ABOUT THIS MANUAL ..................................................................................................................................... 1
Features ........................................................................................................................................................... 2
Basic System Architecture ............................................................................................................................... 2
Unpacking and Inspection ................................................................................................................................ 4
Mounting the Unit ............................................................................................................................................. 4
AC Input/Output Connection ............................................................................................................................ 6
Final Assembly ................................................................................................................................................. 9
Communication Connection ............................................................................................................................. 9
Dry Contact Signal ......................................................................................................................................... 10
Power ON/OFF .............................................................................................................................................. 1 1
Operation and Display Panel ......................................................................................................................... 1 1
This manual describes the assembly, installation, operation and troubleshooting of this unit. Please read
this manual carefully before installations and operations. Keep this manual for future reference.
Scope
This manual provides safety and installation guidelines as well as information on tools and wiring.
SAFETY INSTRUCTIONS
WARNING: This chapter contains important safety and operating instructions. Read and
keep this manual for future reference.
1. Before using the unit, read all instructions and cautionary markings on the unit, the batteries and all
appropriate sections of this manual.
2. CAUTION --To reduce risk of injury, charge only deep-cycle lead acid type rechargeable batteries.
Other types of batteries may burst, causing personal injury and damage.
3. Do not disassemble the unit. Take it to a qualified service center when service or repair is required.
Incorrect re-assembly may result in a risk of electric shock or fire.
4. To reduce risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning.
Turning off the unit will not reduce this risk.
5. CAUTION – Only qualified personnel can install this device with battery.
6. NEVER charge a frozen battery.
7. For optimum operation of this inverter/charger, please follow required spec to select appropriate cable
size. It’s very important to correctly operate this inverter/charger.
8. Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop
a tool to spark or short circuit batteries or other electrical parts and could cause an explosion.
9. Please strictly follow installation procedure when you want to disconnect AC or DC terminals. Please
refer to INSTALLATION section of this manual for the details.
10. Fuses (3pcs 63A, 65VDC for 12VDC and 24VDC units) are provided as over-current protection for the
battery supply.
11. GROUNDING INSTRUCTIONS -This inverter/charger should be connected to a permanent grounded
wiring system. Be sure to comply with local requirements and regulation to install this inverter.
12. NEVER cause AC output and DC input short circuited. Do NOT connect to the mains when DC input
short circuits.
13. Warning!! Only qualified service persons are able to service this device. If errors still persist after
following troubleshooting table, please send this inverter/charger back to local dealer or service center
for maintenance.
1
Page 5
INTRODUCTION
This is a multi-function inverter/charger, combining functions of inverter, solar charger and battery charger to
offer uninterruptible power support with portable size. Its comprehensive LCD display offers
user-configurable and easy-accessible button operation such as battery charging current, AC/solar charger
priority, and acceptable input voltage based on different applications.
There are two different types of built-in solar chargers: PWM or MPPT solar charger. For the detailed product
specification, please consult your local dealers.
Features
Pure sine wave inverter
Configurable input voltage range for home appliances and personal computers via LCD setting
Configurable battery charging current based on applications via LCD setting
Configurable AC/Solar Charger priority via LCD setting
Compatible to mains voltage or generator power
Auto restart while AC is recovering
Overload/ Over temperature/ short circuit protection
Smart battery charger design for optimized battery performance
Cold start function
Basic System Architecture
The following illustration shows basic application for this inverter/charger. It also includes following devices to
have a complete running system:
Generator or Utility.
PV modules (option)
Consult with your system integrator for other possible system architectures depending on your requirements.
This inverter can power all kinds of appliances in home or office environment, including motor-type appliances
such as tube light, fan, refrigerator and air conditioner.
Figure 1 Hybrid Power System
2
Page 6
Product Overview
1. LCD display
2. Status indicator
3. Charging indicator
4. Fault indicator
5. Function buttons
6. Power on/off switch
7. AC input
8. AC output
9. PV input
10. Battery input
11. Circuit breaker
12. USB communication port
13. Dry contact
3
Page 7
INSTALLATION
Unpacking and Inspection
Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. You should
have received the following items inside of package:
The unit x 1
User manual x 1
USB Communication cable x 1
Software CD x 1
Preparation
Before connecting all wirings, please take off bottom cover by removing two screws as shown below.
Mounting the Unit
Consider the following points before selecting where to install:
Do not mount the inverter on flammable construction
materials.
Mount on a solid surface
Install this inverter at eye level in order to allow the LCD
display to be read at all times.
For proper air circulation to dissipate heat, allow a clearance
of approx. 20 cm to the side and approx. 50 cm above and
below the unit.
The ambient temperature should be between -20°C and
55°C to ensure optimal operation.
The recommended installation position is to be adhered to
the wall vertically.
Be sure to keep other objects and surfaces as shown in the
diagram to guarantee sufficient heat dissipation and to
have enough space for removing wires.
SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY.
4
Page 8
Install the unit by screwing three screws.
Battery Connection
CAUTION: For safety operation and regulation compliance, it’s requested to install a separate DC over-current
protector or disconnect device between battery and inverter. It may not be requested to have a disconnect
device in some applications, however, it’s still requested to have over-current protection installed. Please refer
to typical amperage in below table as required fuse or breaker size.
WARNING! All wiring must be performed by a qualified personnel.
WARNING! It's very important for system safety and efficient operation to use
appropriate cable for battery connection. To reduce risk of injury, please use the
proper recommended cable and terminal size as below.
Recommended battery cable and terminal size:
Ring terminal:
Ring Terminal
Dimensions
2
D (mm)L (mm)
Torque
value
Model
Typical
Amperage
Battery
capacity
Wire Size
Cable
mm
1.5KVA 24V 50A 100AH 1*8WG 8 6.4 23.8 2~ 3 Nm
1.5KVA 12V
3KVA 24V
100A
100AH
200AH
1*4AWG 22 6.4 33.2
2~ 3 Nm
2*8AWG 14 6.4 29.2
Please follow below steps to implement battery connection:
1. Assemble battery ring terminal based on recommended battery cable and terminal size.
2. Connect all battery packs as the unit is required. It’s suggested to connect at least 100Ah capacity battery
to the unit.
NOTE: Please only use sealed lead acid battery or sealed GEL/AGM lead-acid battery.
3. Insert the ring terminal of battery cable flatly into battery connector of inverter and make sure the bolts are
tightened with torque of 2-3 Nm. Make sure polarity at both the battery and the inverter/charge is correctly
connected and ring terminals are tightly screwed to the battery terminals.
5
Page 9
WARNING: Shock Hazard
Installation must be performed with care due to high battery voltage in series.
CAUTION!! Do not place anything between the flat part of the inverter terminal and the ring
terminal. Otherwise, overheating may occur.
CAUTION!! Do not apply anti-oxidant substance on the terminals before terminals are
connected tightly.
CAUTION!! Before making the f inal DC connection or closing DC breaker/disconnector, be sure
positive (+) must be connected to positive (+) and negative (-) must be connected to negative
(-).
AC Input/Output Connection
CAUTION!! Before connecting to AC input power source, please install a separate AC breaker between
inverter and AC input power source. This will ensure the inverter can be securely disconnected during
maintenance and fully protected from over current of AC input. The recommended spec of AC breaker is 20A
for 1.5KVA and 30A for 3KVA.
CAUTION!! There are two terminal blocks with “IN” and “OUT” markings. Please do NOT mis-connect input
and output connectors.
WARNING! All wiring must be performed by a qualified personnel.
WARNING! It's very important for system safety and efficient operation to use appropriate cable for AC input
connection. To reduce risk of injury, please use the proper recommended cable size as below.
Suggested cable requirement for AC wires
Model Gauge Torque Value
1.5KVA 16 AWG 0.5~ 0.6 Nm
3KVA 12 AWG 1.2~ 1.6 Nm
Please follow below steps to implement AC input/output connection:
1. Before making AC input/output connection, be sure to open DC protector or disconnector first.
2. Remove insulation sleeve 10mm for six conductors. And shorten phase L and neutral conductor N 3 mm.
3. Insert AC input wires according to polarities indicated on terminal block and tighten the terminal screws. Be
sure to connect PE protective conductor (
→Ground (yellow-green)
L→LINE (brown or black)
N→Neutral (blue)
) first.
6
Page 10
WARNING:
Be sure that AC power source is disconnected before attempting to hardwire it to the unit.
4. Then, insert AC output wires according to polarities indicated on terminal block and tighten terminal screws.
Be sure to connect PE protective conductor (
) first.
→Ground (yellow-green)
L→LINE (brown or black)
N→Neutral (blue)
5. Make sure the wires are securely connected.
CAUTION: Important
Be sure to connect AC wires with correct polarity. If L and N wires are connected reversely, it may cause utility
short-circuited when these inverters are worked in parallel operation.
CAUTION: Appliances such as air conditioner are required at least 2~3 minutes to restart because it’s required
to have enough time to balance refrigerant gas inside of circuits. If a power shortage occurs and recovers in a
short time, it will cause damage to your connected appliances. To prevent this kind of damage, please check
manufacturer of air conditioner if it’s equipped with time-delay function before installation. Otherwise, this
inverter/charger will trig overload fault and cut off output to protect your appliance but sometimes it still causes
internal damage to the air conditioner.
7
Page 11
PV Connection
CAUTION: Before connecting to PV modules, please install separately a DC circuit breaker between inverter
and PV modules.
WARNING! All wiring must be performed by a qualified personnel.
PV Module Selection:
WARNING! It's very important for system safety and efficient operation to use appropriate cable for PV
module connection. To reduce risk of injury, please use the proper recommended cable size as below.
When selecting proper PV modules, please be sure to consider below requirements first:
1. Open circuit Voltage (Voc) of PV modules not exceeds max. PV array open circuit voltage of inverter.
Charging Current (PWM) 50Amp
System DC Voltage 12Vdc 24Vdc
Operating Voltage Range 15~18Vdc 30~32Vdc
Max. PV Array Open Circuit Voltage 50Vdc 75Vdc
2. Max. Power Voltage (Vmpp) of PV modules should be close to best Vmp of inverter or within Vmp range to
get best performance. If one PV module can not meet this requirement, it’s necessary to have several PV
modules in series connection.
Maximum PV module numbers in Series: Vmpp of PV module * X pcs ≒ Best Vmp of Inverter or Vmp
range
PV module numbers in Parallel: Max. charging current of inverter / Impp
Total PV module numbers = maximum PV module numbers in series * PV module numbers in
parallel
Take 12Vdc unit inverter as an example to select proper PV modules. After considering Voc of PV module not
exceeds 50Vdc and max. Vmpp of PV module close to 15Vdc or within 15Vdc ~ 18Vdc, we can choose PV
module with below specification.
Maximum Power (Pmax) 85W Max. PV module numbers in series
Max. Power Voltage Vmpp(V) 17.6V
Max. Power Current Impp(A) 4.83A PV module numbers in parallel
Open Circuit Voltage Voc(V) 21.6V
Short Circuit Current Isc(A) 5.03A
Maximum PV module numbers in Series: 1
PV module numbers in Parallel: 10
Total PV module numbers: 1 x 10 = 10
Take 24Vdc unit inverter as an example to select proper PV module. After considering Voc of PV module not
exceed 75Vdc and max. Vmpp of PV module close to 30Vdc or within 30Vdc ~ 32Vdc, we can choos e PV module
with below specification.
Maximum Power (Pmax) 260W Max. PV module numbers in series
Max. Power Voltage Vmpp(V) 30.9V
Max. Power Current Impp(A) 8.42A PV module numbers in parallel
Open Circuit Voltage Voc(V) 37.7V
Short Circuit Current Isc(A) 8.89A
Maximum PV module numbers in Series: 1
PV module numbers in Parallel: 6
Total PV module numbers: 1 x 6 = 6
(Only for the model with built-in PWM solar charger)
Typical Amperage Gauge Torque Value
50A 8 AWG 1.4~1.6 Nm
1 17.6 x 1 ≒ 15 ~ 18
10 50 A / 4.83
Total PV module numbers
1 x 10 = 10
1 30.9 x 1 ≒ 30 ~ 32
6 50 A / 8.42
Total PV module numbers
1 x 6 = 6
8
Page 12
PV Module Selection: (Only for the model with built-in MPPT solar charger)
When selecting proper PV modules, please be sure to consider below parameters:
3. Open circuit Voltage (Voc) of PV modules not exceeds max. PV array open circuit voltage of inverter.
4. Open circuit Voltage (Voc) of PV modules should be higher than min. battery voltage.
INVERTER MODEL 12Vdc 24Vdc
Max. PV Array Open Circuit Voltage 100Vdc
PV Array MPPT Voltage Range 15~80Vdc30~80Vdc
Please follow below steps to implement PV module connection:
1. Remove insulation sleeve 10 mm for positive and negative conductors.
2. Check correct polarity of connection cable from PV modules and PV input
connectors. Then, connect positive pole (+) of connection cable to positive
pole (+) of PV input connector. Connect negative pole (-) of connection
cable to negative pole (-) of PV input connector.
3. Make sure the wires are securely connected.
Final Assembly
After connecting all wirings, please put bottom cover back by screwing two screws as shown below.
Communication Connection
Please use supplied communication cable to connect to inverter and PC. Insert bundled CD into a computer and
follow on-screen instruction to install the monitoring software. For the detailed software operation, please
check user manual of software inside of CD.
9
Page 13
Dry Contact Signal
There is one dry contact (3A/250VAC) available on the rear panel. It could be used to deliver signal to external
device when battery voltage reaches warning level.
Unit Status Condition
Dry contact port:
NC & C NO & C
Power Off Unit is off and no output is powered. Close Open
Power On
Output is powered from Utility. Close Open
Output is
powered
from Battery
or Solar.
Program 01
set as Utility
Program 01 is
set as SBU or
Solar first
Battery voltage < Low DC
warning voltage
Battery voltage > Setting
value in Program 21 or
battery charging reaches
floating stage
Battery voltage < Setting
value in Program 20
Battery voltage > Setting
value in Program 21 or
battery charging reaches
floating stage
Open Close
Open
Close
Close
Open
Close Open
10
Page 14
OPERATION
Power ON/OFF
Once the unit has been properly installed and the batteries are connected well, simply press On/Off switch
(located on the button of the case) to turn on the unit.
Operation and Display Panel
The operation and display panel, shown in below chart, is on the front panel of the inverter. It includes
three indicators, four function keys and a LCD display, indicating the operating status and input/output
power information.
LCD display
LED indicators
Function keys
LED Indicator
LED Indicator
Green
Function Keys
Function Key Description
ESC To exit setting mode
UP To go to previous selection
DOWN To go to next selection
ENTER To confirm the selection in setting mode or enter setting mode
Green
Red
Solid On Output is powered by utility in Line mode.
Flashing Output is powered by battery or PV in battery mode.
Solid On Battery is fully charged.
Flashing Battery is charging.
Solid On Fault occurs in the inverter.
Flashing
Warning condition occurs in the inverter.
Messages
11
Page 15
LCD Display Icons
Icon Function description
Input Source Information
Configuration Program and Fault Information
Output Information
Indicates the AC input.
Indicates the PV input
Indicate input voltage, input frequency, PV voltage, battery voltage and charger
current.
Indicates the setting programs.
Indicates the warning and fault codes.
Warning:
Fault:
Indicate output voltage, output frequency, load percent, load in VA, load in Watt
and discharging current.
flashing with warning code.
lighting with fault code
Battery Information
Indicates battery level by 0-24%, 25-49%, 50-74% and 75-100% and charging
status.
Indicates the battery type: AGM, Flooded or User-defined battery.
It will present battery capacity when unit is charging.
Status Battery voltage LCD Display
Constant
Current mode /
Constant
<2V/cell 4 bars will flash in turns.
2 ~ 2.083V/cell
2.083 ~ 2.167V/cell
Bottom bar will be on and the other three
bars will flash in turns.
Bottom two bars will be on and the other
two bars will flash in turns.
12
Page 16
Voltage mode
Floating mode. Batteries are fully charged. 4 bars will be on.
> 2.167 V/cell
Bottom three bars will be on and the top
bar will flash.
Battery level icon will present battery capacity when unit is discharged.
Load Percentage Battery Voltage LCD Display
< 1.817V/cell
1.817V/cell ~ 1.9V/cell
Load >20%
1.9 ~ 1.983V/cell
Load < 20%
Load Information
Indicates overload.
Indicates the load level by 0-24%, 25-50%, 50-74% and 75-100%.
0%~25% 25%~50% 50%~75% 75%~100%
Mode Operation Information
> 1.983 V/cell
< 1.867V/cell
1.867V/cell ~ 1.95V/cell
1.95 ~ 2.033V/cell
> 2.033/cell
Mute Operation
Indicates unit connects to the mains.
Indicates unit connects to the PV panel.
Indicates load is supplied by utility power.
Indicates the utility charger circuit is working.
Indicates the solar charger circuit is working.
Indicates the solar charger is MPPT type.
Indicates the DC/AC inverter circuit is working.
Indicates unit alarm is disabled.
13
Page 17
LCD Setting
After pressing and holding ENTER button for 3 seconds, the unit will enter setting mode. Press “UP” or “DOWN”
button to select setting programs. And then, press “ENTER” button to confirm the selection or ESC button to
exit.
Setting Programs:
Program Description Selectable option
Escape
00 Exit setting mode
Solar energy provides power to the
loads as first priority.
If solar energy is not sufficient to
power all connected loads, battery
energy will supply power to the
loads at the same time.
Utility provides power to the loads
only when any one condition
happens:
- Solar energy is not available.
- Battery voltage drops to low-level
warning voltage or the setting point
in program 20.
Utility will provide power to the
loads as first priority.
Solar and battery energy will
provide power to the loads only
when utility power is not available.
Solar energy provides power to the
loads as first priority.
If solar energy is not sufficient to
power all connected loads, battery
energy will supply power to the
loads at the same time.
Utility provides power to the loads
only when battery voltage drops to
either low-level warning voltage or
the setting point in program 20.
voltage range will be within
90-280VAC.
If selected, acceptable AC input
voltage range will be within
170-280VAC.
Output source priority:
01
02AC input voltage range
To configure load power
source priority
Solar first
Utility first (default)
SBU priority
Appliances (default) If selected, acceptable AC input
UPS
14
Page 18
220Vac
230V (Default)
03Output voltage
04Output frequency
05
Power saving mode
enable/disable
Overload bypass:
When enabled, the unit will
06
transfer to line mode if
overload occurs in battery
mode.
07
Auto restart when overload
occurs
240Vac
50Hz (default) 60Hz
Saving mode disable
(default)
If disabled, no matter connected
load is low or high, the on/off
status of inverter output will not be
effected.
Saving mode enable
If enabled, the output of inverter
will be off when connected load is
pretty low or not detected.
Bypass disable (default)
Bypass enable
Restart disable (default)
Restart disable (default)
Restart enable
Restart enable
08
10
Auto restart when over
temperature occurs
Charger source priority:
To configure charger
source priority
If this inverter/charger is working in Line, Standby or Fault
mode, charger source can be programmed as below:
Solar first
Solar energy will charge battery as
first priority.
Utility will charge battery only when
solar energy is not available.
Utility first
Utility will charge battery as first
priority.
Solar energy will charge battery
only when utility power is not
available.
Solar and Utility
(default)
Solar energy and utility will charge
battery at the same time.
Only Solar
15
Solar energy will be the only
charger source no matter utility is
available or not.
Page 19
11
Maximum charging current:
To configure total charging
current for solar and utility
chargers.
(Max. charging current =
utility charging current +
solar charging current)
If this inverter/charger is working in Battery mode or Power
saving mode, only solar energy can charge battery. Solar
energy will charge battery if it's available and sufficient.
60A (default)
40A (default for unit
with MPPT solar
charger)
For unit with MPPT solar charger,
setting range is from 10A to 100A.
For unit with PWM solar charger,
setting range is from 10A to 110A.
Increment of each click is 10A.
When the unit is built with MPPT
solar charger, default setting is 40A.
Setting range is from 10A to 40A
and increment of each click is 10A.
12
13
Maximum solar charging
current
Maximum utility charging
current
50A (default for unit
with PWM solar
charger)
2A
20A 30A (default)
40A 50A
60A
When the unit is built with PWM
solar charger, default setting is 50A.
Setting range is from 10A to 50A
and increment of each click is 10A.
10A
14Battery type
15Charger stage selection
AGM (default)
User-Defined
Auto
16
Flooded
If “User-Defined” is selected,
battery charge voltage and low DC
cut-off voltage can be set up in
program 17, 18 and 19.
2 Step
Page 20
3 Step
16CV charging time setting
Auto
10min
40min
90min
150min
No CV charging time
20min
60min
120min
180min
17
Bulk charging voltage
(C.V voltage)
210min
240min
12V model default setting: 14.1V
24V model default setting: 28.2V
If self-defined is selected in program 14, this program can be
set up. Setting range is from 12.0V to 15.3V for 12Vdc model
and 24.0V to 30.6V for 24Vdc model.
Increment of each click is 0.1V.
12V model default setting: 13.5V
18Floating charging voltage
24V model default setting: 27.0V
17
Page 21
If self-defined is selected in program 14, this program can be
set up. Setting range is from 12.0V to 15.3V for 12Vdc model
and 24.0V to 30.6V for 24Vdc model.
Increment of each click is 0.1V.
12V model default setting: 10.2V
24V model default setting: 20.4V
19
Low DC cut off battery
voltage setting
If self-defined is selected in program 14, this program can be
set up. Setting range is from 10.2V to 12.0V for 12Vdc model
and 20.4V to 24V for 24Vdc model. Increment of each click is
0.1V. Low DC cut-off voltage will be fixed to setting value no
matter what percentage of load is connected.
Available options for 12V models:
11.0V
11.3V
11.5V (default) 11.8V
12.0V
12.3V
20
Setting voltage point back
to utility source when
selecting “SBU priority” or
“Solar first” in program 01.
12.5V
12.8V
Available options for 24V models:
22.0V 22.5V
23.0V (default)
23.5V
24.0V 24.5V
18
Page 22
25.0V 25.5V
Available options for 12V models:
Battery fully charged 12.0V
21
Setting voltage point back
to battery mode when
selecting “SBU priority” or
“Solar first” in program 01.
12.3V
12.8V 13.0V
13.3V
13.8V
14.3V
12.5V
13.5V (default)
14.0V
14.5V
Available options for 24V models:
Battery fully charged 24V
24.5V
25V
25.5V 26V
26.5V
27V (default)
19
Page 23
27.5V
28V
22
23
Auto return to default
display screen
Backlight control
28.5V
Return to default
display screen (default)
29V
If selected, no matter how users
switch display screen, it will
automatically return to default
display screen (Input voltage
/output voltage) after no button is
pressed for 1 minute.
Stay at latest screen If selected, the display screen will
stay at latest screen user finally
switches.
Backlight on (default) Backlight off
24Alarm control
25
27
Beeps while primary source
is interrupted
Record Fault code
Alarm on (default)
Alarm on (default)
Record enable(default)
Alarm off
Alarm off
Record disable
20
Page 24
Display Setting
The LCD display information will be switched in turns by pressing “UP” or “DOWN” key. The selectable
information is switched as below order: input voltage/output voltage, input frequency, PV voltage,
charging current, output frequency, load percentage, load in VA, load in Watt, battery voltage/DC
discharging current, main CPU Version and secondary CPU Version.
Selectable information LCD display
Input Voltage=230V, output voltage=230V
Input voltage/Output voltage
(Default Display Screen)
Input frequency=50Hz
Input frequency
PV voltage=60V
PV voltage
Charging current
Output frequency
Load percentage
Charging current=80A
Output frequency=50Hz
Load percent=60%
21
Page 25
When connected load is lower than 1kVA, load in
VA will present xxxVA like below chart.
Load in VA
Load in Watt
When load is larger than 1kVA (≧1KVA), load in
VA will present x.xkVA like below chart.
When load is lower than 1kW, load in W will
present xxxW like below chart.
When load is larger than 1kW (≧1KW), load in W
will present x.xkW like below chart.
Battery voltage/ DC discharging current
Main CPU version checking
Secondary CPU version checking
Battery voltage=25.8V, discharging current=80A
Main CPU version 00001.00
Secondary CPU version 00001.00
22
Page 26
Operating Mode Description
Operation mode Description LCD display
Standby mode / Power
saving mode/ Fault mode
Note:
*Standby mode: The inverter
is not turned on yet but at this
time, the inverter can charge
battery without AC output.
*Power saving mode: If
enabled, the output of inverter
will be off when connected
load is pretty low or not
detected.
*Fault mode: Errors are
caused by inside circuit error
or external reasons such as
over temperature, output
short circuited and so on.
No output is supplied by the
unit but it still can charge
batteries.
Charging by utility and PV energy.
Charging by utility.
Charging by PV energy.
No charging.
Line Mode
Battery Mode
The unit will provide output
power from the mains. It
will also charge the battery
at line mode.
The unit will provide output
power from battery and PV
energy.
Charging by utility and PV energy.
Charging by utility.
Charging by PV energy.
Power from battery and PV energy.
Power from battery only.
23
Page 27
Fault Reference Code
Fault Code Fault Event Icon on
01 Fan is locked when inverter is off.
02 Over temperature
03 Battery voltage is too high
05
06 Output voltage is too high.
07 Overload time out
08 Bus voltage is too high
09 Bus soft start failed
51 Over current or surge
52 Bus voltage is too low
53 Inverter soft start failed
55 Over DC voltage in AC output
56 Battery detection circuit error
Output short circuited.
57 Current sensor failed
58 Output voltage is too low
Warning Indicator
Warning
Code
01
03 Battery is over-chargedBeep once every second
04 Low battery Beep once every second
07 Overload Beep once every 0.5 second
10 Output power derating Beep twice every 3 seconds
Warning Event Audible Alarm Icon flashing
Fan is locked when
inverter is on.
Beep three times every
second
24
Page 28
SPECIFICATIONS
Table 1 Line Mode Specifications
INVERTER MODEL 1.5K-12V / 1.5K-24V / 3K-24V
Input Voltage Waveform Sinusoidal (utility or generator)
Nominal Input Voltage 220/230/240Vac
Low Loss Voltage
Low Loss Return Voltage
High Loss Voltage 280Vac±7V
High Loss Return Voltage 270Vac±7V
Max AC Input Voltage 300Vac
Nominal Input Frequency 50Hz / 60Hz (Auto detection)
Low Loss Frequency 40±1Hz
Low Loss Return Frequency 42±1Hz
High Loss Frequency 65±1Hz
High Loss Return Frequency 63±1Hz
Output Short Circuit Protection Circuit Breaker
Efficiency (Line Mode) >95% ( Rated R load, battery full charged )
170Vac±7V (UPS);
90Vac±7V (Appliances)
180Vac±7V (UPS);
100Vac±7V (Appliances)
Transfer Time
Output power derating:
When AC input voltage drops to 170V,
the output power will be de-rated.
10ms typical (UPS);
20ms typical (Appliances)
25
Page 29
Table 2 Inverter Mode Specifications
Inverter Mode
Inverter Model
Rated Output Power
Output Voltage Waveform
Output Voltage Regulation
Output Frequency
Peak Eff iciency
Overload Protection
Surge Capacity
Nominal DC Voltage
Cold Start Voltage
Low DC Warning Voltage
@ load < 20%
@ load ≥ 20%
Low DC Warning Recovery Voltage
@ load < 20%
@ load ≥ 20%
Low DC Cut-off Voltage
@ load < 20%
@ load ≥ 20%
High DC Recovery Voltage
High DC Cut-off Voltage
1.5K-12V 1.5K-24V 3K-24V
1500VA/1200W 3000VA/2400W
Pure Sine Wave
220Vac/230Vac/240Vac±5%
50Hz
90%
5s@≥150% load; 10s@110%~150% load
2 x rated power for 5sec
12Vdc 24Vdc
11.5Vdc 23.0Vdc
11.0Vdc
10.7Vdc
22.0Vdc
21.4Vdc
11.5Vdc
11.2Vdc
23.0Vdc
22.4Vdc
10.5Vdc
10.2Vdc
21.0Vdc
20.4Vdc
15.0Vdc 31.0Vdc
16.0Vdc 32.0Vdc
DC Voltage Accuracy +/-0.3%V@ no load
THDV
DC Offset
<3% for linear load,<5% for non-linear load @ nominal voltage
≦100mV
No Load Power Consumption
Saving Mode Power Consumption
<25W
<10W
26
Page 30
Table 3 Charge Mode Specifications
INVERTER MODEL 1.5K-12V 1.5K-24V / 3K-24V
Charging Algorithm 3-Step
Utility Charging Mode
AC Charging Current 2/10/20/30/40/50/60Amp (@V
Bulk Charging
Voltage
Flooded Battery 14.6Vdc 29.2Vdc
AGM / Gel Battery 14.1Vdc 28.2Vdc
=230Vac)
I/P
Floating Charging Voltage 13.5Vdc 27.0Vdc
Charging Curve
PWM Solar Charging Mode
Charging Current 50Amp
System DC Voltage 12Vdc 24Vdc
Operating Voltage Range 15~18Vdc 30~32Vdc
Max. PV Array Open Circuit Voltage 50Vdc 75Vdc
DC Voltage Accuracy +/-0.3%
Joint Utility and Solar Charging
Max Charging Current 110Amp
Default Charging Current
60Amp
MPPT Solar Charging Mode
Charging Current
PV Array MPPT Voltage Range
Max. PV Array Open Circuit Voltage
15Vdc ~ 80Vdc 30Vdc ~ 80Vdc
40Amp
100Vdc
DC Voltage Accuracy +/-0.3%
Joint Utility and Solar Charging
Max Charging Current 100Amp
Default Charging Current
60Amp
Table 4 General Specifications
INVERTER MODEL 1.5K-12V / 1.5K-24V / 3K-24V
Safety Certification CE
Operating Temperature Range -20°C to 55°C
Storage temperature -30°C~ 60°C
Humidity
Dimension (DxWxH), mm
Net Weight, kg
5% to 95% Relative Humidity (Non-condensing)
100 x 272 x 355
7
27
Page 31
TROUBLE SHOOTING
Problem LCD/LED/Buzzer Explanation / Possible cause What to do
Unit shuts down
automatically
during startup
process.
No response after
power on.
Mains exist but the
unit works in
battery mode.
Buzzer beeps
continuously and
red LED is on.
LCD/LEDs and buzzer
will be active for 3
seconds and then
complete off.
No indication.
Input voltage is
displayed as 0 on the
LCD and green LED is
flashing.
Green LED is flashing.
Green LED is flashing.
Fault code 07
Fault code 05 Output short circuited.
Fault code 02
Fault code 03
Fault code 01 Fan fault Replace the fan.
Fault code 06/58 Output abnormal.
Fault code
08/09/53/57
Fault code 51 Over current or surge.
Fault code 52 Bus voltage is too low.
Fault code 55 Output voltage is unbalanced.
Fault code 56 Battery detection circuit error.
The battery voltage is too low
(<1.91V/Cell)
1. The battery voltage is far too
low. (<1.4V/Cell)
2. Battery polarity is connected
reversed.
Input protector is tripped
Insufficient quality of AC power.
(Shore or Generator)
Set “Solar First” or “SBU” as the
priority of output source.
Overload error. The inverter is
overload 110% and time is up.
Internal temperature of inverter
component is over 80°C.
Battery is over-charged. Return to repair center.
The battery voltage is too high.
Internal components failed. Return to repair center.
1. Re-charge battery.
2. Replace battery.
1. Check if batteries and the
wiring are connected well.
2. Re-charge battery.
3. Replace battery.
Check if AC breaker is tripped
and AC wiring is connected
well.
1. Check if AC wires are too
thin and/or too long.
2. Check if generator (if
applied) is working well or if
input voltage range setting is
correct. (UPSAppliance)
Change output source priority
to Utility first.
Reduce the connected load by
switching off some
equipment.
Check if wiring is connected
well and remove abnormal
load.
Check whether the air flow of
the unit is blocked or whether
the ambient temperature is
too high.
Check if spec and quantity of
batteries are meet
requirements.
1. Reduce the connected
load.
2. Return to repair center
Restart the unit, if the error
happens again, please return
to repair center.
If the battery is connected
well, please return to repair
center.
28
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.