ............................................................................................................................6
Fireplace Dimensions ................................................................................................................6
Clearances .� 7
Locating Fireplace .....................................................................................................................7
Gas Supply .............................................................................................................................8-9
Installation .........................................................................................................................10-11
Venting ...............................................................................................................................12-13
Log Placement (BVD34 and BVD36) (5 Log Set) .................................................................14
Log Placement (BVP42) (3 Log Set) ......................................................................................15
Operating Instructions ........................................................................................................16-17
Standing Pilot Wiring Diagram ...............................................................................................18
Standing Pilot Lighting Instructions .......................................................................................19
Standing Pilot Troubleshooting ............................................................................................... 20
Standing Pilot Propane/LP Gas Conversion .......................................................................21-22
Direct Ignition Wiring Diagram ..............................................................................................23
Optional Remote Control (120V Direct Ignition) ...................................................................23
Direct Ignition Lighting Instructions .......................................................................................24
Direct Ignition Troubleshooting ..............................................................................................25
Direct Ignition Propane/LP Gas Conversion ......................................................................25-26
Maintenance and Service .........................................................................................................27
BVD34 and BVD36 Parts List ................................................................................................28
BVD34 and BVD36 Parts View ..............................................................................................29
BVP42 Parts List ..................................................................................................................... 30
BVP42 Parts View ...................................................................................................................31
FBB4 Optional Variable Speed Blower Installation Instructions .......................................32-33
Junction Box Wiring Installation Instructions .........................................................................34
Optional Accessories ...............................................................................................................35
Decorative Accessories ............................................................................................................36
How To Order Repair Parts ..................................................................................................... 37
Service Notes ......................................................................................................................37-39
Page 2 19400-3-0406
IMPORTANT SAFETY INFORMATION
Before enclosing the vent pipe assembly, operate the appliance to ensure it is venting properly.
• If this appliance is installed directly on carpeting, tile or other combustible material other than wood flooring the appliance shall be installed on a metal or wood panel extending the full width and depth of the appliance.
The base referred to above does not mean the fireproof
base as used on wood stoves. The protection is for rugs that are extremely thick and light colored tile.
• Children and adults should be alerted to the hazards of high surface temperatures and should stay away to avoid burns or clothing ignition.
• Young children should be carefully supervised when they are in the same room as the appliance.
• Due to high temperatures the appliance should be located out of traffic and away from furniture and draperies.
• Any part removed for servicing the appliance must be replaced prior to operating the appliance. Work should be done by a qualified service person.
• Keep burner and control compartment clean.
• Clothing or other flammable material should not be placed on or near the appliance.
• Adequate accessibility clearances for servicing and proper operation.
• This appliance must not share or be connected to a flue serving a separate solid-fuel burning appliance.
• Keep the area around your appliance clear of combustible materials, gasoline and other flammable vapor and liquids.
• Under no circumstances should any solid fuels (wood, coal, paper or cardboard etc.) be used in this appliance.
• The flow of combustion and ventilation air must not be obstructed in any way.
• DO keep the appliance area clear and free from combustible material, gasoline and other flammable vapors and liquids.
• DO examine venting system periodically and replace damaged parts.
• DO make a periodic visual check of pilot and burners. Clean and replace damaged parts.
• Vent cap is hot while fireplace is in operation.
• Installation and repair should be done by a QUALIFIED SERVICE PERSON. The appliance should be inspected before use and at least annually by a qualified service person. More frequent cleaning may be required due to excessive lint from carpeting, bedding materials, etc. It is imperative that control compartments, burners and circulating air passageways of the appliance be kept clean.
• DO NOT put anything around the fireplace that will obstruct the flow of ventilation air.
• Clearance in accordance with local installation codes and the requirements of the gas supplier.
• DO NOT use this fireplace if any part has been under water. Immediately call a qualified service technician to inspect the heater and to replace any part of the control system and any gas control which has been under water.
• Any safety screen or guard removed for servicing an appliance must be replaced prior to operating the appliance.
Page 319400-3-0406
SAFETY INFORMATION FOR USERS OF LP GAS
Propane (LP-Gas) is a flammable gas which can cause fires and explosions. In its natural state, propane is odorless and colorless. You may not know all the following safety precautions which can protect both you and your family from an accident. Read them carefully now, then review
LP-GAS WARNING ODOR
If a gas leak happens, you should be able to smell the gas because of the odorant put in the LP-Gas.
That’s your signal to go into immediate action!
Do not operate electric switches, light matches, use your phone. Do not do anything that could ignite the gas.
• Get everyone out of the building, vehicle, trailer, or area. Do that IMMEDIATELY.
• Close all gas tank or cylinder supply valves.
• LP-Gas is heavier than air and may settle in low areas such as basements. When you have reason to suspect a gas leak, keep out of basements and other low areas. Stay out until firefighters declare them to be safe.
NO ODOR DETECTED - ODOR FADE
Some people cannot smell well. Some people cannot smell the odor of the chemical put into the gas. You must find out if you can smell the odorant in propane. Smoking can decrease
your ability to smell. Being around an odor for a time can affect your sensitivity or ability to detect that odor. Sometimes other odors in the area mask the gas odor. People may not smell the gas odor or their minds are on something else. Thinking about smelling a gas odor can make it easier to smell.
The odorant in LP-Gas is colorless, and it can fade under some circumstances. For example, if there is an underground
leak, the movement of the gas through soil can filter the odorant. Odorants in LP-Gas also are subject to oxidation. This fading
them point by point with the members of your household. Someday when there may not be a minute to lose, everyone’s safety will depend on knowing exactly what to do. If, after reading the following information, you feel you still need more information, please contact your gas supplier.
• Use your neighbor’s phone and call a trained LP-Gas service person and the fire department. Even though you may not continue to smell gas, do not turn on the gas again. Do not re-enter the building, vehicle, trailer, or area.
Finally, let the service man and firefighters check for escaped gas. Have them air out the area before you return. Properly trained LP-Gas service people should repair the leak, then check and relight the gas appliance for you.
can occur if there is rust inside the storage tank or in iron gas pipes.
The odorant in escaped gas can adsorb or absorb onto or into walls, masonry and other materials and fabrics in a room. That will take some of the odorant out of the gas, reducing its odor intensity.
LP-Gas may stratify in a closed area, and the odor intensity could vary at different levels. Since it is heavier than air, there may be more odor at lower levels. Always be sensitive to the slightest gas odor. If you detect any odor, treat it as a serious leak. Immediately go into action as instructed earlier.
SOME POINTS TO REMEMBER
Learn to recognize the odor of LP-Gas. Your local LP-Gas Dealer can give you a “Scratch and Sniff” pamphlet. Use it to find out what the propane odor smells like. If you suspect that your LP-Gas has a weak or abnormal odor, call your LP-Gas Dealer.
• If you are not qualified, do not light pilot lights, perform service, or make adjustments to appliances on the LP-Gas system. If you are qualified, consciously think about the odor of LP-Gas prior to and while lighting pilot lights or performing service or making adjustments.
• Sometimes a basement or a closed-up house has a musty smell that can cover up the LP-Gas odor. Do not try to light pilot lights, perform service, or make adjustments in an area where the conditions are such that you may not detect the odor if there has been a leak of LP-Gas.
• Odor fade, due to oxidation by rust or adsorption on walls of new cylinders and tanks, is possible. Therefore, people should be particularly alert and careful when new tanks or cylinders are placed in service. Odor fade can occur in new tanks, or reinstalled old tanks, if they are filled and allowed
Page 4 19400-3-0406
to set too long before refilling. Cylinders and tanks which have been out of service for a time may develop internal rust which will cause odor fade. If such conditions are suspected to exist, a periodic sniff test of the gas is advisable. If you
have any question about the gas odor, call your LP-Gas dealer. A periodic sniff test of the LP-Gas is a good safety measure under any condition.
• If, at any time, you do not smell the LP-Gas odorant and you think you should, assume you have a leak. Then take the same immediate action recommended above for the occasion when you do detect the odorized LP-Gas.
• If you experience a complete “gas out,” (the container is under no vapor pressure), turn the tank valve off immediately. If the container valve is left on, the container may draw in some air through openings such as pilot light orifices. If this occurs, some new internal rusting could occur. If the valve is left open, then treat the container as a new tank. Always be sure your container is under vapor pressure by turning it off at the container before it goes completely empty or having it refilled before it is completely empty.
INTRODUCTION
Instructions to Installer
1. Installer must leave instruction manual with owner after installation.
2. Installer must have owner fill out and mail warranty card supplied with the fireplace.
3. Installer should show owner how to start and operate the fireplace.
This is a B-Vent gas appliance and must be installed with a listed B-Vent vent system. The information contained in this manual pertains to all models and gas control systems unless otherwise noted.
Warning: This unit is not for use with solid fuels.
Appliance Certification
This fireplace is design certified in accordance with American National Standard/CSA Standard ANSI Z.21-50/CSA 2.22 and by Underwriters Laboratories as a Vented Gas Appliance and shall be installed according to these instructions.
Consult your local building code agency, prior to installation, to ensure compliance with local codes-including permits and inspections.
The fireplace, when installed, must be electrically grounded in accordance with local codes or, in absence of local codes, with the National Electric Code ANSI/NFPA 70 if an external electrical source is utilized.
These models may be installed in a bedroom or bed-sitting room in the U.S.A.
Qualified Installing Agency
Installation and replacement of gas piping, gas utilization equipment or accessories and repair and servicing of equipment shall be performed only by a qualified agency. The term “qualified agency” means any individual, firm, corporation or company which either in person or through a representative is engaged in and is responsible for (a) the installation or replacement of gas piping or (b) the connection, installation, repair or servicing of equipment, who is experienced in such work, familiar with all precautions required and has complied with all the requirements of the authority having jurisdiction.
State of Massachusetts: The installation must be made by a licensed plumber or gas fitter in the Commonwealth of Massachusetts. The state of Massachusetts requires that a flexible appliance connector cannot exceed three feet in length.
The installation must conform with local codes or, in the absence of local codes, with the National Fuel Gas Code ANSI Z223.1/NFPA
54* Natural Gas and Propane Installation Code, or CSA B149.1 in Canada. *Available from the American National Standards Institute, Inc. 11
West 42nd St., New York, N.Y. 10036.
Warning: ANY CHANGE TO THIS FIREPLACE OR ITS CONTROLS CAN BE DANGEROUS. Improper installation or use of the fireplace can cause serious injury or death from fire, burns, explosions, or carbon monoxide poisoning.
Any alteration of the original design, installed other than as shown in these instructions or use with a type of gas not shown on the rating plate is the responsibility of the person and company making the change. Important
All correspondence should refer to complete Model Number, Serial Number and type of gas.
High Altitude
When installing this unit at an elevation above 2000 feet (in the United States) it may be necessary to decrease the input rating by changing the existing burner orifice to a smaller size. Generally, input should be reduced 4 percent for each 1000 feet above sea level. However, if the heating value of the gas has been reduced, this general rule may not apply. Check with local gas utility for proper orifice size identification.
Canadian High Altitude
Altitude: 0-4500 feet (0-1370 m)
When installing this unit at an elevation above 4500 feet (in Canada), check with local authorities.
Consult your local gas utility for assistance in determining the proper orifice for location.
Preparation
This gas fireplace and its components are tested and safe when installed in accordance with this Installation Manual. Report to your dealer any parts damaged in shipment, specifically check glass condition. Do not install unit with damaged, incomplete, or substitute parts. Read all instructions before starting installation and follow these instructions carefully during installation to insure maximum benefit and safety. Failure to follow them will void your warranty and may present a fire hazard.
The warranty will be voided by, and the warrantor disclaims any responsibility for the following actions:
• Installation of any damaged fireplace or vent system component.
• Modification of the fireplace or vent system.
• Installation other than as instructed by Empire Comfort Systems, Inc.
• Improper positioning of the logs, glass door, optional accessories or decorative rock.
• Installation and/or use of any component part not manufactured or approved by manufacturer.
Glass Specifications
Optional glass door kits manufactured with tempered glass may be installed in hazardous locations such as bathtub enclosures as defined by the Consumer Product Safety Commission (CPSC). The tempered glass has been tested and certified to the requirements of ANSI Z97.1 and CPSC 16 CFR 1202 (Safety Glazing Certification Council SGCC# 1595 and 1597. Architectural Testing, Inc. Reports 02-31919.01 and 02-31917.01).
This statement is in compliance with CPSC 16 CFR Section
1201.5 "Certification and labeling requirements" which refers
to 15 U.S. Code (USC) 2063 stating "...Such certificate shall accompany the product or shall otherwise be furnished to any
Page 519400-3-0406
RIGHT SIDE VIEW
J
H
GAS CONTROLS BEHIND LOWER LOUVER OR UNDER SLIDING HEAR
TH ACCESS DOOR
K
K
L
M
M
G
O
N
P
G
SPECIFICATIONS
BVD34FP BVD36FP BVP42FP
Input Btu/hr Maximum 21,000 25,000 30,000
KWH (Maximum) 6.2 7.3 8.8
B-Vent Size 4" Diameter 6" Diameter 6" Diameter
NAT. (Standard)
Orifice
Air Shutter Opening 1/8" (3.2mm) 1/8"(3.2mm) 1/8" (3.2mm)
*LP (Conversion Kit Required)
Orifice
Air Shutter Opening 5/16" (7.9mm) 5/16" (7.9mm) Full Open
Height without standoff 32 3/4"(832mm) 34 3/4"(883mm) 34 3/4"(883mm)
Width 37" (940mm) 39" (990mm) 43" (1,092mm)
Depth 14 7/8" (378mm) 18 3/8" (467mm) 18 3/8" (467mm)
Gas Inlet Shutoff Valve (Pipe) 1/2 NPT 1/2 NPT 1/2NPT
*NOTE: LP Conversion kits are included on the 120v. direct ignition model fireplaces. For millivolt models, use kit #19160 for BVD34FP Series, kit #19161 for BVD36FP Series, and kit #19162 for BVP42FP Series.
#44 (.086) P-252
1.35mm P-289
#42 (.0935) P-286
1.45 mm P-208
#37 (.104) P-213
1.65mm P-250
NO T E: A i r s hu t te r sett i n gs ar e f acto r y minimum settings. Some venting configurations may require minor air shutter adjustments for optimum performance.
Remote Control Options &
Accessories
FRBC MILLIVOLT BATTERY REMOTE ON/OFF
FREC DIRECT IGNITION/MILLIVOLT 120V ON/OFF REMOTE
FWS-1 DIRECT IGNITION/MILLIVOLT WALL SWITCH
Description
FIREPLACE DIMENSIONS
Dim BVD34 BVD36 BVP42
37"
A
940mm 34"
Figure 1
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
864 mm 22 7/8"
581mm 35 5/8"
905 mm 32 3/4"
832mm 14 7/8"
378mm 6 3/8"
162mm 5 7/8"
149mm 24 1/2"
622mm 12 1/4"
311mm 1 1/4"
32mm 31 3/4"
807mm 32 11/16"
830mm 2 1/16"
53mm 5 5/8"
143mm 4 7/8"
124mm
Page 6 19400-3-0406
39" 990mm
36" 914mm
24 7/8" 632mm
37 5/8" 956 mm
34 3/4" 883 mm
18 3/8 467mm
6 3/8" 162mm
8 3/8" 213mm
22 1/2" 572mm
11 1/4" 286mm
1 1/4" 32mm
33 3/4" 857mm
34 11/16" 881mm
2 1/16" 53mm
5 5/8" 143mm
4 7/8" 124mm
43" 1092mm
40" 1,016mm
24 7/8" 632mm
37 5/8" 956 mm
34 3/4" 883 mm
18 3/8" 467mm
6 3/8" 162mm
6 3/8" 162mm
26 1/2" 673mm
13 1/4" 337mm
1 1/4" 32mm
33 3/4" 857mm
34 11/16" 881mm
2 1/16" 53mm
5 5/8" 143mm
4 7/8" 124mm
Clearance to Combustibles
12”
TO
P EDGE OF FIREPLACE
12” (305mm)
10” (254mm)
MANTEL
COMBUSTIBLE TRIM
AND MANTELS
ALLOWED
IN SHADED AREA
1/4”
(6.35mm)
3”
4”
5”
6”
8”
10 3 /4”
3/4”
1 ½
2 1
/4”
3”
3 3
/4”
4 ½
6”
8”
1”
2”
SEE MANTLE CHART
FOR
MAXIMUM MANTLE DEPTH
NAILING FLANGES
GLASS
FRONT
(OPTIONAL)
TO
P FRAMING
LEDGE
FINISHED
WALL
(COMBUSTIBLE)
SEE
MANTLE CHAR
T FOR MINIMUM HEIGHT OF
MANTLE ABOVE
UNI
T
2" x 4
" HEADER
STAND
OFF 3" (76 mm) HEIGHT ABOVE TOP O
F
FIREPLACE
Back 0" (0 mm)
Side 0" (0 mm)
Floor 0" (0 mm)
Top Stand-off 0" (0 mm)
Top Framing Edge 1" (25mm)
CLEARANCES
Mantel Chart (Figure 3)
Figure 3
Clearances (Figure 4)
Clearance from top front edge of fireplace to ceiling is 36" Clearance from side of fireplace to adjacent sidewall is 6".
Combustible Material
No greeting cards, stockings or ornamentation of any type should be placed on or attached to the fireplace. The flow of heat can ignite combustibles.
Note: When you install your Firepl a c e o n w a l l c o r n er positions, a minimum of 6 inches clearance must be maintained from the perpendicular side wall and the screened opening of the appliance.
Figure 2
LOCATING FIREPLACE
Figure 4
Figure 5
Page 719400-3-0406
GAS SUPPLY
The gas pipeline can be brought in through the right or left side of the appliance. Consult the current National Fuel Gas Code, ANSI Z223.1 CAN/CGA-B149 (.1 or .2) installation code.
Recommended Gas Pipe Diameter
Pipe Length
(Feet)
0-10 1/2"
11-40 1/2"
41-100 1/2"
101-150 3/4"
Schedule 40 Pipe Inside Diameter
Nat. L.P. Nat. L.P.
3/8"
12.7mm
12.7mm
12.7mm
19mm
9.5mm
1/2"
12.7mm
1/2"
12.7mm
1/2"
12.7mm
Tubing, Type L Outside Diameter
1/2"
12.7mm
5/8"
15.9mm
3/4" 19mm
7/8"
22.2mm
3/8"
9.5mm
1/2"
12.7mm
1/2"
12.7mm
3/4"
1.9 mm
Note: Never use plastic pipe. Check to confirm whether your local codes allow copper tubing or galvanized. Note: Since some municipalities have additional local codes, it is always best to consult your local authority and installation code.
The use of the following gas connectors is recommended:
— ANS Z21.24 Appliance Connectors of Corrugated Metal
Tubing and Fittings.
— ANS Z21.45 Assembled Flexible Appliance Connectors of
Other Than All-Metal Construction The above connectors may be used if acceptable by the authority having jurisdiction. The state of Massachusetts requires that a flexible appliance connector cannot exceed three feet in length.
Installing a New Main Gas Cock
Each appliance should have its own manual gas cock.
A manual main gas cock should be located in the vicinity of the unit. Where none exists, or where its size or location is not adequate, contact your local authorized installer for installation or relocation.
Compounds used on threaded joints of gas piping shall be resistant to the action of liquefied petroleum gases. The gas lines must be checked for leaks by the installer. This should be done with a soap solution watching for bubbles on all exposed connections, and if unexposed, a pressure test should be made.
Never use an exposed flame to check for leaks. Appliance must be disconnected from piping at inlet of control valve and pipe capped or plugged for pressure test. Never pressure test with appliance connected; control valve will sustain damage!
NOTE: The millivolt gas controls are equipped with a captured
screw type pressure test point, therefore it is not necessary to provide a 1/8" test point up stream of the control.
On direct ignition valves, hex plugs may be replaced with hose fittings for pressure checks, then reinstalled before operating fireplace.
When using copper or flex connector use only approved fittings.
The appliance and it’s individual shut off valve must be disconnected from supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psig (3.5kPa).
The appliance must be isolated from the gas supply piping system by closing its individual manual shut off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig (3.5kPa).
Attention! If one of the procedures results in pressures in excess of 1/2 psig (14" w.c.) (3.5 kPa) on the fireplace gas valve, it will result in a hazardous condition.
Figure 6
Gas Supply Pressure (inches w.c.)
Minimum Normal Maximum
Natural Gas 4.5" 7.0" 14.0"
LP (Propane) 10.8" 11.0" 14.0"
Manifold Pressure (inches w.c.)
Normal (HI)
Natural Gas 3.5"
LP (Propane) 10.0"
Page 8 19400-3-0406
FROM FRONT OF APPLIANCE TO GAS LINE HOLE
3 ½”
GAS LINE HOLE
BVD34 SERIES - 10” BVD,P (36,42) - 13 ½”
BURNER ASSEMBLY
REAR TA
B (BURNER BASE)
LOCATIONS
FLEXIBLE GAS CONNECTOR
GAS SUPPL
Y LINE
FIREBOX BOTTOM CUTOUT ACCESS
SLIDING VALV
E ACCESS
COVER
PIEZO IGNITER
GAS SUPPLY (CONT)
Checking Manifold Pressures
Both Propane and Natural gas valves have a built-in pressure regulator in the gas valve. Natural gas models will have a manifold pressure of approximately 3.5" w.c. (.871kPa) at the valve outlet with the inlet pressure to the valve from a minimum of 4.5" w.c. (1.120kPa) for the purpose of input adjustment to a maximum of
14.0" w.c. (3.484kPa). Propane gas models will have a manifold pressure approximately 10.0" w.c. (2.49kPa) at the valve outlet with the inlet pressure to the valve from a minimum of 10.8" w.c. (2.68kPa) for the purpose of input adjustment to a maximum of
14.0" w.c. (3.484kPa).
Figure 7
Figure 8
Page 919400-3-0406
B-
TO
COMBUSTIBLES
NAIL OR OTHER SUITABLE FASTENER
MOUNTING BRACKETS
INSTALLATION
Framing and Finishing
1. Choose unit location.
2. Frame in fireplace with a header across the top. It is important
to allow for the finished face thickness when setting the depth of the frame. See Figures 9 & 11.
3. Attach fireplace to framing using (4) adjustable nailing flanges.
Preset depth to suit facing material (adjustable to 1/2", 5/8" or 3/4" depths).
4. Use (8) 1/2" hex-head screws supplied in hardware package
to screw through slotted holes in nailing flanges, then screw into pre-drilled holes on fireplace side. Measure from face of fireplace to face of the nailing flanges to determine final depth.
Install the Fresh Air Kit - BVA1
A fresh air kit is available as an optional feature with this appliance. The fresh air kit helps to decrease the amount of room air taken by utilizing outside air for combustion. It is strongly recommended that it be installed. Installation of the fresh air kit should be performed at the framing stage of the fireplace installation.
The fresh air kit installs on the left side of the fireplace. To install the BVA1 fresh air kit, refer to the installation instructions provided with the kit.
Note: The outside air kit can terminate at any level with the exception that it must terminate at least 1 ft below the vent termination cap. The fresh air kit inlet hood should be positioned at least 2 ft above the ground level, in a manner that will not allow snow, leaves, etc. to block the inlet.
WARNING: Exhaust products of gasoline engines are hazardous. The outside air must not be taken from a garage space, attic spaces, basements, or above the roofing where other heating appliance, fans, or chimneys exhaust or utilize the air.
Framing (Figure 11)
Fireplace framing can be built before or after the fireplace is set in place. Framing should be positioned to accommodate wall covering and fireplace facing material. The fireplace framing should be constructed of 2 x 4 lumber or heavier. The framing headers may rest on the fireplace standoffs. Refer to Figure 11 for minimum framing dimensions.
CAUTION: MEASURE FIREPLACE DIMENSIONS AND VERIFY FRAMING METHODS, AND WALL COVERING DETAIL S B E F O RE F R AMING CON S T R UCTION BEGINS.
Figure 9
Vent Pipe Clearance Note: Maintain one inch (1") of clearance around vertical vent pipe.
Framing dimension "A" includes a three inch clearance for standoffs on firebox.
Follow the B-Vent system instructions for installation requirements and clearances. Failure to follow the B-Vent manufacturer's instructions may cause improper draft and possible fire hazard.
Figure 10
Page 10 19400-3-0406
FINISHED WALL
JOINT BETWEEN FINISHED
WALL AND
UNIT SEALED WITH
300° F 149
MATERIAL (SEALANT IS OPTIONAL)
° C
SEALANT
COMBUSTIBLE SURROUND
MANTELSHELF
2 X 4 HEADER
STAND OFF
FRONT TRIM OR NON-COMBUSTIBLE MATERIAL MA
Y OVERLAP BLACK PAINTED
FACE (INSTALLATION IS OPTIONAL)
INSTALLATION (CONT)
Minimum Framing Dimensions
BVD34 BVD36 BVP42
"A" 35 3/4"
(908mm)
"B" 37 3/8"
(949mm)
"C" 14 3/8"
(378mm)
Note: Dimension "C" is the minimum with the fireplace face extending 1/2" in
front of the framing to allow for finishing materials.
37 3/4" (959mm)
39 3/8" (1,000mm)
17 7/8" (454mm)
Figure 11
37 3/4" (959mm)
43 3/8" (1,102mm)
17 7/8" (454mm)
Combustible Surround Installation
Figure 12
Attention: Add 3-3/4" to “A” dimensions when using a flush
mantel base. Attention: If a base or mantel is not used and the appliance is installed directly on carpeting, tile or other combustible material other than wood flooring, it shall be installed on a metal or wood panel extending the full width and depth of the appliance. The vertical dimension in Figure 11 must be adjusted when a metal or wood panel is placed beneath the appliance.
Finishing (Figure 12)
Finish the walls with the material of your choice. Only non­combustible materials may be used to cover the black fireplace front.
Warning: When finishing the fireplace never obstruct or modify the air inlet/outlet louvers in any manner. Provide adequate clearances around air openings into the combustion chamber.
Caution: If the joints between the finished wall and the fireplace
surround (top and sides) are sealed, a 300°F minimum sealant material must be used. These joints are not required to be sealed. Only non-combustible material (using 300°F minimum adhesive if needed), can be applied as facing to the fireplace surround.
Attention: Cold climate installation recommendation: When installing this unit against a non-insulated exterior wall, it is recommended that the outer walls be insulated to conform to applicable insulation codes.
Page 1119400-3-0406
VENT CAP
GAS VENT
H
LOWEST DISCHARGE OPENING
H (Min.) - Minimum height from roof
to lowest discharge opening
ROOF PITCH
IS X/12
VENTING
Vent Runs
In planning the installation for the fireplace, it is necessary to install certain components before the appliance is completely positioned and installed. These include the vent system, gas piping for the appliance, Fresh Air Kit, and the electrical wiring. (The fan option is available for louvered models only. Electric ignition models will require electrical service to junction box).
The appliance can be mounted on any of the following surfaces:
1. A flat, hard combustible (burnable) surface.
2. A raised wooden platform.
3. Four (4) corner supports. (Example: Four (4) concrete masonry
blocks.) These supports must be positioned so they contact all four (4) perimeter edges on the bottom of the unit.
Locate and mark the center point of the vent pipe using a nail on the underside of the roof. Drive the nail through the center point. Mark the outline of the roof hole around this center point.
NOTE: Size of the roof hole dimensions depend on the pitch of
the roof. There must be a 1 inch clearance (25mm) to the vertical pipe sections. This clearance is to all combustible material.
Cover the opening of the vent pipe and cut and frame the roof hole. Use framing lumber the same size as the roof rafters and install the frame securely. Flashing anchored to frame must withstand high winds. The storm collar is placed over this joint to make a water­tight seal. Non-hardening sealant should be used to completely seal this flashing installation.
Determining Minimum Vent Height Above the Roof.
WARNING: Major U.S. building codes specify minimum chimney and/or vent height above the roof top. These minimum heights are necessary in the interest of safety. These specifications are summarized in Figures 14 and 15.
ROOF PITCH H (Min.)
Flat to 6/12 12" (305 mm)
6/12 to 7/12 15" (381 mm)
Over 7/12 to 8/12 18" (457 mm)
Over 8/12 to 16/12 24" (610 mm)
Over 16/12 to 21/12 36" (914 mm)
Note that for steep roof pitches, the vent height must be increased. In high wind conditions, nearby trees, adjoining roof lines, steep pitched roofs, and other similar factors can result in poor draft, or down-drafting. In these cases, increasing the vent height may solve this problem.
General Maintenance
Conduct an inspection of the venting system semi-annually. Recommended areas to inspect are as follows:
1. Check areas of the venting system which are exposed to the elements for corrosion. These will appear as rust spots or streaks and, in extreme cases, holes. These components should immediately be replaced.
2. Remove the cap and shine a flashlight down the vent. Remove any bird nests or other foreign material.
3. Check for evidence of excessive condensate, such as water droplets forming in the inner liner and subsequently dripping out at joints. Condensate can cause corrosion of caps, pipe and fittings. It may be caused by having excessive lateral runs, too many elbows and exterior portions of the system being exposed to cold weather.
4. Inspect joints to verify that no pipe sections or fittings have been disturbed and, consequently, loosened. Also, check mechanical supports, such as wall straps or plumbers’ tape for rigidity.
A removable panel or other means must be provided in the enclosure for visual inspection of the flue connection.
NOTE: This also pertains to vertical vent systems installed on the outside of the building.
Installing the Vent System in a Chase
A chase is a vertical box-like structure built to enclose the gas appliance and/or it’s vent system. Vertical vent runs on the outside of a building may be, but are not required to be installed inside a chase.
CAUTION: Treatment of firestop spacers and construction of the chase may vary with the type of building. These instructions are not substitutes for the requirements of local building codes. Therefore, your local building codes must be checked to determine the requirements for these steps.
NOTE: When installing this vent system in a chase, it is always
good building practice to insulate the chase as you would the outside walls of your home. This is especially important for cold climate installations. Upon completion of building your chase framing, install the vent system by following the instructions in this manual. Remember to build the chase large enough so that minimum clearance of combustible materials (including insulation) to the vent system are maintained.
WARNING! This appliance must not be connected to a chimney flue servicing a separate solid fuel or gas fuel burning appliance.
Figure 13
Page 12 19400-3-0406
Vent supports are per vent manufacturer’s specifications
Minimum clearances are per vent manufacturer’s specifications
40 ft. Max. 11
ft. Min.
90 - degree or 45 - degree Elbows
Straight Section
2 ft. Minimum off top of unit before using elbows
Ve
nt supports per
manufacturers
vent
specifications
Horizontal v
ent to maintain a 1/4” rise per ft. Min.
11
ft. Min.
Maxi mum horizontal distance i
s 50% of
vertical vent h
eight
5 f t . M a x . Horizontal at 11
ft. Min.
Vertical
VENTING (CONT)
Vent Size
Model BVD34FP series uses a 4" B-Vent for operation. Models BVD36FP and BVP42FP series use a 6" B-Vent for operation.
Never downsize venting diameters.
Clearances
Vent clearances are per vent manufacturer's specifications
Vent Configuration
Various venting configurations are shown in Figures 14 and 15 from which maximum vent runs can be determined.
WARNING - RISK OF FIRE! Always maintain minimum clearances or greater around the vent system. Do not pack air spaces with insulation or other material.
Vertical Venting - No Elbows
Offset Venting - With Elbows
Figure 14
Figure 15
Page 1319400-3-0406
1
4
5
3
2
1
2
3
5
4
EMBER MATERIAL PLACEMENT
LOG PLACEMENT (5 LOG SET)
Before you begin: if you are installing logs into the BVD34 or BVD36 model, then this fireplace is supplied with a set of five ceramic fiber logs. Do not handle these logs with your bare hands! Always wear gloves to prevent skin irritation from ceramic fibers. After handling logs, wash your hands gently with soap and water to remove any traces of fibers.
The positioning of the logs is critical to the safe and clean opera­tion of this fireplace. Sooting and other problems may result if the logs are not properly and firmly positioned in the fireplace. Please refer to Figure 16 and Figure 17 and corresponding WARNING when completing following log placement instructions.
1. Place front logs (#1 and #2) between front grate flange and main burner. Align notches on front logs with locator tabs in base.
2. Place middle log (#3) between front and rear loop of burn­er.
Note: Do not place log on top of pilot assembly.
3. Place rear log (#4) on rear log shelf. Bottom flange of log must be placed between the log shelf and burner tube.
4. Place branch (#5) onto (#1) log and flat area on (#3) log. The bottom of the branch is to be placed behind the grate tang that is second from the left.
5. Place decorative rock in front of grates and sides of main burner pan.
ATTENTION: Do not place decorative rock on logs or burner. The decorative rock should only be placed on the fireplace floor.
Figure 16
WARNING: Failure to position the parts in accordance with this diagram or failure to use only parts specifically approved with this appliance may result in property damage or personal injury.
Attention: Do not use Figure 16 or Figure 17 to order logs. Refer
to parts list on page 28 and parts view on page 29 to order logs and/or ember material for your appropriate fireplace model.
EMBER MATERIAL PLACEMENT ON BURNER
6. After all logs are positioned properly, apply Rockwool ember material to the front burner port area. To apply, carefully separate the ember material into small amounts no larger than "dime size" pieces. Fluffed up pieces one layer thick on top of the burner generally works best, and will provide the best ember glow. Do not place ember material more than one layer thick. No more than (1) small packet of ember material (part no. 15999) evenly placed on the burner, is recommended on BVD34 and BVD36 models. Using additional ember material will decrease the amount of ember glow effect. Extra ember material should be saved for future ember applications as necessary. See Figure 17.
Optional Platinum Bright Ember Kits are available from your Fireplace Dealer. These embers may be used with all BVD/BVP Series fireplaces. Order and use as indicated as below.
Platinum Bright Embers PE-20-1
Figure 17
Note: A signle layer of embers is to be used when applying Platinum Bright Embers (alone or in combination with production embers) to the burner.
Page 14 19400-3-0406
TOP BRANCH
REAR LOG
BOTTOM
LOG
EMBER PLACEMENT
REAR LOG LOCATOR TABS
BOTTOM LOG LOCATOR PINS
LOG PLACEMENT (3 LOG SET)
Before you begin: If you are installing logs into the BVP42 model then this fireplace is supplied with a set of three ceramic fiber logs. Do not handle these logs with your bare hands. Always wear gloves to prevent skin irritation from ceramic fibers. After handling logs, wash your hands gently with soap and water to remove any traces of fiber.
The positioning of logs is critical to safe and clean operation of this fireplace. Sooting and other problems may result if the logs are not properly and firmly positioned in the fireplace. Please refer to Figure 18, Figure 19, and Figure 20 and corresponding WARNING, when completing the following log placement steps.
1. Place bottom log onto main burner. Align holes on bottom log with (4) locator pins on burner.
2. Place rear log on rear log shelf. Place rear log so that the locator holes align with the (2) locator tabs in the log support shelf.
3. Place top branch onto flat area of rear log and over the front of the bottom log.
4. Place decorative rock in front of grates and sides of main burner.
ATTENTION: Do not place decorative rock on logs or on burner. The decorative rock should only be placed on the fireplace floor.
Figure 19
WARNING: Failure to position the parts in accordance with
this diagram or failure to use only parts specifically approved with this appliance may result in property damage or personal injury.
Attention: Do not use Figure 19 or Figure 20 to order logs. Refer to parts view on page 30 and parts list on page 31 to order logs and/or ember material for your appropriate fireplace model.
5. After all logs are properly positioned, place small "dime" size pieces of Rockwool lightly across the front round "blue flame" ports. Place the ember material (Rockwool pieces) side by side. Do not stack more than one layer of embers across the burner ports. See Figure 18.
Figure 18
Figure 20
Page 1519400-3-0406
GAS CONTROL KNOB SHOWN IN "OFF" POSITION.
V
E
N
T
P
I
L
O
T
IN
OPERATING INSTRUCTIONS
750 Millivolt System
The standing pilot (750 millivolt system) is a continuous burning pilot. The pilot remains ON even when the main burner is OFF.
When you ignite the pilot, the thermopile produces millivolts (electrical current) which energizes the magnet in the gas valve. After 30 seconds to 1 minute time period you can release the gas control knob and the pilot will stay ON. Allow your pilot flame to operate an additional one (1) to two (2) minutes before you turn the gas control knob from the PILOT position to the ON position. This time period allows the millivolts (electrical current) to build-up to a sufficient level allowing the gas control to operate properly.
1. Follow the SAFETY and LIGHTING INSTRUCTIONS for standing pilot controls found in this manual and on labels found in control compartment behind the door assembly.
CAUTION: During the initial purging and subsequent lightings, never allow the gas valve control knob to remain depressed in the “pilot” position without pushing the piezo ignitor button at least once every second.
2. During the operating season, leave the control valve knob in the “ON” position. This will allow the pilot flame to remain lit. Turn the burner flame on or off with the fireplace wall switch or remote controls.
3. When the operating season is over, turn the wall switch or remote to “OFF” and the control valve to “OFF”. The system, including the pilot light, will be shut down.
The OWNER should carefully read and follow these operating instructions at all times. Lower the door assembly to view the gas controls for the fireplace.
Initial Lighting
Upon completing the gas line or turning the gas valve on after it has been in the “OFF” position, a small amount of air will be in the lines. When first lighting the fireplace, it will take a few minutes for the lines to purge themselves of this air. Once the purging is complete, the fireplace will light and operate satisfactorily.
Subsequent lightings of the appliance will not require such purging if the gas valve is not turned to “OFF.”
Pilot Flame (Figure 22)
The thermopile (standing pilot) tips should be covered with flame.
Figure 22
Figure 21
Page 16 19400-3-0406
OPERATING INSTRUCTIONS (CONT)
STANDING PILOT OPERATING INSTRUCTIONS
The fireplace is equipped with a 15 foot length of wire that can be used to connect the valve to a wall switch (installer provided) or remote control receiver.
See instructions packed with each of the following optional switches or controls for proper installation, operation, and maintenance.
Wall Switch, FWS-1 (optional)
On millivolt valve models, a 15' wall switch wire is included. Connect the two leads to a wall switch (installer supplied). See Figure 23.
FRBC Battery Operated Remote Control
To connect the FRBC remote to the millivolt gas valve on your "B-Vent" Fireplace, disconnect one wire terminal lead (wall switch wire) from gas valve, seperate/split wall switch wire lead approximately 18 inches. Cut the removed lead 12 inches long and strip both cut ends. After stripping and baring the wire ends, connect the two stripped ends to the remote receiver. Reconnect the 1/4" insulated wire terminal (short 18" wire) to the gas valve wire terminal. See Figure 23.
Electric (120 volt) Operated Remote Control, FREC
CAUTION: Disconnect all electrical supply to the fireplace prior to installing the remote control optional equipment.
Installation of the 120 Volt Receiver
Note: If you have a louvered model fireplace and will be installing
the blower option, the fireplace junction box receptacle should be wired in accordance with Figure 28 for proper independent operation of the FREC remote and the optional FBB4 Blower kit.
To connect the FREC Remote to the millivolt gas valve on your "B"-Vent fireplace, disconnect both of the insulated wall switch wire terminal leads from the gas valve and discard the wall switch wire. Connect the two wire leads from the FREC receiver to the TH and TH/TP terminals on the gas valve.
Next, attach the short power cord to the remote receiver, then plug the power cord into the junction box receptacle located at the bottom right side of the fireplace.
The remote receiver should be located on the floor of the fireplace to the right of the gas valve.
Attention: The Velcro loop and hook are not necessary in this installation but can be used to secure remote receiver.
Refer to remote control installation and operating instructions for more details on remote control.
Millivolt Control
The valve regulator controls the burner pressure which should be checked at the pressure test point. Turn captured screw counter clockwise 2 or 3 turns and then place tubing to pressure gauge over test point (Use test point “A” closest to control knob). After taking pressure reading, be sure and turn captured screw clockwise firmly to re-seal. Do not over torque. Check for gas leaks.
Millivolt thermopile is self generating. Gas valve does not require 24 volts or 110 volts.
Check System Operation
Millivolt system and all individual components may be checked with a millivolt meter 0-1000 MV range.
It is important to use wire of a gauge proper for the length of the wire:
Recommended Wire Gauges
Maximum Length Wire Gauge
1' to 10' 18
10' to 25' 16
25' to 35' 14
Page 1719400-3-0406
THERMOPILE
GAS VALVE
(OPTIONAL) REMOTE CONTROL RECEIVER
DU RECEPTEUR(FACULTATIVE) CONTROLE E DISTANCE
WALL SWITCH INTERRUPTEUR MURAL
(OPTIONAL) THERMOSTAT (FACULATIVE) THERMOSTAT
GAS VALVE VALVE D
E GAZ
WALL SWITCH/REMOTE CONTROL RECEIVER/ THERMOSTAT CONTROLE E DIST
ANCE
DU RECEPTEUR
H
N
PILOT VEILLEUSE
LIMIT SWITCH
V
E
N
T
P
I
L
O
T
IN
STANDING PILOT WIRING DIAGRAM
Figure 23
Page 18 19400-3-0406
GAS CONTROL KNOB SHOWN IN "OFF" POSITION.
V
E
N
T
P
I
L
O
T
IN
ELECTRODE
PILOT
THERMOPILE
STANDING PILOT LIGHTING INSTRUCTIONS
FOR YOUR SAFETY, READ BEFORE LIGHTING
WARNING: IF YOU DO NOT FOLLOW THESE INSTRUCTIONS EXACTLY, A FIRE OR EXPLOSION MAY RESULT CAUSING PROPERTY DAMAGE, PERSONAL INJURY, OR LOSS OF LIFE
A. This appliance has a pilot which must be lighted by hand.
When lighting the pilot, follow these instructions exactly.
B. BEFORE LIGHTING smell all around the appliance area
for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance
• Do not touch any electric switch.
• Do not use any phone in your building.
• Immediately call your gas supplier from a neighbor's phone.
LIGHTING INSTRUCTIONS
1. STOP! Read the safety information above.
2. Set wall switch or remote to "OFF."
3. Turn of f all electr ic power to the appliance (if applicable).
4. Open bottom louver assembly, or open valve access door.
5. Push in gas control knob slightly and turn clockwise to "OFF."
NOTE: Knob cannot be turned
from "PILOT" to "OFF" unless knob is pushed in slightly. Do not force.
6. Wait ten (10) minutes to clear out any gas. Then smell for gas, including near the floor. If you smell gas, STOP! Follow "B" in the safety information on reverse. If you do not smell gas, go to the next step.
7. Find pilot - Follow metal tube from gas control. The pilot is behind the burner on the right side.
8. Turn gas control knob counterclockwise
• Follow the gas supplier's instructions.
• If you can not reach your gas supplier, call the fire department.
C. Use only your hand to push in or turn the gas control knob.
Never use tools. If the knob will not push in or turn by hand, don't try to repair it, call a qualified service technician. Force or attempted repair may result in a fire or explosion.
D. Do not use this appliance if any part has been under water.
Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
to "PILOT."
9. Push in control knob all the way and hold in. Repeatedly push the Piezo Ignitor Button until the pilot is lit. Continue to hold the control knob in for about one (1) minute after the pilot is lit. Release knob, and it will pop back up. Pilot should remain lit. If it goes out, repeat steps 5 through 9.
• If knob does not pop up when released, STOP and IMMEDIATELY call a qualified service technician or gas supplier.
• If the pilot will not stay lit after several tries, turn the gas control knob to "OFF" and call your service technician or gas supplier.
10. Turn gas control knob counterclockwise to "ON."
11. Close bottom louver assembly, or close valve access door.
12. Turn on all electric power to the appliance (if appli­cable).
13. Set wall switch or remote to "ON."
TO TURN OFF GAS TO FIREPLACE
1. Set wall switch or remote to "OFF."
2. Turn off all electric power to the appliance if service is to be performed (if applicable).
3. Open bottom louver assembly, or open valve access door.
4. Push in gas control knob slightly and turn clockwise to "OFF." Do not force.
5. Close bottom louver assembly, or close valve access
door.
Page 1919400-3-0406
STANDING PILOT TROUBLESHOOTING
With proper installation and maintenance, your new Gas Fireplace will provide years of trouble-free service. If you do experi­ence a problem, refer to the Trouble Shooting Guide below. This guide will assist a qualified service person in the diagnosis of problems and the corrective action to be taken.
1. Spark ignitor will not light pilot after repeated triggering of piezo ignitor button.
a. Defective ignitor (no spark electrode) —Check for spark at electrode and pilot; if no spark and
electrode wire is properly connected, replace ignitor. b. No gas or low gas pressure. —Check remote shut off valves from fireplace. Usually
there is a valve near the main. There can be more than one
(1) valve between the fireplace and main. —Low pressure can be caused by a variety of situations
such as a bent line, too narrow diameter of pipe, or low line
pressure. Consult with plumber or gas supplier. c. No LP in tank. —Check LP (propane) tank. Refill tank.
2. Pilot will not stay lit after carefully following lighting instructions.
a. Defective thermopile. —Check that pilot flame impinges on thermopile. Clean
and/or adjust pilot for maximum flame impingement.
—Ensure the thermopile connections at the gas valve are
fully tight.
3. Pilot burning, no gas to burner, valve knob “ON.”
a. Wall switch, remote control or wires defective. —Check wires for proper connections. Place jumper wires
across terminal at switch. If burner comes on, replace defective switch. If OK, place jumper wires across switch wires at gas valve-if burner comes on, wires are faulty or
connections are bad. b. Thermopile may not be generating sufficient millivolts. —If the pilot flame is not close enough physically to the
thermopile, adjust the pilot flame. —Be sure the wire connections from the thermopile at the
gas valve terminals are tight and the thermopile is fully
inserted into the pilot bracket. —Check the thermopile with a millivolt meter. Take the
reading at TH-TP & TP terminals of the gas valve. The
meter should read 350 millivolts minimum, while holding
the valve knob depressed in the PILOT position, with the
pilot lit, and the switch in the OFF position. Replace the
faulty thermopile if the reading is below the specified
minimum. —With the pilot in the ON position, disconnect the
thermopile leads from the valve. Take a reading at the
thermopile leads. The reading should be 350 millivolts
minimum. Replace the thermopile if the reading is below
the minimum. c. Defective valve. —Turn valve knob to ON. Place Remote/Off/On switch to
ON. Check with millivolt meter at thermopile terminals.
Millivolt meter should read greater than 200 millivolts. If
the reading is okay and the main burner does not ignite,
replace the gas valve. d. Plugged main burner orifice. —Check main burner orifice for blockage and remove.
4. Frequent pilot outage problem.
a. Pilot flame may be too high or too low, or blowing (high),
causing pilot safety to drop out.
—Clean and adjust flame for maximum flame impingement
on the thermocouple. Follow lighting instructions carefully.
5. The pilot and main burner extinguish while in operation.
a. No LP (Propane) in tank. Check LP (Propane) tank. Refill fuel tank. b. Bad thermopile or thermocouple. —Replace if necessary. c. Improper vent cap installation. —Check for proper installation and freedom from debris
or blockage.
6. (Glass) Sooting
a. Flame impingement on logs. —Check and adjust log position. Contact Empire Comfort
Systems, Inc. b. Debris around throat of main burner. —Inspect the opening at the base of the main burner. It is
imperative that NO material be placed in this opening.
Page 20 19400-3-0406
V
E
N
T
P
I
L
O
T
IN
STANDING PILOT PROPANE/LP GAS CONVERSION
"B-VENT" FIREPLACES
Model Conversion Kit Model
(Part Number)
BVD34FP3 SERIES BVCK34P (19160)
BVD36FP3 SERIES BVCK36P (19161)
BVP42FP3 SERIES BVCK42P (19162)
FOR CONVERSION TO LIQUEFIED PETROLEUM GAS
WARNING
This conversion kit is to be installed by an Empire Comfort Systems, Inc. dealer (or other qualified agency1)* in accordance with the manufacturer's instructions and all codes and requirements of the authority having jurisdiction. Failure to follow instructions could result in serious injury or property damage. The qualified agency performing this work assumes responsibility for this conversion.
1
National Fuel Gas Code Z223.1 (Latest Edition), Natural Gas and Propane
Installation Code, CSA B149.1
*The term "qualified agency" means any individual, firm, corporation or company which either in person or through a representative is engaged in and is responsible for (a) the installation of gas piping or (b) the connection, installation repair, or servicing of equipment, who is experienced in such work, familiar with all precautions required, and has complied with all the requirements of the authority having jurisdiction.
CHECK SAFETY SHUTDOWN PERFORMANCE
WARNING Perform the safety shutdown test any time work is done on a gas system to avoid the possibility of fire or explosion with property damage, personal injury or loss of life.
SAFETY SHUTDOWN SYSTEM
Continuous Ignition Systems
1. Place gas control knob in Pilot position. Main burner should go off and pilot should remain lit.
2. Extinguish pilot flame. Pilot gas flow should stop within 3 minutes. Safety shutoff of pilot gas proves complete shutdown since safety shutoff valve blocks flow of gas to main burner and pilot.
3. Wait 5 minutes, then relight pilot burner and operate system through one complete cycle to make sure all controls operate properly.
PARTS LIST
Conversion Kit
Model
Part
Description
Fireplace BVD34FP3
Pilot Orifice #35 (R-7658) #35 (R-7658) #35 (R-7658) 1
Main Burner
Orifice
Dexen 10" w.c.
Regulator
Gas Conversion
Label
BVCK34P BVCK36P BVCK42P
Kit No. 19160 Kit No. 19161 Kit No. 19162 Quantity
SERIES
P-289
1.35mm
R-7548 R-7548 R-7548 1
2139 2139 2139 1
BVD36FP3
SERIES
P-208
1.45mm
BVP42FP3
SERIES
P-250
1.65mm
Supplied
1
Gas input for "B-Vent" fireplace converted to Liquefied Petroleum Gas:
BVD34FP3 SERIES 21,000 BTU per hour
BVD36FP3 SERIES 25,000 BTU per hour
BVP42FP3 SERIES 30,000 BTU per hour
The "B-Vent" fireplace when converted to LP Gas will have manifold pressure of 10.0" w.c. at the valve outlet with the inlet pressure to the valve from a minimum of 10.8" w.c., for the purpose of input adjustment, to a maximum of 14.0" w.c.
INSTRUCTIONS FOR CONVERSION
1. If the fireplace is installed, turn off gas and electric supply before making the gas conversion.
2. Identify the fireplace model to be converted, and read all instruction steps prior to converting the gas valve.
3. Remove all logs from the burner assembly.
4. Open the sliding valve access door.
5. Depress and turn the gas cock dial to the "OFF" position.
VALVE CONVERSION
6. Remove two (2) screws, regulator, and gasket from gas valve control body.
7. Install the new gasket, regulator, and gasket from gas valve control body.
BURNER ORIFICE CONVERSION - Tube style burners
8a. On models BVD(34,36)FP3 series fireplaces, you will have a
U-shaped burner tube. To gain access to the main orifice, simply bend over the small retainer tab located at the front right end of the tube using pliers.
9a. Remove the 1/4" long screw from the air shutter at the left end
of the tube.
10a. Pull up on the back of the burner and rotate forward to gain access
to the main orifice. Remove the orifice and replace with the LP orifice designated in the orifice reference chart. Secure the new orifice.
11a. Pivot the burner tube back down in its original position mating
with the air shutter, and reinstall the 1/4" long screw. Set the air shutter opening in accordance with the dimension shown in the reference chart for the appropriate model fireplace.
Page 2119400-3-0406
BURNER ORIFICE CONVERSION - Slope style burners
“A”
8b. On model BVP42FP3 series fireplaces, you will have a
rectangular slope style burner. To gain access to the main orifice, disconnect the gas supply tubing at the air shutter.
9b. Remove the orifice holder from the air shutter, then remove
the NG orifice.
10b. Replace the removed NG orifice with the new LP orifice
designated in the orifice reference chart for your fireplace model. Secure the new orifice and replace the orifice/orifice holder back into the air shutter and secure.
11b. Loosen the air shutter screw and reset the air shutter opening
in accordance with the dimension shown in the reference chart for the appropriate model fireplace.
PILOT ORIFICE CONVERSION
12. Locate the pilot assembly.
13. Pull upward on the round pilot flame hood to remove.
14. Using a 5/32" Hex Allen wrench, remove the pilot orifice, then replace with the new pilot orifice marked #35.
IMPORTANT: Failure to install the correct orifice will result in unit over-firing that could overheat the appliance and result in a fire.
15. Refer to log placement found in your fireplace installation manual to place logs onto the burner assembly.
16. Loosen screw and attach a manometer or pressure gauge to the outlet pressure tap of the control valve.
17. Turn on the gas supply. Turn on the electrical supply to the appliance. Check for gas leaks using a soap and water solution or leak detection solution. Bubbles indicate a leak that MUST be corrected. Do not use an open flame to test for gas leaks.
18. Check the air shutter opening. See chart and illustration below.
19. Relight the main burners and verify proper burner ignition and operation.
20. With the main burner burning, read the pressure on the manometer or pressure gauge. The pressure on the gauge should read between 9.8" and 10.2"w.c.
21. Turn off the gas supply. Turn off the electrical supply to the appliance.
22. Remove the manometer or pressure gage. Tighten the screw in the pressure tap.
23. Turn on the gas supply. Turn on the electrical supply to the appliance.
24. Immediately test all gas line connections and the control valve for gas leaks using a soap and water solution or gas detection for solution. Bubbles indicate a leak that MUST be corrected. Do not use an open flame to check for gas leaks.
25. Using a ball point pen, fill out the conversion label that is supplied with the conversion kit. Place the conversion label adjacent to the rating plate.
26. Test operation of fireplace once again. Allow the fireplace to operate for at least 10 minutes and check flame coloration. Flame on rear of burner should be yellow without any orange-colored tip. Minor adjustment of the air shutter may be necessary to "tune in" the proper flame color.
The burner flame and pilot flame must be checked for proper flame characteristics, as outlined in this manual.
V E R IF Y I N G I N P U T R AT E OF CO N V E RT E D FIREPLACE
The input of the fireplace must be checked as follows:
1. Turn off all other gas appliances. Clock the gas meter and determine the number of seconds required to consume one cubic foot of gas.
2. 3600 ÷ time (in seconds) = cu. ft. per hour.
3. Then cu. ft. per hour x heating value of gas = input rate
(BTU/Hr). On installation without gas meters, check manifold
for proper pressure.
Note: The rate noted on the data plate is measured after 45 minutes
of continuous operation and adjusted for test conditions such as temperature, and barometric pressure. The above procedure is a check for correct conversion only.
PLACEMENT OF GAS CONVERSION LABEL
Conversion label 2139 is to be filled out completely and placed with the data plate attached near the valve.
If the appliance has not been installed, or a warranty card has not been returned to Empire Comfort Systems, Inc., check off type of gas converted to on card (for reference once the unit is installed). Also, indicate conversion by adding "Conv." behind gas.
MODEL AIR SHUTTER
SETTINGS
Opening "A" Propane/LP
BVD34 5/16"
(7.9mm)
BVD36 5/16"
(7.9mm)
BVP42 FULL OPEN 1.65mm
BURNER ORIFICE
1.35mm P-289
1.45mm P-208
P-250
Air shutter settings shown are factory settings. Some venting configurations may require minor air shutter adjustments for optimum performance.
Page 22 19400-3-0406
LED LIGHT LED LUMIÈRE
BLACK NOIR
GREEN VERT
WHITE BLANC
RED ROUGE
BLACK NOIR
GAS VALVE VALVE D
E GAZ
(OPTIONAL) WALL SWITCH INTERRUPTEUR MURAL (FACULTATIVE)
120 VAC LINE
120 VAC RTN
JUNCTION BOX JONCTION BOÎTE
SPARK IGNITOR ÉTINCELLE ALLUMER
(OPTIONAL) REMOTE CONTROL RECEIVER 120V (FACULATIVE) CONTROLE E DISTANCE DU RECEPTEUR
MAI N V AL
VE RETURN
1
12
13
GROUND
2
120V
AC RETURN
4
120V
AC HOT
6
MAI N V AL
VE HOT
8
CONTROL MODULE AUTORITÉ MODULE
LIMIT SWITCH
DIRECT IGNITION WIRING DIAGRAM
Figure 24
LED CODES
Steady ON Normal operation, power ON to control
2 Flashes 3 unsuccessful ignition trials
3 Flashes Main burner flame failed 4 times during a single heating cycle
4 Flashes Interrupt power for 5 seconds to reset control
Steady Flash Flame detected out of sequence
OPTIONAL REMOTE CONTROL (120V DIRECT IGNITION)
Electric (120 volt) Operated Remote Control (FREC)
1. Disconnect 3-prong power cord from receptacle.
2. Remove wire from 120 VAC hot terminal on control module.
3. Connect female terminal from receiver onto 120 VAC hot terminal on control module.
4. Connect remaining wire from remote control (male terminal) to (female terminal) on power cord removed from control module (step 2).
5. Insert electric remote control power cord plug into the junction box on the right side of fireplace.
6. Connect 3-prong plug into receptacle. See wiring diagram on page 34.
Page 2319400-3-0406
ON
OFF
DIRECT IGNITION LIGHTING INSTRUCTIONS
FOR YOUR SAFETY READ BEFORE LIGHTING
WARNING: IF YOU DO NOT FOLLOW THESE INSTRUCTIONS EXACTLY, A FIRE OR EXPLOSION MAY RESULT CAUSING PROPERTY DAMAGE, PERSONAL INJURY, OR LOSS OF LIFE.
A. BEFORE LIGHTING smell all around the appliance area for
gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance
• Do not touch any electrical switch
• Do not use any phone in your building.
• Immediately call your gas supplier from a neighbor's phone.
• Follow the gas supplier's instructions.
LIGHTING INSTRUCTIONS
1. STOP! Read the safety information above.
2. Turn off all electric power to the appliance.
3. This appliance is equipped with an ignition device that
automatically lights the burner. Do not try to light the burner by hand.
4. Open bottom louver assembly, or open valve access door.
5. Turn gas line valve to "ON."
6. Wait five (5) minutes to clear out any gas. Then smell for gas,
including near the floor. If you smell gas, STOP! Follow "A" in the safety information on reverse. If you do not smell gas, go to the next step.
7. Close bottom louver assembly, or close hearth access plate.
• If you can not reach your gas supplier, call the fire department.
B. Use only the wall switch or remote control switch to turn the
gas control on/off. Any attempted repairs or adjustments should be performed by a qualified service technician. Applying force or attempted repair may result in a fire or explosion.
C. Do not use this appliance if any part has been under water.
Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
8. Turn on all electric power to the appliance.
9. If the appliance will not operate, follow the instructions "TO TURN OFF GAS TO APPLIANCE," and call your service technician or gas supplier.
TO TURN OFF GAS TO APPLIANCE
1. STOP! Read the safety information above.
2. Turn off all electric power to the appliance.
3. Open bottom louver assembly, or open the valve access door.
4. Turn gas line valve to "OFF."
5. Close bottom louver assembly, or close valve access door.
INITIAL START UP GAS LINE PURGE
NOTE: UNIT MUST BE PROPERLY GROUNDED FOR ELECTRONIC IGNITION TO FUNCTION.
On initial installation, or after extended periods where the fireplace has not been used, gas lines may require purging.
Page 24 19400-3-0406
DIRECT IGNITION TROUBLESHOOTING
With proper installation and maintenance, your new Gas Fireplace will provide years of trouble-free service. If you do experience a problem, refer to the troubleshooting guide below. This guide will assist a qualified service person in the diagnosis of problems and the corrective action to be taken. Refer to page 24 for initial startup and GAS Line purge instructions.
SYMPTOM CHECK ACTION
No spark when system is turned to “ON” and reset cycle* has been completed.
Spark for six (6) seconds at ignitor, but no ignition of burner.
Spark for six (6) seconds, main burner lights, but goes out when spark stops.
Main burner lights normally and then goes out.
Check for 120V between black “hot” line at control module and “white” return at module.
a. Check that gas is turned on and system
purged.
b. Check that tips of ignitor are directly
above ports on main burner. Spark is between electrodes and not from one electrode to burner.
c. Check for 120V at each coil on the gas
valve and listen for click, indicating gas valve is opening.
Check for clean ground path between electrode bracket and fireplace chassis. Check wiring to wiring diagram label. Check for broken electrode on high-tension lead attachment to module.
a. Check ignitor to burner gap. Igniter should be located 1/4" to 3/8" above
b. Check high-tension lead and connector
for shorts.
c. Refer to inst a l l a t i o n instruction s
troubleshooting guide for issues such as venting.
If 120V not present, check fuse or circuit breaker or re p a i r wiring le a d i n g to fireplace.
Turn gas on and/or purge system.
Position electrodes so tips are directly above burner port ports and about ¼" to
3
/8" above burner.
If 120V present, but gas valve does not click, replace gas valve.
Clean, position according to wiring diagram, and repair defective electric connections. If all electrical connections are clean and correct, replace module.
burner area.
Replace spark electrode assembly.
Repair as required.
DIRECT IGNITION PROPANE/LP GAS CONVERSION
The conversion shall be carried out in accordance with the requirements of the provincial authorities having jurisdiction and in accordance with the requirements of the CSA B149.2 installation code (Canada) and with the requirements of the National Fuel Gas Code Z223.1/NFPA 54 (United States).
WARNING: This conversion kit shall be installed by a qualified service agency in accordance with the manufacturer's instructions and all applicable codes and requirements of the authority having jurisdiction. If the information in this instruction is not followed exactly, a fire, explosion, or production of carbon monoxide may result causing property damage, personal injury, or loss of life. The qualified service agency is responsible for the proper installation of this kit. The installation is not proper and complete until the operation of the converted appliance is checked as specified in the manufacturer's instructions supplied with the kit.
Installer notice: Using an ink pen, fill out the required information
on the conversion label. Remove the backing from label and stick label in a visible position on bottom of fireplace close to gas valve.
Installer notice: These instructions must be left with the appliance.
Instructions for converting your direct ignition fireplace from natural gas to propane/LP gas.
All direct ignition fireplaces are shipped from the factory equipped to operate on natural gas. To convert the direct ignition fireplace to operate on propane/LP gas, follow the instructions on Page
26. Please see the appropriate parts list for your model for parts included with the direct ignition fireplace.
Check the items in the kit with the parts list. Notify the supplier of any items that are missing before installing the conversion kit.
Page 2519400-3-0406
“A”
REGULATOR FITTING
NOTE: STAMPED WITH GAS TYPE SET FOR USE
DIRECT IGNITION PROPANE/LP GAS CONVERSION
1. Turn off the gas supply.
2. Turn off the electrical sup ply to the app lianc e if so equipped.
3. Open or remove glass doors if applicable.
4. Remove top louver and lower bottom louver.
5. Remove logs from burner assembly.
VALVE CONVERSION
6. Remove plastic cap from regulator fitting. Unscrew fitting using a 7/16" wrench. Turn fitting over so end of fitting marked "LPG" is visible. Tighten fitting (snug only). Replace plastic cap.
7. Remove 1/4" screw from air shutter.
8. Located to the right of electrodes is a burner hold-down tab. Using needle-nose pliers, bend burner hold-down tab off the main burner.
9. Remove main burner by pivoting main burner forward as you slide main burner from left to right. Be careful as you remove main burner in order to protect the electrodes from being damaged.
10. Remove air shutter from orifice fitting.
11. Remove natural gas main burner orifice from orifice fitting.
12. Install propane/LP main burner orifice marked 1.35mm for BVD34FP50, marked 1.45 mm for BVD36FP52, or marked
1.65mm for BVP42FP52.
Important: Failure to install the correct orifice will result in
unit over-firing that could overheat the appliance and result in a fire.
13. Replace air shutter onto orifice fitting. Air shutter must be threaded and bottomed-out onto orifice fitting.
14. Replace main burner onto burner assembly. Place main burner beneath electrodes, slide main burner from right to left into burner location, and pivot main burner away from you and into air shutter.
15. Set air shutter opening as indicated by the chart below. Tighten air shutter in place with 1/4" screw from step 7.
16. Using needle-nose pliers, bend burner hold-down tab over main burner.
17. Refer to log placement, pages 14 and 15 to place logs onto burner assembly.
18. Loosen screw and attach a manometer or pressure gauge to the outlet pressure tap of the control valve.
19. Turn on the gas supply. Turn on the electrical supply to the appliance. Check for gas leaks using soap and water solution or leak detection solution. Bubbles indicate a leak that MUST be corrected. Do not use an open flame to test for gas leaks.
20. Check the air shutter opening. See chart and illustration below.
21. Relight the main burners and verify proper burner ignition and operation.
22. With the main burner burning, read the pressure on the manometer or pressure gauge. The pressure on the gauge should read between 9.8" and 10.2" w.c.
23. Turn off the gas supply. Turn off the electrical supply to the appliance.
24. Remove the manometer or pressure gauge. Tighten the screw in the pressure tap.
25. Turn on the gas supply. Turn on the electrical supply to the appliance.
26. Immediately test all gas line connections and the control valve for gas leaks using a soap and water solution or other gas detection solution. Bubbles indicate a leak that MUST be corrected. Do not use an open flame to test for gas leaks.
27. Using a ball point pen, fill out the conversion label that is supplied with the conversion kit. Place the conversion label adjacent to the rating plate.
28. Test operation of fireplace once again. Allow the fireplace to operate for at least 10 minutes and check flame coloration. Flames on rear of burner should be yellow without any orange-colored tip. Minor adjustment of the air shutter may be necessary to "tune in" the proper flame color.
Maxitrol Valve Conversion
Model AIR SHUTTER
BURNER ORIFICE
SETTINGS
Opening "A" Propane/LP Orifice
BVD34 5/16" (8mm) 1.35mm
BVD36 5/16" (8mm) 1.45mm
BVP42 Full Open 1.65mm
Page 26 19400-3-0406
MAINTENANCE AND SERVICE
PLEASE NOTE It is normal for appliances fabricated of steel to give off some expansion and/or contraction noise during the start up or cool down cycle. Similar noises are found with your furnace heat exchanger or car engine.
It is not unusual for your gas fireplace to give off some odor the first time it is burned. This is due to the curing of the paint and any undetected oil from the manufacturing process.
Please ensure that your room is well ventilated - open all windows.
It is recommended that you burn your fireplace for at least six (6) hours the first time you use it. If optional fan kit has been installed, place fan in the “OFF” position during this time.
IMPORTANT: Turn off gas before servicing appliance. It is
recommended that a qualified service person perform these check-ups at the beginning of each heating season.
• Clean Burner and Control Compartment
Keep the control compartment, logs, and burner areas surrounding
the logs clean by vacuuming or brushing at least twice a year.
Cleaning Procedure
1. Turn off pilot light at gas valve.
2. Vacuum burner compartment.
3. Ignite pilot (if applicable). (See Lighting Instructions)
4. Operate the pilot burner (if applicable). If it appears abnormal call a service person.
• Check Vent System
The appliance and venting system should be inspected before
initial use and at least annually by a qualified service person. Inspect the external vent cap on a regular basis to make sure that no debris is interfering with the air flow.
Glass Cleaning (Optional Kits)
It will be necessary to clean the glass periodically. During start-up condensation, which is normal, forms on the inside of the glass and causes lint, dust and other airborne particles to cling to the glass surface. Also initial paint curing may deposit a slight film on the glass. It is therefore recommended that the glass be cleaned two or three times with a non-abrasive household cleaner and warm water (we recommend gas fireplace glass cleaner). After that the glass should be cleaned two or three times during each heating season depending on the circumstances present.
General Glass Information
Only glass approved for use by the manufacturer may be used for replacement. The glass replacement should be done by a licensed or qualified service person.
WARNING:
1. The use of substitute glass will void all product warranties.
2. Care must be taken to avoid breakage of glass.
3. Do not abuse the glass by striking or hitting the glass.
WARNING: Do not use abrasive cleaners on glass. Do not attempt to clean glass when glass is hot.
Page 2719400-3-0406
BVD34 & BVD36 PARTS LIST
INDEX
NO.
BVD34L BVD34F BVD36L BVD36F 1 19506 19506 19507 19507 TOP SHIELD 2 17301 17301 17301 17301 TOP STANDOFF (2 REQUIRED) 3 10554 10554 10554 10554 NAILING FLANGE (4 REQUIRED) 4 M163 M163 M178 M178 FLUE OUTLET GASKET 5 19387 19387 19422 19422 FLUE OUTLET ASSEMBLY 6 19398 19398 19398 19398 DOWNDRAFT BAFFLE 7 19402 19402 19434 19434 DRAFT BAFFLE 8 R7052 R7052 R7052 R7052 SCREEN ROD 9 R8137 R8137 R8148 R8148 SCREEN 10 17127 N/A 18807 N/A UPPER LOUVER ASSEMBLY 11 17128 N/A 18808 N/A LOWER LOUVER ASSEMBLY 12 17162 17162 17162 17162 JUNCTION BOX ASSEMBLY (DIRECT IGNITION & LOUVERED
12a 17163 17163 17163 17163 JUNCTION BOX COVER PLATE 13 R3492 R3492 R3492 R3492 RECEPTACLE (DIRECT IGNITION & LOUVERED MODELS ONLY) 14 19435 19435 19436 19436 VALVE ACCESS DOOR 15 17235 17235 17235 17235 LOG LOCATOR BRACKET 16 R7580 R7580 R8020 R8020 BURNER TUBE 17 R5676 R5676 R5676 R5676 AIR SHUTTER 18 P252 P252 P286 P286 ORIFICE (NAT) 19 R7572 R7572 R7572 R7572 JAMB NUT 20 P212 P212 P212 P212 ORIFICE HOLDER 21a 19384 19384 19420 19420 TUBING ASSEMBLY 21b 19404 19404 19440 19440 TUBING ASSEMBLY 22 R2423 R2423 R2423 R2423 MALE ADAPTOR 23 R7590 R7590 R7590 R7590 SPARK IGNITOR (DIRECT IGNITION) 24 17315 17315 17315 17315 SPARK IGNITOR MOUNTING PLATE (DIRECT IGNITION) 25 R8132 R8132 R8132 R8132 PILOT (MILLIVOLT) 25a R5710 R5710 R5710 R5710 THERMOPILE 26 R7617 R7617 R7617 R7617 PILOT GASKET 27 19382 19382 19418 19418 BURNER BASE ASSEMBLY 28a 19381 19381 19381 19381 VALVE BRACKET (MILLIVOLT) 28b 19403 19403 19403 19403 VALVE BRACKET (DIRECT IGNITION) 29a R8380 R8380 R8380 R8380 VALVE, GAS (MILLIVOLT) 29b R7568 R7568 R7568 R7568 VALVE, DIRECT IGNITION (120V) 30 R2708 R2708 R2708 R2708 PIEZO IGNITOR (MILLIVOLT) 31 R7613 R7613 R7613 R7613 IGNITOR WIRE (SPARK PLUG WIRE) (DIRECT IGNITION) 32 R8143 R8143 R8143 R8143 CONTROL MODULE, ELECTRONIC (DIRECT IGNITION) 33 R8144 R8144 R8144 R8144 WIRE ASSEMBLY (DIRECT IGNITION) 34 R7615 R7615 R7615 R7615 CORD SET (DIRECT IGNITION) 35a R8133 R8133 R8133 R8133 WIRE ASSEMBLY, LIMIT SWITCH (MILLIVOLT) 35b R8147 R8147 R8147 R8147 WIRE ASSEMBLY, LIMIT SWITCH (DIRECT IGNITION) 36 R8145 R8145 R8145 R8145 WIRE ASSEMBLY, WALL SWITCH (ON/OFF) 37 R7587 R7587 R7556 R7556 REAR LOG 38 R7586 R7586 R7555 R7555 MIDDLE LOG 39 R7585 R7585 R7553 R7553 FRONT LEFT LOG 40 R-7588 R7588 R7557 R7557 "Y" BRANCH 41 R7554 R7554 R7554 R7554 FRONT RIGHT LOG 42 R7591 R7591 R7591 R7591 FLEX LINE/SHUTOFF VALVE 43 R8593 R8593 R8375 R8375 SWITCH, LIMIT 44 - - 19918 19918 BRICK PANEL, PAINTED
PART NUMBER DESCRIPTION
MODELS ONLY)
USE ONLY MANUFACTURER’S REPLACEMENT PARTS. USE OF ANY OTHER PARTS COULD CAUSE INJURY OR DEATH.
Page 28 19400-3-0406
8
7
6
5
4
2
3
1
8
9
9
10
11
12
13
14
15
16
17 18
19
20
21
22
23
24 26
27
28b
25
19
17 18
26
27
28a
21
20
15
29a
30
31
32
33
35a
34
35b
36
37
38
39
16
22
29b
40
41
DIRECT IGNITION BURNER ASSEMBLY
MILLIVOL
T BURNER ASSEMBLY
5 PIECE LOG ASSEMBLY
43
44
42
25a
BVD34 & BVD36 PARTS VIEW
Page 2919400-3-0406
BVP42 PARTS LIST
INDEX NO. PART NUMBER PART NUMBER DESCRIPTION
BVP42L BVP42F
1 19508 19508 TOP SHIELD
2 17247 17247 TOP STANDOFF (2 REQUIRED)
3 10554 10554 NAILING FLANGE (4 REQUIRED)
4 M178 M178 FLUE OUTLET GASKET
5 19422 19422 FLUE OUTLET ASSEMBLY
6 19398 19398 DOWNDRAFT BAFFLE
7 19467 19467 DRAFT BAFFLE
8 R7053 R7053 SCREEN ROD
9 R8148 R8148 SCREEN
10 17187 N/A UPPER LOUVER ASSEMBLY
11 17188 N/A LOWER LOUVER ASSEMBLY
12 17162 17162 JUNCTION BOX ASSEMBLY (DIRECT IGNITION AND LOUVERED MODELS ONLY)
12a 17163 17163 JUNCTION BOX COVER PLATE
13 R3492 R3492 RECEPTACLE (DIRECT IGNITION & LOUVERED MODELS ONLY)
14 19437 19437 VALVE ACCESS DOOR
15 P200 P200 ORIFICE HOLDER
16 P213 P213 ORIFICE
17 R5676 R5676 AIR SHUTTER
18 11499 11499 BURNER SUPPORT LEFT SIDE
19 17370 17370 BURNER ASSEMBLY
20a 19457 19457 TUBING ASSEMBLY
20b 19470 19470 TUBING ASSEMBLY
21 R2423 R2423 MALE ADAPTER
22 11377 11377 BURNER SUPPORT RIGHT
23 R7590 R7590 SPARK IGNITOR (DIRECT IGNITION)
24 R7612 R7612 PILOT (MILLIVOLT)
24a R5710 R5710 THERMOPILE
25 19545 19545 SPARK IGNITOR SHIELD (DIRECT IGNITION)
26 R7617 R7617 PILOT GASKET (MILLIVOLT)
26a M173 M173 PILOT GASKET (DIRECT IGNITION)
27 19455 19455 BURNER BASE ASSEMBLY
28a 19381 19381 VALVE BRACKET (MILLIVOLT)
28b 20207 20207 VALVE BRACKET (DIRECT IGNITION)
29a R8380 R8380 VALVE, MILLIVOLT GAS
29b R7733 R7733 VALVE, DIRECT IGNITION GAS (120V)
30 R2708 R2708 PIEZO IGNITOR (MILLIVOLT)
31 R7613 R7613 IGNITOR WIRE (SPARK PLUG WIRE) (DIRECT IGNITION)
32 R8143 R8143 CONTROL MODULE, ELECTRONIC (DIRECT IGNITION)
33 R8144 R8144 WIRE ASSEMBLY (DIRECT IGNITION)
34 R7615 R7615 CORD SET (DIRECT IGNITION)
35a R8133 R8133 WIRE ASSEMBLY, LIMIT SWITCH (MILLIVOLT)
35b R8147 R8147 WIRE ASSEMBLY, LIMIT SWITCH (DIRECT IGNITION)
36 R8145 R8145 WIRE ASSEMBLY, THERMOSTAT
37 R7643 R7643 TOP BRANCH
38 R7642 R7642 REAR LOG
39 R7641 R7641 BOTTOM LOG
40 R8594 R8594 SWITCH, LIMIT
41 19958 19958 BRICK PANEL, PAINTED
42 R7591 R7591 FLEX LINE/SHUTOFF VALVE
Page 30 19400-3-0406
USE ONLY MANUFACTURER’S REPLACEMENT PARTS. USE OF ANY OTHER PARTS COULD CAUSE INJURY OR DEATH.
8
7
6
5
4
2
3
1
8
9
9
10
11
12
13
14
21
22
29b
28a
29a
30
21
20a
31
32
33
34
35a
35b
36
37
38
39
DIRECT IGNITION BURNER ASSEMBLY
MILLIVOL
T BURNER ASSEMBLY
3 PIECE LOG ASSEMBLY
28b
16
19
17
18
27
20b
15
26
24
22
25
16
19
17
18
27
15
26a
23
40
41
42
24a
BVP42 PARTS VIEW
Page 3119400-3-0406
VALVE BRACKET
F
AN
SWITCH
FA
N KIT
SPEED
CONTROL
JUNCTION
BOX
SWITCH
HOLDER
(TOP
OF VALV
E BRACKET)
SEE NOTE
OP T IO N A L
BL O WE
R
I N S T
A L L A T I O N
I S
I N T E N D E D
F O R
LO UV ER ED
MO DE LS
ONLY.
FBB4 OPTIONAL VARIABLE SPEED BLOWER INSTALLATION
Attention: Install blower assembly before connecting gas inlet
supply line
Note: Junction box on right side of fireplace must be pre-wired at
time of fireplace installation for use with blower assembly. It is recommended that an ON/OFF wall switch be installed that will activate the power supply to the furnace by a qualified electrician.
1. If installed, turn OFF gas supply to fireplace.
2. If applicable, turn OFF electric supply to fireplace.
3. Lower bottom louver on fireplace.
4. Refe r to page 34, "Junction Box Wiring Ins tallation Instructions" to complete wiring of junction box.
Attention: If installed, do not damage gas inlet supply line
when blower assembly is inserted into fireplace. If necessary, remove gas inlet supply line.
5. Insert blower assembly into interior, bottom of fireplace. Position blower assembly behind gas valve, align notch on back of blower assembly with center screw on fireplace back and push blower assembly against fireplace back. The magnets on the back and bottom of blower assembly will sufficiently hold blower assembly in place.
6. Position speed control box to the right of gas valve. Attach speed control box to bottom of fireplace. The magnets on bottom of speed control box will sufficiently hold speed control box in place.
7. With base (flush face) of fan control switch facing upward, insert base of fan control switch under the mounting tabs on valve bracket. The base (flush face) of fan control switch must be in contact with bottom of firebox.
8. Insert power cord plug into junction box.
9. Close bottom louver on fireplace.
10. Installation of FBB4 optional variable speed blower assembly is completed.
Figure 25
Note: Refer to wiring instructions on page 33 for proper operation.
Page 32 19400-3-0406
110 VOLT AC
JUNCTION BOX
WHITE
SPEED CONTROL
FA
N
SWITCH
GROUND
BLACK
FA
N
FBB4 OPTIONAL VARIABLE SPEED BLOWER INSTALLATION
Figure 26
1 FBB4 BLOWER ASSEMBLY
COMPLETE
2 R7649 FAN CONTROL
3 R4192 SPEED CONTROL
KNOB
4 R4186 SPEED CONTROL
Figure 27
Page 3319400-3-0406
JUNCTION BOX WIRING INSTALLATION INSTRUCTIONS
STANDARD MILLIVOLT VALVE MODELS
CAUTION: ALL WIRING SHOULD BE DONE BY A QUALIFIED ELECTRICIAN AND SHALL BE IN COMPLIANCE WITH ALL LOCAL, CITY AND STATE BUILDING CODES. BEFORE MAKING THE ELECTRICAL CONNECTION, MAKE SURE THAT MAIN POWER SUPPLY IS DISCONNECTED. THE APPLIANCE, WHEN INSTALLED, MUST BE ELECTRICALLY GROUNDED IN ACCORDANCE WITH LOCAL CODES OR, IN THE ABSENCE OF LOCAL CODES, WITH THE NATIONAL ELECTRICAL CODE ANSI/NFPA 70 (LATEST EDITION).
A factory installed junction box is located on the lower right side of the fireplace. Wiring must be fed to the junction box and attached to the receptacle that is provided. Leave approximately 6" of wire in the junction box for connection.
Attach black wire to one side of the receptacle and white wire to opposite side of receptacle. The ground wire should be attached to the green (ground) screw.
Install the receptacle into the junction box. Attach cover plate.
120V DIRECT IGNITION VALVE MODELS
Figure 28
Figure 29
1. To wire Junction Box Receptacle, remove the tab on the side of the receptacle (hot side) to split receptacle. This will be required to separate blower and valve circuits.
2. Power for switched and live sides of Duplex Receptacle must come from the same power source. (One circuit breaker on main panel must switch all power off.)
Page 34 19400-3-0406
3. From the wall box to the fireplace a 3-wire conductor with ground is recommended, however (2) two-wire conductors with grounds may be used in place of a 3-wire conductor with a ground if the black wires from the thermostat and blower switch are identified.
4. Two wall switches, or a wall switch and thermostat may be used to activate the two receptacle plugs independently.
OPTIONAL ACCESSORIES
The following accessory parts can be obtained from your Empire Comfort Systems dealer. If you need additional information beyond what your dealer can furnish, contact Empire Comfort Systems Inc., Nine Eighteen Freeburg Ave., Belleville, Illinois 62220-2623.
Accessory Description Model Number
Fan Kit This fan kit was designed to provide forced air flow (for
louvered models only).
Variable Speed FBB4
Simulated Brick Panels The simulated brick panels were designed to enhance
the appearance of your fireplace, imitating the look of authentic masonry.
HERRINGBONE
Simulated Brick Panels The simulated brick panels were designed to enhance
the appearance of your fireplace, imitating the look of authentic masonry.
AGED BRICK
Fresh Air Kit Installs to side of fireplace to provide fresh air make up
when operating fireplace (optional).
Note: Requires standard 4" diameter flexible or hard pipe connector (not included with kit)
BVD2SH (BVD34FP) BVD36SH (BVD36FP) BVD3SH (BVP42FP)
BVD2SA (BVD34FP) BVD36SA (BVD36FP) BVP3SA (BVP42FP)
BVA1
Optional Bifold Glass Door Accessory.
Includes bifold tempered glass doors and decorative canopy to give a finishing touch to your fireplace. Operational doors that can remain open or closed when operating the fireplace.
Optional One-Piece Clearspan Style Door.
Used to enhance the look of the fireplace. This is a fixed door system for those who prefer a non-operable glass door option.
Please refer to the instructions included with the optional accessory kits for proper installation.
BVX2BL (BVD34FP) BVX36BL (BVD36FP) BVX3BL (BVP42FP)
BVC2BL (BVD34FP)
Page 3519400-3-0406
DECORATIVE ACCESSORIES
Decorative Louver Mission
Decorative Frame Rectangle
with hinges
Decorative Frame Arch with
hinges
Decorative Louver Arch
Decorative Door Leaf
Rectangle
Decorative Door Leaf Arch
Decorative Louver Leaf
Decorative Door Mission
Rectangle
Decorative Door Mission Arch Decorative Door Plain Arch
Decorative Door Plain
Rectangle
Decorative Frame Arch without
hinges only Black
Bottom Trim Frame
STD Louvers 45 Deg
Outside Frame Kits
Please contact your nearest dealer/distributor for more information on all available optional decorative accessories.
Page 36 19400-0-1005
SERVICE NOTES
HOW TO ORDER REPAIR PARTS
Parts can be ordered only through your service person or dealer. For best results, the service person or dealer should order parts through the distributor. Parts can be shipped directly to the service person/dealer.
All parts listed in the Parts List have a Part Number. When ordering parts, first obtain the Model Number from the name plate on your equipment. Then determine the Part Number (not the Index Number) and the Description of each part from the following appropriate illustration and list. Be sure to give all this information . . .
Fireplace Number Part Description
Fireplace Serial Number Part Number
Type of Gas (Propane or Natural)
Do not order bolts, screws, washers or nuts. They are standard hardware items and can be purchased at any local hardware store.
Shipments contingent upon strikes, fires and all causes beyond our control.
Empire Comfort Systems, Inc. Nine Eighteen Freeburg Ave. Belleville, Illinois 62222-2623
Page 3719400-3-0406
SERVICE NOTES
Page 38 19400-3-0406
SERVICE NOTES
Page 3919400-3-0406
Empire Comfort Systems, Inc. 918 Freeburg Ave. Belleville, IL 62220 PH: 618-233-7420 or 800-851-3153 FAX: 618-233-7097 or 800-443-8648 info@empirecomfort.com
www.empirecomfort.com
Page 40 19400-3-0406
Loading...