VSI PWM 2.1H-S25, PWM Series, PWM 5.25H-S25, PWM 3.5H-S25, PWM 7H-S25 User Manual

...
PWM SERIES
STATIC DIGITAL
AC AUTOMATIC VOLTAGE STABILISER
USER MANUAL
Thank you for purchasing a VSi PWM Series
Static Digital AC Automatic Voltage Stabiliser
1
IMPORTANT
PLEASE READ
This User / Operator Manual contains information concerning the safe and proper installation and operating procedures applicable to the PWM range of Single Phase Static Digital AC Automatic Voltage Stabilisers.
The Manual should be read in full before attempting to use, or operate the equipment.
If any problems are encountered with the procedures contained within this Manual then seek assistance from VSi or the distributor from whom you purchased the equipment.
Whilst every precaution has been taken to ensure the accuracy and completeness of this User Manual, VSi assumes no responsibility and disclaims all liabilities for damages resulting from misuse of this information or any error or omission.
Voltage Stabilisers International Limited
Tel: +44 (0) 345 504 6324
Web: http://www.VSi.uk.com
Email
Sales: Sales@VSi.uk.com General: Info@VSi.uk.com Support: Support@VSi.uk.com
PWM SERIES - User Manual
VSi-PWM-2018-06
http://www.VSi.UK.com
2
Table of Contents
1.1
Overview
…………………………………………………………………
……………..
3
1.2
Basic Principle of Op
eration
……………………………………
……………..
3
2.1
Input
………………………………………………………………………………………
4
2.2
Output
……………………………………………………………………………………
4
2.3
Metering, Status Indicators, Alarms & Communication
………….
5
2.4Protection
………………………………………………………………………………
5
2.5
Environment
…………………………………………………………………………..
6
2.6
Physical
………………………………………………………………………………….
6
2.7
Certification & Compliance
…………………………………………………….
6
2.8
Warranty
………………………………………………………………………………..
7
3.1
Introduction
…………………………………………………………………………..
8
3.2
General Installation and Usag
e
………………………………………………
8
4.1
Front View
…………………………………………………
……………………………
10
4.2
Rear View
……………………………………………………………………………….
1
2
4.3
Display View
…………………………………………………………………………..
1
5
5.1
Unpacking & Inspection
………………………………………………………...
185.2
Positionin
g
……………………………………………………………………………..
1
8
5.3
Hardwire Installation
……………………………………………………………..
1
9
5.4
Plug N Play Installation
…………………………………………………………..
20
5.5
Normal Operation
………………………………………………………………….
21
5.6
Manual Bypass Operation
……………………………………………………
…22
7.1
Warranty
………………………………………………………………………………..
2
7
7.2
Returns Procedure
…………………………………………………………………
2
8
Pages
1. Introduction ………………………………………………………………………. 3
2. General Specification ………………………………………………………… 4-7
3. Safety Instructions …………………………………………………………….. 8-9
4. Visual External Appearance ………………………………………………. 10-17
5. Installation & Operating Instructions ………………………………… 18-22
6. Troubleshooting ………………………………………………………………… 23-26
7. Warranty & Returns …………………………………………………………… 27-28
PWM SERIES - User Manual
VSi-PWM-2018-06
http://www.VSi.UK.com
3
1. Introduction
1.1 Overview
PWM SERIESmicroprocessor controlled Single Phase Static Digital Voltage Stabilisers automatically correct brownouts (by boosting low voltage) and over-voltages (by reducing high voltage). They are, designed to ensure the delivery of a stable and quality output voltage.
Being designed for many years of reliable service, VSi’s PWM models provide protection from incoming line voltage sags, spikes and surges / swells. As Static Digital solutions they are virtually maintenance free and offer an exceptional fast speed of correction, making them ideal for the most sensitive of electrical and electronic loads.
1.2 Basic Principle of Operation
PWM SERIES AC Voltage Stabilisers are designed around a traditional well proven ‘Buck / Boost’ design topology, utilising the latest in IGBT Power Devices and digital PWM (Pulse Width Modulated) controls.
Please Note: PWM Voltage Stabilisers are NOT FOR USE with life sustaining equipment, or any device where the power requirements
exceed the “Maximum Output Rating” listed in the General Specification
tables. These Stabilisers are not designed to support / protect voltage “back feed” applications, where energy is required to be also fed back into the utility supply.
PWM SERIES - User Manual
VSi-PWM-2018-06
http://www.VSi.UK.com
4
2. General Specification
2.1 Input
Model No
Input Voltages
PWM
2.1H-S25
PWM
3.5H-S25
220V - 230V - 240V AC Single Phase, 2 Wire (L, N & G/E)
PWM
5.25H-S25
PWM
7H-S25
PWM
10.5H-S25
PWM
14H-S25
Voltage Range
Max Input Current
Input Connectors
Operating Frequency
13 Amps 21 Amps 32 Amps 42 Amps 63 Amps 84 Amps
IEC 320 (16 Amp)
230V ±25% (173V to 287V) AC Single Phase, 2 Wire (L, N & G/E)
(220V & 240V to Special Order)
Hardwire
50 / 60 Hz
2.2 Output
Model No
Max Output Rating
Output Voltage
Waveform
Output Connectors
Harmonics <3% of THD for Linear Load
PWM
2.1H-S25
2.1
kVA/kW
2 x IEC320 (10 Amp)
PWM
3.5H-S25
3.5
kVA/kW
230V ±1%, Single Phase, 2 Wire (L, N & G/E)
PWM
5.25H-S25
5.5
kVA/kW
(220V & 240V to Special Order)
Sine Wave
Hardwire
PWM
7H-S25
7.0
kVA/kW
PWM
10.5H-S25
10.5
kVA/kW
PWM
14H-S25
14.0
kVA/Kw
Speed of Correction
Power Factor
Frequency 50 / 60 Hz (what goes in comes out)
PWM SERIES - User Manual
VSi-PWM-2018-06
http://www.VSi.UK.com
Ultra-Fast – Within 200 milliseconds
(0.2 Seconds)
No effect on performance providing the Stabiliser
is being used within its rated capacity
5
2.3 Metering, Status Indicators, Alarms & Communication
Model No
Digital Metering
Status Indicators
Audib le Alarms
Comms RS-232
PWM
2.1H-S25
PWM
3.5H-S25
PWM
5.25H-S25
Input & Output Volts (V)
Input & Output Frequency (Hz)
Internal Temperature (°c)
Load Current (Amps)
Load Level Indicator (%)
Line, Normal, Bypass & Fault
Fault & Over Voltage
PWM
7H-S25
PWM
10.5H-S25
2.4 Protection
Model No
Over Current
Overload More than 105% Output Automatically Disconnected – requiring Manual Restart
Under & Over Voltage
Over Voltage Surge Protection
Noise Protection
PWM
2.1H-S25
PWM
3.5H-S25
Input & Output Breakers – as Standard
Automatic Disconnect requiring Manual Restart
(Output Under Limit 188V ±4V / Over Limit 270V ±4V)
PWM
5.25H-S25
MOV (Varistor)
EMI Filter
PWM
7H-S25
PWM
10.5H-S25
PWM
14H-S25
PWM
14H-S25
Man ual Byp ass
NO YES – inbuilt as Standard
PWM SERIES - User Manual
VSi-PWM-2018-06
http://www.VSi.UK.com
6
2.5 Environment
Model No
Operating Temp Range
Maximum Altitude
Relative Humidity
Audible Noise
PWM
2.1H-S25
PWM
3.5H-S25
Derate by 2% for each additional ºc up to a max. of 60 ºc
Derate by 1% for each additional 100 metres
Suitable for indoor use up to 90% Relative Humidity
PWM
5.25H-S25
0 to 40ºc
2000 metres
(non-condensing).
<50 dBA (@1 Metre)
PWM
7H-S25
PWM
10.5H-S25
2.6 Physical
Model No
Construction Freestanding Enclosures to IP20 (NEMA 1 Style) - BS/EN 60529
Colour RAL 7047 (Telegray 4)
Physical Size 258(W) x 333(H) x 422(D) mm
Weight 23 Kg 29 Kg 30 Kg 32 Kg 58 Kg 62 Kg
Packed Size 38.1 (W) x 44.5(H) x 54(D) cm
PWM
2.1H-S25
PWM
3.5H-S25
PWM
5.25H-S25
PWM
7H-S25
PWM
10.5H-S25
258 (W) x 546(H) x
40.2 (W) x 78(H) x
PWM
14H-S25
PWM
14H-S25
532(D) mm
68(D) cm
Packed Weight
25.5 Kg 31.5 Kg 32.5 Kg 34.5 Kg 68.5 Kg 72.5 Kg
2.7 Certification & Compliance
Model No
EMC Compliance
CE
Certification
PWM
2.1H-S25
CE Marked – being fully compliant with European Union Directives
PWM SERIES - User Manual
VSi-PWM-2018-06
http://www.VSi.UK.com
PWM
3.5H-S25
Complies with BS/EN 55022 & the relevant part of
2014/35/EU (The Low Voltage Directive)
PWM
5.25H-S25
BS/EN 61000 Standards
2014/30/EU (The EMC Directive) and
PWM
7H-S25
10.5H-S25
PWM
PWM
14H-S25
7
2.8 Warranty
Model No
Standard Warranty
PWM
2.1H-S25
PWM
3.5H-S25
PWM
5.25H-S25
24 Months / 2 Years
PWM
7H-S25
PWM
10.5H-S25
PWM
14H-S25
PWM SERIES - User Manual
VSi-PWM-2018-06
http://www.VSi.UK.com
8
3. Safety Instructions
Read and follow all Safety Instructions
Please save these instructions for future reference
3.1 Introduction
These instructions are addressed to the installer and End User / Operator of the PWM SERIES of Single Phase Static Digital AC Voltage Stabilisers. We strongly suggest you keep this manual next to the equipment for future reference.
3.2 General Installation & Usage
Do not use the Stabiliser for other than the intended use.
Do not install Stabiliser in back feed circuits, such as solar panel and wind turbine applications, where the energy is supplied back to the grid, nor should the input voltage supply be connected to the output of stabiliser.
If on delivery there is evidence of visible damage, do not attempt to install or start the Stabiliser. Advise the transport delivery company and inform VSi, or the resale partner from whom you purchased the equipment.
The Stabiliser can contain potentially dangerous voltages – up to 300V AC. As there are no user replaceable components, once installed there should be no reason to remove the protective covers. If the covers are removed, use extreme caution and do not leave the unit unattended with the covers
off.
Hazardous voltages can be present at the unit’s output any time AC input power is applied. To avoid possible personal injury, or equipment
damage, and to make certain there is no output voltage, turn the unit off
and disconnect the AC Input.
To reduce the risk of fire, or electrical shock, install the unit in an indoor
area free from conductive contaminants.
PWM SERIES - User Manual
VSi-PWM-2018-06
http://www.VSi.UK.com
9
Do not use outdoors.
Do not place the unit near water or liquids, gas and combustible materials or in an excessively humid environment where condensation is very likely to occur.
To reduce the risk of overheating, do not block the unit’s ventilation panels and try to avoid positioning the unit in direct strong sunlight or close to other heat sources.
Do not allow liquids or foreign object to enter the unit.
The installation and use of this product must comply with all relevant current electrical installations that are in force in the territory of installation.
Where the system is required to be hardwired into the input utility mains
supply we would strongly suggest that a qualified electrician should install
the equipment. The electrician should install the AC input accordingly to the instructions contained in this manual. Standard safety practices should be followed at all times.
The unit must be grounded / earthed at all times when in use.
PWM SERIES - User Manual
VSi-PWM-2018-06
http://www.VSi.UK.com
Loading...
+ 22 hidden pages