Vtronix TE56M, TF56M Installation Manual

Vtronix
1
TE56M, TF56M
Thermostats
INSTALLATION MANUAL
APPLICATION
The TE56M and TF56M Thermostats provide universal replacement of single-stage, 24Vac (10 mA to 1.5A) thermostats used in electric, gas, and oil heating and cooling systems.
These thermostats are mercury free and require no batteries. The TE56M and TF56M use advanced proportional plus integral (P+I) control for optimum temperature
control and comfort.
Model Mounting System Selection Fan Selection Powering Method
TE56M Vertical COOL-OFF-HEAT ON-AUTO Power Stealing TF56M Horizontal COOL-OFF-HEAT ON-AUTO Power Stealing
SPECIFICATIONS
ELECTRICAL RATINGS
Power Supply Load Current Range
24 Vac nominal, 18-30 Vac, 50/60 HZ. 10 mA – 1.5A.
TEMPERATURE RATINGS
Temperature setting range
40 to 99 °F (4 to 37 °C)
Ambient temperature range
40 to 110 °F (4 to 43 °C)
Shipping temperature range
-20 to 120 °F (-29 to 49 °C)
OPERATING RELATIVE HUMIDITY
5 to 90% RH, non-condensing
CYCLE RATES
Cooling mode 4 Cycles per hour Heating mode 6 Cycles per hour
TF56M
TE56M
Fig. 1. TE56M and TF56M Thermostats.
Vtronix
2
INSTALLATION
Read these instructions thoroughly before installing product. Failure to follow these instructions could damage the product or cause a hazardous condition. Check the voltage and current ratings on the product to ensure that it is suitable for your application. Installer must be a trained, experienced service technician. Check product for proper operation after installation.
CAUTION
Damage to heating and cooling system may occur. Disconnect power from the equipment at the main breaker/fuse block while installing the thermostat.
Take out the front cover by sliding it to the right and remove. See Fig.3.
Mounting Location
Mount the thermostat approximately 5 ft. (1.5m) above the floor in a location that is free from direct sunlight, heat from appliances, hot or cold air from ducts, concealed pipes and chimneys, and drafts or dead spots behind doors or in corners. Do not mount on exterior wall, if possible. Failure to locate thermostat mounting as indicated will result in poor temperature control.
NOTE:
Level thermostat mounting is for appearance only and is not required for proper thermostat operation.
Using the thermostat base as a guide, mark two mounting holes on the wall. Drill two mounting holes. Thread the wires from the heating and cooling equipment through the wiring hole on the thermostat base. Holding the base in place on the wall, secure it to the wall using appropriately sized screws (Fig. 4).
Mount and Wire the Thermostat
Remove the locking screw at the side of the thermostat. Pull the temp. knob upward and remove it.
Fig. 2. Remove temperature setting knob.
Fig. 3. Remove thermostat cover.
Fig. 4. Mount thermostat on wall.