VSI PWM 2.1H-S25, PWM Series, PWM 5.25H-S25, PWM 3.5H-S25, PWM 7H-S25, PWM 10.5H-S25, PWM 14H-S25 User Manual
Specifications and Main Features
Frequently Asked Questions
User Manual
PWM SERIES
STATIC DIGITAL
AC AUTOMATIC VOLTAGE STABILISER
USER MANUAL
Thank you for purchasing a VSi PWM Series
Static Digital AC Automatic Voltage Stabiliser
Page
1
IMPORTANT
PLEASE READ
This User / Operator Manual contains information concerning the safe and
proper installation and operating procedures applicable to the PWM range of
Single Phase Static Digital AC Automatic Voltage Stabilisers.
The Manual should be read in full before attempting to use, or operate the
equipment.
If any problems are encountered with the procedures contained within this
Manual then seek assistance from VSi or the distributor from whom you
purchased the equipment.
Whilst every precaution has been taken to ensure the accuracy and completeness
of this User Manual, VSi assumes no responsibility and disclaims all liabilities for
damages resulting from misuse of this information or any error or omission.
PWM SERIESmicroprocessor controlled Single Phase Static Digital Voltage
Stabilisers automatically correct brownouts (by boosting low voltage)
and over-voltages (by reducing high voltage). They are, designed to
ensure the delivery of a stable and quality output voltage.
Being designed for many years of reliable service, VSi’s PWM models
provide protection from incoming line voltage sags, spikes and surges /
swells. As Static Digital solutions they are virtually maintenance free and
offer an exceptional fast speed of correction, making them ideal for the
most sensitive of electrical and electronic loads.
1.2 Basic Principle of Operation
PWM SERIES AC Voltage Stabilisers are designed around a traditional well
proven ‘Buck / Boost’ design topology, utilising the latest in IGBT Power
Devices and digital PWM (Pulse Width Modulated) controls.
Please Note: PWM Voltage Stabilisers are NOT FOR USE with life
sustaining equipment, or any device where the power requirements
exceed the “Maximum Output Rating” listed in the General Specification
tables. These Stabilisers are not designed to support / protect voltage
“back feed” applications, where energy is required to be also fed back
into the utility supply.
PWM SERIES - User Manual
VSi-PWM-2018-06
http://www.VSi.UK.com
Page
4
2.General Specification
2.1 Input
Model No
Input
Voltages
PWM
2.1H-S25
PWM
3.5H-S25
220V - 230V - 240V AC Single Phase, 2 Wire (L, N & G/E)
PWM
5.25H-S25
PWM
7H-S25
PWM
10.5H-S25
PWM
14H-S25
Voltage
Range
Max Input
Current
Input
Connectors
Operating
Frequency
13 Amps21 Amps32 Amps42 Amps63 Amps84 Amps
IEC 320
(16 Amp)
230V ±25% (173V to 287V) AC Single Phase, 2 Wire (L, N & G/E)
(220V & 240V to Special Order)
Hardwire
50 / 60 Hz
2.2 Output
Model No
Max Output
Rating
Output
Voltage
Waveform
Output
Connectors
Harmonics<3% of THD for Linear Load
PWM
2.1H-S25
2.1
kVA/kW
2 x IEC320
(10 Amp)
PWM
3.5H-S25
3.5
kVA/kW
230V ±1%, Single Phase, 2 Wire (L, N & G/E)
PWM
5.25H-S25
5.5
kVA/kW
(220V & 240V to Special Order)
Sine Wave
Hardwire
PWM
7H-S25
7.0
kVA/kW
PWM
10.5H-S25
10.5
kVA/kW
PWM
14H-S25
14.0
kVA/Kw
Speed of
Correction
Power
Factor
Frequency50 / 60 Hz (what goes in comes out)
PWM SERIES - User Manual
VSi-PWM-2018-06
http://www.VSi.UK.com
Ultra-Fast – Within 200 milliseconds
(0.2 Seconds)
No effect on performance providing the Stabiliser
is being used within its rated capacity
Page
5
2.3 Metering, Status Indicators, Alarms & Communication
Model No
Digital
Metering
Status
Indicators
Audib le
Alarms
CommsRS-232
PWM
2.1H-S25
PWM
3.5H-S25
PWM
5.25H-S25
Input & Output Volts (V)
Input & Output Frequency (Hz)
Internal Temperature (°c)
Load Current (Amps)
Load Level Indicator (%)
Line, Normal, Bypass & Fault
Fault & Over Voltage
PWM
7H-S25
PWM
10.5H-S25
2.4 Protection
Model No
Over
Current
OverloadMore than 105% Output Automatically Disconnected – requiring Manual Restart
Under & Over
Voltage
Over
Voltage
Surge
Protection
Noise
Protection
PWM
2.1H-S25
PWM
3.5H-S25
Input & Output Breakers – as Standard
Automatic Disconnect requiring Manual Restart
(Output Under Limit 188V ±4V / Over Limit 270V ±4V)
PWM
5.25H-S25
MOV (Varistor)
EMI Filter
PWM
7H-S25
PWM
10.5H-S25
PWM
14H-S25
PWM
14H-S25
Man ual
Byp ass
NOYES – inbuilt as Standard
PWM SERIES - User Manual
VSi-PWM-2018-06
http://www.VSi.UK.com
Page
6
2.5 Environment
Model No
Operating
Temp
Range
Maximum
Altitude
Relative
Humidity
Audible
Noise
PWM
2.1H-S25
PWM
3.5H-S25
Derate by 2% for each additional ºc up to a max. of 60 ºc
Derate by 1% for each additional 100 metres
Suitable for indoor use up to 90% Relative Humidity
PWM
5.25H-S25
0 to 40ºc
2000 metres
(non-condensing).
<50 dBA (@1 Metre)
PWM
7H-S25
PWM
10.5H-S25
2.6 Physical
Model No
ConstructionFreestanding Enclosures to IP20 (NEMA 1 Style) - BS/EN 60529
ColourRAL 7047 (Telegray 4)
Physical Size258(W) x 333(H) x 422(D) mm
Weight23 Kg29 Kg30 Kg32 Kg58 Kg62 Kg
Packed Size38.1 (W) x 44.5(H) x 54(D) cm
PWM
2.1H-S25
PWM
3.5H-S25
PWM
5.25H-S25
PWM
7H-S25
PWM
10.5H-S25
258 (W) x 546(H) x
40.2 (W) x 78(H) x
PWM
14H-S25
PWM
14H-S25
532(D) mm
68(D) cm
Packed
Weight
25.5 Kg31.5 Kg32.5 Kg34.5 Kg68.5 Kg72.5 Kg
2.7 Certification & Compliance
Model No
EMC
Compliance
CE
Certification
PWM
2.1H-S25
CE Marked – being fully compliant with European Union Directives
PWM SERIES - User Manual
VSi-PWM-2018-06
http://www.VSi.UK.com
PWM
3.5H-S25
Complies with BS/EN 55022 & the relevant part of
2014/35/EU (The Low Voltage Directive)
PWM
5.25H-S25
BS/EN 61000 Standards
2014/30/EU (The EMC Directive) and
PWM
7H-S25
10.5H-S25
PWM
PWM
14H-S25
Page
7
2.8 Warranty
Model No
Standard
Warranty
PWM
2.1H-S25
PWM
3.5H-S25
PWM
5.25H-S25
24 Months / 2 Years
PWM
7H-S25
PWM
10.5H-S25
PWM
14H-S25
PWM SERIES - User Manual
VSi-PWM-2018-06
http://www.VSi.UK.com
Page
8
3.Safety Instructions
Read and follow all Safety Instructions
Please save these instructions for future reference
3.1 Introduction
These instructions are addressed to the installer and End User / Operator
of the PWM SERIES of Single Phase Static Digital AC Voltage Stabilisers. We
strongly suggest you keep this manual next to the equipment for future
reference.
3.2 General Installation & Usage
Do not use the Stabiliser for other than the intended use.
Do not install Stabiliser in back feed circuits, such as solar panel and wind
turbine applications, where the energy is supplied back to the grid, nor
should the input voltage supply be connected to the output of stabiliser.
If on delivery there is evidence of visible damage, do not attempt to install
or start the Stabiliser. Advise the transport delivery company and inform
VSi, or the resale partner from whom you purchased the equipment.
The Stabiliser can contain potentially dangerous voltages – up to 300V AC.
As there are no user replaceable components, once installed there should
be no reason to remove the protective covers. If the covers are removed,
use extreme caution and do not leave the unit unattended with the covers
off.
Hazardous voltages can be present at the unit’s output any time AC input
power is applied. To avoid possible personal injury, or equipment
damage, and to make certain there is no output voltage, turn the unit off
and disconnect the AC Input.
To reduce the risk of fire, or electrical shock, install the unit in an indoor
area free from conductive contaminants.
PWM SERIES - User Manual
VSi-PWM-2018-06
http://www.VSi.UK.com
Page
9
Do not use outdoors.
Do not place the unit near water or liquids, gas and combustible materials
or in an excessively humid environment where condensation is very likely
to occur.
To reduce the risk of overheating, do not block the unit’s ventilation
panels and try to avoid positioning the unit in direct strong sunlight or
close to other heat sources.
Do not allow liquids or foreign object to enter the unit.
The installation and use of this product must comply with all relevant
current electrical installations that are in force in the territory of
installation.
Where the system is required to be hardwired into the input utility mains
supply we would strongly suggest that a qualified electrician should install
the equipment. The electrician should install the AC input accordingly to
the instructions contained in this manual. Standard safety practices
should be followed at all times.
The unit must be grounded / earthed at all times when in use.