Von Duprin CX33A, CX98, CX35A, CX99 Installation Instructions Manual


911352-00
Chexit Device
CX98/99
Installation Instructions - Electrical
PUSH UNTIL ALARM SOUNDS
DOOR CAN BE OPENED
IN 15 SECONDS
CX Exit Device
(CX98/99 Rim shown)
Chexit Module
Cable
Door Sign
GENERAL INFORMATION
The Von Duprin Chexit device is designed for accident hazard or fire exit applications. It meets both life safety and security needs as well as all requirements of NFPA101® for “Special Locking Arrangement” and UBC “Special Egress-Control Devices.”
The Von Duprin Chexit device sounds an alarm and keeps an exit door secured for 15 seconds following an attempt to exit. The Chexit releases immediately upon a fire alarm condition.
ELECTRICAL SPECIFICATIONS
Voltage .................................................... 24 VDC
Current (Chexit).......................................0.4 A
Current (Electric mortise) ......................... 0.3 A
Current on arming ................................... 300-mS 16-A in-rush
External alarm dry contacts (NO and C) ... 24 VDC, 1 A rating
Normally closed inputs ............................ Fire alarm (FA; required)
External inhibit (EI) Door position switch (DPS)
WARNING
!
Do not exceed rated
specifications.
WARNING
!
The Chexit device must be
installed in accordance
with these instructions by
a qualified electrician.
Customer Service
1-877-671-7011 www.allegion.com
WARNING
!
Wiring must be in
accordance with all local
codes and regulations.
911352-00 Rev. 01/14-d
© Allegion 2014
Printed in U.S.A.
PRE-INSTALLATION CHECKLIST
Complete the items on the checklist below before installing the Chexit module. Each component listed should be prepared and installed according to the installation instructions supplied with it.
Mechanical Preparation
1. Door and frame have been prepared for power transfer.
2. Chexit device has been installed. (See instructions packaged with Chexit device.)
3. Trim such as a lever handle, if used, has been installed.
4. Suggested: Obtain a 1 1/4” mortise cylinder. (It is easier to install the mortise cylinder
during electrical installation than after electrical installation.)
Electrical Preparation
1. Read all of these instructions before installing the Chexit module.
2. If available, get a wiring diagram for your installation. Otherwise, refer to Figures 2, 3, 5, 7 and
Table 1 in “Typical Wiring” and mark the components you use in Table 1.
3. Determine the physical location of each component used (see Figure 1, 4, and 6).
4. Pull field wiring between component locations and frame side of power transfer (see Figure 1, 4,
and 6).
!
The wiring requirements in Table 2 in
“Typical Wiring” must be followed.
5. Mount components and connect them to field wiring (see Figure 2, 3, 5, or 7).
6. Connect field wiring to frame side of power transfer. (Route wires through frame back box.)
!
Components must be connected to
wire colors as shown in Figures 2, 3,
5, and 7 in “Typical Wiring.”
7. Install frame back box and frame side of power transfer.
8. Get requirements for Chexit option switches, record in Table 3 in “Options,” and set switches.
IMPORTANT
IMPORTANT
9. Complete steps 1 through 9 of “Installation.”
To install mortise cylinder after electrical installation:
1. Remove end cap and end cap bracket (see “Installation” step No. 1).
2. Slide cover plate out until knurled ring is visible; install cylinder (see “Installation” step No. 4).
3. Complete steps No. 4, 6, 7, and 9 of “Installation.”
2
Table 1. Installation Components
FIRE
ComponentPicture
PS914
24 VDC power supply
E7500 Electric Mortise Lock
Building fire alarm
(normally closed contacts)
Power transfer
(EPT-10 shown)
External inhibit device
(card reader, key switch, etc.)
Rim and vertical -
(normally closed contacts)
Electric Mortise Fail safe -
(normally closed contacts)
Electric Mortise Fail secure -
(normally open contacts)
Door position switch
(normally closed contacts)
External horn
Function
Supplies power to Chexit
Serves as locking device on
CXE9975 mortise applications
Unlocks Chexit in case
of fire alarm
Transfers electrical power
through frame to door
(wires concealed)
Allows authorized egress
or ingress without alarm
Allows authorized egress
or ingress without alarm
Allows authorized egress
or ingress without alarm
Arms Chexit 2.5 seconds
after door closes; sounds
alarm if door forced open
Provides louder alarm than
Chexit internal horn
Optional/Required If Not Used...
Required
(Von Duprin PS914)
Optional
(for CXE9975)
Required
Highly
recommended
Optional (wire multiple
external inhibit devices
in series)
Used?
Yes
Yes
Yes
Required
Optional
(for CXE9975)
Required
Use door loop or
electric hinge
Connect green
wire to
white wire
Optional (wire multiple
external inhibit devices
in series)
Optional (wire multiple
external inhibit devices
in parallel)
Connect orange
Optional
wire to white
wire
Insulate blue and
Optional
brown wires
separately
Table 2. Wiring Requirements
Type of Power
Wiring
Transfer
(door to frame)
Power Supply Input
N/A
EPT-10
Power Supply Output
(+24 and GND)
EPT-10
Electric Hinge
Electric Hinge
External Alarm, Fire Alarm,
Door Position Switch,
External Inhibit Device
!
EPT-10,
Electric Hinge
IMPORTANT
The wiring requirements in Table 2
above must be followed.
3
Maximum Wire
Length from Power
Supply to Power
Transfer
Per code
100 feet
200 feet
75 feet
150 feet
Not critical
Minimum
Wire Gauge
Per code
14 GA
12 GA
14 GA
12 GA
18-22 GA
Table 3. Wire Functions
Red
Blue
Brown
Violet
Gray
Yellow
Orange
Green
White
Black
+24
C
NO
CM-
CM+
FA
DPS
E I
SC
GND
Power supply +24 VDC
Common for NO output; 24 VDC, 1 A maximum
Normally open output; closes during alarm
Communication line; used to connect Chexits
Communication line; used to connect Chexits
Fire alarm input; 0 VDC = fire, 24 VDC = no fire
Door position switch input; 0 VDC = door open, 24 VDC = door closed
External inhibit input; 0 VDC = Chexit inhibited, 24 VDC = Chexit active
Signal common +24 VDC; can be used to power FA, DPS, and EI inputs
Power supply ground
Loading...
+ 5 hidden pages