Vulcan Hart AHP-636 Operator’s Manual

INSTALLATION & OPERATION MANUAL FOR
MODELS
VHP212 VHP424 VHP636 VHP848
VHP636
AHP212 AHP424 AHP636 AHP848
©ITW Food Equipment Group, LLC 3600 North Point Blvd. Baltimore, MA 21222
AHP636
RETAIN THIS MANUAL FOR FUTURE USE
FORM F-38334 (03-12)
IMPORTANT FOR YOUR SAFETY
THIS MANUAL HAS BEEN PREPARED FOR PERSONNEL QUALIFIED TO INSTALL GAS EQUIPMENT, WHO SHOULD PERFORM THE INITIAL FIELD START-UP AND ADJUSTMENTS OF THE EQUIPMENT COVERED BY THIS MANUAL.
POST IN A PROMINENT LOCATION THE INSTRUCTIONS TO BE FOLLOWED IN THE EVENT THE SMELL OF GAS IS DETECTED. THIS INFORMATION CAN BE OBTAINED FROM THE LOCAL GAS SUPPLIER.
IMPORTANT
IN THE EVENT A GAS ODOR IS DETECTED, SHUT DOWN UNITS AT MAIN SHUTOFF VALVE AND CONTACT THE LOCAL GAS COMPANY OR GAS SUPPLIER FOR SERVICE.
FOR YOUR SAFETY
DO NOT STORE OR USE GASOLINE OR OTHER FLAMMABLE VAPORS OR LIQUIDS IN THE VICINITY OF THIS OR ANY OTHER APPLIANCE.
adjustment, alteration, service or maintenance can cause property damage, injury, or death. Read the installation, operating and maintenance instructions thoroughly before installing or servicing this equipment.
IN THE EVENT OF A POWER FAILURE, DO NOT ATTEMPT TO OPERATE THIS DEVICE.
Improper installation,
- 2 -
INSTALLATION, OPERATION AND CARE OF
GAS HOTPLATES
GENERAL
Gas Countertop Hotplates are designed for commercial use only and feature fast, efficient gas heat. Each burner is controlled by an adjustable gas valve. Cast grates and burners are easily removed for cleaning when cool.
BTU/hr Input Rating
Model Number Of Burners
Natural Gas Propane
VHP212/AHP212 2 60,000 55,000
VHP424/AHP424 4 120,000 110,000
VHP636/AHP212 6 180,000 165,000
VHP848/AHP848
8
240,000
220,000
INSTALLATION
UNPACKING
Immediately after unpacking, check for possible shipping damage. If the hotplate is found to be damaged, save the packaging material and contact the carrier within 15 days of delivery.
LOCATION
The installation location must be kept free and clear of combustibles. Do not obstruct the flow of combustion and ventilation air. DO NOT install the hotplate adjacent to fryers.
Sufficient air should be allowed to enter the room to compensate for the amount of air removed by any ventilating system and for combustion of the gas burners. Do not obstruct the air flow into and around the hotplate. Position the hotplate in its final location. Check that there are sufficient clearances to service the hotplate and to make the required gas supply connection(s). Provide 24" clearance at the front for cleaning, maintenance, service and proper operation.
Minimum clearances to combustible construction are 6" to the back and 6" to the sides. Minimum clearances to non-combustible walls are 0" to the rear and 0" to the sides.
- 3 -
INSTALLATION CODES AND STANDARDS
The hotplate must be installed in accordance with:
In the United States of America:
1. State and local codes.
2. National Fuel Gas Code, ANSI-Z223.1/NFPA #54 (latest edition). This shall include but not be limited to: NFPA #54 Section 10.3.5.2 for Venting. Copies may be obtained from The American Gas Association Accredited Standards Committee Z223, @ 400 N. Capital St. NW, Washington, DC 20001 or the Secretary Standards Council, NFPA, 1 Batterymarch Park Quincy, MA 02169-7471
NOTE: In the Commonwealth of Massachusetts
All gas appliances vented through a ventilation hood or exhaust system equipped with
a damper or with a power means of exhaust shall comply with 248 CMR.
3. NFPA Standard # 96 Vapor Removal from Cooking Equipment, latest edition, available from the National Fire Protection Association, Batterymarch Park, Quincy, MA 02269.
In Canada:
1. Local codes.
2. CAN/CSA-B149.1 Natural Gas Installation (latest edition)
3. CAN/CSA-B149.2 Propane Installation Code (latest edition), available from the Canadian Gas Association, 178 Rexdale Blvd., Etobicoke, Ontario, Canada M9W 1R3
CASTER EQUIPPED APPLIANCES
Hotplates mounted on stands with casters must use a flexible connector (not supplied) that complies with the Standard for Connectors for Movable Gas Appliances, ANSI Z21.69
• CSA 6.16 and a quick-disconnect device that complies with the Standard for Quick-
Disconnect Devices for use With Gas Fuel, ANSI-Z21.41 • CSA 6.9. In addition, adequate means must be provided to limit movement of the hotplate without depending on the connector and the quick-disconnect device or its associated piping to limit hotplate movement. Attach the restraining device at the rear of the hotplate. If disconnection of the restraint is necessary, turn off the gas supply before disconnection. Reconnect the restraint prior to turning the gas supply on and return the hotplate to its installation position.
If the Hotplate is installed on casters and is moved for any reason, it is recommended that it be re-leveled (see LEVELING).
LEVELING
If the hotplate is equipped with legs or is mounted on the optional stand equipped with legs, turn the feet at the bottom of the legs in or out to level the hotplate in the final installed location. If the hotplate is mounted on the optional stand equipped with casters, position the hotplate on a level floor.
VENTILATION HOOD
The hotplate should be installed under a suitable ventilation hood. For safe operation and proper ventilation, keep the space between the hotplate and vent hood free from any obstructions.
- 4 -
GAS CONNECTIONS
Gas supply connections and any pipe joint compound must be resistant to the
action of propane gases.
Purge the supply line to clean out any dust, dirt, or any foreign matter before connecting the line to the unit.
Codes require that a gas shut-off valve be installed in the gas line ahead of the appliance. The gas supply line must be at least the equivalent of ¾” iron pipe.
An adequate gas supply is necessary. Undersized or low pressure lines will restrict the volume of gas required for satisfactory performance. A minimum supply pressure of 7" W.C. for natural gas and 11" W.C. for propane gas is recommended. With all units operating simultaneously, the manifold pressure on all units should not show any appreciable drop.
When testing the gas supply piping system, if test pressures exceed ½ psig (3.45 kPa), the appliance and its individual shutoff valve must be disconnected from the gas supply piping system. When test pressures are ½ psig (3.45 kPa) or less, the appliance must be isolated from the gas supply piping system by closing its individual manual shut-off valve during any pressure testing of the system.
Prior to lighting, check all joints in the gas supply line for leaks.
Use soap and water solution. Do not use an open flame.
GAS PRESSURE REGULATOR INSTALLATION
Gas regulator pressure is preset at 5” Water Column (W.C.) for natural gas, and 10” W.C. for propane gas. Minor adjustments may be required based on site specific gas pressure.
Install the regulator as close to the hotplate on the gas supply line as possible. Make sure that the arrow on the underside of the regulator is oriented in the direction of gas flow to the hotplate (Fig. 1) and the regulator is positioned with the vent plug and adjustment screw upright(Fig. 2).
Fig. 1
Fig. 2
The minimum supply pressure (upstream of the regulator) should be 7-9” W.C. for natural gas and 11-12” W.C. for propane gas. At no time should the hotplate be connected to supply pressure greater than ½ psig (3.45 kPa) or 14” W.C.
Prior to lighting, check all joints in the gas supply line for leaks.
Use soap and water solution. Do not use an open flame.
- 5 -
OPERATION
The hotplate and its parts are hot. Use care when operating,
cleaning or servicing the hotplate.
CONTROLS
There is one pilot for every two burners. The hotplate is equipped with standing, unmonitored pilots. Gas will flow from the pilots as soon as the main gas supply to the unit is turned on. See pilot lighting procedure below.
Each burner is independently controlled by an infinite heat control valve. Once the pilots are lit, turning the control knob to the ON position will light each burner. The burners will be in the full ON position when the control knobs are turned all the way to the left. The burners will be in the full OFF position when the control knobs are turned all the way to the right.
LIGHTING INSTRUCTIONS
1. See Fig 5. Turn main gas shut-off valve
and all burner control knobs to the OFF position and wait 5 minutes to allow any accumulated gas to escape.
2. Remove grates.
3. Turn main gas shut-off valve ON.
Light the pilots. Adjust the pilot valve screw(See Fig.6) until the pilot flame has a slight yellow tip.
4. To light burners, turn individual burner
valves to the ON position.
5. If burners fail to light, turn all valves
and the main gas shut-off to the OFF position and contact an authorized service agency.
PILOTS
Fig. 5
- 6 -
PILOT ADJUSTMENT
Using a flathead screwdriver, turn the slotted hex-head pilot adjustment screw clockwise to decrease the flame, and counterclockwise to increase the flame. See Fig. 6.
Fig. 6
PILOT ADJUSTMENT SCREWS
CLEANING
The hotplate and its parts are hot. Use care when operating,
cleaning or servicing the hotplate.
Grates may be immersed in commercial cleaning compound overnight. In the morning, rinse with hot water to remove any residues of cleaning compound. Thoroughly dry and apply a cooking oil to prevent rusting.
Burner ports and burner rest should be thoroughly cleaned. Venturi must be free from grease and lint. When cleaning, do not insert a pick into the burner port holes – soap and water will normally do the job. Heavy spattering or spill-over may require cleaning with a mild oven cleaner. After cleaning, rinse with clean water and dry with a dry cloth. Be sure to apply a thin coat of cooking oil for protection after cleaning.
Stainless steel surfaces may be cleaned using damp cloth with mild detergent and water solution.
Places where fat, grease, or food can accumulate must be cleaned regularly.
- 7 -
MAINTENANCE
The hotplate and its parts are hot. Use care when operating,
cleaning or servicing the hotplate.
LUBRICATION
All valves must be checked and lubricated periodically. Check with your service agency for details.
VENT SYSTEM
At least twice a year the exhaust hood (venting system) should be examined and cleaned.
SERVICE
Contact your local Service Agency for any repairs or adjustments needed on this equipment. For a complete listing of Service and Parts depots refer to
www.vulcanequipment.com
When calling for service, the following information should be available from the appliance identification plate: Model Number and Serial Number.
.
- 8 -
Loading...
+ 16 hidden pages