This Manual is prepared for the use of trained Vulcan Service
Technicians and should not be used by those not properly
qualified.
This manual is not intended to be all encompassing. If you have
not attended a Vulcan Service School for this product, you should
read, in its entirety, the repair procedure you wish to perform to
determine if you have the necessary tools, instruments and skills
required to perform the procedure. Procedures for which you do
not have the necessary tools, instruments and skills should be
performed by a trained Vulcan Service Technician.
The reproduction, transfer, sale or other use of this Manual,
without the express written consent of Vulcan, is prohibited.
This manual has been provided to you by ITW Food Equipment
Group LLC ("ITW FEG") without charge and remains the property
of ITW FEG, and by accepting this manual you agree that you will
return it to ITW FEG promptly upon its request for such return at
any time in the future.
A product of Vulcan-Hart3600 North Point Blvd Baltimore, MD 21222
F45559 (0615)
Page 2
C24EA-LWE SERIES COUNTERTOP STEAMER
TABLE OF CONTENTS
GENERAL .................................................................................................. 4
This manual is applicable to the models and ML numbers listed on the cover page. Procedures apply to all models
unless specified otherwise.
LWE Series Steamers
The low water and energy use steamers (LWE) provide energy and water saving steam generation that meets
ENERGY STAR® performance levels. The steamers feature an electronic PID Controller and Solid State Contactor
that work together to "pulse" power to the heating elements during a cook cycle and reduce the amount electrical
energy and water consumed.
Steam Cooking
Atmospheric steamers offer an efficient way to produce many foods in either small portions or larger batches.
Atmospheric convection steam cooking will steam cook fresh foods or will steam defrost and cook frozen foods
providing the maximum color, flavor and nutritional value with the least expenditure of energy and labor. The
atmospheric steaming compartment allows the operator to open and close the door anytime during a cooking cycle.
The generator element will shut off when the door is opened then re-start when the door is closed.
INSTALLATION, OPERATION AND MAINTENANCE
For detailed installation, operation and cleaning instructions refer to F35428 Installation & Operation Manual sent
with each unit. The manual is also available online at www.vulcanequipment.com.
MODELS
Model Designations (based on 2.5 inch pan depth)
C24EA3-LWE three pan capacity and professional controls*
C24EA5-LWE five pan capacity and professional controls*
NOTE: (*) Low Water & Energy (LWE) models do not use a super heater as due other countertop models with
professional controls.
SPECIFICATIONS
NOTE: All C24EA LWE steamers are shipped pre-wired for 208/50/60/3 or 480V/50/60/3 operation. 208V 3 phase
is an unbalanced load and the value listed for amperage is the maximum on any leg. The steamer can be field
converted from 208V/50/60/3 electrical service by disconnecting the fourth heating element wires to the contactors.
See WIRING DIAGRAM - HEATING ELEMENTS for proper connections. If field converting, check transformer for
proper voltage setting. The LWE units are not designed to operate on single phase.
0.1 ppm will cause permanent damage to the steam
generator and cooking compartment. Contact water
filter system manufacturer to ensure this requirement
is met.
Hardness above 4 grains/gal should be treated by
water conditioner, water softener or in-line treatment.
Water Conditioning
It is recommended that a local water treatment
specialist be consulted before the installation of any
steam generating equipment.
TOTAL
kW
Chlorine and Chloramine above levels of
Hz.
208V240V480V
L1L2L3L1L2L3L1L2L3
—
2.Causes premature failure of the heaters.
3.Water level probes will give false readings.
4.Thermostat bulbs will sense temperature
incorrectly.
These problems are common to any manufacturer's
steamer regardless of design, but they can all be
prevented by furnishing the steam generator tank with
properly conditioned water.
Other chemical properties in water supplies can also
affect good steam generation and vary from within
each state and locality.
The water level probes in the steam generator tank
use ions in the water to detect the water level. Do notuse fully demineralized or de-ionized water since it is
non-conductive and the water level cannot be
detected.
NOTE: The use of strainers or filters will not remove
minerals from the water.
Steamers that operate over a long period of time
without the benefit of properly conditioned water,
which have developed a heavy scale build up, should
be cleaned before connecting to a conditioned water
supply.
Furnishing the steam generator with properly
conditioned water to reduce scale formation is
important. Scale formation will reduce steam output,
cause premature component failure and shorten
equipment life. Most water supplies contain scale
producing minerals such as calcium and magnesium.
As steam is generated, the minerals remain and
dissolve into the remaining water. As the
concentration of these minerals increases past a
certain point, they precipitate from the water and coat
the inside of the tank, heating elements, thermostat
bulbs and water level probes. Because of the high
temperature of these surfaces, the precipitated
minerals bake onto them and become very difficult to
remove.
This phenomenon causes several problems:
1.Reduces the heat transfer efficiency of the
heaters.
Page 5 of 57F45559 (0615)
LUBRICATION AND SEALANT
ComponentType
Heating Element Screws Never Seez®
Door Handle Sliding
Bracket
Rotary Shaft Seal (timer) Petrogel, lubricant
All NPT Fittings
Door Striker Threads
Door Housing Screw
Threads
Lubriplate® 630AA
Loctite® 565™, pipe
thread sealant,
Loctite® 271™, thread
sealer
Loctite® 242™, thread
sealer
Page 6
C24EA-LWE SERIES COUNTERTOP STEAMER - GENERAL
TOOLS
•Standard set of hand tools.
•Pipe thread sealant.
•VOM with ability to measure micro amp current.
VOM with minimum of NFPA-70E CAT III 600V,
UL/CSA/TUV listed. Sensitivity of at least 20,000
ohms per volt. Meter leads must also be rated at
CAT III 600V.
•Clamp on type amp meter for measuring heating
element current.
Special
•Torque Wrench - Capable of measuring 70 in-lb.
•RTV 109 Silicone Sealant or equivalent for use
when replacing door gasket.
•High temperature aluminum foil tape for use
when securing insulation around cooking
compartment.
Fig. 1
•Anti-static kit for handling electronic circuit
boards (purchase locally).
•Pressure Gauge Assembly for use when
checking and adjusting pressure switch:
•Pressure Gauge - 0 to 15 psi, 1/4" NPT,
recommended Grainger Part No. 36TW02
or equivalent for steamers with nonadjustable pressure switch.
•Low Pressure Gauge - 0 to 5 psi, 1/4" NPT,
recommended Grainger Part No. 2C641 or
equivalent for steamers with adjustable
pressure switch.
•Water Hose to Pipe Coupling - 3/4" FGHT x
½" FNPT- swivel type, double female brass,
Grainger Part No. 4KG87 or equivalent.
•Reducer Bushing - ½" MNPT x 1/4" FNPT
brass, Grainger Part No. 6AYW8, package
of 10 or single bushing equivalent (purchase
locally).
F45559 (0615)Page 6 of 57
Page 7
C24EA-LWE SERIES COUNTERTOP STEAMER - COVERS AND PANELS
COVERS AND PANELS
RIGHT AND LEFT SIDE PANELS
Disconnect the
electrical power to the machine and
follow lockout / tagout procedures.
NOTE: Removal of left side panel is identical to the
procedure for the right side panel.
1.Remove screws (qty. 2) from the bottom of panel
being removed.
Fig. 3
2.Lift top cover at the rear to access vent hose Fig.
4 then remove clamp securing hose to vent tube.
Fig. 2
2.Pull bottom of panel out and slide down to clear
top cover.
3.Reverse procedure to install.
TOP COVER
Disconnect the
electrical power to the machine and
follow lockout / tagout procedures.
1.Remove screws Fig. 3 (qty. 2) securing top cover
to rear panel.
Fig. 4
3.Remove RIGHT AND LEFT SIDE PANELS.
4.Remove mounting hardware [1] Fig. 5 securing
top cover to front panel. The mounting hardware
is located on both sides of the cooking
compartment.
5.Disconnect the delime hose [2] Fig. 5 from delime
port fitting.
Page 7 of 57F45559 (0615)
Page 8
C24EA-LWE SERIES COUNTERTOP STEAMER - COVERS AND PANELS
Fig. 5
6.Lift top cover off machine.
7.Reassemble parts removed in reverse order.
REAR PANEL
2.Remove RIGHT SIDE PANEL.
3.Disconnect vacuum relief hose Fig. 7 from fitting
on rear panel.
Fig. 7
4.Lift top cover at the rear to access vent hose Fig.
8 then remove clamp securing hose to vent tube.
Disconnect the
electrical power to the machine and
follow lockout / tagout procedures.
1.Remove screws
cover to rear panel and the rear panel to steamer
frame.
Fig. 6 (qty. 4) securing the top
Fig. 8
5.Remove rear panel from machine.
6.Reassemble parts removed in reverse order.
Fig. 6
NOTE: If water or drain connections interfere with rear
panel removal, turn off water supply and disconnect
from machine.
F45559 (0615)Page 8 of 57
Page 9
C24EA-LWE SERIES COUNTERTOP STEAMER - DOOR
REMOVAL
Disconnect the
electrical power to the machine and
follow lockout / tagout procedures.
1.Close door.
2.Remove LEFT SIDE PANEL.
3.Remove nuts from upper hinge located inside
front panel.
DOOR
Fig. 10
3.Remove gasket plate.
4.Remove gasket from inner door panel.
Fig. 9
4.Open door slightly, and while holding door, pull
upper hinge away from front panel. Open door
slightly, and while holding door, pull upper hinge
away from front panel.
5.Pull upper hinge out of upper door hinge bushing.
6.Lift door assembly up and off lower door hinge.
7.Reinstall parts removed in reverse order of
removal.
8.Check door for fit and proper sealing of gasket.
GASKET
1.Open door.
2.Remove the shoulder screws and pan pusher
bracket from gasket plate.
5.Remove RTV from bottom part of inner door
panel. Apply new RTV 109 to bottom of door
where shown when assembling gasket to door.
Fig. 11
6.Place a small amount of RTV109 into the inner
door panel gasket screw holes before assembly.
7.Position the new gasket on gasket plate and
reverse procedure to install.
DOOR HANDLE
Removal
1.Open door.
2.Remove screws (qty. 4) from the top and bottom
of door assembly.
3.Pull outer door housing away from inner door
panel starting at the hinge side of door to
separate the door halves.
Page 9 of 57F45559 (0615)
Page 10
C24EA-LWE SERIES COUNTERTOP STEAMER - DOOR
Fig. 12
NOTE: The smaller radius of the step spacers fit into
the slots of the outer door housing and is used to
provide clearance for handle operation.
4.Remove lock nuts and stepped spacers from
threaded studs of door handle.
Fig. 14
4.Install lock nuts and tighten until no gap exists
between handle, step spacer and lock nut. Do not
over-tighten lock nuts.
5.Close inner door panel so that latch mechanism
engages striker on front panel.
6.Install outer door housing onto inner door panel.
7.Align the top and bottom screw holes of outer
door housing with inner door panel.
Fig. 13
Installation
1.Apply Lubriplate 630AA around slots of outer
door housing where the step spacers contact
housing.
2.Install door handle into outer door housing such
that hinge side of door housing is to the left and
arrow on handle is pointed upward.
3.Install step spacer with smaller radius toward
handle and door housing. Smaller radius is a slip
fit with outer door housing slot.
Fig. 15
8.Apply Loctite 242 to threads of screws before
assembling.
9.Install screws to secure door halves together.
10. Check opening and closing operation of door.
LATCH ASSEMBLY
Removal and Disassembly
1.Separate outer door housing assembly from
inner door panel as outlined under DOOR
HANDLE.
2.Remove screws securing latch assembly to inner
door panel and remove latch mechanism.
F45559 (0615)Page 10 of 57
Page 11
C24EA-LWE SERIES COUNTERTOP STEAMER - DOOR
Fig. 16
3.Remove E-clip from latch assembly pins and pull
pins from latch mechanism.
3.Assemble sliding bracket into stationary bracket.
4.While holding head of spring pin against bottom
of sliding bracket, insert spring pin into keeper
hole in bottom of stationary bracket.
Fig. 19
A.Secure spring pin in place with retaining pin.
Fig. 17
4.Remove retaining pin from spring pin.
5.Separate sliding bracket from stationary bracket.
NOTE: Install pins such that heads of pins will be
facing inward toward hinge side of inner door panel
when latch assembly is installed.
5.Install pins to assemble stationary and sliding
brackets together.
A.Secure pins into position with E-clip.
Installation
1.Install latch assembly onto inner door panel with
spring pin toward bottom of door panel.
A.Apply Loctite 271 to threads of screws
before assembly and secure latch assembly
to inner door panel.
Fig. 18
Assembly
1.Apply Lubriplate 630AA to sides of sliding
bracket.
2.Insert spring pin into bottom of sliding bracket.
A.Place spring over spring pin.
Fig. 20
2.Install outer door housing assembly as outlined
in DOOR HANDLE.
3.Check opening and closing operation of door.
Page 11 of 57F45559 (0615)
Page 12
C24EA-LWE SERIES COUNTERTOP STEAMER - DOOR
4.Check steamer for proper operation and leaks
around door seal.
HINGE BEARINGS
Disconnect the
electrical power to the machine and
follow lockout / tagout procedures.
1.Close door.
2.Remove LEFT SIDE PANEL.
3.Remove nuts from upper hinge located inside
front panel.
4.Open door slightly, and while holding door, pull
upper hinge away from front panel.
Fig. 22
A.Press hinge bearing fully into door assembly
using a C-clamp or equivalent.
10. Reassemble parts removed in reverse order.
11. Check door for fit and proper door gasket sealing.
DOOR LATCH ADJUSTMENT
Fig. 21
5.Pull upper hinge out of upper door hinge bearing.
6.Lift door assembly up and off lower door hinge.
7.Pry hinge bearing out from door assembly.
8.Remove outer door housing.
Do not drive bearing into place. The inner
door panel could be damaged. Press bearing into
position.
NOTE: When replacing door hinge bearings, replace
both hinge bearings.
9.Position replacement hinge bearing over hinge
opening in door assembly.
Disconnect the
electrical power to the machine and
follow lockout / tagout procedures.
Should the steamer door jam and cannot
be opened, do not force or pry the door as damage
will occur.
Opening a Jammed Door
1.Lift up on bottom of door at the handle end to
disengage latch.
A.If door does not open, remove RIGHT SIDE
PANEL.
B.Locate the striker [1] Fig. 23 that catches on
door latch beside front panel of steamer.
F45559 (0615)Page 12 of 57
Fig. 23
Page 13
C24EA-LWE SERIES COUNTERTOP STEAMER - DOOR
C.Remove the mounting nut and lockwasher
[1] Fig. 24 from striker to release it from the
front panel.
Fig. 24
D.Open door.
2.Remove striker.
3.Remove any burrs on striker that may cause latch
to stick.
4.Apply Loctite 271 to threads of striker.
5.Reinstall striker with slot pointing upward. Hand
tighten striker nut then perform
proper door latching.
Adjustment
1.With striker installed and the mounting nut ready
to be tightened, close door to center the striker in
front panel mounting hole.
2.Open door and check striker slot for horizontal
alignment. The slot on striker must be kept
horizontal in order for door latch to catch properly
and latch.
3.Once proper slot alignment has been set, hold
striker close to its base then tighten the striker
nut.
Do not damage striker slot when
tightening or door may not latch properly.
NOTE: Do not over-tighten nut. If over-tightened,
striker may turn and change alignment.
4.Check door latching for proper operation.
Adjustment for
NOTE: If door does not open easily, add shims
between striker and cabinet front. When adding shims
make certain that door gasket seals properly and
steamer does not leak. Remove shims as necessary
until leaking stops.
Page 13 of 57F45559 (0615)
Page 14
C24EA-LWE SERIES COUNTERTOP STEAMER - DRAIN BOX
DRAIN BOX
REMOVAL AND REPLACEMENT
Disconnect the
electrical power to the machine and
follow lockout / tagout procedures.
1.Turn off machine to drain steam generator tank.
Allow steamer to complete drain cycle.
A.Turn off water supply.
2.Disconnect the drain plumbing from drain box
outlet fitting at the rear of steamer.
3.Remove RIGHT AND LEFT SIDE PANELS.
4.Disconnect condensate thermostat wires [1] Fig.
25.
Fig. 26
7.Remove mounting nuts Fig. 27 (qty. 2) securing
drain box to valve cabinet bracket at rear of
steamer.
A.Remove condensate thermostat [2] Fig. 25
from drain box. Retain for use on
replacement drain box.
5.Disconnect drain water cooling solenoid hose [3]
Fig. 25 and cooking compartment drain hose [4]
Fig. 25 from drain box.
Fig. 25
6.Access steam generator drain hose Fig. 26 from
right side of machine and disconnect from drain
box.
Fig. 27
8.Remove drain box from steamer.
9.Remove hose barb fitting for the drain water
cooling solenoid hose from drain box. Retain for
use on replacement drain box.
10. Reassemble parts removed in reverse order.
NOTE: When installing condensate thermostat and
hose barb fitting, apply thread sealant to pipe threads.
11. Check steamer for proper operation and leaks
around condensate thermostat and hose
connection points.
F45559 (0615)Page 14 of 57
Page 15
C24EA-LWE SERIES COUNTERTOP STEAMER - COOKING COMPARTMENT
COOKING COMPARTMENT
REMOVAL AND REPLACEMENT
Disconnect the
electrical power to the machine and
follow lockout / tagout procedures.
NOTE: The cooking compartment and front panel are
constructed as an assembly and cannot be separated.
1.Turn off machine to drain steam generator tank.
Allow steamer to complete drain cycle.
A.Turn off water supply.
2.Remove and TOP COVER.
3.Remove DOOR from steamer.
A.Remove lower hinge from compartment
front panel.
4.Remove TIMER, INDICATOR LIGHT
ASSEMBLY, ON/OFF SWITCH and STRIKER
as outlined in each procedure.
5.Remove mounting nut [1] Fig. 28 securing the top
of door switch assembly [2] Fig. 28 to
compartment front panel.
Fig. 29
8.Disconnect compartment drain hose [1] Fig. 30
from rear of cooking compartment [2] Fig. 30.
Fig. 30
9.Remove bolts securing cooking compartment
front panel to louvered panel below it. Three of
the bolts are located on the controls side and one
bolt on the opposite side.
Fig. 28
6.Remove the vacuum breaker [1] Fig. 29 from
cooking compartment.
7.Disconnect steam hose [2] Fig. 29 from the
steam port inlet fitting on cooking compartment.
C24EA-LWE SERIES COUNTERTOP STEAMER - COOKING COMPARTMENT
Fig. 32
11. Remove SENSOR PROBE from sensor tube.
A.Remove sensor probe fitting from sensor
tube. Retain for reuse.
12. Remove mounting nuts [1] Fig. 33 (qty. 4)
securing rear of cooking compartment to the
vertical mounting brackets [2] Fig. 33.
Fig. 33
13. Remove cooking compartment assembly from
steamer frame.
14. Remove mounting nuts (qty. 2) securing sensor
tube bracket to cooking compartment. Retain
sensor tube bracket for reuse.
15. Remove insulation from old cooking
compartment and install it around the
replacement cooking compartment. Secure
using high temperature aluminum foil tape.
16. Reinstall parts removed in reverse order.
17. Check DOOR LATCH ADJUSTMENT.
F45559 (0615)Page 16 of 57
Page 17
C24EA-LWE SERIES COUNTERTOP STEAMER - THERMOSTATS
THERMOSTATS
HOLD THERMOSTAT
Disconnect the
electrical power to the machine and
follow lockout / tagout procedures.
1.Turn off machine to drain steam generator tank.
Allow steamer to complete drain cycle.
A.Turn off water supply.
2.Remove RIGHT SIDE PANEL.
3.Disconnect electrical lead wires [1] Fig. 34 from
hold thermostat.
4.Remove hold thermostat [2] Fig. 34 from steam
generator tank.
HIGH-LIMIT THERMOSTAT
Disconnect the
electrical power to the machine and
follow lockout / tagout procedures.
Removal
1.Turn off machine to drain steam generator tank.
Allow steamer to complete drain cycle.
A.Turn off water supply.
2.Remove RIGHT AND LEFT SIDE PANELS and
TOP COVER.
3.Access HEATING ELEMENT.
4.Note mounting position of capillary bulb [1] Fig.
35 on heating element then compress the spring
clamp [2] Fig. 35 to remove bulb from heating
element.
5.Fully loosen the small capillary tube compression
nut [3] Fig. 35 and slide it away from heating
element.
Fig. 34
NOTE: Apply Loctite 565 to threads of hold
thermostat before assembly.
5.Reassemble parts removed in reverse order of
removal.
6.Check steamer for proper operation and leaks
around hold thermostat.
6.Remove large capillary tube mounting nut [4] Fig.
35 from heating element plate and slide it away
from heating element.
Fig. 35
7.Pull capillary bulb through mounting hole in
heating element plate.
8.Disconnect electrical wiring from high-limit
thermostat.
9.Remove high-limit thermostat [1] Fig. 36 from
mounting bracket.
Page 17 of 57F45559 (0615)
Page 18
C24EA-LWE SERIES COUNTERTOP STEAMER - THERMOSTATS
Fig. 36
Installation
1.Insert capillary bulb through large capillary tube
mounting nut.
A.Route capillary bulb through the mounting
hole in heating element plate.
B.Position capillary bulb [1] Fig. 37 at the
second bank of heating elements then
secure the bulb to heating element using
spring clamp [2] Fig. 37. Position bulb so
that it is centered across heating elements.
2.Apply pipe thread sealant to threads of large
capillary tube mounting nut then install nut to
heating element plate.
A.Pull excess capillary tubing out of heating
element through large capillary tube
mounting nut. Route capillary tube such that
there are no sharp bends or kinks.
B.Tighten small capillary tube compression
nut into the large capillary tube mounting
nut.
Fig. 37
NOTE: Install a new gasket when reassembling
steam generator tank. Temporarily secure gasket in
place with RTV 109.
3.Reinstall remaining parts removed in reverse
order.
4.Torque heating element screws to 70 in-lb
following the heating element tightening
sequence as found under HEATING ELEMENT.
5.Check steamer for proper operation and leaks
around heating element gasket and small
capillary tube compression nut.
CONDENSATE THERMOSTAT
Disconnect the
electrical power to the machine and
follow lockout / tagout procedures.
1.Turn off machine to drain steam generator tank.
Allow steamer to complete drain cycle.
2.Remove
3.Disconnect condensate thermostat wires.
F45559 (0615)Page 18 of 57
A.Turn off water supply.
LEFT SIDE PANEL.
Page 19
C24EA-LWE SERIES COUNTERTOP STEAMER - THERMOSTATS
Fig. 38
4.Remove condensate thermostat from drain box.
5.Reassemble parts removed in reverse order of
removal.
NOTE: When installing condensate thermostat, apply
thread sealant to pipe threads.
6.Check steamer for proper operation and leaks
around condensate thermostat.
Page 19 of 57F45559 (0615)
Page 20
C24EA-LWE SERIES COUNTERTOP STEAMER - TIMER
REMOVAL AND REPLACEMENT
Disconnect the
electrical power to the machine and
follow lockout / tagout procedures.
NOTE: When the timer reaches zero, an external
buzzer will sound and steam will stop entering the
cooking compartment. The steamer has extra
components to utilize the constant steam setting
allowing the steamer to operate continuously.
1.Remove RIGHT SIDE PANEL.
2.Note electrical connections then disconnect
wiring to timer.
TIMER
Fig. 40
4.Apply a small amount of Petrogel under rotary
shaft seal.
5.Reverse procedure to install.
Fig. 39
3.Pull knob from timer shaft.
A.Remove rotary shaft seal from timer shaft
then remove timer from front panel.
B.Inspect rotary shaft seal. Replace if
damaged, worn or signs of moisture
migration into control area around timer
shaft is evident.
6.Check steamer for proper operation.
F45559 (0615)Page 20 of 57
Page 21
C24EA-LWE SERIES COUNTERTOP STEAMER - SOLID STATE CONTACTOR, PID CONTROLLER AND
SENSOR PROBE
SOLID STATE CONTACTOR, PID CONTROLLER AND
SENSOR PROBE
SOLID STATE CONTACTOR
Disconnect the
electrical power to the machine and
follow lockout / tagout procedures.
Removal & Replacement
1.Remove LEFT SIDE PANEL.
2.Note load wire locations [1] Fig. 41 and
disconnect from solid state contactor.
3.Disconnect control signal wires [2] Fig. 41 and
ground wire [3] Fig. 41 from solid state contactor.
4.Disconnect wires [4] Fig. 41 from cooling fan
terminals.
6.Reverse procedure to install and check for proper
operation.
PID CONTROLLER
Disconnect the
electrical power to the machine and
follow lockout / tagout procedures.
Removal and Replacement
1.Remove LEFT SIDE PANEL.
2.Remove screws [1] Fig. 43 (qty. 3) securing solid
state contactor mounting bracket [2] Fig. 43 to the
rear of electrical panel [3] Fig. 43.
Fig. 41
5.Remove screws Fig. 42 (qty. 4) securing solid
state contactor to mounting plate. The left screws
are easily accessible through the space between
the cooling fan and solid state contactor.
Fig. 42
Fig. 43
3.Pull the assembly away from electrical panel to
access PID Controller.
4.Lift the locking tabs [1] Fig. 44 on both sides of
the mounting collar to unlatch them from the
ridges [2] Fig. 44 on PID controller. Use a 1.5"
putty knife or equivalent thin tool underneath
each locking tab to hold the teeth away from
ridges. Slide the mounting collar away from the
mounting bracket [3] Fig. 44 as shown.
Page 21 of 57F45559 (0615)
Page 22
C24EA-LWE SERIES COUNTERTOP STEAMER - SOLID STATE CONTACTOR, PID CONTROLLER AND
SENSOR PROBE
When powered, the PID controller performs a selfdiagnostic test and displays the program version such
as "13.00" for several seconds then enters operation
mode. If controller passes diagnostic test, the display
reverts to the actual sensor probe temperature in the
top of the display, turns ON the output signal to solid
state contactor (if temperature is below set point) and
heating begins. The set point temperature is displayed
at the bottom of the display.
Fig. 44
5.Lift the locking tabs [1] Fig. 45 on PID controller
to unlatch the wire connection strips then remove
the strips [2] Fig. 45 from PID controller as
shown.
Fig. 45
6.Slide mounting collar off the PID controller then
remove the controller from panel.
7.Re-assemble in reverse order and check for
proper operation.
NOTE: When installing, insert the PID controller into
panel opening, slide mounting collar over controller
and push it up against mounting bracket to engage
locking tabs and secure the controller.
Diagnostic Test
The PID controller governs the operation of Solid
State contactor (3CON) to provide power at the load
contacts on the Regulating contactor (2CON) to power
the heating elements. The PID controller and
regulating contactor (2CON) are powered at the same
time through K1 relay contacts during initial heating or
timed cooking. See SCHEMATIC DIAGRAM.
Fig. 46
PID CONTROLLER DISPLAY
Item No.Description
Program version during power on/self-
1
diagnostics test.
Sensor probe temperature inside sensor
2
tube (°F or °C).
Set point temperature - Highest
3
operational temperature setting for sensor
tube.
Output number 1 - Output is active when
4
displayed. If blinking, power is being
pulsed to heating elements.
If PID controller or the sensor probe is malfunctioning,
an error code will display.
Error codes
•If the error code displayed is Er.i1, check sensor
probe (thermocouple) as outlined under Sensor
Probe Test.
•If a different error code is displayed, note the
code then contact the appropriate Technical
Support department for further instructions.
F45559 (0615)Page 22 of 57
Page 23
C24EA-LWE SERIES COUNTERTOP STEAMER - SOLID STATE CONTACTOR, PID CONTROLLER AND
SENSOR PROBE
•If display is not coming ON and the water level
and temperature conditions have been met,
check wiring connections and power to the PID
controller.
PID Operation Check
•Verify the output number "1" appears in the top
right corner of display when PID controller is
powered and the temperature in sensor tube is
below set point (209°F).
•Number "1" indicates the output signal to the
solid state contactor (3CON) is ON.
•Number "1" constantly displayed indicates solid
state contactor is ON 100%.
•Number "1" blinking indicates solid state
contactor is turning ON/OFF to pulse power to
the heating elements.
•Pulsing of power to the heating elements begins
when the sensor tube temperature reaches
approximately 180°F.
4.Reverse procedure to install and check for proper
operation.
Disconnect the
electrical power to the machine and
follow lockout / tagout procedures.
Removal and Replacement
1.Remove LEFT SIDE PANEL.
2.Disconnect sensor probe wires Fig. 47 from PID
controller at lead wire connections.
NOTE: Apply pipe thread sealant to probe threads.
Sensor Probe Test
NOTE: The sensor probe is a J type thermocouple
and the lead wires are polarity sensitive. The negative
lead (red) must be connected to S1 for proper
operation of the PID Controller.
1.Access SENSOR PROBE wires connected to
PID controller.
2.Remove sensor probe wires from PID controller.
3.Check thermocouple for a measurable
resistance (approximately 5 to 10 ohms at room
temperature). If meter reads an overload (OL)
condition (open), or zero ohms (short) replace
the thermocouple and check temperature
controller for proper operation.
Fig. 47
Page 23 of 57F45559 (0615)
Page 24
C24EA-LWE SERIES COUNTERTOP STEAMER - HEATING ELEMENT
HEATING ELEMENT
Disconnect the electrical power to the machine and follow lockout / tagout
procedures.
REMOVAL AND REPLACEMENT
1.Turn off machine to drain steam generator tank.
Allow steamer to complete drain cycle.
A.Turn off water supply.
2.Remove RIGHT SIDE PANEL and TOP
COVER.
3.Note heating element wire connection points
then disconnect heating element lead wires from
Limiting contactor [1] Fig. 49 and Regulating
contactor [2] Fig. 49.
Fig. 49
4.Remove vent hose [1] Fig. 50 from sensor tube
and vent tube.
Fig. 50
5.Position high-limit thermostat capillary tube [1]
Fig. 51 to facilitate heating element removal.
Avoid creating sharp bends or kinks in the
capillary tube.
6.Remove screws and lock washers [2]
(qty.10) securing heating element [3] Fig. 51 to
tank.
Fig. 51
Fig. 51
7.Pull heating element out of steam generator tank.
8.Note mounting position of high-limit bulb then
F45559 (0615)Page 24 of 57
remove bulb from heating element.
A.Remove high-limit capillary tube
compression fitting [1] Fig. 52 then remove
high-limit capillary tube and bulb [2] Fig. 52
from heating element.
Page 25
C24EA-LWE SERIES COUNTERTOP STEAMER - HEATING ELEMENT
Fig. 52
NOTE: Install a new gasket when reassembling
steam generator tank. Temporarily secure gasket in
place with RTV 109.
9.Remove gasket from steam generator tank.
A.Clean remaining sealant from top lip of
steam generator tank.
NOTE: Refer to HIGH-LIMIT THERMOSTAT for
proper placement of capillary bulb.
10. Reassemble parts removed in reverse order of
removal. Tighten heating element screws evenly
to 70 in-lbs. Follow tightening sequence pattern
as shown in Fig. 53 (top view of heating element
shown).
DIAGNOSTIC CHECKS
Certain procedures in
this section require electrical test or
measurements while power is applied
to the machine. Exercise extreme
caution at all times and follow Arc Flash
procedures. If test points are not easily
accessible, disconnect power and
follow Lockout/Tagout procedures,
attach test equipment and reapply
power to test.
1.Check voltage across heating element wires at
Limiting (1CON) and Regulating (2CON)
contactor load terminals and verify against data
plate voltage as outlined in the steps below. See
WIRING DIAGRAM - HEATING ELEMENTS for
connections.
A.Voltage should be measured after PID
controller has energized solid state
contactor (3CON) during initial heat up
(longest ON time); or during temperature
recovery after door has been opened to
allow cooking compartment to cool down
then closed (timer must be on).
B.When temperature in the sensor tube (vent)
reaches approximately 180°F, the PID
controller will signal the solid state contactor
(3CON) to begin pulsing power to the
heating elements to reduce energy use. If
voltage is measured during the pulsing
state, the meter readings will not be steady
for a good reading.
Fig. 53
11. Check steamer for proper operation and leaks
around heating element.
2.If voltage is correct, check current draw (step 3).
If voltage is not correct, check the following:
A.Voltage supply to steamer at terminal block.
B.Fuses or breakers blown.
C.Power to contactor coils (Limiting 1CON)
(Regulating 2CON).
D.Limiting (1CON) or Regulating (2CON)
contactors not pulling in. (Mechanical).
E.Solid State Contactor (3CON) not energized
by PID controller to provide power to the
load contacts on regulating contactor
(2CON).
1)Verify PID controller operation as
outlined under Diagnostic Test.
Page 25 of 57F45559 (0615)
Page 26
C24EA-LWE SERIES COUNTERTOP STEAMER - HEATING ELEMENT
2)Check control signal wiring between
PID controller and solid state contactor
(3CON); and ensure ground wire is
connected to solid state contactor
(3CON). See WIRING DIAGRAM HEATING ELEMENTS for
connections.
3)Verify LED (green) [1] Fig. 54 on Solid
State contactor (3CON) is lit during
heating. LED will be constantly lit
during initial heat up and temperature
recovery after door has been opened
to allow cooking compartment cool
down then closed (timer must be on
and door closed). LED will blink to
indicate Solid State contactor (3CON)
is pulsing power to the load contacts on
regulating contactor (2CON).
B.When temperature in the sensor tube (vent)
reaches approximately 180°F, the PID
controller will signal the solid state contactor
(3CON) to begin pulsing power to the
heating elements to reduce energy use. If
current draw is measured during the pulsing
state, the meter readings will not be steady
for a good reading.
4.If current is correct, then heating element is ok. If
current is not correct, check element resistance
(step 5).
5.Disconnect power to machine.
6.Remove one lead wire of each heating element
from the Regulating contactor (2CON) (T1, T2,
T3). Check individual element resistance
between heating element lead wire and load
terminal on Limiting contactor (1CON) using a
VOM. Compare resistance readings to the
values in table below. See WIRING DIAGRAM HEATING ELEMENTS for connections.
A.If resistance readings are not correct,
replace heating element as outlined under
REMOVAL AND REPLACEMENT.
NOTE: Values in table are nominal. Tolerance is ±10
%.
7.Check steamer for proper operation.
Notes on Heating elements connected per
Fig. 54
3.Check current draw (amps) through heating
element lead wires using an amp clamp meter
and compare them to the values listed in table as
outlined in the steps below.
A.Full load amps should be measured when
PID controller has energized solid state
contactor (3CON) during initial heat up
(longest ON time); or during temperature
recovery after door has been opened to
allow cooking compartment cool down then
closed (timer must be on).
MODELVOLTAGETOTAL kW
3 Pan208*8.510.220.3
3 Pan240**8.511.820.3
3 Pan480Y/277***8.510.227.1
5 Pan208*1518.111.5
5 Pan240**1520.911.5
5 Pan480Y/277***1518.015.4
CURRENT PER
ELEMENT
machine voltage listed in table below:
•*All four heating elements are connected.
•**Three heating elements connected (fourth
element is not connected).
•***Heating elements of 480V machines are
connected in Wye configuration for 277V across
each element.
RESISTANCE PER ELEMENT
(OHMS)
F45559 (0615)Page 26 of 57
Page 27
C24EA-LWE SERIES COUNTERTOP STEAMER - WATER LEVEL CONTROL COMPONENTS
WATER LEVEL CONTROL COMPONENTS
WATER LEVEL CONTROL -
OPERATION
Low Level Cut-Off & Differential Control
The steamer is equipped with three water level
sensing probes (high, low and low level cut-off) and a
water level control board Fig. 55. The water level
control board performs two functions: 1) Provide low
level cut-off protection to shut off the heat source in
case the water level drops below the low level cut-off
(LLCO) probe. 2) Perform as a differential level control
to maintain the water level between the low and high
water level probes.
The water level control (WLC) board has input voltage
(120VAC) across terminals 11 and 12 which powers
the primary side of the transformer. See schematic
diagram of the water level control circuit Fig. 56. On
one side of the transformer secondary, power is
provided to the control by a series path through
chassis ground (terminal 10). The other side of the
transformer secondary (12VAC) is attached to the
probe that directs power to the other side of WLC
board relay coils (LLCO and HL) and to the inverse
latching relay (ILR) electronic circuit on the WLC
board. As water enters the generator, it becomes part
of the WLC board circuit. When the water level in the
generator reaches a probe, that circuit is completed.
energized and locked through the low level probe (LL)
and ILR-1 contacts. With ILR-2 contacts open, HL
relay is de-energized and the HL LED goes out. With
the HL-1 contacts open, the fast fill solenoid is deenergized, stopping the flow of water into the
generator.
When the water level drops below the low level (LL)
probe, power is removed from the inverse latching
relay, the HL relay energizes through ILR-2 and HL
contacts change state. The slow fill solenoid is
energized through HL-1 to refill the generator and the
HL LED is lit. The HL relay and LED will toggle on and
off during a cooking cycle as needed.
The inverse latching relay of the WLC board is deenergized, leaving the ILR-1 (N.O.) and ILR-2 (N.C.)
contacts in their shelf state.
When the main power switch is turned on, power is
supplied to the WLC board which energizes the high
level (HL) relay, closes HL-1 normally open contacts,
and illuminates the HL relay LED. With the HL-1
contacts closed, the fast fill solenoid is energized and
water begins filling the generator.
When the water level reaches the low level cut-off
(LLCO) probe, the LLCO relay is energized and
illuminates the LLCO LED. With the LLCO-1 contacts
closed, the heat source can be energized provided the
auxiliary control(s) in the heating circuit are satisfied.
The LLCO relay will remain energized and its LED will
stay lit until the water level in the generator drops
below the LLCO probe.
When the water level reaches the low level (LL) probe,
power to terminal 2 on the WLC board is present but
no switching occurs.
After the water level reaches the high level (HL) probe,
the inverse latching relay of the WLC board is
Fig. 55
Item
Description
No.
1Ground
2Low Level (L) Probe Connection
3High Level (H) Probe Connection
4Low Level Cut-Off (LLCO) Probe Connection
5L1 Incoming Voltage
6L2 Incoming Voltage
7Relay (LLCO) and Contacts
8LLCO LED
9Relay (HL) and Contacts
10HL LED (Fill)
Page 27 of 57F45559 (0615)
Page 28
C24EA-LWE SERIES COUNTERTOP STEAMER - WATER LEVEL CONTROL COMPONENTS
Fig. 57
3.Note electrical wiring connection points then
disconnect lead wires from water level control
board (WLC). Refer to the machine wiring
diagram when installing water level control
board.
Fig. 56
WATER LEVEL CONTROL BOARD
Disconnect the
electrical power to the machine and
follow lockout / tagout procedures.
Certain components in this system are
subject to damage by electrostatic discharge during
field repairs. A field service grounding kit is available
to prevent damage. The field service kit must be used
anytime the control board is handled.
1.Remove RIGHT SIDE PANEL.
2.Squeeze tab on plastic standoff to release circuit
board from standoff. Water level control board is
secured with pins in five locations.
4.Reassemble parts and wiring removed in reverse
order of removal.
5.Check steamer for proper operation.
WATER LEVEL PROBES
Disconnect the
electrical power to the machine and
follow lockout / tagout procedures.
1.Remove
COVER.
2.Note location of wires then disconnect from water
level probes [1] high level, [2] low level, [3] low
level cut off as shown in Fig. 58.
3.Remove probes from probe housing assembly.
RIGHT SIDE PANEL and TOP
F45559 (0615)Page 28 of 57
Page 29
C24EA-LWE SERIES COUNTERTOP STEAMER - WATER LEVEL CONTROL COMPONENTS
Fig. 58
WATER LEVEL PROBE ELECTRICAL
CONNECTIONS
Item
Number
1H# 5A - Blue
2L
3LLCO# 7C - Red
4
(not shown)
NOTE: Probes should be cleaned thoroughly.
Remove all accumulated deposits from insulator using
a soft cloth. Do not use anything abrasive on
insulators. If probes are dirty, delime steam generator
tank after assembling.
NOTE: When installing, apply thread sealant to pipe
threads.
4.Reverse procedure to install.
5.Check for proper operation.
Water
Level
Controller
G
(ground
connection
at tank)
Wiring
# 6B Yellow
# 8 - Green Ground
Water
Level
Probe
HL - High
Level Probe
LL - Low
Level Probe
LLCO - Low
Level Cut
Off
FILTERED AND NON-FILTERED
WATER SOLENOID VALVES
Disconnect the
electrical power to the machine and
follow lockout / tagout procedures.
NOTE: The filtered and non-filtered water solenoid
valves are constructed as dual water valve
assemblies. To differentiate between the fast and slow
fill valves, hold the dual water valve assembly with the
inlet up and the outlets facing forward. The fast flow
valve is the left valve and the slow flow valve is the
right valve. The two dual assemblies used on the
steamer have different flow rates and should not be
interchanged.
DUAL WATER VALVE
DUAL WATER VALVE FLOW RATES
Valve Type
Fill (Filtered
Water)
Condensate
(NonFiltered
Water)
Filtered Water Solenoid Valve
Machine
Type
3 & 5 Pan4.8.15
3 - Pan4.8.75
5 - Pan4.81.35
Flow Rate (GPM)
Fast Flow
Valve
Slow Flow
Valve
1.Turn off machine to drain steam generator tank.
Allow steamer to complete drain cycle.
A.Turn off water supply.
2.Disconnect the incoming filtered water hose to
machine.
3.Remove the REAR PANEL.
Page 29 of 57F45559 (0615)
Page 30
C24EA-LWE SERIES COUNTERTOP STEAMER - WATER LEVEL CONTROL COMPONENTS
4.Remove the screws securing the solenoid valve
to the back plate.
Fig. 60
5.Pull solenoid valve toward right side of machine
enough to access electrical connections.
A.Note connection points of electrical wires
then disconnect wires from solenoid valve.
B.Disconnect hoses from solenoid valve then
remove solenoid valve from steamer.
4.Note connection points of electrical connections
then disconnect wiring from solenoid valve.
VIEW FROM LEFT SIDE OF STEAMER
5.Remove the screws securing non-filtered cold
water solenoid valve to back plate.
6.Note hose connections to solenoid valve then
disconnect hoses from valve.
A.Remove solenoid valve from steamer.
7.Reassemble parts removed in reverse order of
removal.
Fig. 61
6.Reassemble parts removed in reverse order of
removal.
7.Verify that the filtered water supply is connected
to the input of the filtered water solenoid valve.
8.Check steamer for leaks and proper operation.
Non-Filtered Cold Water Solenoid Valve
1.Turn off machine to drain steam generator tank.
Allow steamer to complete drain cycle.
A.Turn off water supply.
2.Disconnect incoming water hose to non-filtered
cold water solenoid valve.
3.Remove LEFT SIDE PANEL.
A.Connect the outputs of the non-filtered
water cooling solenoid to the drain box and
Tee mounted to the drain valve under the
steam generator.
8.Verify that the filtered water supply is connected
to the input of the filtered water solenoid valve.
9.Check steamer for leaks and proper operation.
MOTORIZED DRAIN VALVE
Disconnect the
electrical power to the machine and
follow lockout / tagout procedures.
1.Turn steamer off by using the on/off switch on the
front panel of steamer.
A.Allow steamer to complete drain cycle.
B.If motorized drain valve has malfunctioned
and the tank will not drain normally, refer to
Drain Tank Manually.
Drain Tank Manually
1.Turn off water supply to steamer.
F45559 (0615)Page 30 of 57
Page 31
C24EA-LWE SERIES COUNTERTOP STEAMER - WATER LEVEL CONTROL COMPONENTS
2.Disconnect power to steamer allowing time for
water in steam generator tank to cool to 140°F
before attempting to manually open drain valve.
3.Remove RIGHT SIDE PANEL.
4.Locate the motorized drain valve [1] Fig. 63 found
at lower right side of steam generator tank.
B.Return manual drain override knob to the
closed position by rotating the knob 90° CW
(slot in horizontal position).
Removal
1.Turn off water supply to steamer.
2.Remove the RIGHT SIDE PANEL and REAR
PANEL for added accessibility.
3.Press in on spring catch [1] Fig. 65 and hold down
to release from locking posts on the valve body
then lift motorized control assembly [2] Fig. 65 off
the valve.
Fig. 63
5.Push in on the manual drain override knob to
disengage the gear set.
A.Rotate knob 90° CCW [1] Fig. 64 to
manually open the drain valve. Turning knob
such that the slot in knob is in a vertical
orientation indicates the drain valve is open.
If slot in knob is in a horizontal orientation,
the drain valve is closed.
Fig. 65
4.Note location of electrical connections then
disconnect electrical wiring from motorized
control assembly.
NOTE: The two electrical plugs on the motorized
control assembly are identical. If the electrical wiring
is not connected correctly, the motorized drain valve
will not function.
5.Disconnect the drain flush hose [1] Fig. 66 and
drain hose [2] Fig. 66 from the Tee fittings located
below drain valve.
Fig. 64
Page 31 of 57F45559 (0615)
Page 32
C24EA-LWE SERIES COUNTERTOP STEAMER - WATER LEVEL CONTROL COMPONENTS
Fig. 66
6.Remove drain valve body from steam generator
tank.
7.Separate the Tee and pipe nipple from drain
valve body for installation on replacement
motorized drain valve.
Fig. 67
9.Verify On/Off switch is in the off position and the
motorized drain valve is closed before applying
power to steamer.
NOTE: When power is applied and power switch is
off the steamer will enter a drain cycle.
10. Check steamer for proper operation and leaks
around drain valve.
8.Reassemble parts removed in reverse order.
Apply pipe thread sealant to threads of plumbing
connections.
NOTE: When installing motorized control assembly,
manually turn flat of "D" shaped stem down to close
the drain valve [1] Fig. 67 and align with "D" shape
fitting on motorized control assembly [2] Fig. 67. Install
motorized control assembly in the closed position (slot
in manual knob horizontal). If motorized drain valve is
in the open position (slot in manual knob vertical)
when power is applied to the steamer and the power
switch is on, motorized drain valve will not close and
the fill water will flow through the tank and into the
drain.
F45559 (0615)Page 32 of 57
Page 33
C24EA-LWE SERIES COUNTERTOP STEAMER - SWITCHES, LIGHTS, BUZZER AND SOLENOIDS
SWITCHES, LIGHTS, BUZZER AND SOLENOIDS
ON/OFF SWITCH
Disconnect the
electrical power to the machine and
follow lockout / tagout procedures.
1.Remove RIGHT SIDE PANEL.
2.Locate the on/off switch [1] Fig. 68 mounted to
the front panel.
Fig. 69
Fig. 68
3.Disconnect electrical plug from switch.
4.Remove switch from front panel.
5.Reassemble parts removed in reverse order.
INDICATOR LIGHT ASSEMBLY
Disconnect the
electrical power to the machine and
follow lockout / tagout procedures.
3.Disconnect electrical plug from indicator lights.
4.Remove indicator light assembly from the front
panel.
5.Reassemble parts removed in reverse order.
DOOR SWITCH
Disconnect the
electrical power to the machine and
follow lockout / tagout procedures.
Removal
1.Remove
2.Open cooking compartment door.
3.Note wiring connections and disconnect
electrical wiring from switch.
RIGHT SIDE PANEL.
NOTE: The indicator light assembly contains the
green ready lamp and red cook lamp.
1.Remove
2.Locate the indicator light assembly [1] Fig. 69
mounted to front panel.
RIGHT SIDE PANEL.
Page 33 of 57F45559 (0615)
Page 34
C24EA-LWE SERIES COUNTERTOP STEAMER - SWITCHES, LIGHTS, BUZZER AND SOLENOIDS
4.Check steamer for proper operation.
5.Reinstall RIGHT SIDE PANEL.
PRESSURE SWITCH (NON-
ADJUSTABLE)
Disconnect the
electrical power to the machine and
follow lockout / tagout procedures.
NOTE: Steamers built June 2015 and later.
Fig. 70
4.Remove switch from door switch mounting
bracket. Retain hardware.
Installation
1.Verify E-clip is installed on door switch linkage in
groove nearest front panel (if two grooves in
linkage are present).
Removal
1.Turn off machine to drain steam generator tank.
Allow steamer to complete drain cycle.
A.Turn off water supply.
2.Remove
3.Locate pressure switch [1] Fig. 72 in the piping
that extends from the water level probe housing.
RIGHT SIDE PANEL.
Fig. 71
2.Loosely install door switch onto door switch
mounting bracket.
A.Close door.
B.Push switch up against switch linkage as far
as possible.
C.Tighten switch mounting hardware.
3.Check door switch operation.
A.Set meter to measure resistance and place
meter leads across the COMMON and
NORM OPEN terminals of switch. With door
closed, meter should indicate a closed
circuit.
B.Open door. Meter should indicate an open
circuit as door is opened.
F45559 (0615)Page 34 of 57
4.Disconnect electrical wiring to pressure switch.
5.Remove pressure switch from piping.
6.Reassemble parts removed in reverse order.
7.Check for proper operation.
Check
1.Turn off machine to drain steam generator tank.
2.Remove RIGHT SIDE PANEL.
Fig. 72
A.Apply pipe thread sealant to threads of
pressure switch before installation.
Allow steamer to complete drain cycle.
A.Turn off water supply.
Page 35
C24EA-LWE SERIES COUNTERTOP STEAMER - SWITCHES, LIGHTS, BUZZER AND SOLENOIDS
NOTE: Pressure can be checked using the small air
pocket that exists between the delime port cap and
water level probe housing in the delime hose. Make
certain that no leaks exist in generator tank or
pressure gauge fittings.
NOTE: When temperature in the sensor tube (vent)
reaches approximately 180°F, the PID controller will
signal the solid state contactor (3CON) to begin
pulsing power to the heating elements to reduce
energy use.
3.Remove cap from delime port [1] Fig. 73 and
install pressure gauge [2] Fig. 73. See TOOLS.
Fig. 74
6.While observing pressure gauge, temporarily
clamp steam outlet hose to close it off. Use
adjustable plyers or other method for clamping
hose.
NOTE: If pressure should rise above 6.0 psi when
performing check, release clamp on steam outlet
hose. Pressure switch is malfunctioning and should be
replaced.
Fig. 73
4.Close cooking compartment door.
5.Turn steamer on.
A.Set timer for approximately 10 minutes.
B.Wait for full steam production to stabilize.
Monitor the temperature display on the PID
controller. After the temperature passes
195°F, wait approximately 5 minutes then
continue with procedure.
C.Observe pressure gauge Fig. 74 as steam
is being generated. Gauge should level out
at approximately 1.25 to 2.0 psi, but will
oscillate with respect to fill water entering
generator tank.
NOTE: Operating pressures will vary slightly between
steamer being serviced and gauge used.
NOTE: With steam outlet house clamped off, the
temperature in sensor tube will drop rapidly. The PID
controller will call for heat and energize the solid state
contactor at 100% ON time until clamp is released and
sensor tube temperature approaches 180°F to begin
pulsing power to heating elements again.
A.Listen for the Limiting and Regulating
contactors to release indicating that
pressure switch contacts have opened. The
correct range for pressure switch cut out is
between 4.0 to 6.0 psi.
B.Release clamp from steam outlet hose.
Listen for switch contacts to close
(contactors will energize) and record
pressure reading.
C.Repeat clamping of steam outlet hose a
total of three times to find the average cutout pressure.
D.If cut-out pressure pressure is outside range
listed, install a replacement pressure switch.
E.If cut-out pressure is within specifications,
turn steamer off. Allow time for steamer to
drain.
7.Remove test gauge and reinstall delime cap.
Page 35 of 57F45559 (0615)
Page 36
C24EA-LWE SERIES COUNTERTOP STEAMER - SWITCHES, LIGHTS, BUZZER AND SOLENOIDS
PRESSURE SWITCH
(ADJUSTABLE)
Disconnect the
electrical power to the machine and
follow lockout / tagout procedures.
Certain procedures in
this section require electrical test or
measurements while power is applied
to the machine. Exercise extreme
caution at all times and follow Arc Flash
procedures. If test points are not easily
accessible, disconnect power and
follow Lockout/Tagout procedures,
attach test equipment and reapply
power to test.
NOTE: Steamers built before June 2015.
Removal
1.Turn off machine to drain steam generator tank.
Allow steamer to complete drain cycle.
A.Turn off water supply.
2.Remove
RIGHT SIDE PANEL.
B.Verify Mylar™ cover [1] Fig. 76 is in position
covering electrical connections.
Fig. 76
NOTE: Refinement of pressure switch cut out setting
is found under Adjustment. Always check and adjust
pressure switch setting whenever pressure switch is
being serviced.
C.If pressure switch is being replaced, make
an initial pressure switch setting by aligning
the top surface of adjustment wheel [1] Fig.
77 with the 5 psi reference scale mark [2]
Fig. 77 on pressure switch.
3.Locate pressure switch [1] Fig. 75 in the piping
that extends from the water level probe housing.
Fig. 75
4.Disconnect electrical wiring to pressure switch.
5.Remove pressure switch from piping.
6.Reassemble parts removed in reverse order.
A.Apply pipe thread sealant to threads of
pressure switch before installation.
Fig. 77
7.Perform pressure switch Check.
NOTE: Pressure can be checked with the small air
pocket that exists between the delime port cap and
water level probe housing in the delime hose. Make
certain that no leaks exist in generator tank or
pressure gauge fittings.
NOTE: When temperature in the sensor tube (vent)
reaches approximately 180°F, the PID controller will
signal the solid state contactor (3CON) to begin
pulsing power to the heating elements to reduce
energy use.
F45559 (0615)Page 36 of 57
Page 37
C24EA-LWE SERIES COUNTERTOP STEAMER - SWITCHES, LIGHTS, BUZZER AND SOLENOIDS
Check
1.Turn off machine to drain steam generator tank.
Allow steamer to complete drain cycle.
A.Turn off water supply.
2.Remove RIGHT SIDE PANEL and TOP
COVER.
3.Place top cover on top of steamer to enable
viewing of pressure switch scale from hinge side
of steamer. Connect delime hose to delime port
fitting.
4.Remove cap from delime port [1] Fig. 78 and
install pressure gauge [2] Fig. 78. See TOOLS.
B.Wait for full steam production to stabilize.
This is accomplished by allowing
approximately five cycles of fill to occur once
steam is being produced by the generator
tank. Observe LED on water control board
to count cycles.
NOTE: Operating pressures will vary slightly between
steamer being serviced and gauge used.
C.Observe pressure gauge Fig. 80 once
steam begins to be generated. Gauge
should level out at approximately 1.25 to 2.0
psi, but will oscillate with respect to fill water
entering generator tank.
Fig. 78
5.Close cooking compartment door.
6.Mark one tooth of pressure switch adjustment
wheel Fig. 79 and make a second mark straight
down onto the body of pressure switch to aid in
identifying position of wheel.
Fig. 79
7.Turn steamer on.
A.Set timer for approximately 10 minutes.
Fig. 80
NOTE: If pressure should rise above 5.0 psi when
performing check, release clamp on steam outlet
hose. Pressure switch is out of tolerance and must be
adjusted. Refer to Adjustment for procedure.
NOTE: With steam outlet house clamped off, the
temperature in sensor tube will drop rapidly. The PID
controller will call for heat and energize the solid state
contactor at 100% ON time until clamp is released and
sensor tube temperature approaches 180°F to begin
pulsing power to heating elements again.
8.While observing pressure gauge, temporarily
clamp steam outlet hose to close it off. Use
adjustable plyers or other method for clamping
hose.
A.Listen for the Limiting and Regulating
contactors to release indicating that
pressure switch contacts have opened. The
correct range for pressure switch cut out is
between 4.5 to 4.7 psi.
B.Release clamp from steam outlet hose.
Listen for switch contacts to close
(contactors will energize) and record
pressure reading.
Page 37 of 57F45559 (0615)
Page 38
C24EA-LWE SERIES COUNTERTOP STEAMER - SWITCHES, LIGHTS, BUZZER AND SOLENOIDS
C.Repeat clamping of steam outlet hose a
total of three times to find the average cutout pressure.
D.If pressure is outside tolerance (4.5 to 4.7
psi), adjustment is necessary. Refer to
Adjustment.
E.If cut-out pressure is within specifications,
turn steamer off. Allow time for steamer to
drain.
9.Remove test gauge and reinstall delime cap.
Adjustment
1.Allow full steam production to stabilize. This is
accomplished by allowing approximately five
cycles of fill to occur once steam is being
produced by the generator tank. Observe LED on
water control board to count cycles.
NOTE: Make small incremental adjustments (1/8 turn
of toothed adjustment wheel) when adjusting cut-out
pressure.
2.Referring to cut-out pressure recorded in Check
procedure, turn adjustment wheel [1] Fig. 81 to
bring cut-out pressure into tolerance.
VACUUM RELIEF SOLENOID
Disconnect the
electrical power to the machine and
follow lockout / tagout procedures.
1.Turn off machine to drain steam generator tank.
Allow steamer to complete drain cycle.
A.Turn off water supply.
2.Remove RIGHT SIDE PANEL.
3.Locate vacuum relief solenoid [1] Fig. 82 in the
plumbing line that extends from water level probe
housing.
4.Disconnect hose [2] Fig. 82 from solenoid valve.
5.Disconnect electrical wiring [3] Fig. 82 from
solenoid coil.
6.Remove retaining clip [4] Fig. 82 securing coil to
valve body then remove coil and spring washer.
7.Rotate valve body clockwise to remove from the
pipe nipple in the plumbing line.
8.Note orientation of hose barb elbow at the top of
valve body then remove pipe fittings from valve
body for use on replacement valve.
9.Reassemble parts removed in reverse order.
NOTE: Apply thread sealant to threads of piping
before assembly.
Fig. 81
B.Check cut-off pressure after making
adjustment. Repeat Check and Adjustment
as necessary until cut-out pressure is within
4.5 to 4.7 psi.
F45559 (0615)Page 38 of 57
NOTE: When installing, position valve body with the
direction arrow pointing down so the outlet (OFF) side
of valve body is connected to the water level probe
housing plumbing line.
10. Check for proper operation.
Page 39
C24EA-LWE SERIES COUNTERTOP STEAMER - SWITCHES, LIGHTS, BUZZER AND SOLENOIDS
BUZZER
Disconnect the
electrical power to the machine and
follow lockout / tagout procedures.
1.Remove RIGHT SIDE PANEL.
2.Locate the buzzer [1] Fig. 83 mounted to the door
switch mounting bracket.
Fig. 84
6.Remove buzzer from door switch mounting
bracket.
Fig. 83
3.Disconnect electrical wiring from the buzzer and
door switch.
4.Remove the mounting nut and lockwasher
securing door striker [1] Fig. 84 and the door
switch mounting bracket to front panel.
5.Remove the remaining mounting nut and
lockwasher [2] Fig. 84 securing door switch
mounting bracket to front panel then remove door
switch mounting bracket with electrical
components attached.
7.Reassemble parts removed in reverse order.
Perform DOOR LATCH ADJUSTMENT.
Page 39 of 57F45559 (0615)
Page 40
C24EA-LWE SERIES COUNTERTOP STEAMER - STEAM GENERATOR TANK
STEAM GENERATOR TANK
Disconnect the electrical power to the machine and follow lockout / tagout
procedures.
REMOVAL AND REPLACEMENT
1.Turn off machine to drain steam generator tank.
Allow steamer to complete drain cycle.
A.Turn off water supply.
2.Remove RIGHT PANEL, TOP COVER and
REAR PANEL.
3.Disconnect the fill hoses (fast & slow) [1] Fig.
85 from water inlet fittings on steam generator
tank. Remove pipe tee [2] Fig. 85 from generator
tank and retain for reuse.
Fig. 85
4.Remove HOLD THERMOSTAT from steam
generator tank.
NOTE: It is not necessary to disconnect the electrical
wiring to the motorized drain valve in order to remove
the motor from valve.
5.Remove drain valve motor as outlined under
MOTORIZED DRAIN VALVE.
6.Disconnect drain flush hose [1] Fig. 86 and drain
hose [2] Fig. 86 from the pipe tee fittings located
below the drain valve.
Fig. 86
7.Remove drain valve as outlined under
MOTORIZED DRAIN VALVE.
9.Remove delime hose [2] Fig. 87 from steam
generator tank.
10. Remove hose [3] Fig. 87 from the vacuum relief
solenoid.
F45559 (0615)Page 40 of 57
Page 41
C24EA-LWE SERIES COUNTERTOP STEAMER - STEAM GENERATOR TANK
14. Remove VACUUM RELIEF SOLENOID and
PRESSURE SWITCH (NON-ADJUSTABLE)
from the piping that extends from the water level
probe housing.
15. Remove WATER LEVEL PROBES from probe
housing.
16. Remove piping that extends from the water level
probe housing and retain for reuse.
17. Remove gasket from steam generator tank and
discard the gasket.
NOTE: Install a new gasket when reassembling
steam generator tank. Temporarily secure gasket in
place with RTV 109.
A.Clean remaining sealant from top lip of
steam generator tank.
Fig. 87
NOTE: It is not necessary to remove high-limit
capillary tube from heating element or disconnect
heating element wires when removing steam
generator tank. When lifting the heating element out
of steam generator tank, flip the element over and
place it on top of cooking compartment with the top
surface of the mounting plate toward rear of machine.
13. Remove elbow fitting [2] Fig. 88 for the delime
hose from steam generator tank and retain for
reuse.
18. Remove bolts Fig. 89 (qty. 3) securing steam
generator tank to the machine frame (3rd bolt opposite side of tank). Remove tank from
machine.
Fig. 89
19. When installing steam generator tank, install
insulation around tank sides and on the bottom.
Secure into position using high temperature
aluminum foil tape.
20. Reinstall parts removed in reverse order of
removal. Apply thread sealant to all pipe threads
connected to the steam generator tank.
Fig. 88
21. Torque heating element bolts and follow
tightening sequence as outlined under HEATING
ELEMENT.
22. Check steamer for proper operation. Inspect
plumbing connections and gasket seal on steam
generator tank for leaks.
Page 41 of 57F45559 (0615)
Page 42
C24EA-LWE SERIES COUNTERTOP STEAMER - ELECTRICAL OPERATION
ELECTRICAL OPERATION
COMPONENT FUNCTION
PID Controller ........ Monitors input signal from temperature sensor mounted in the sensor tube and regulates
solid state contactor (3CON) as needed to maintain tank temperature for steam
generation. On initial startup, the controller keeps the solid state contactor energized at
100% until temperature sensor approaches set point then begins pulsing power to the
contactor as needed to maintain tank temperature.
Temperature
Sensor ................
Solid State Contactor
(3CON) ................
Contactor, Limiting
(1CON) ................
Contactor, Regulating
(2CON) ................
Drain Valve, Motorized
(Ball type) .............
Element, Heating ..... Located in steam generator tank. Heats water to produce steam.
Fuse, (1FU) ........... Slow blow 4A fuse. Located on primary side of main transformer. Protects control circuitry
Fuse, (2FU) ........... Slow blow 4A fuse. Located on primary side of main transformer. Protects control circuitry
Light (3LT), Power .... Amber (AM) colored light. On when power switch is on (internal to power switch).
Light (2LT), Cook ..... Red (RD) colored light. On when hold thermostat is satisfied and door is closed and timer
Light (1LT), Ready .... Green (GN) colored light. On when hold thermostat is satisfied. Latches on when hold
J type thermocouple mounted in the sensor tube (vent). Provides input signal to PID
controller.
Modulates power to the tank heaters (through regulating contactor 2CON) when signaled
by the PID controller.
Connects one side of heating elements to incoming power. Energized whenever WLC
(LLCO) coil is energized and the high limit thermostat and pressure switch are both
closed.
Connects one side of heating elements to power. On constantly during cooking cycle.
Motorized control for opening and closing drain valve.
from over-currents.
from over-currents.
is set.
thermostat is satisfied.
Water Level Control
(WLC) Board ..........
Probe (H) ............. High water level probe connected to internal latch relay circuit of the water level control
Probe (L) .............. Low water level probe connected to internal latch relay circuit of the water level control
Probe (LLCO) ......... Low Level Cut-Off (LLCO) probe. Controls power to heating and timer circuitry. Controls
Relay (K1) ............ Controlled by hold thermostat. Enables timer circuit.
Relay (K2), LLCO ..... Low Level Cut-Off (LLCO) external relay. Only energized during drain. Controls Flush,
Relay (K3), Drain
Relay .................
Relay (K4) ............ Latches Ready light on.
F45559 (0615)Page 42 of 57
Controls water level by monitoring conditions of the 3 water level probes H, L and LLCO.
board. Water must reach this level before internal latch relay is energized.
board.
fast fill solenoid.
Fast Fill and Vacuum Relief solenoids.
Controlled by Time Delay Relay. Only energized during drain cycle. Controls WLC board
and LLCO relay K2 during the drain cycle. Disables heating and timer circuitry.
Page 43
C24EA-LWE SERIES COUNTERTOP STEAMER - ELECTRICAL OPERATION
Relay, Time Delay .... Controlled by the power switch. Output becomes active for 90 seconds when power
switch is turned to off. Only used during drain cycle.
Solenoid (1SOL),
Cooling ...............
Solenoid (2SOL),
Flush .................
Solenoid (3SOL), Fast
Fill ....................
Solenoid (4SOL), Slow
Fill ....................
Solenoid (5SOL),
Vacuum Relief ........
Switch (1S), Power ...Two position rocker switch that controls machine steam and drain operations. Internal
Switch (2S), Door ..... Plunger activated, switch is wired in series with timer. When switch is closed and timer
Switch (1PAS),
Pressure ..............
Thermostat (1TAS),
Condensate ...........
Controlled by the condensate thermostat. Mixes cold water with hot condensate water
from cooking chamber to reduce water temperature at drain.
On only during drain cycle. Mixes cold water with tank water before entering drain box.
Keeps drain hose clear of debris.
Initial tank fill at a fast rate. Used during last stage of drain cycle to flush drain opening
free of debris.
Secondary tank fill at a slow rate to prevent tank temperature from dropping rapidly.
Energized as necessary during operation to replenish water in tank.
Provides open air line for vacuum relief during drain cycle to prevent cooking chamber
flex.
power light (3LT) indicates when switch is on.
is set to a time or constant, regulating contactor will be energized 100% of the time once
ready light is on (hold thermostat satisfied).
Pressure cut-out protection. Cuts off electrical energy to the controls circuit if pressure
rises above the upper tolerance level for the switch.
Monitors temperature of water entering the facility drain system. Controls the cooling
solenoid during cooking operation and the cooling and flush solenoids during drain cycle
(135°F cut-in).
Thermostat (2TAS),
High-Limit ............
Thermostat (3TAS),
Hold ..................
Timer (1TR) ........... Used for timed cook cycles from 0 to 60 minutes. Professional models have a
Transformer (1T),
Main ..................
Transformer (2T),
Drain ..................
Buzzer ................ Creates audible signal when timed cook cycle is complete.
Protects against heating element over temperatures generally caused by tank boiling dry.
A capillary tube device. Bulb is mounted directly to the heating element and high-limit
body is mounted to a bracket on the frame rail (257°F cut-out).
Controls temperature of water in steam generator tank to 195°F (closes at 195°F).
CONSTANT position for continuous steam operation.
Step down transformer from line voltage to control voltage level (120 VAC).
Provides 24 VAC for motorized drain valve during drain cycle.
Page 43 of 57F45559 (0615)
Page 44
C24EA-LWE SERIES COUNTERTOP STEAMER - ELECTRICAL OPERATION
COMPONENT LOCATION
Electrical Control Panel - Front
Fig. 90
ITEM NO.DESCRIPTION
1PID Controller
2Time Delay Relay (TDR)
3Relay, K1
4Relay, K2
5Relay, K3
6Relay, K4
7Transformer (2T), Drain (120V in, 24V out)
8Fuses (1FU & 2FU)
9Terminal Block, Line Service
10Ground Lug
11Thermostat (2TAS), High Limit
12Contactor (2CON), Regulating
13Contactor (1CON), Limiting
14Transformer (1T), Main (Line voltage in, 120V out)
15Water Level Control (WLC) Board
F45559 (0615)Page 44 of 57
Page 45
C24EA-LWE SERIES COUNTERTOP STEAMER - ELECTRICAL OPERATION
Electrical Control Panel - Rear
Fig. 91
ITEM NO.DESCRIPTION
1Cooling Fan (supplied with Solid State Contactor)
2Solid State Contactor
3PID Temperature Controller
4Sensor Probe Connection, J Type Thermocouple
Page 45 of 57F45559 (0615)
Page 46
C24EA-LWE SERIES COUNTERTOP STEAMER - ELECTRICAL OPERATION
Water Level Control Board
Fig. 92
ITEM NO.DESCRIPTION
1Ground
2Low Level (L) Probe Connection
3High Level (H) Probe Connection
4Low Level Cut-Off (LLCO) Probe Connection
5L1 Incoming Voltage
6L2 Incoming Voltage
7Relay (LLCO) and Contacts
8LLCO LED (remains lit when low water level is satisfied)
9
10HL LED (Fill)
Relay (HL) and Contacts (remains lit when calling for
water)
F45559 (0615)Page 46 of 57
Page 47
C24EA-LWE SERIES COUNTERTOP STEAMER - ELECTRICAL OPERATION
Front Panel
Fig. 93
ITEM NO.DESCRIPTION
1Power Switch
2Indicator lights
3Timer
4Buzzer
5Door Switch
Page 47 of 57F45559 (0615)
Page 48
C24EA-LWE SERIES COUNTERTOP STEAMER - ELECTRICAL OPERATION
Steam Generator - Controls Side & Rear
Fig. 94
ITEM NO.DESCRIPTION
1Vacuum Relief Solenoid
2Pressure Switch
3Water Level Probes
4Heating Element
5Condensate Thermostat (out of view)
6Non-Filtered Water Solenoid Valve
7Filtered Water Solenoid Valve
8Motorized Drain valve
9Hold Thermostat
10High Limit Thermostat
F45559 (0615)Page 48 of 57
Page 49
C24EA-LWE SERIES COUNTERTOP STEAMER - ELECTRICAL OPERATION
Sensor Probe (Thermocouple)
ITEM NO.DESCRIPTION
1Sensor probe (J type thermocouple) (left side of steamer)
2Sensor tube
SEQUENCE OF OPERATION
Refer to the correct wiring diagram for model being
serviced when reviewing sequence of operation.
NOTE: If power switch is set to off when service
voltage is applied, steamer will enter the timed drain
cycle.
1.Conditions
A.Steamer connected to correct voltage.
1)120VAC potential across X1 & X2 on
secondary side of main transformer
(1T).
B.Steamer connected to water supply with
correct water requirements.
C.Power switch is in off position.
1)Time delay relay timed out. Timer has
no output on terminal 1.
D.Condensate thermostat (1TAS) open.
E.High limit thermostat (2TAS) closed.
F.Pressure switch (1PAS) closed.
G.Hold thermostat (3TAS) open.
H.Drain closed and steam generator tank
(referred to as tank) is empty.
Fig. 95
I.Steamer door open.
J.Timer is off.
K.Water level control (WLC) and tank properly
grounded.
L.PID controller and Solid State contactor
(3CON) are off.
2.Power switch (1S) is turned on.
A.Power light (3LT - Amber) illuminates.
B.X1 potential to L1 of WLC board.
1)120VAC across L1 & L2 of WLC board.
2)High level coil (HL) energized on WLC
board. HL LED on WLC board lights.
C.Fast Fill Solenoid (3SOL) energized through
N.C. contacts K3-1/5, N.C. contacts WLC
(LLCO) and N.C. contacts K2-5/1. Tank
begins to fill with water.
C24EA-LWE SERIES COUNTERTOP STEAMER - ELECTRICAL OPERATION
C.LLCO N.O. contacts close enabling timer
and heating element circuits.
4.Limiting contactor coil (1CON) and cooling fan on
the Solid State Contactor energize through N.C
K3-6/2 contacts.
5.Regulating contactor coil (2CON) and power to
the PID controller energize through N.C. contacts
K1-1/5.
6.Temperature measured in the sensor tube (vent)
is below PID controller set point. PID controller
signals solid state contactor (3CON) to modulate
power to the heating elements through regulating
contactor (2CON) load contacts. Tank water
heats.
7.Tank water reaches 195°F. Hold thermostat
(3TAS) contacts close.
A.Slow Fill Solenoid (4SOL) is energized
through closure of hold thermostat (3TAS)
and closed WLC (HL) N.O. contacts. Tank
continues to fill.
B.Relay K1 energizes.
1)Timer circuit is enabled through
closure of N.O. contacts K1-6/4 and
K1-5/3.
a.Relay K4 energizes - Latch circuit
is completed by closure of N.O.
contacts K4-5/3.
C.Slow Fill Solenoid (4SOL) de-energized by
opening of HL contacts on WLC board.
D.HL LED on WLC board turns off.
10. Timer knob set to CONSTANT for continuous
steam operation or Timer knob is turned to a
timed setting.
A.Power (120VAC) present to Door Switch
wire #19.
B.If Timer is set to a timed setting, Timer motor
is energized through closure of N.O.
contacts K1-6/4. Count down time begins
when door is closed.
11. Steamer door is closed.
A.Door Switch (2S) contacts close. Cook light
(2LT - Red) illuminates.
B.Regulating contactor and PID controller
remain energized as long as door is closed
and Timer is set to CONSTANT or time
remains on timed cycle.
C.Steam flows from the steam generator into
the cooking compartment to begin cooking
product. Uncondensed steam flows out of
the cooking compartment through the
compartment drain and up the sensor tube
(vent) where the temperature sensor is
mounted. The temperature sensor output is
monitored by the PID controller.
b.Ready light (1LT - green) lights.
2)Regulating contactor (2CON) and PID
controller de-energized when K1-1/5
N.C. contacts open.
a.The PID controller governs the
operation of the solid state
contactor (3CON) and provides
power to the load contacts on the
regulating contactor (2CON) to
power the heating elements.
Temperature in tank is maintained
at 195°F (min) by the hold
thermostat and PID controller set
point temperature of 209°F (max).
8.Water level reaches Low level (L) probe.
A.No action. The internal latching relay (ILR-1)
contacts are open.
9.Water level reaches high level (H) probe.
A.Internal latching relay (ILR) coil on WLC
board energizes.
B.High level (HL) coil de-energized by ILR-2
contacts opening.
F45559 (0615)Page 50 of 57
12. Under some conditions, the temperature of
13. Door opened during timed cook cycle.
As temperature in sensor tube approaches
set point, the PID controller signals the Solid
State Contactor (3CON) to reduce power to
the steam generator heating elements,
limiting the production of excess steam (unabsorbed energy). Reduced power to the
heating elements is achieved by the PID
controller signaling the Solid State
Contactor to pulse voltage to heating
elements.
condensate exiting the cooking compartment
and entering the drain box may exceed 135°F.
When this occurs:
A.Condensate thermostat closes and
energizes cooling solenoid (1SOL).
Condensate is cooled in drain box before
entering facility drain system.
A.Timer continues count down until time
equals zero even if steamer door is opened.
B.Regulating contactor (2CON) and PID
controller de-energize. Tank heat turns off.
Page 51
C24EA-LWE SERIES COUNTERTOP STEAMER - ELECTRICAL OPERATION
1)Cook light turns off.
14. Time reaches zero.
A.Buzzer is energized through N.O. contacts
K1-6/4 and Timer - 11/14.
1)Buzzer remains energized until timer
knob is turned to OFF, new time or
CONSTANT is selected or steamer is
turned off.
15. Power Switch (1S) pushed to off.
A.Power (3LT), Cook (2LT) and Ready (1LT)
lights turn off.
B.Time delay relay is energized through
terminals 2 & 3. Output (120VAC) on
terminal 1 for 90 seconds.
C.Time delay relay output energizes K3 coil.
1)X1 potential to L1 of WLC board
through N.O. contacts K3-3/5.
2)Relay K2 coil energized through WLC
N.O. contacts LLCO and N.O. contacts
K3-6/4.
A.Cooling Solenoid (1SOL) energized through
closure of Condensate Thermostat
contacts.
B.Flush Solenoid (2SOL) energized through
closure of N.O. contacts K2-3/5 and drain
valve N.O. contacts.
17. Tank water level drops below L probe.
A.Internal latching relay (ILR) de-energizes.
1)High level coil (HL) energized on WLC
board. HL LED on WLC board lights.
18. Tank water level drops below LLCO probe.
A.Relay K2 de-energized through opening of
WLC board LLCO N.O. contacts.
B.Vacuum Relief Solenoid (5SOL) energized
through N.C. contacts K2-2/6.
C.Fast Fill Solenoid (3SOL) energized through
WLC (LLCO) N.C. contacts and N.C.
contacts K2-5/1.
D.Flush Solenoid (2SOL) remains energized
through WLC (LLCO) N.C. contacts.
3)Heating element and timer control
circuits are disabled by opening of N.C.
contacts K3-6/2.
D.Power (120VAC) across primary of drain
transformer (2T). Motorized drain valve
energized. Drain valve opens and tank
begins to drain.
1)Drain valve N.O. contacts close.
E.Power removed from PID controller. Solid
State contactor (3CON) de-energized.
16. Condensate Thermostat (1TAS) reaches 135°F,
contacts close. Drain water temperature is
regulated through condensate thermostat.
19. Time Delay Relay time elapses.
A.Power (120VAC) removed from output of
Time Delay Relay terminal 1.
1)All Solenoids, coils and WLC board are
de-energized.
C24EA-LWE SERIES COUNTERTOP STEAMER - ELECTRICAL OPERATION
ELECTRICAL SYMBOLS DIAGRAM
Fig. 96
F45559 (0615)Page 52 of 57
Page 53
C24EA-LWE SERIES COUNTERTOP STEAMER - ELECTRICAL OPERATION
WIRING DIAGRAM - HEATING ELEMENTS
Fig. 97
Page 53 of 57F45559 (0615)
Page 54
C24EA-LWE SERIES COUNTERTOP STEAMER - ELECTRICAL OPERATION
Fig. 98
F45559 (0615)Page 54 of 57
Page 55
C24EA-LWE SERIES COUNTERTOP STEAMER - ELECTRICAL OPERATION
SCHEMATIC DIAGRAM
Fig. 99
Page 55 of 57F45559 (0615)
Page 56
C24EA-LWE SERIES COUNTERTOP STEAMER - TROUBLESHOOTING
TROUBLESHOOTING
TROUBLESHOOTING
NOTE: The PID controller performs a self-diagnostics test and displays program version such as "13.00" when
initially powered then reverts to the actual sensor probe temperature in the top display. If PID controller or sensor
probe is malfunctioning, an error code should display. If the code displayed is Er.i1, perform Sensor Probe Test
(thermocouple). If a different code is displayed, note the code and contact the appropriate Technical Support
department for further instructions.
SYMPTOMPOSSIBLE CAUSES
1.Unit not level.
2.Compartment drain screen obstructed.
Compartment leaks water or steam
around door.
Cold water condenser not operating
properly.
Steam generated inside cooking
compartment when timer is off.
Water or steam leaking inside panels.
Tank water level too high.
3.Drain line obstructed, undersized, exceeds 6 feet or not to an open
gap drain.
4.High water pressure to steamer (exceeds 60 psi).
5.Door gasket worn or damaged. Refer to GASKET for removal
procedure.
1.Flush Solenoid (2SOL) inoperative or plugged.
2.Lack of water supply.
3.Condensate thermostat (1TAS) stuck open.
4.Cooling Solenoid (1SOL) valve inlet screen clogged or malfunction.
1.Cycling thermostat (2TAS) or related heat control circuitry
malfunction.
2.Relay K1 malfunction.
1.Steam generator gasket not sealing.
2.Loose clamps around steam hose or hose malfunction; or loose
steam line plumbing connections.
3.Cooking compartment or steam generator malfunction.
1.Slow fill solenoid (4SOL) or fast fill solenoid (3SOL) does not shut
off.
2.High level probe malfunction (open circuit).
3.Water level control board inoperative (WLC).
1.Water supply not on.
2.Slow fill solenoid (4SOL) or fast fill solenoid (3SOL) not being
Tank does not fill.
F45559 (0615)Page 56 of 57
energized or plugged.
3.Water level control board malfunction (WLC).
4.Water level probes shorted to ground.
Page 57
C24EA-LWE SERIES COUNTERTOP STEAMER - TROUBLESHOOTING
SYMPTOMPOSSIBLE CAUSES
1.Dirty low level cut-off probe (shorted to ground) or low level cut-off
Heat coming on without water in tank.
(No error message on PID display)
Steamer will not heat.
probe wire grounded.
2.Limiting (1CON) or Regulating Contactor (2CON) malfunction.
3.WLC- LLCO contacts stuck closed. Water level controller (WLC)
malfunction.
1.No incoming voltage (circuit breaker tripped or fuses open).
2.Tank not filled (supply water off; fast fill solenoid clogged or
malfunction).
3.Power switch malfunction.
4.Water Level Control malfunction.
5.Relay (K1) malfunction.
6.High-limit thermostat open (2TAS).
7.Heating elements inoperative (open circuit).
8.PID controller not calling for heat to energize Solid State contactor
(3CON).
A.Sensor probe open or disconnected from PID controller.
Display cycles between:
1)Top row "----" and "Er.i1".
2)Bottom row "Attn" and "0.0".
B.Solid state contactor (3CON) malfunction.
9.Limiting contactor (1CON) or regulating contactor (2CON)
malfunction.
10. Hold thermostat open (3TAS).
11. Relay (K3) malfunction.
12. Water too pure for probes to properly conduct electricity.
Timer motor does not run.
Water running out of drain during fill.
Door not closing properly.
Door won’t open.1.Latch won’t release. Refer to Adjustment.
Buzzer not operating.
1.Relay K1-6/4 contacts not closing.
2.Timer malfunction.
1.Motorized drain valve stuck open.
2.Time delay relay malfunction.
3.Condensate thermostat (1TAS) malfunction.
1.Door latch assembly.
2.Striker adjustment.
1.Timer malfunction.
2.Buzzer malfunction.
Page 57 of 57F45559 (0615)
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.