or reliability, we reserves the right to make changes to the
products described in this document without notice.
Trademarks
Mobaline is a registered trademark of Moser Baer AG
Microsoft, Windows and Windows NT are registered
trademarks of Microsoft Corporation.
All other trademarks and registered trademarks are property
of their respective owners and are recognised.
Customer Support
For assistance with installation, configuration or operation of
your TimeLord system, please contact us or your vendor’s
representative.
For further technical information and support for your TimeLord
or any other Vortex product, please visit the Vortex Communications
Web site:
http://www.vtx.co.uk
Statutory Notices
Warning - To prevent fire or shock hazard, do not
expose the unit to rain or moisture.
Some TimeLord-Lite and TimeLord-MTG Versions Only
This equipment has a built-in rechargeable Nickel Metal
Hydride (NiMh) battery, which should only be replaced by
qualified personnel.
Nickel Metal Hydride battery, dispose of properly.
You can return your unwanted Nickel Metal Hydride batteries
to the manufacturer or their agent.
Note: In some areas disposal of Nickel Metal Hydride batteries
in household or business trash may be prohibited.
Caution: Do not handle damaged or leaking Nickel Metal
Hydride batteries.
All other TimeLord versions
This equipment has a built-in Lithium battery which in normal
operation should have a service life greater than 10 years. The
Lithium battery should only be changed by a suitably qualified
engineer.
CAUTION
Danger of explosion if battery is incorrectly replaced.
Replace only with the same or equivalent type
recommended by the manufacturer. Dispose of used
batteries according to the manufacturer’s instructions.
You can return your unwanted Lithium batteries to the
manufacturer or their agent.
Note: In some areas disposal of Lithium batteries in household
or business trash may be prohibited.
Caution: Do not handle damaged or leaking Lithium batteries.
For Customers in Europe
Electromagnetic Compatibility & Safety
The TimeLord Master Clock, when used in accordance with
our recommendations, complies with the European Community
Electromagnetic Compatibility Directive 89/336/EEC and Low
Voltage Directive 73/23/EEC and conforms to the following
standards:
• EN 50081-155022 class B
• EN 50082-1IEC 801-2 level 3
IEC 801-3 level 3
IEC 801-4 level 3
• EN 60950
For Customers in the USA
The equipment has been tested and certified to comply with
the limits for a Class B digital device, pursuant to Part 15 of the
FCC Rules. These limits are designed to provide reasonable
protection against harmful interference in a residential
installation. The equipment generates, uses and can radiate
radio frequency energy and, if not installed and used in
accordance with the instructions, may cause harmful
interference to radio communications. However, there is no
guarantee that interference will not occur in a particular
installation. If this equipment does cause harmful interference
to radio or television reception, which can be determined by
turning the equipment off and on, the user is encouraged to try
and correct the interference by one or more of the following
measures:
•Reorientate or relocate the receiving antenna.
•Increase the separation between the equipment and
receiver.
•Connect the equipment into an outlet on a circuit
different from that to which the receiver is connected.
•Consult the dealer or an experienced radio/TV technician
for help.
You are cautioned that any changes or modifications not
expressly approved in this manual could void your authority to
operate this equipment.
Warranty
The TimeLord Master Clock is fully guaranteed, on a return to
works basis, against failure due to faulty parts or workmanship
for one year from date of purchase. In the event of failure,
either within or outside the warranty period, please pack the
unit with care and return to the manufacturer, or their agent,
for examination and repair.
In no event shall the manufacturer, or their agent, be liable for
any direct, incidental or consequential damages of any nature, or
losses or expenses resulting from any defective product or the
use of any product, irrespective of whether the manufacturer, or
their agent, has advance notice of the possibility of such
damages.
Manual revision
This manual version 2.0 applies to VA software version 05.01
and later, unless otherwise specified.
Issue 2.0
Contents
1Introduction
Features1-1
Package Contents1-1
2Quick Start and TimeLord Programming
Quick Start 1-42-1
Quick Start 5-82-2
Frequently Asked Questions2-3
TimeLord Programming2-4
Programming menus2-4
Setting the time and date2-6
Leap second insertion2-7
Status display2-7
System set-up2-8
3Installation
4Location Setup
City / Location Table4-2
TimeLord Master Clocks
Operating and Installation Instructions
5Synchronisation Setup
GPS Synchronisation5-1
MSF and DCF Synchronisation5-3
TimeLord series Master Clocks provides an ideal time
synchronisation solution for complete systems of equipment,
including computer networks, CCTV security, voice recording,
industrial process control and CCC applications. Available as
standard with MSF, DCF and GPS input synchronisation options,
optionally the TimeLord can be supplied to synchronise from an
NTP time source or from IRIG-B time code. This flexibility
allows the TimeLord to be used as a universal solution for
providing time synchronisation to many different devices.
Features
•Operational
High visibility 6 digit display.
Display and timecode output messages can be
referenced to UTC or ‘Local’ time.
‘Set Once’ local time zone setup, automatically
calculating future time zone changes for local time
zone.
256 Year Calendar, 4 digit year setting. (Range 2000-
2255)
Easy to install, ‘setup and forget’ operation.
•Timing accuracy
Integrated TCXO module standard on TimeLord versions.
Unsynchronised: 0.1sec/day @ 0-45ºC (20-25 ºC on
TimeLord-Lite)
Locked to MSF or DCF: within 30mS of UTC
Locked to GPS: within 50uS of UTC (100uS on TimeLord-Lite)
•Network Timing Accuracy (TimeLord-Net)
Clients typically synchronised within 1-10 milliseconds
of TimeLord-Net timebase depending on network delay and
jitter. (NTP)
•RS232 and RS485/422 interface
One, two (.S2 versions only) or four (.S4 versions
only) RS232 and RS485 serial outputs.
71 preset data formats for specific CCTV and
embedded equipment. Output interval programmable
for every second, every minute, 5 minutes, every hour,
every day or on request.
User selection of 1200, 2400, 4800, 9600 or 19200
baud, 7 or 8 data bits and odd, even or no parity on
nonspecific message formats
•Relay
30v dc. @ 500mA rated change-over contacts
0.1 second programmable contact change-over to
occur; every 5 seconds; every minute; every hour; once
per day at a user programmable time; on power
failure; whilst locked to an external time reference and
during an error state.
• w482 digital time/date code interface
Supports up to 50x V-400A series digital clocks and
time zone displays.
‘Set Once’ time zone setup, automatically calculating
future seasonal time changes for 15 time zones.
The TimeLord-Net Master Clock is supplied fitted with a 10Base-T
Ethernet interface to allow it to act as a time server on a TCP/IP
network. The TimeLord-Net interface supports the following
protocols:
•NTP and SNTP
Network Time Protocol (NTP) v2, v3 and v4 clients are
supported. (RFC1305 & RFC1119)
Simple Network Time Protocol (SNTP) v3 and v4 clients
are supported. (RFC2030 & RFC1769)
•Impulse outputs - for analogue clocks (with hands)
Dual 24V alternate polarity impulse outputs rated at
200mA per channel.
Each output programmable for one second, half minute
or one minute alternate polarity impulses.
Fully protected output drive circuitry detects power
failure and short circuit line conditions which are
automatically corrected for on fault removal.
Environment
Power supply: Rackmount TimeLords - 110-240V AC 50/60Hz
Desktop version- 12v DC via supplied external 110v
or 230v AC PSU (specifiy required PSU at time of order)
Power consumption: < 0.4A @ 230V AC
Battery Backup:TimeLord-Net>1 Year.
TimeLord-Lite and -MTG > 50 hours
(The battery backup maintains the internal time count during
periods of mains failure - figures for fully-charged battery)
Enclosure:Rackmount TimeLords - 1u high 19” rack mount
483mm wide x 185mm deep x 44mm high (19” x 7.3” x 1.75”)
Weight: 2.8Kg
-T Dekstop - Table top case
173mm wide x 178mm deep x 49mm high (6.8” x 7” x 2”)
Weight: 0.5Kg
Operating temperature: 0-50ºC
Relative Humidity: 0% to 90% (non-condensing.)
Altitude: 0 to 3,000m
MTBF: > 50,000 hours
Package Contents
The product package should contain the following items:
1TimeLord Master Clock.
2IEC Mains lead (Rackmount TimeLords) or AC power adapter
(-T Desktop). (Either UK, EU, US or AU style depending on
order code)
39-pin RS-232 serial cable.
4This manual.
5TimeLord software CD-ROM (available on request).
6RJ45 patch lead ( TimeLord-Net versions only)
For systems supplied with GPS receiver V-488C.00:
6GPS antenna / receiver module.
725 metres of 4 core cable
or systems suppled with MSF or DCF radio receiver.
6 V-484.02 / V-484.06 MSF or V-484.03 / V-484.07 DCF
radio receiver with 5 metres of cable.
1-1
Issue 2.0
2 - Quick Start, FAQ and TimeLord Programming
For V-488C & V-488B GPS
synchronisation
see pages 5-1 and 5-2.
For radio synchronisation
(V-484)see pages 5-1 & 5-3.
TimeLord Master Clocks
Operating and Installation Instructions
See sections 7 and appendix
A of manual and application
notes on TimeLord CD for
further information.
2 - Connecting V-488B, V-488C GPS and V-484 series radio receivers
4 - Connecting third-party equipment using RS232 or RS422/485
For details on synchronising
V-400A series clocks and
time-zone displays see
pages 6-1 and 6-2.
1 - Unpack the TimeLord and check contents matches list on page 1-1.
Issue 2.0
3 - Connecting V-400A and V-470/474A slave displays
2-1
TimeLord Master Clocks
Operating and Installation Instructions
For further information on
connecting a TimeLord-Net
Clock to an Ethernet network
see chapter 9.
clock to the mains power
See page 3-1 for information
on connecting the Master
system. See pages 2-4, 2-5
and 2-6 for information on
programming the time.
6 - Connecting the TimeLord-Net to an Ethernet network.
For further information on
connecting a TimeLord with
IRIG-OUT option to
equipment using IRIG
For further information on
connecting a TimeLord
with EBU-OUT to
other equipment using
EBU timecode see pages
11-1 and 11-2.
timecode see page 10-1.
8 - Apply power and set time on TimeLord.
For further information on
connecting a TimeLord with
-02 interface to Impulse
slave clocks see chapter 12.
5 - Connecting third-party equipment using EBU and IRIG.
2-2
7 - Connecting Impulse slave clocks.
Issue 2.0
Frequently Asked Questions
TimeLord Master Clocks
Operating and Installation Instructions
Will the V-488C / V-488B GPS receiver system work
indoors?
Both the V-488C and the V-488B GPS receiver systems are
designed for external mounting. We would recommend
positioning the post-mounting V-488C GPS system on the roof
of the building with a clear view of at least 75% of the sky.
The post mounting antenna supplied with the V-488B GPS
system should be mounted in a similar position. The decoder
box supplied with the V-488B GPS system should be mounted
within 5 metres of this (either indoors or outdoors).
Please refer to chapter 5 for further information.
Can I extend the cable supplied with the V-488C GPS
receiver system?
The system is supplied with 25 metres of four-core screened
cable for connection between the V-488C GPS system and the
TimeLord master clock. This cable length may be increased
up to a maximum of 50 metres using a similar type of cable or
up to a maximum of 200 metres using a heavier gauge cable.
Please refer to chapter 5 and appendix A for further
information.
Can I extend the cables supplied with the V-488B GPS
receiver system?
The V-488B GPS receiver system is supplied with a 5 metre fixed
length of cable for connection between the post-mount
antenna and the decoder box. This cable length cannot be
adjusted.
The system is also supplied with 25 metres of four-core
screened cable for connection between the decoder box and
the TimeLord master clock. This cable length may be
increased up to a maximum of 50 metres using a similar type
of cable or up to a maximum of 200 metres using a heavier
gauge cable.
Please refer to chapter 5 and appendix A for further
information.
The V-484.06 MSF and V-484.07 DCF radio time code receivers are
suitable for indoor use only.
Please refer to page 5-3 for further information.
Can I extend the cable to my V-484 series radio time
code receiver?
The cable connection to a V-484 series radio time code receiver
may be extended up to a maximum of 10m using a similar
specification cable. This connection may be extended up to a
maximum of 200 metres using a screened twisted pair cable
as specified in appendix A.
How can I tell if the TimeLord master clock has
synchronised to my chosen synchronisation time
source?
When the TimeLord master clock is synchronised, the ‘Lock’
LED will illuminate.
Why does the master clock not show the correct time,
even though the ‘lock’ LED is illuminated?
Check that the location is set correctly. Please refer to chapter
4 for further details.
How do I synchronise / time-stamp a CCTV device from
the TimeLord master clock?
Appendix C lists the supported devices and any relevant
application note. The application notes detail how to connect
the TimeLord master clock to your chosen device and may be
found on the CD-ROM supplied.
How do I connect analogue impulse clocks to the
TimeLord master clock equipped with the -02 O/P option?
Please refer to chapter 12 for details on impulse output setup.
Why will the TimeLord master clock not synchronise
to the MSF or DCF radio time code signal?
Under normal circumstances the MSF signal provides reliable
operation at distances of up to 1000km from Rugby in the
United Kingdom. The DCF signal is normally usable up to
1500km from Frankfurt in Germany.
In good conditions the TimeLord master clock, when used
with a V-484 series radio time code receiver should synchronise
to MSF or DCF within 3 minutes. During this period, the ‘code’
LED should flash once per second.
However, MSF and DCF suffer greatly from electromagnetic
interference which can cause the TimeLord master clock not
to synchronise. In this instance, the ‘code’ LED on the front
panel of the TimeLord may flash erratically. To minimise
interference problems, we would recommend mounting the
V-484 series radio time code receiver away from any computer or
electronic equipment, fluorescent lighting, lift equipment,
metal girders, reinforced concrete walls or any other sources of
electrical noise.
MSF is off-air for a maintenance period of two weeks during
the summer, and the first Tuesday of every January, April, July
and October. Please refer to page 5-3 for further information.
Will the V-484 series radio time code receiver work
indoors?
The V-484.02 MSF and 484.03 DCF radio time code receivers are
suitable for either indoor or protected outdoor mounting. For
reliable operation, we would recommend mounting these units
externally if possible though they normally work indoors also.
Issue 2.0
2-3
TimeLord Master Clocks
Operating and Installation Instructions
TimeLord Progamming
The TimeLord Master Clock has a user friendly interface
based on the use of four buttons.
The buttons are located to the right hand side of the display
and are labelled
The
and
mode settings whereas the
alter the values of settings.
On pressing the
pressing the
the available modes for set up of the TimeLord .
The modes will be displayed in the following order:
usable on TimeLord-Net versions only)
buttons are used to step between and save
and
Time Setting Mode
Location Setting Mode
Synchronisation Setting Mode
Network Setting Mode (visible on all TimeLords -
Zone Setting Mode
S1 Serial Output Setting Mode
and
button the function mode is entered. By
buttons the user can scroll through all
.
and buttons are used to
S2 Serial Output Setting mode (.S2 & .S4 versions
only)
S3 Serial Output Setting mode (.S4 versions only)
S4 Serial Output Setting mode (.S4 versions only)
Relay Setting Mode
IRIG Setting Mode (visible on all versions - usable on
To select any of the modes whilst they are displayed in the
function mode press the
enter a specific mode and make any necessary changes to the
related settings.
To progress through the options use the
the values for these options use the
completion of any changes the
used to save the settings and to either step forward or
backward through any other options before returning to the
normal time display.
button. This allows the user to
button and to alter
and
and
buttons. On
buttons can be
Programming menus
‘Network Setting
Mode’ will appear
expandable
on all
versions, but only
be usable on net
versions.
Normal time display
Function ‘Time Setting Mode’.
‘^’ to select, ‘+’ or ‘-’ to change.
Function ‘Location Setting Mode’.
‘^’ to select, ‘+’ or ‘-’ to change.
Function ‘Synchronisation Mode’.
‘^’ to select, ‘+’ or ‘-’ to change.
Function ‘Network Setting Mode’.
‘^’ to select, ‘+’ or ‘-’ to change.
Time Setting Mode selected, with
seconds flashing. See page 2-6.
Location Setting Mode selected,
with zone flashing. See page 4-1.
Synchronisation Mode selected.
See page 5-1.
Network Setting Mode selected, with
IP address flashing. See page 9-1.
Continued on page 2-5
2-4
Issue 2.0
Programming menus cont.
TimeLord Master Clocks
Operating and Installation Instructions
‘Serial 2 Setting
Mode’ will only
appear on .S2
& .S4 versions.
‘Serial 3 Setting
Mode’ & ‘Serial 4
Setting Mode’ will
only appear on
.S4 versions.
‘IRIG Setting
Mode’ will appear
on all versions, but
only be usable on
-IRIG-OUT
versions.
Function ‘Zone Setting Mode’. ‘^’
to select, ‘+’ or ‘-’ to change.
Function ‘Serial 1 Setting Mode’.
‘^’ to select, ‘+’ or ‘-’ to change.
Function ‘Serial 4 Setting Mode’.
‘^’ to select, ‘+’ or ‘-’ to change.
Function ‘Relay Setting Mode’. ‘^’
to select, ‘+’ or ‘-’ to change.
Function ‘IRIG Setting Mode’. ‘^’ to
select, ‘+’ or ‘-’ to change.
Zone Setting Mode selected, with
location 2 flashing. See page 6-1.
Serial 1 Setting Mode selected,
with code flashing. See page 7-1.
Serial 4 Setting Mode selected,
with code flashing. See page 7-1.
Relay Setting Mode selected, with
setting flashing. See page 8-1.
IRIG Setting Mode selected, with
type flashing. See page 10-1.
‘EBU Setting
Mode’ will only
appear on
EBU-OUT
versions.
‘Impulse Channel
1 Setting Mode’ &
‘Impulse Channel
2 Setting Mode’
will only appear
on -02 impulse
versions.
Function ‘EBU Setting Mode’. ‘^’ to
select, ‘+’ or ‘-’ to change.
Function ‘Impulse channel 1 Setting
Mode’. ‘^’ to select, ‘+’ or ‘-’ to change.
Function ‘Impulse channel 2 Setting
Mode’. ‘^’ to select, ‘+’ or ‘-’ to change.
Function ‘System Setup’. ‘^’ to
chang the system seeting.
Normal time display
EBU Setting Mode selected, with
type flashing. See page 11-1.
Impulse channel 1 Setting Mode selected,
with status flashing. See page 12-1.
Impulse channel 2 Setting Mode selected,
with status flashing. See page 12-1.
Brightness Mode selected, with
brightness flashing. See page 2-8.
Issue 2.0
2-5
TimeLord Master Clocks
Operating and Installation Instructions
Setting the Time
A detailed diagram with full instructions on manually setting
the time and date is shown below.
Normal time display
Function ‘Time Setting Mode’.
Press ‘^’ to select.
Time setting mode selected, with
seconds flashing.
Time setting mode selected, with
minutes flashing.
Time setting mode selected, with
hours flashing.
Time setting mode selected, with
year flashing.
Time setting mode selected, with
month flashing.
‘+’ increments the seconds count, ‘-’ holds
the seconds count at the current value.
‘+’ and ‘-’ change the minutes
value.
‘+’ and ‘-’ change the hours value.
‘+’ and ‘-’ change the years value.
‘+’ and ‘-’ changes the month
value.
2-6
Time setting mode selected, with
day flashing.
Time setting mode selected, with
leap second flashing.
Normal time display
‘+’ and ‘-’ changes the day value.
‘+’ and ‘-’ changes the leap
second value. Please refer to
page 2-7 for further information.
Issue 2.0
Leap Second Insertion
The TimeLord can be programmed to allow for leap second
insertion (one second is sometimes added at the end of March,
June, September or December), to compensate for the
deceleration of the Earth’s rotational time with respect to the
the Atomic clock (UTC).
This function is enabled by programming the ‘LS’ setting to yes
(as shown on page 2-6).
Date, Sychronisation, Impulse Time and
temperature Status Displays
When in normal time display mode the plus and minus buttons
can be used to cycle through the date, synchronisation, impulse
time (-02 versions) and temperature (expandable versions) status
displays. When any of these displays is selected the TimeLord
will return to normal time display mode after 2 minutes.
The Synchronisation status display provides useful information
regarding the current quality of the MSF or DCF signals that
are being received by a V-484 series radio receiver.
The two Impulse time displays indicate the Impulse time of
both Impulse channels. Please refer to chapter 12 for further
information.
The Temperature status display shows the internal
temperature of the TimeLord Master Clock (not TimeLord-Lite).
TimeLord Master Clocks
Operating and Installation Instructions
Normal time display
Date display.
Synchronisation Status Display
The synchronisation status display provides the following
information relating to MSF or DCF signal reception.
Indicates the number of seconds of the
current time message that have been
received. ‘Aq’ indicates that the
is trying to acquire the first second
of a new time message.
Indicates the number of valid time
messages received. Incremented for
every good message decremented for
every corrupt message. (Range 0-F)
The number of minutes before the
declares that it has lost lock to
the input signal. (Range 0-F)
The synchronisation lockout counter, the
number of minutes of valid, but
different time messages required
before the
to the new time. (Range 0 - 9)
TimeLord will synchronise
TimeLord
TimeLord
Impulse time
screens will only
appear on -02
impulse versions.
Temperature
status screen will
only appear on
expandable versions.
Synchronisation status display.
Impulse channel 1 time display.
Impulse channel 2 time display.
Temperature status display.
Issue 2.0
Normal time display
2-7
TimeLord Master Clocks
Operating and Installation Instructions
System Set-up
The system set-up menu contains general set-up options for
the TimeLord Master Clock. The table below details the
available options.
unempu-tesmetsyS
Normal time display
edoCnoitcnuFsnoitpO
irBssenthgirByalpsiD)tsemmiD=1(.4-1
tuoepyttuptuo284w,FSM-,FCD-,FSM,FCD,284w
AVerawtfosTimeLord
BVerawtfoskrowten
GnEylnoesuyrotcaf
w482 Timecode output
As shown in the table above, the w482 timecode output port
may be set to output either w482 timecode or unmodulated
MSF, DCF or HBG timecodes. The MSF, DCF & HBG outputs may
be set to pulse high or low as required (MSF, DCF & HBG pulse
high, -MSF, -DCF & -HBG pulse low). The L48 option
implements longer w482 code pulse lengths for use with older
400 series digital clocks. The S48 option implements shorter
than standard w482 code pulse lengths.
noisrev
noisrev
)noisrev
GBH-,GBH,84S,84L
erawtfossihtnidelbasid(
If your TimeLord
is fitted
Function ‘Time Setting Mode’.
Press ‘+’ eight times to move to
system setting mode.
Function ‘System Setting Mode’.
Press ‘^’ to select.
Brightness setting mode, with
brightness flashing. Use ‘+’ and ‘-’
to alter brightness and ‘^’ to store.
w482 timecode output setting mode,
with w482 flashing. Use ‘+’ and ‘-’ to
alter output type and ‘^’ to store.
with NTP,
EBU, S2, S4
or .IMP
options, you
may need to
press the ‘+’
switch more
than 8 times.
2-8
TimeLord software version. Press
‘^’ to continue.
Network software version
(disabled in this software
revision). Press ‘^’ to continue.
Factory use only. Press ‘^’ to
continue.
Normal time display
Issue 2.0
3 - Installation
TimeLord-Lite - no expansion capability
TimeLord-Net and TimeLord-Net-Client
TimeLord Master Clocks
Operating and Installation Instructions
TimeLord-Lite/T Desktop version
Warning - dangerous voltages - the TimeLord
master clock must be disconnected from the mains
supply prior to removing the top cover.
Power Supply Connection
The TimeLord family of master clocks are fitted with universal
power supplies suitable for 110v - 240v ac operation. The
desktop version may be supplied for 230v AC, 110vAC or 12v DC
operation. Please specify appropriate end user location at
time of order to enable correct power adapter or connector
type to be supplied.
PSU order codes:
.AU - Australian style, 240v 50Hz ac.
.EU - European style, 230v 50Hz ac.
.UK - UK style, 230v 50Hz ac.
.US - US style, 110v 60Hz ac.
The TimeLord rackmount master clock is supplied with an IEC
style mains lead.
The TimeLord-Lite/T is supplied with an external 12v DC PSU.
If an alternative PSU is to be used, it should have a rating of
greater than 0.4A at 12v DC.
The master clock must be connected to the appropriate supply
after first verifying the correct voltage by reference to the
supply voltage label fixed to the rear of the clock (rackmount
versions) or on the external power supply (desktop).
A connection to the earth line must be made to ensure safe
operation and ensure compliance with EMC regulations.
To ensure conformance with EN60950:
(A)For installations where the TimeLord master clock
is to be permanently connected into the mains
power circuit, a readily accessible disconnect device
should be incorporated in the fixed wiring.
(B )For installations where the TimeLord master clock
is to be plugged into the mains power circuit, a
socketed outlet should be installed near the
equipment and should be easily accessible.
All installation work should be performed in accordance
with the Sixteenth Edition of the IEE Wiring Regulations.
Battery backup.
Expandable TimeLords are fitted with a Lithium battery which will
maintain the internal time count for a period normally in excess of
1 year if the mains supply is interrupted.
The TimeLord-Lite is fitted with an automatically recharging battery
which will, when fully charged, maintain the internal time
count for a period in excess of 50 hours if the mains supply is
interrupted.
Fuses and Output protection.
The TimeLord circuit board makes use of advanced automatically
resettable fuse technology so that it is protected under fault
conditions.
The universal power supply within the TimeLord uses a
20mm fuse rated at 2 Amps 250V. Please note that this fuse is
not a user serviceable part.
External Connections
The external connections located on the rear of the TimeLord
provide the following inputs and outputs:
ConnectionSection
GPS / Synchronisation Connection5
Relay Connection8
IRIG* and EBU* Connection10 & 11
RS232 and RS422/485 S1, S2*, S3* & S4*7
* denotes optional items which may or may not be fitted in your
unit.
Please see the relevant sections of this manual for further
information.
Operation
Please see section 2 for a quick start guide to getting your
TimeLord system up and running.
Issue 2.0
3-1
TimeLord Master Clocks
Operating and Installation Instructions
4 - Location Setup
The TimeLord Master Clock provides advanced time zone
functionality. Regardless of time synchronisation source, the
TimeLord can be used to provide time and date information
referenced to UTC, user ‘local’ time or other custom time zone.
Incorporating ‘Set Once’ technology, the TimeLord will
automatically calculate future seasonal time changes for all 64
of the preset time location code settings.
Setting the location
For installations where the output of the TimeLord is to be
referenced to UTC / GMT, the location code should be set to 00.
For installations where the output of the TimeLord is to be
referenced to the ‘local’ time zone, select the appropriate
location code from the table opposite. (eg. For a unit installed
in Birmingham, England, where ‘local’ time output is required,
location code 01 should be used.)
User Programmable Time Zone
For time-offsets and daylight saving time change dates not
covered by the location codes on page 4-2, a user
programmable time zone is provided. Information regarding
the time offset from UTC and any daylight saving change rules
may be input via a 12 digit code.
Please contact our technical department for further information
regarding this function.
Normal time display
Function ‘Time Setting Mode’. Press ‘+’
to move to ‘Location Setting Mode’.
Function ‘Location Setting Mode’. Press
‘^’ to select.
‘Location Setting Mode’ selected, with
current location flashing. Use ‘+’ and
‘-’ to select the required location from
the table on page 4-2.
Press ‘^’ to store the new location
setting and return to normal time
display.
--ve Power for V-488B/C GPS
++ve Power for V-488B/C GPS
ASignal A from V-488B/C GPS
BSignal B from V-488B/C GPS
EMC grounding point
Note:
A Screened cable should be used to
connect the V-488C / V-488B GPS receiver
to the TimeLord . The screen should
be connected to the EMC grounding
point on the TimeLord and on the
V-488B GPS receiver.
MSF and DCF connection
10 way terminal block
-Green or uncovered wire from
V-484 radio receiver.
+Link to ‘A’ connector.
ALink to ‘+’ connector.
BRed or clear wire from V-484
radio receiver.
EMC grounding point
Note:
A Screened cable should be used to
connect the V-484 radio receiver to the
TimeLord in areas of high electrical
noise. The screen should be
connected to the EMC grounding
point on TimeLord only.
puteSnoitasinorhcnyS
OXCTlanretni
noitasinorhcnyS-metsyS
.setilletasSPGmorf
ehtmorfnoitasinorhcnyS
.langisemitFCD
ehtmorfnoitasinorhcnyS
.langisemitFSM
namorfnoitasinorhcnyS
.margeletetad&emit
namorfnoitasinorhcnyS
ecruoSemiTPTN
.ecruosedocemiTB-GIRI
GPS Synchronisation
The V-488C and V-488B GPS receiver systems are designed to be
automatically synchronised to time signals transmitted from
the Global Positioning System (GPS) navigation network. The
GPS constellation consists of 28 operational satellites,
operating in 12 hour orbits at an altitude of 20,200km.
Both the V-488C and the V-488B GPS receiver have been designed
for simple installation and operation by the end-user, requiring
only a 4 wire interconnection to the TimeLord Master Clock.
When synchronised to a V-488C or 488B GPS receiver system the
TimeLord-Net Master Clock output signals are maintained within
50uS of UTC (100uS of UTC on TimeLord-Lite versions).
The reception gain pattern of both GPS systems is designed
for full, upper hemispherical coverage with the gain
diminishing at low elevations. This cross-section is consistent
through 360 degrees and so the 3 dimensional gain pattern is
a symmetrical spheroid surface.
Advantages of GPS time synchronisation:
•Very accurate synchronisation
•Can be used anywhere in the world
•Not subject to EM interference
Disadvantages of GPS time synchronisation:
•Antenna needs to be mounted externally with a clear
view of 75% of the sky.
The V-488C GPS Synchronisation System
The V-488C GPS synchronisation system is housed in a single
IP66 rated case containing an advanced combined Sony active
antenna and 12 channel parallel GPS receiver module and a
microprocessor based communications interface. The system
is supplied complete with a post mounting clamp to enable
the unit to be fixed to a suitable horizontal or vertical post of
up to 2cm diameter. The antenna should be mounted on the
roof of a building or under a suitable skylight.
setoN
The V-488B GPS Synchronisation System
The V-488B GPS receiver system comprises a post mounting
active antenna and a separate receiver/decoder unit. The
,ecnereferlanretxeoN
1.0nahtrettebycarucca
Cº52-02(Cº54-0.yad/ces
.TimeLord-Liteno
.ecruosemitetaruccayreV
nierehwynadesuebnaC
.dlroweht
antenna module transmits the received GPS signals and
receives power (5Vdc @ 25mA) from the GPS receiver/decoder
module via a single 5 metre long RG58 coaxial cable. A post
mounting clamp is supplied to enable the antenna to be fixed to
a suitable horizontal or vertical post of up to 2cm diameter. The
antenna may be mounted on the roof of a building or under a
suitable skylight.
The GPS receiver/decoder unit contains a Motorola 8 Channel
parallel receiver and a microprocessor based communications
interface. The receiver/decoder module is housed in a robust
aluminium case fitted with mounting points for wall mounting
and protected to IP65. The module should be mounted in a
protected location within 5 metres of the antenna.
V-488C and V-488B System Installation
noitpOredrOlaicepS**noitpOredrOlaicepS**
noitpOredrOlaicepS**noitpOredrOlaicepS**
1morfdetarenegesabemiT
noitpOredrOlaicepS**
laires584SR/232SRtaSPP
noitpOredrOlaicepS**noitpOredrOlaicepS**
noitpOredrOlaicepS**noitpOredrOlaicepS**
noitpOredrOlaicepS**
IICSAlaires584SR/232SR
To ensure ease of operation and to remove the possibility of
operator error, both the V-488C and V-488B GPS systems are
designed to self initialise.
Ensure that the TimeLord is disconnected from the
mains power supply when making connections to the
V-488C / V-488B GPS receiver systems.
1Install the V-488C unit or V-488B antenna module
DxidneppaotreferesaelP
horizontally using the post mounting kit provided.
Ensure that the unit has a clear view of at least 75% of
the sky. If the sky view is reduced the interval between
‘switch-on’ and system time synchronisation will be
noitpOredrOlaicepS**noitpOredrOlaicepS**
noitpOredrOlaicepS**
considerably increased.
2Connect the antenna module to the GPS receiver using
noitpOredrOlaicepS**noitpOredrOlaicepS**
noitpOredrOlaicepS**noitpOredrOlaicepS**
noitpOredrOlaicepS**
the special 5m cable provided (V-488B systems only).
5-1
Issue 2.0
TimeLord Master Clocks
Operating and Installation Instructions
Both the V-488C and the V-488B GPS Receiver systems are
supplied with 25 metres of 4 core cable. Cable distance can
be extended up to a maximum distance of 200 metres using
the cable specifications detailed in appendix A.
V-488B Receiver decoder unit.
Housed in IP65 case, suitable for mounting
in a sheltered external location.
20mm dia. post
(not supplied)
5 metre cable
(cannot be extended)
V-488C GPS Receiver
Should be mounted with a
view of at least 75% of the
sky.
V-488B Antenna
Should be mounted with a
view of at least 75% of the
sky.
20mm dia. post
(not supplied)
3A connection between the V-488C / V-488B and the
TimeLord should be made using the 25 metre four core
cable supplied. If a longer cable distance is required
Appendix A should be consulted for suitable cable
specifications. The maximum distance between the
GPS system and the TimeLord master clock is 200m.
If a screened cable is used, the cable screen should be
connected to the EMC ground connection on the 10 way
terminal block, located on the rear of the
TimeLord.
On 488B systems, the screen should be connected to
the screw fitting on the 488B receiver/decoder case.
The screen is supplied pre-connected on
V-488C units
with captive cable connections.
4The 4 GPS input connections located on the 10 way
terminal block on the rear of the
TimeLord, should be
wired as shown in the diagram on page 5.1.
5Connect the power supply to the
TimeLord Master
Clock.
6Once the power has been applied the receiver will
automatically begin to search the sky for all available
satellites, during this process the green LED will flash.
After three satellites have been acquired the green LED
will stop flashing and become constantly illuminated,
indicating that a precise date and time has been
calculated from the satellite data transmissions. From a
‘cold’ start this process will typically take less than 10
minutes.
7Ensure that the
TimeLord is configured to synchronise
from the GPS signal by following the procedure on
page 5-3.
V-488C GPS Integral Receiver/Interface
V-488B GPS Separate Receiver/Interface
Antenna
Lead
Internal antenna socket
two part power/data
plug-in terminal block
B A + -
m TimeLord to V-488C / V-488BorfsnoitcennoC
B88488C/4-V
TimeLord
noitcennoCSPG
noitcennoC
++deR
25metre captive
cable for connection
to TimeLord
Master Clock.
POWER
STATUS
ABCD
)elbacm52
ruoloCnoitcennoC
deilppusgnisu(
Once the green LED has illuminated the synchronising time
signals are transmitted from the GPS system to the
TimeLord.
The TimeLord Master Clock should lock in and display
the correct time within 5 minutes.
-- eulB
AA wolleY
BB neerG
Issue 2.05-2
TimeLord Master Clocks
Operating and Installation Instructions
MSF and DCF synchronisation
MSF and DCF are the two most widely used radio time code
signals. The DCF signal is derived from the atomic clocks at the
Physics Institute of Brunswick and transmitted at a frequency
of 77.5KHz from Manflingen, near Frankfurt in Germany. The
MSF signal is referenced to the Caesium Beam Oscillators at
the National Physical Laboratory and transmitted on a
frequency of 60KHz from Rugby in the United Kingdom.
Under normal circumstances the DCF signal provides reliable
operation at distances of up to 1500km, MSF signals are
normally usable up to 1000km from the transmitter. Greater
operating ranges are possible at night.
When synchronised to MSF or DCF using a V-484 radio receiver
the TimeLord Master Clock output signals are maintained
within 30mS of UTC.
Advantages of MSF and DCF time synchronisation:
•Lower purchase cost than GPS
•Can sometimes be installed internally.
Disadvantages of MSF and DCF time synchronisation:
•Can be difficult to find good location for signal
reception.
•Suffers greatly from EM interference - Avoid locating
near computers, electronic equipment, fluorescent
lighting, lift equipment, metal girders, reinforced
concrete walls and all other sources of electrical noise.
•MSF is off-air for a maintenance period of two weeks
during the summer, and the first Tuesday of every
January, April, July and October. MSF status can be
checked by telephoning 020 8943 6493.
Normal time display
Function ‘Time Setting Mode’. Press ‘+’
twice to move to synchronisation mode.
Function ‘Synchronisation Mode’. Press
‘^’ to select.
Synchronisation mode selected with
current mode flashing. Use ‘+’ and ‘-’
to select required setting.
Installation
The V-484 series time code receiver should be mounted:
•At least 2.5 metres from the TimeLord Master Clock.
•At greatest practical distance from:
Other electronic equipment including computers,
fluorescent lights and signs, metal girders, reinforced
concrete walls and any other sources of electrical noise.
•O n the side of the building nearest Rugby (MSF) or
Frankfurt (DCF).
•Preferably on the outside of the building (V-484.02 and
V-484.03 only) as high as possible. The case is
weatherproof to IP65 (484.02 and 484.03 only) but it is
preferable to provide some protection from direct rain.
•With the cable entry on the lower face of the case.
(V-484.02 and V-484.03 only)
The antenna is supplied with 5 metres of two core cable, if a
longer cable distance is required Appendix A should be consulted
for suitable cable specifications. The maximum distance
between the V-484 radio receiver and the TimeLord Master
Clock is 200m.
If a screened cable is used, the cable screen should be connected
to the EMC grounding terminal on the 10 way terminal block,
located on the rear of the TimeLord.
Alignment
The V-484.02 (MSF) and V-484.03 (DCF) radio receivers have dual
ferrite antennas, which normally permit location regardless of
orientation to the transmitter. The receiver is mounted by means
of four fixing holes in the rear surface which are accessed after
removing the front cover. The four mounting holes are located
outside of the central sealed compartment.
The V-484.06 (MSF) and V-484.07 (DCF) receivers have a single
antenna element and are supplied with an adjustable
mounting bracket so that the installer can ensure that the
orientation of the longest face of the receiver is at 90
o
to the
direction of the transmitter.
Press ‘^’ to save synchronisation mode
and return to normal time display.
Normal time display.
The front cover of the V-484.02 and V-484.03 receivers may be
removed to enable the indicator LED to be viewed. The indicator
LED on the V-484.06 and V-484.07 receiver is located on the front
face of the unit.
The alignment of the receiver is correct when the LED flashes
once per second. The Code LED located on the front of the
TimeLord will flash at the same time as the LED in the V-484.
Signal reception
In good conditions the TimeLord master clock will take three
minutes to synchronise with the transmitted time code from
either DCF or MSF. When the TimeLord is ‘locked’ to the
transmitted signal, the locked LED, located after the seconds
display, is illuminated continuously. During periods of signal
failure or signal corruption the clock will maintain timekeeping
using its internal crystal oscillator.
1 PPS / Serial ASCII Synchronisation
Special order versions of the TimeLord Master Clock are available
to facilitate synchronisation with an RS232 / RS485 level serial
ASCII data string or timebase generation from an RS232 /
RS485 level 1 Pulse Per Second source. The Serial variant will
synchronise to Serial format 1 (as shown on page 7.1)
transmitted at 9600 baud, 8 data bits, no parity, 1 stop bit at a
1 second repetition rate.
5-3
Issue 2.0
6 - w482 Time Zone Setup
TimeLord w482 Code Output
10 way terminal block
Aw482 Code +
Bw482 Code -
EMC grounding point
Note:
Polarity of connection is not critical.
If a screened cable is used for system
interconnection, the screen should
only be connected to the EMC
grounding point on the TimeLord.
The w482® signal was developed for controlling electronic
clocks, using a single cable pair data interconnection, in
electrically noisy environments. A principal advantage of
®
w482
is the ability to provide time information in any one of
fifteen different synchronised time zones. All fifteen time
zones can be individually configured from the front panel of
the TimeLord, using ‘Set Once’ technology to allow automatic
seasonal time change correction.
The w482
50 bits per second data rate. The signal is virtually immune to
electro-magnetic interference.
One TimeLord unit can control up to fifty 400A series slave
displays located up to 1km from the master clock unit using a
simple, non-critical cable pair.
Setup Procedure
1Decide what time you want to display on your slave
®
signal is transmitted at 4-24v amplitude and at a
clocks. If you just want to display Local Time, as
previously programmed during ‘location’ setting (section
4), proceed to stage 2.
TimeLord Master Clocks
Operating and Installation Instructions
Normal time display
Function ‘Time Setting Mode’. Press ‘+’
four times to move to w482 zone
setting mode.
Function ‘w482 Zone Setting Mode’.
Press ‘^’ to select.
w482 Zone Setting Mode, zone 2
selected with current location flashing.
Use ‘+’ and ‘-’ to change.
If you have more than one time zone to display or want
to display a different time zone from that set in the
location setting, determine the zone location codes
(Page 4-2) and program w482 zones ‘2’ - ‘A’ accordingly.
Ensure that the TimeLord system is disconnected
from the mains power supply when making
connections to the w482 output.
2Connect the V-400A slave clocks to the TimeLord w482
output terminals. (See above and page 6-2).
Check that the V-400A (or V-470A) slave clock is programmed
for w482 time code synchronisation. If the V-400A (or
V-470A) slave clock is to be synchronised by a w482 time
zone which is not zone 1, program the V-400A (or V-470A)
clock accordingly.
Refer to the V-400A (or V-470A) series operating and
installation manual for more details.
3Apply power to the TimeLord.
Note: If you using the IRIG output (IRIG-OUT versions
only) or EBU output (EBU-OUT versions only) and are
using it in an application that requires the location setting to
be set to a time zone other than the local time zone, w482 zone
2 should be programmed for the local time zone and the slave
displays should be configured accordingly.
Press ‘^’ to store the new zone 2
setting and move on to the w482 time
zone 3 setting.
Zone 3 selected, press ‘+’ and ‘-’ to
change current setting, ‘^’ to move to
next zone.
w482 zone settings 4 - F
Zone F selected, press ‘+’ and ‘-’ to
change current setting, ‘^’ to return to
normal time display.
Issue 2.0
Normal time display.
6-1
TimeLord Master Clocks
Operating and Installation Instructions
w482 time code system interconnection
MAC Address
xx xx xx xx xx xx
RS232/RS485 S4RS232/RS485 S3
Data
Link
10Base-TRS232/RS485 S2
Net Update
GPS Receiver
A-+ B
w482
BAno
Relay
nc
C
RS232/RS485 S1
IRIG-B
6-2
Issue 2.0
TimeLord Master Clocks
Operating and Installation Instructions
7 - RS232 & RS422/485 Serial Output
TimeLord RS232 & RS485/422
Interface
DB9-F Connector
RS232/RS485 S1
Operation
The TimeLord Master Clock is fitted as standard with one
RS232 & RS485/RS422 serial data output. The signals are
accessed via the female DB9 connector labelled RS232/RS485
S1 mounted on the rear of the unit.
Additional serial outputs (.S2 & .S4 versions only)
The TimeLord is optionally available with two or four RS232/RS485
serial data outputs. Where installed, these signals are
accessed via the S2, S3 and S4 female DB9 connectors. If your
TimeLord is fitted with multiple serial ports, extra serial setting
modes (S2, S3 & S4) will appear in the main programming
menu to allow these ports to be individually configured using
the procedure detailed below. (Please note: The RS232 level 1
pulse per second output is not present on pin1 of serial ports
S3 & S4).
Setting the Message Format
The TimeLord has 71 different preprogrammed serial output
messages. The desired message can be selected from the
lists on page 7-2 and programmed into the TimeLord using
the procedure on page 7-5. Please also refer to Appendix C for
details of products compatible with the TimeLord.
Setting the Output Message Time Offset
The TimeLord serial output message may be referenced to
the current location setting (see section 4) or UTC/GMT as
detailed in the procedure on page 7-5 .
RS232
11PPS
2Transmitted Data (TXD)
3Received Data (RXD)
5Signal Ground (GND)
RS485/422
8‘A’ - non-inverting
9‘B’ - inverting
Note:
The 1PPS signal is at RS232 levels and
goes high for 100ms on the second
edge.
Data Formats
The serial messages numbered from 01 to 09 are user
programmable. This allows the user to program information
concerning the baud rate, data bits, parity, stop bits and serial
repetition to ensure that the format chosen meets their
requirements.
Some of the other serial data messages have factory preset
transmission formats to ensure that system interconnection is
trouble free.
Message Format
Serial Format 1 (Code 1)
STX Su St Mu Mt Hu Ht Du Dt Mtu Mtt Yu Yt St ETX
Serial Format 2 (Code 4)
TYt Yu :Mtt Mtu :Dt Du :0W:Ht Hu :Mt Mu :St Su CR LF
Bit 10 = Winter time, 1 = Summer Time
Bit 20 = not synchronised, 1 = synchronised
Bit 30 = no early warning bit, 1 = early warning bit
Application Notes
The TimeLord Information CD contains application notes
detailing the use of the TimeLord with many different types
of equipment. If you are unable to access the CD or require
further information on the setup and use of the serial output
please contact our technical support representatives.
The Serial Messages table on page 7.2 contains references to
application notes which contain additional information specific
to that serial message.
User Programmable User Programmable01 Std-serial Format 1
02 Std-serial Format without status User Programmable User Programmable
03 Std-serial Format 2 User Programmable User Programmable
04 Std-serial Format 2 with day of week User Programmable User Programmable
Function ‘Time Setting Mode’.
‘^’ to select, ‘+’ or ‘-’ to change.
Function ‘Serial Mode’. Press ‘^’
to select.
Serial Mode with serial type
flashing. Use ‘+’ and ‘-’ to select.
Baud rate selected, with current
setting flashing.
Data bits selected, with current
setting flashing.
Parity selected, with current
setting flashing.
Stop bits selected, with current
setting flashing.
‘+’ and ‘-’ change the selected
serial output message.
‘+’ and ‘-’ change the baud rate. ‘PRESET’
indicates the setting cannot be changed.
‘+’ and ‘-’ changes the data bits. ‘PRESET’
indicates the setting cannot be changed.
‘+’ and ‘-’ changes the parity. ‘PRESET’
indicates the setting cannot be changed.
‘+’ and ‘-’ changes the stop bits. ‘PRESET’
indicates the setting cannot be changed.
Serial repeat selected, with
current setting flashing.
Message time offset with messgage
referenced to current location setting.
Normal time display
Issue 2.07-5
‘+’ and ‘-’ changes the repeat rate. ‘PRESET’
indicates the setting cannot be changed.
‘+’ and ‘-’ changes the message to output
time referenced to UTC.
TimeLord Master Clocks
Operating and Installation Instructions
8 - Relay Setup
TimeLord Relay Connections
10 way terminal block
noN.O. Contact
ncN.C. Contact
CCommon
Note:
The relay is configured so that
contacts no-C are normally open and
contacts nc-C are normally closed.
For example, if the relay is set to
close every hour for 100ms, contacts
no-C will close for 100ms on the hour,
while contacts nc-C will open for
100mS.
Operation
The relay can be programmed to operate every 5 seconds,
every minute, every hour, once per day at a user programmable
time or to signal a fault condition.
The relay contacts are rated for 500mA @ 30v DC operation.
The minimum contact load is 1mA @ 5v DC. The contact
closure duration is 100mS.
Normal time display.
Function ‘Time Setting Mode’. Press ‘+’
six times to move to relay setting mode.
Function ‘Relay Setting Mode’.
Press ‘^’ to select.
If your
TimeLord
is fitted
with NTP,
EBU, S2, S4
or .IMP
options, you
may need to
press the ‘+’
switch more
than 6 times.
Setting the Programmable Relay Time
When the TimeLord is used to provide one contact closure
per day it is recommended that the time chosen is at 03:00.
This allows the synchronised equipment to be adjusted for the
seasonal time change on the day that it occurs. Most
conventional systems use a contact closure at 00:00 which will
not update the synchronised equipment for the seasonal time
change until the next day.
elbaTsedoMyaleR
edoCedoM
rPrewoPrewoP
rErorrErorrE
coLkcoLkcoL
ES5sdnoceS5sdnoceS5
rewoPrewoP
rewoP
stcatnoCC-onC-on
C-onC-on.tneserpsirewopelihwdesolc
C-on
stcatnoCC-cnC-cn
C-cnC-cn.devomersirewopnehwdesolc
C-cn
rorrErorrE
rorrE
stcatnoCC-onC-on
C-onC-ongnitarepositinuelihwdesolc
C-on
stcatnoC.yltcerrocC-cnC-cn
C-cnC-cnnisitinuehtnehwdesolc
C-cn
.derewoptsrifsawtinu
kcoLkcoL
kcoL
stcatnoCC-cnC-cn
C-cnC-cnsi0684/0584ehtelihwdesolc
C-cn
.desinorhcnysnusitinuelihwdesolc
sdnoceS5sdnoceS5
sdnoceS5
.sdnoces
stcatnoc(erusolctcatnocsm001C-onC-on
C-onC-onevifyreve)
C-on
stcatnoC.ecruoslanretxenaotdesinorhcnysC-onC-on
ecnistesneebtonsahemitehtroetatsrorrena
C-onC-on
C-on
Current mode flashing. Press ‘+’ and ‘-’ to
change relay mode. Press ‘^’to exit, see
below if selected mode is ‘PRO’.
Selected relay mode is ‘Program’.
Press ‘^’ to set activation time.
Use ‘+’ and ‘- to program relay
operation minutes time. Press ‘^’
to set operation time hours.
Use ‘+’ and ‘- to program relay
operation hours time. Press ‘^’
to exit.
RJ4510Base-T Ethernet Connector
DB9Network software update port
LinkLink LED indicating connection to network
Data Data LED indicating data on the network
Operation
The TimeLord-Net operates as a Network Time Server on a TCP/IP
Computer network. The quick setup procedure should be
followed to get the TimeLord-Net up and running quickly. Page 9-3
details the various protocols that the TimeLord-Net supports while
pages 9-1 and 9-2 detail the basics behind IP addresses,
subnets and gateways.
Pages 9-4 and 9-5 show the setting procedure in more detail.
The TimeLord-Net master clock has a 10Base-T Ethernet interface
and must be connected either to a dedicated 10Base-T port or
a switchable 10Base-T / 100Base-T port on your network.
Net Update
Quick Setup
Install the TimeLord-Net as detailed in section 3 of this manual.
Attention: If you are unsure of the following network
settings please contact your network administrator.
Incorrect settings can adversely affect the
performance of your network.
1)Program the IP address of the TimeLord-Net in dotteddecimal notation. (e.g. 192.168.0.41) Use the plus and
minus buttons to increment and decrement each value.
The up arrow will move on to the next value, the down
arrow will return to the previous value.
2)Program the Subnet Mask of the TimeLord-Net in dotteddecimal notation. (e.g. 255.255.255.0) Use the plus
and minus buttons to increment and decrement each
value. The up arrow will move on to the next value, the
down arrow will return to the previous value.
3)Program the default Gateway of TimeLord-Net in dotteddecimal notation. (e.g. 192.168.0.1). Use the plus and
minus buttons to increment and decrement each value.
The up arrow will move on to the next value, the down
arrow will return to the previous value.
4)Use the CAT5 patch cable (supplied) to connect the
TimeLord-Net to your TCP/IP Computer network. Ensure
that the network connection used is compatible with
10Base-T. Check the green link led illuminates,
confirming that correct connection has been made to
the network.
TCP/IP is todays most prevalent networking technology. It can
be used for small Local Area Networks (LAN) of two or three
users, right through to the other end of the spectrum where it
is used as the protocol connecting every machine on the
elbaTsgnitteSkrowteN
Internet.
Each connected computer must have a unique address to
gnitteS
ensure that data transmitted from one location reaches the
correct destination.
Blocks of addresses are assigned to organizations by the
Internet Assigned Numbers Authority (IANA). Users and small
organisations usually obtain their addresses from their Internet
Service Provider while larger organisations liaise directly with
the IANA.
The Internet Protocol (IP) uses 32 bit addresses, which when
displayed to humans are usually written in dotted-decimal
notation. Dotted-decimal notation is where the address is
written as four decimal numbers, one for each byte of the
address.
For example the dotted-decimal IP address 195.112.5.193 can
be represented in the following formats:
The IP address of a computer is constructed of two parts. The
first part of the address identifies the network to which the
computer or host is connected, the second part specifies the
actual host itself. The TCP/IP software on each host can
automatically determine the class of an IP address by
examining the first byte of that address.
Issue 2.09-1
TimeLord Master Clocks
Operating and Installation Instructions
stib7stib42
AssalC0 krowteNtsoH
stib41stib61
BssalC10krowteNtsoH
stib12stib8
CssalC110krowteNtsoH
stib82
DssalC1110puorgtsacitluM
stib72
EssalC11110latnemirepxE
There are five different classes of address:
Class A - 1.x.x.x - 126.x.x.x
These addresses have a 8 bit network number and a 24 bit
host number addresses. Each class A network can have
16,777,214 hosts.
Class B - 128.1.x.x - 191.254.x.x
These addresses have a 16 bit network number and a 16 bit
host addresses. This means that each class B network can have
65,354 hosts.
Class C - 192.0.1.x - 223.255.254.x
These addresses have a 24 bit network number and an 8 bit
host addresses. This means that each class C network can
have 254 hosts.
Class D - 224.0.0.0 - 239.255.255.255
Class D network addresses are used for multicasting, which is
where information sent from one address can be sent to many
different hosts simultaneously.
Class E - 240.0.0.0 - 254.255.255.255
Class E network addresses are used for experimental
purposes.
For each unique network number, the base address of the
range (i.e. host number zero) is known as the network address
and is not assigned to a host. The top address of the range is
(i.e. host number set to all ones) the broadcast address which
is used as the address for sending to all hosts on the same
network number simultaneously.
Subnet Addressing
Subnet addressing allows us to split one IP network address
into several smaller physical networks known as subnets. This
is especially useful with Class A and Class B addresses where
there are very large numbers of network hosts with the same
network address.
A subnet is created by splitting the host address part of the IP
address into two, the first being subnet address and the
second host ID.
stib41stib8
BssalC10krowteNtenbuStsoH
In the class B example shown above the address has been
subnetted into 254 subnets, each with a possible 254 hosts.
Subnet Mask
The subnet mask is a 32 bit number which specifies how many
bits of the IP address are for the network / subnet address and
how many are for the host address.
stib8
For the class B subnet example used above the subnet mask
would be as follows:
stib42
BssalC11111111111111111111111100000000
The following table details a few typical subnet masks and the
network classes / subnets they describe.
&krowteN
tibtenbuS
htgnel
80.0.0.552htiwsserddaAssalC
610.0.552.552htiwsserddaBssalC
420.552.552.552htiwsserddaCssalC
Private IP addresses
With the massive growth of the Internet there was a real
danger that the IANA would run out of IP addresses. To avoid
this situation three blocks of IP addresses have been reserved
for use in private networks. It is recommended that on an
organisation’s TCP/IP networks use these private network
numbers for their networks and make use of a technology like
NAT (Network Address Translation) to allow their users access
to the Internet.
10.0.0.0 - 10.255.255.255
172.16.0.0 - 172.31.255.255
192.168.0.0 - 192.168.255.255
ARP & MAC
When one device (A) wants to send data to another device (B)
on the same Ethernet LAN it must convert the IP address of the
destination device to the Ethernet Media Access Control (MAC)
address of that device. Each Ethernet device has a globally
unique 48 bit MAC address which is assigned at time of
manufacture.
If device A does not have B’s MAC address an Address
Resolution Protocol (ARP) request is broadcast onto the local
Network. The ARP request contains the IP address of device B,
so device B is the only device to respond. Device B sends its
MAC address to device A and it is stored in device A’s ARP
table.
Device A can now send data directly to device B.
Gateway Address
The gateway address is used when a device on a network
sends data to another device that is connected to a different
network segment. The gateway device is typically a router
connecting two different networks together.
When one device sends data to another device the TCP/IP
software checks to see if the destination network address is
the same as its own network address. If the network address
is the same the data is transmitted normally, using ARP to
resolve the destination MAC address if required.
If the network address is different the data is forwarded to the
IP address specified in the ‘Gateway’ setting for routing
onwards to the specified network. This routing process may
occur several times as the data travels across different
networks enroute to its destination.
ksaMtenbuSegasUlacipyT
stib8
stenbuson
AssalCrostenbuson
cte,stenbus452htiw
BssalCrostenbuson
.stenbus452htiw
9-2
Issue 2.0
Supported Protocols
Time Protocol (RFC868)
RFC868 defines the original TIME protocol, which provides siteindependent, machine-readable date and time in response to
a request from a client PC.
When a request is received the TimeLord-Net responds with a 32-bit
time value corresponding to the number of seconds since
midnight of January 1
st
1900. This representation of time will
serve until the year 2036.
Time Protocol is supported in the UDP mode of operation.
(RFC868)
NTP (RFC1305 & RFC1119)
The Network Time Protocol (NTP) is the most widely used
computer time synchronisation protocol in use today. It
provides a mechanism to both organise a synchronisation
subnet and distribute precise time synchronisation information
to the local clocks of all participating computers. In most parts
of the Internet today it is possible to use NTP to provide
accuracy’s of tens of milliseconds, depending on the
characteristics of the synchronisation source, stratum of
operation, the local network paths and the client software
used.
The NTP standard has been designed so that it can provide
reliable operation with clients and servers of vastly different
specifications and across network paths with diverse delay and
jitter characteristics. Most users of Internet NTP
synchronisation make use of the standard NTP distribution
available from http://www.ntp.org. This software package
includes the full suite of NTP options and algorithms and has
been ported to a wide variety of hardware platforms ranging
from Personal Computers (PC’s) to supercomputers.
We would recommend that, in large hierarchical time
distribution projects, the standard NTP distribution be used on
the Stratum 2 and 3 servers for maximum redundancy and
client availability.
Network Time Protocol (NTP) v2, v3 and v4 clients are
supported in both unicast and broadcast modes of operation.
(RFC1305 & RFC1119)
TimeLord Master Clocks
Operating and Installation Instructions
SNTP (RFC2030 & RFC1769)
Simple Network Time Protocol (SNTP) v3 and v4 clients are
supported in both unicast and broadcast modes of operation.
(RFC2030 & RFC1769)
Simple Network Time Protocol (SNTP) is an adaptation of NTP,
which can be used for applications where the ultimate
performance and associated overhead of the full NTP
implementation is not required.
Most PC client software is based on the SNTP specification and
certainly for most intranet applications will provide a higher
degree of accuracy than is required.
Simple Network Time Protocol (SNTP) v3 and v4 clients are
supported in both unicast and broadcast modes of operation.
(RFC2030 & RFC1769)
Synchronisation Alarm Status
The NTP/SNTP version 4 message format has provision for a
two-bit ‘Leap Indicator’ code that gives indication of an
impending leap second and synchronisation alarm status.
When ‘nLoc’ is set (y), the TimeLord-Net Master Clock will return an
LI (Leap Indicator) value of ‘0’ if the clock is synchronised and
‘3’ if the clock is unsynchronised. When ‘nLoc’ is not set (n), the
TimeLord-Net Master Clock will return an LI (Leap Indicator) value of
‘0’ regardless of synchronisation status.
If the synchronisation source is set to ‘none’ and ‘nLoc’ is set,
the TimeLord-Net will return an LI (Leap Indicator) value of ‘3’.
Function ‘Time Setting Mode’. Press ‘+’ three
times to move to Network setting mode.
Function ‘Network Setting Mode’. Press
‘^’ to select.
Network Setting Mode, with IP address
1st byte flashing.
Network Setting Mode, with IP address
2nd byte flashing.
Network Setting Mode, with IP address
3rd byte flashing.
Network Setting Mode, with IP address
4th byte flashing.
Network Setting Mode, with Subnet
mask 1st byte flashing.
Use ‘+’ and ‘-’ to change setting.
Use ‘+’ and ‘-’ to change setting.
Use ‘+’ and ‘-’ to change setting.
Use ‘+’ and ‘-’ to change setting.
Use ‘+’ and ‘-’ to change setting.
9-4
Network Setting Mode, with Subnet
mask 2nd byte flashing.
Network Setting Mode, with Subnet
mask 3rd byte flashing.
Use ‘+’ and ‘-’ to change setting.
Use ‘+’ and ‘-’ to change setting.
Issue 2.0
TimeLord Master Clocks
Operating and Installation Instructions
Network Setting Mode, with Subnet
mask 4th byte flashing.
Network Setting Mode, with Gateway
address 1st byte flashing.
Network Setting Mode, with Gateway
address 2nd byte flashing.
Network Setting Mode, with Gateway
address 3rd byte flashing.
Network Setting Mode, with Gateway
address 4th byte flashing.
Use ‘+’ and ‘-’ to change setting.
Use ‘+’ and ‘-’ to change setting.
Use ‘+’ and ‘-’ to change setting.
Use ‘+’ and ‘-’ to change setting.
Use ‘+’ and ‘-’ to change setting.
Network Setting Mode, with
synchronisation alarm status flashing.
Network Setting Mode, with
Network update flashing.
Normal time display
Use ‘+’ and ‘-’ to change setting.
Use ‘+’ and ‘-’ to change setting. When
set to ‘y’ the netUpdate software on the
TimeLord CDROM is planned to allow
installation of software upgrades into the
TimeLord (available on future versions)
Issue 2.09-5
TimeLord Master Clocks
Operating and Installation Instructions
10 - IRIG Output (IRIG-OUT Option)
Optional IRIG Interface
BNC Connector
1KHz AM modulated balanced signal.
IRIG is a series of time codes originally developed in the 1940s
by the International Range Instrumentation Group (IRIG) for
recording time information on magnetic tape and wire for rocket
test range instrumentation purposes. IRIG-B code is normally
transmitted at a 100Hz bit rate, amplitude modulated on a 1KHz
carrier, where the amplitude of a ‘1’ bit is three times that of a
‘0’ bit.
Standard IRIG-B code contains day-of-year and hours, minutes
and seconds information, however a number of organisations
have added their own extensions to the standard format.
AFNOR NFS 87 500 timecode is a development of IRIG-B which is
widely used in Europe and contains additional day, day-of-month
and year information.
The IRIG output is available on the TimeLord-Lite and
TimeLord-Net / Net-Client versions.
If your TimeLord
is fitted
with NTP, S2
Normal time display
Function ‘Time Setting Mode’. Press ‘+’
seven to times to move to IRIG setting mode.
Function ‘IRIG Setting Mode’. Press ‘^’
to select.
or S4 options,
you may need
to press the
‘+’ switch
more than 7
times.
IRIG Setup
The different IRIG settings are detailed in the table below. The
IRIG setting procedure is shown graphically in the diagram to
the right of this text.
Setting the IRIG Signal Time Offset
The IRIG signal is referenced to the current Location setting
(see section 4). If the output message is to be referenced to
UTC/GMT the location setting should be set to 0.
RS485 level IRIG output
The IRIG signal is available at RS485/422 levels from the S1
serial output if the ‘i485’ setting is selected. Please note that if
the ‘i485’ option is set to ‘yes’, the S1 RS485 interface cannot
be used for serial data output.
i485 Interface
5Signal ground
8‘A’ - non-inverting
RS232/RS485 S1
puteSGIRI
edoCepyTtiB
9‘B’ - inverting
setoN
etaR
IRIG Setting Mode, with IRIG type flashing. Use
‘+’ and ‘-’ to select required IRIG type.
Press ‘^’ to store IRIG format and move
to RS485 level IRIG output setting.
Press ‘^’ to store RS485 level IRIG
setting and exit programming mode.
Normal time display
b-B-GIRIdradnatS
)321B(
FA005-78SFNronfA
)AtnairaV(
EIB-GIRI4431EEEIzH0014431EEEIhtiwB-GIRI
ENB-GIRIANENzH001xxxANENhtiwB-GIRI
2N02CIMzH001etadtuohtiwB-GIRI
10-1
zH001detaludomMAzHK1
zH001ehtfollasniatnoC
taelbaliavaosladna
.slevel584SR
noitamrofniyrotagilbo
.snoisnetxe
.snoisnetxe
.noitamrofni
Issue 2.0
11 - EBU Output (EBU-OUT option)
TimeLord Master Clocks
Operating and Installation Instructions
Ω
TimeLord-Net EBU Timecode Interface
6 way terminal block
Low Z Low impedance signal
600Ω Balanced 600Ω signal
TimeLord-Lite EBU Interface
BNC Connector
EBU
Balanced 600Ω signal
EBU timecode is used in broadcast applications for ‘stamping’
time information on recordings and for the control of clocks
and other intelligent systems. EBU time code is used in PAL
and SECAM applications at 25 frames per second.
The signal data rate for EBU is 2000 bits per second, with each
frame of data comprising 80 bits. The EBU standard defines
the format for hours, minutes, and seconds information. Date
information can be added to the signal in a number of formats
within ‘user bit’ areas.
The EBU output is available on the TimeLord-Lite and
TimeLord-Net / Net-Client versions.
TimeLord-Net versions are fitted with both 600Ω and low impedance
outputs. Please note: Only one pair of outputs should be used
at one time.
The TimeLord-Lite version is fitted with a 600Ω output.
If your TimeLord
is fitted wtih
NTP, S2 or S4
Normal time display
serial options,
you may need
to press the
‘+’ switch
more than 8
times.
Function ‘Time Setting Mode’. Press ‘+’ eight
to times to move to EBU setting mode.
Function ‘EBU Setting Mode’. Press ‘^’
to select.
EBU Setting Mode, with EBU type flashing. Use
‘+’ and ‘-’ to select required EBU type.
Press ‘^’ to store EBU format and exit
programming mode.
Normal time display
EBU Setup
The different EBU settings are detailed in the table below.
Please see table on page 11-2 for EBU code formats.
The TimeLord master clock is optionally available with dual channel
24V alternate polarity impulse outputs (Option V-02).
Each output may be programmed by the user for one of a
number of different combinations of pulse length and
repetition rate to drive impulse slave clocks requiring one
second, half minute or one minute alternate polarity impulses.
The fully protected output drive circuits detect power failure
and short circuit line fault conditions which are automatically
corrected for on fault removal.
Automatic Correction
Automatic time correction following power failures, the
removal of fault conditions and after seasonal time changes is
carried out by increasing the pulse repetition rate or by
stopping the impulses depending on which action will result in
a shorter correction time.
In the 1 second - standard mode the system will take one hour
to correct for each hour that the slave clocks are behind the
master.
In the 1 second - slow correction mode the system will take
approximately one and a half hours to correct for each hour
that the slave clocks are behind the master.
The 1 second - seconds synchronisation only mode is intended
for use with 4 wire slave clocks requiring both minute and
second impulses.
elbaTepyTtuptuOeslupmI
edoCedoM
nontuptuooNtuptuooN
AS1dradnats-dnoces1dradnats-dnoces1
bS1noitcerrocwols-dnoces1noitcerrocwols-dnoces1
cS1ylnosdnoces-dnoces1ylnosdnoces-dnoces1
S03etunim2/1etunim2/1
An1dradnats-etunim1dradnats-etunim1
Bn1noitcerrocwols-etunim1noitcerrocwols-etunim1
tuptuooNtuptuooN
tuptuooN
dradnats-dnoces1dradnats-dnoces1
dradnats-dnoces1
.deepspu-hctac
noitcerrocwols-dnoces1noitcerrocwols-dnoces1
noitcerrocwols-dnoces1
.deepspu
ylnosdnoces-dnoces1ylnosdnoces-dnoces1
ylnosdnoces-dnoces1
.smsinahcem
etunim2/1etunim2/1
etunim2/1
.deepspu
dradnats-etunim1dradnats-etunim1
dradnats-etunim1
.deepspu
noitcerrocwols-etunim1noitcerrocwols-etunim1
noitcerrocwols-etunim1
.deepspu
etunimrepseslup021,eslupmignol.ces4.0
-hctacetunimrepseslup58,eslupmignol.ces4.0
tnemevomsdnocesehtrof-eslupmignol.ces4.0
setunimdnasdnocesetarapeshtiwskcolcevalsfo
-hctacetunimrepseslup03,eslupmignol.ces5.0
-hctacetunimrepseslup03,eslupmignol.ces0.1
-hctacetunimrepseslup6,eslupmignol.ces0.3
Commissioning
Please perform the following four procedures to commission
your impulse clock system.
Setup Part A - Initial Setup Procedure
Before commencing this procedure, please ensure that all of
the clocks are displaying the same time.
1)Install the TimeLord master clock as detailed in section
3 of this manual.
2)Program the required location as detailed in section 4
of this manual.
3)Connect any synchronisation option as detailed in
section 5 of this manual.
4)Connect the analogue clocks to your chosen impulse
channel as shown on page 12-4. Please refer to
appendix A for recommended cable specifications.
5)For your chosen impulse channel, program the required
‘Impulse output type’. This is part of the impulse
channel setup procedure shown graphically on page
12-2. The ‘Impulse Output Type Table’ below details
the options available.
Setup Part B - Synchronisation of clocks
This procedure ensures that all clocks on your chosen impulse
channel are synchronised together. Before starting this
procedure you should ensure that all clocks are displaying the
same time.
6)Referring to the ‘starting the impulses’ procedure on
page 12-3, select the ‘pulse’ option and press the ‘^’
key. This action transmits a single pulse to all of the
connected clocks.
7)Now examine the slave clocks. Reverse the impulse
connections to all slave clocks that appear to have
‘missed’ a pulse and manually advance these clocks by
two impulses. All clocks connected to this channel
should now be in synchronisation.
Setup Part C - Programming the Impulse time
8)For your chosen impulse channel, program the ‘Impulse
Time’. This is part of the impulse channel setup
procedure shown graphically on page 12-2. The
‘Impulse Time’ is the time that the analogue clocks are
currently displaying. Please note that you must ensure
that all of the analogue clocks on your chosen impulse
channel are showing the same time.
Setup Part D - Starting the Impulses
9)Referring to the ‘starting the impulses’ procedure on
page 12-3, select the ‘run’ option and press the ‘^’ key
to exit.
The channel will now be running and the master clock will
calculate whether it will be quicker to output catch-up
impulses or wait for the current time to reach the impulse time
(as previously programmed).
Visual Indication of Operation and Error status
The TimeLord.IMP master clock provides full time visual indication
of impulse channel operation and alarm status. When an
impulse is transmitted, the relevant channel LED will illuminate
below the time display on the front panel. If an overload or
short circuit line fault occurs, the impulse alarm LED will flash
along with the relevant channel LED.
The current impulse time of channels 1 and 2 may be
examined by pressing the ‘+’ key three or four times
respectively when on the standard time display.
Please refer to page 12-3 for further details.
Issue 2.0
12-1
TimeLord Master Clocks
Operating and Installation Instructions
Impulse channel setup procedure
Normal time display
Function ‘Time Setting Mode’. Press ‘+’ eight times
If your TimeLord is
fitted with
EBU, S2 or S4
options, you
will need to
press the ‘+’
switch more
than 8 times.
to move to Impulse channel 1 setting mode.
Function ‘Impulse Channel 1 Setting
Mode’. Press ‘^’ to select.
Impulse Channel 1 setting mode, with
current operation status flashing.
This procedure enables the master clock to know what time the
slave clocks are displaying and thus calculate the required
number of catch-up pulses. It also ensures that the correct
type of impulses are output. This procedure must be
performed for both channels (if used) on initial
commissioning.
Impulse Channel 1 setting mode, with
impulse time seconds count flashing.
Impulse Channel 1 setting mode, with
impulse time minutes count flashing.
Impulse Channel 1 setting mode, with
impulse time hours count flashing.
Impulse Channel 1 setting mode, with
impulse type flashing.
Impulse Channel 1 setting mode. Press ‘^’ to amend the
settings or ‘v’ to exit.
Use ‘+’ and ‘-’ to program the channel 1
impulse time seconds count.
Use ‘+’ and ‘-’ to program the channel 1
impulse time minutes count.
Use ‘+’ and ‘-’ to program the channel 1
impulse time hours count.
Use ‘+’ and ‘-’ to alter the channel 1
impulse output type. (Please refer to
table on page 12-1).
12-2
Function ‘Impulse Channel 1 Setting
Mode’. Press ‘v’ to exit.
Normal time display
Issue 2.0
TimeLord Master Clocks
Operating and Installation Instructions
Starting the Impulses
If your TimeLord
is fitted with
EBU, S2 or S4
options, you
will need to
press the ‘+’
switch more
than 8 times.
This procedure will start the impulses running and should only
be performed once the impulse channel setup procedure has
been completed. Once the channel has been started, the
master clock will calculate whether it will be quicker to output
catch-up impulses or wait for the current time to reach the
impulse time (as previously programmed). This procedure
must be performed for both channels (if used).
Normal time display
Function ‘Time Setting Mode’. Press ‘+’ eight times
to move to Impulse channel 1 setting mode.
Function ‘Impulse Channel 1 Setting
Mode’. Press ‘^’ to select.
Impulse Channel 1 setting mode, with current operation status flashing.
Press ‘+’ to start impulses. Press ‘-’ to send single set-up pulse.
Before selecting the ‘run’ option, you may wish to use the
‘pulse’ option to ensure all the slave clocks are synchronised to
the same polarity. Please refer to page 12-1 for further details.
Impulse Channel 1 setting mode, with
impulses running. Press ‘^’ to exit.
Normal time display
Indication of current Impulse time
Impulse alarm
Normal time display. Press ‘+’ key three
times to move to Impulse channel 1 time.
Impulse channel 1 time. Press ‘+’ key to
move to Impulse channel 2 time.
Channel 1 active
Channel 2 active
Impulse channel 2 time. Press ‘+’ key to
exit.
Normal time display
Issue 2.012-3
TimeLord Master Clocks
Operating and Installation Instructions
MAC Address
xx xx xx xx xx xx
Data
Link
10Base-TRS232/RS485 S2
Net Update
Impulse system interconnection
GPS Receiver
A-+ B
w482
BAno
Relay
nc
C
RS232/RS485 S1
IRIG-B
12-4
Issue 2.0
TimeLord Master Clocks
Operating and Installation Instructions
Appendix A - Cable Specifications
TimeLord-> V-488B/C GPS interconnection
The V-488B and V-488C GPS Receiver systems are supplied with
25 metres of four core 7/0.2 (0.22mm
screen should be grounded at the TimeLord end by means of
the EMC rear grounding terminal and on the V-488B GPS receiver
using the screw fitting provided.
For distances of up to 50 metres the length can be extended by
adding an additional length of 7/0.2 cable. For greater
distances, up to a maximum of 200m, 16/0.2 (0.5mm
should be used.
Please note that the 5m cable which links the antenna to the
V-488BGPS Receiver cannot be extended.
TimeLord -> V-484 MSF and DCF radio receiver
interconnection
The V-484 series radio receiver is supplied with a 5m long
unscreened cable as standard.
2
) screened cable. The cable
2
) cable
In areas of high electrical noise a screened twisted pair should
be used. The cable screen should be grounded at the TimeLord
end only by means of the rear grounding terminal.
A suitable screened cable is RS 361-361, (twin 16/0.254 - 18
awg) equivalent to Alpha 2421, BICC H8093, UL style 2092
which is adequate for a spur controlling 25 clocks over a 1km
cable run or a greater number of clocks over a shorter distance.
For screened LSOH applications RS 362-140 (two pairs 7/0.25 22 awg) may be used. Two conductors may be connected in
parallel to provide a similar performance to 18 awg.
Equivalent to UL style 2493.
For a Cat 5 installation, (24 awg) a single pair can be used to
connect up to 10 400A series clocks or time-zone displays at a
distance of up to 250m. For further distances or greater
numbers of clocks, additional cores should be paired together,
lowering the cable resistance.
The cable length may be extended to 10m using unscreened
cable, RS 367-943 - 22 awg or equivalent. In areas of high
electrical noise a screened twisted pair should be used. The
cable screen should be grounded at the TimeLord end only.
Cable length may be extended to 200m using a screened
twisted pair cable, RS 368-340 - 22 awg or equivalent. (UL
style 2092, Alpha 2401)
For screened LSOH (Low Smoke Zero Halogen) applications RS
362-140 (two pairs 7/0.25 - 22 awg) may be used. Equivalent
to UL style 2493.
TimeLord -> Digital Displays w482 code interconnection
The w482 time code system is designed to have considerable
immunity to external electrical interference and screened cable
is only required in areas of high electrical noise.
If in doubt one should always consider the use of the next
heavier gauge cable as this invariably increases system
integrity at minimal additional system cost and allows for
future system expansion.
All installation work should be performed in accordance with
current Building Regulations and the Sixteenth Edition of the
IEE Wiring Regulations, or equivalent local regulations.
Cabling for analogue clock systems is highly dependent on the
number of clocks, power consumption of the clock movements
and distance of cable involved.
Based on the use of 10mA clock movements, each channel of
the TimeLord.IMP master clock could drive 20 clocks (a total of
40 clocks). Alternatively, each channel of the TimeLord.IMP could
drive 25x 8mA clock movements (a total of 50 clocks).
Normal installations may use standard mains cable. (e.g. twin
2
1.5mm
) The size of the cable depends on the overall cable
length, the number of clocks and their spacing on the cable.
The use of twin 1.5mm
2
cable will be adequate for installations
of up to 50 clocks, calendar clocks or time-zone displays using
up to 1km of cable. For LSOH applications low smoke cable to
IEC332 and BS4066 may be used. RS212-7882 (1.5mm
2
Pirelli
PSX™).
epyTelbaCfooN.xaM
2
mm5.0
2
mm0.1
2
mm5.1
skcolC
GWA02/02m003
GWA71/02m056
GWA51/02m0001
ecnatsiD
Unscreened data cables should not be run in proximity to
power cables supplying fluorescent lighting or other sources of
electrical noise.
Listed below are some CCTV and other devices with known
time synchronisation support from the TimeLord Master
Clock. Please refer to the relevant chapters of this manual
(and if applicable, the application notes located on the CDROM supplied) for further information on synchronisation
procedures.
sredroceRlatigiD/sRCV
TimeLord Master Clocks
Operating and Installation Instructions
If the product you wish to synchronise is not detailed, please
contact our technical department for further clarification.
Please note: Inclusion or exclusion of any product from these
lists in no-way indicates an endorsement or otherwise of the
respective products.
Appendix D - NTP Synchronisation option
(TimeLord-Net-Client versions only)
Link
10Base-T
Data
MAC Address
xx xx xx xx xx xx
TimeLord Network Interface
RJ4510Base-T Ethernet Connector
DB9Network software update port
LinkLink LED indicating connection to network
Data Data LED indicating data on the network
Operation
The Network Time Protocol (NTP) synchronisation option
enables the TimeLord-Net-Client to synchronise to an NTP time
source on a TCP/IP Computer network. The quick setup procedure
should be followed to get the TimeLord-Net-Client up and running
quickly. With NTP selected as the synchronisation source, a
reduced set of options will appear in the Network Setting
menu as detailed in the NTP Network Settings Table below.
Please refer to chapter 9 for further information regarding TCP/
IP concepts and NTP. Please note that the TimeLord-Net-Client
cannot operate as a Network Time Server.
The TimLord-Net Client has a 10Base-T Ethernet
interface and must be connected either to a dedicated 10BaseT port or a switchable 10Base-T / 100Base-T port on your
network.
yalpsiD
edoC
PIsserddAPIsserddAPI
TimeLord-Net uses on the computer network.
bSksaMtenbuSksaMtenbuS
tGsserddAyawetaGsserddAyawetaG
Net Update
elbaTsgnitteSkrowteNPTN
gnitteS
sserddAPIsserddAPI
sserddAPI
ehttahtsserddalocotorPtenretnIehtsisihT
ksaMtenbuSksaMtenbuS
ksaMtenbuS
PIehthtiwdenibmocnehwksamtenbusehT
reggibehtfotrap(tenbusehtsefitnedisserdda
e TimeLord-Net is connected to.httaht)krowten
sserddAyawetaGsserddAyawetaG
sserddAyawetaG
nehwten0684ehtybdesusisserddayawetagehT
dnasretupmocotnoitamrofnidnesotsdeenti
skrowtenrehtootdetcennocerahcihwsecived
.stenbusdna
Quick Setup
Install the TimeLord-Net-Client as detailed in section 3 of this manual.
Attention: If you are unsure of the following network
settings please contact your network administrator.
Incorrect settings can adversely affect the
performance of your network.
1)Select ntP (NTP - Network Time Protocol) as the
synchronisation source in the ‘Synchronisation Mode’
menu. Please refer to chapter 5 for further details.
2)In the Network Setting menu, program the IP address
of the TimeLord-Net-Client in dotted-decimal notation. (e.g.
192.168.0.41) Use the plus and minus buttons to
increment and decrement each value. The up arrow will
move on to the next value, the down arrow will return
to the previous value. This procedure is shown
graphically on pages D-3 & D-4. Please refer to the
NTP Network Settings Table below and chapter 9 for
further information.
3)In the Network Setting menu, program the Subnet
Mask of the TimeLord-Net-Client in dotted-decimal notation.
(e.g. 255.255.255.0) Use the plus and minus buttons to
increment and decrement each value. The up arrow will
move on to the next value, the down arrow will return
to the previous value. This procedure is shown
graphically on pages D-3 & D-4. Please refer to the
NTP Network Settings Table below and chapter 9 for
further information.
4)In the Network Setting menu, program the default
Gateway of TimeLord-Net-Client in dotted-decimal notation.
(e.g. 192.168.0.1). Use the plus and minus buttons to
increment and decrement each value. The up arrow will
move on to the next value, the down arrow will return
to the previous value. This procedure is shown
graphically on pages D-3 & D-4. Please refer to the
NTP Network Settings Table below and chapter 9 for
further information.
5)In the Network Setting menu, program the IP address
of the NTP time server in dotted-decimal notation. (e.g.
192.168.0.41) Use the plus and minus buttons to
increment and decrement each value. The up arrow will
move on to the next value, the down arrow will return
to the previous value. This procedure is shown
graphically on pages D-3 & D-4. Please refer to the
NTP Network Settings Table below and chapter 9 for
further information.
6)Having returned to the time screen, cycle the power on
the TimeLord-Net-Client Master Clock.
7)Manually set on the time on the TimeLord-Net-Client Master
Clock to within half an hour of the real time (please
refer to page 2-4 for further details of this procedure).
8)Use the CAT5 patch cable (supplied) to connect the
TimeLord-Net-Client to your computer network. Ensure that
the network connection used is compatible with
10Base-T. Check the green link led illuminates,
confirming that correct connection has been made to
the network.
tnsserddAPIrevreSPTNsserddAPIrevreSPTN
D-1
sserddAPIrevreSPTNsserddAPIrevreSPTN
sserddAPIrevreSPTN
PTNehtfosserddalocotorPtenretnIehtsisihT
e TimeLord-Net-Client uses as its Timehttahtrevresemit
.ecruoS
Issue 2.0
Synchronisation Status Display
When in normal time display mode the plus and minus buttons
can be used to cycle through the date, synchronisation and
temperature status displays, as detailed on page 2-5.
However, when NTP is selected as the synchronisation source,
the synchronisation status display operates as detailed below
NTP Synchronisation status - please
refer to the table below for further
information.
Indicates the number of valid time
messages received. Incremented for
every good message decremented for
every corrupt message. (Range 0-F)
The number of minutes before the TimeLord
declares that it has lost lock to the input
signal. (Range 0-F)
The synchronisation lockout counter, the
number of minutes of valid, but
different time messages required
before the TimeLord will synchronise to the
new time. (Range 0 - 9)
TimeLord Master Clocks
Operating and Installation Instructions
yalpsiD
edoC
00gnisilaitinIgnisilaitinI
10rorrErorrE
20eruliafnoissimsnarTeruliafnoissimsnarT
30eruliafevieceReruliafevieceR
40rorreevieceRrorreevieceR
50desinorhcnySdesinorhcnyS
60rorreecnereffidemiTrorreecnereffidemiT
elbaTsutatSnoitasinorhcnySPTN
gnisilaitinIgnisilaitinI
gnisilaitinI
rorrErorrE
rorrE
eruliafnoissimsnarTeruliafnoissimsnarT
e TimeLord-Net-Client is not able to transmit data to thehT
e TimeLord-Net-Client is not receiving data from the hT
e TimeLord-Net-Client is receiving unreliable data fromhT
e TimeLord-Net-Client is syncrhonised to the NTP TimehT
.revreS
e TimeLord-Net-Client has received NTP informationhT
eruliafnoissimsnarT
.revreSemiTPTN
eruliafevieceReruliafevieceR
eruliafevieceR
.revreSemiTPTN
rorreevieceRrorreevieceR
rorreevieceR
.revreSemiTPTNeht
desinorhcnySdesinorhcnyS
desinorhcnyS
rorreecnereffidemiTrorreecnereffidemiT
rorreecnereffidemiT
e TimeLord-Net-Client is ±30 minutes.htnoemit
.gnisilaitinisitroptenrehtEehT
.rorrecificeps-nonasierehT
ehtneewtebecnereffidemitehtsetacidnitaht
.The TimeLord-Net-Client will reject this information.
Issue 2.0
D-2
TimeLord Master Clocks
Operating and Installation Instructions
When the TimeLord master clock is programmed to synchronise
from an NTP time source, the network setting menu will be
replaced by the following netclient setup menu.
Normal time display
Function ‘Time Setting Mode’. Press ‘+’ three
times to move to Netclient setting mode.
The 2nd, 3rd and 4th bytes of the
IP address will apear before the
Subnet mask setting.
The 2nd, 3rd and 4th bytes of the
Subnet mask will apear before
the Gateway address setting.
Function ‘Netclient Setting Mode’. Press
‘^’ to select.
Netclient Setting Mode, with IP address
1st byte flashing.
Netclient Setting Mode, with Subnet
mask 1st byte flashing.
Netclient Setting Mode, with Gateway
address 1st byte flashing.
Use ‘+’ and ‘-’ to change setting.
Use ‘+’ and ‘-’ to change setting.
Use ‘+’ and ‘-’ to change setting.
The 2nd, 3rd and 4th bytes of the
Gateway address will apear before
the NTP Server IP address setting.
D-3
Netclient Setting Mode, with NTP Server
IP Address 1st byte flashing.
IP Address 2nd byte flashing.
Use ‘+’ and ‘-’ to change setting.
Use ‘+’ and ‘-’ to change setting.Netclient Setting Mode, with NTP Server
Issue 2.0
TimeLord Master Clocks
Operating and Installation Instructions
Netclient Setting Mode, with NTP Server
IP Address 3rd byte flashing.
Netclient Setting Mode, with NTP Server
IP Address 4th byte flashing.
Netclient Setting Mode, with Network update
flashing. This mode cannot be exited if set to ‘y’.
Normal time display
Use ‘+’ and ‘-’ to change setting.
Use ‘+’ and ‘-’ to change setting.
Use ‘+’ and ‘-’ to change setting. When
set to ‘y’ the netUpdate software on the
TimeLord CDROM can be used to install a
software upgrade into the TimeLord.
(Available on future versions)
Issue 2.0D-4
Vortex Communications Ltd
75 The Grove, Ealing, London. W5 5LL
Email: info@vtx.co.uk WWW: http://www.vtx.co.uk
Telephone: +44 (0) 20 8579 2743
Fax: +44 (0) 20 8840 0018
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.