Von Duprin 5100 Installation Instructions Manual

*931029-00*
Figure 2
1.
2.
931029-00
Electric Strike
For lock preparation, see lock instructions.
5100
Installation Instructions
Install correct faceplate onto strike (Figure 1).
#10-24 flat head
nyloc screws
4-7/8”
Standard ANSI,
Sharp Corner
4-7/8”
Standard ANSI,
Round Corner
7-15/16” Long,
Round Corner
Figure 1
Prepare frame for strike (see page 4 for dimensions).
3.
Note: Prepare room for RCP rectifier if needed.
Make sure strike operates in correct mode. Lip of fail-safe (FS) strike can be moved when strike is not powered. Lip of
4.
fail-secure (FSE) strike cannot be moved when strike is not powered. If necessary, remove backbox cover (Figure 2) and change strike mode by repositioning actuator (Figure 3).
Wiring must
stay in slot
Backbox cover
NOTE
!
When using the electric strike in fail-secure mode, the local
authority having jurisdiction shall be consulted to assure
compliance in allowing emergency exit from the secured area.
Actuator
Actuator
Figure 3
Page 2 of 4
1
5.
Check power source voltage (12 or 24 VAC or VDC).
When using 12 VAC or 24 VAC power, install SO kit to convert AC power to DC (Figure 4).
6.
7. Wire strike solenoid for proper voltage (Figure 5). Caution: Do not connect 24 VDC to 12 VDC configured strike.
For DC operation, Von Duprin PS 861 and Locknetics 593 DC series power supplies
are recommended.
AC operation, Von Duprin SO-12 or 24
For AC/DC convertor kit (shown below) is recommended.
White
White
SO kit
Yellow for 12 V
Red for 24 V
Figure 4
SOLENOID POWER
REQUIREMENTS
12 VDC, 0.38 A 24 VDC, 0.19 A
Black
Red
12 VDC input
nonpolarized
tuptuo CDV 21tupni CAV 2
Red-White
Black
Black-White
24 VDC Strike Wiring
Red
24 VDC input
nonpolarized
tuptuo CDV 42tupni CAV 42
Black
Red-White
Black-White
Figure 5
8. Test strike: Apply solenoid power. Fail secure (FSE) lip unlocks. Fail safe (FS) lip locks.
9. If cut-out for strike is too large along edge (Figure 6), cut neoprene filler and stick onto strike as shown (Figure 7).
Note: This could occur in some retrofit applications.
12 VDC Strike Wiring
Figure 6
Neoprene filler
Cut to length and
stick on strike
Figure 7
Gap filled