Voltex VMS-2 Installation Manual

Installation Guide
Voltex Indoor 360°Motion Sensor - IP43 - 2 relay
© Voltex Electrical 2016. All Rights Reserved.
®
1. Power: 220-240V~ 50Hz.
2. Range of detection: 360°, 7m(typ.) diameter at 2.5m height, 20°C. (Figure 1)
3. TIME 1 adjustment: , 30 sec, 1 min, 5 min, 10 min and 30 min, maximum=TEST mode. TIME 2 adjustment: 10 sec, 30 sec, 1 min, 2 min, 3 min, 5 min, 10 min and 15 min.
4. Lux control: Adjustable “Light level” sensing from 5 Lux to 1000 Lux, maximum=LUX
Memory.
5. Load:
1. Turn OFF power at the circuit breaker or fuse.
2. Determine the best location for the sensor.
3. Drill a 64mm diameter hole in the ceiling.
4. Connect as shown in wiring diagram. (Figure 4)
5. Insert the power module into the ceiling first and then fix the sensor with metal spring.
(Figure 2)
Specifications:
Installation:
Warning: This equipment must be installed only by a qualified electrician. Installation must follow local building codes as well as the instruction contained in this manual. Turn off power at circuit breaker or fuse box, to make sure power is off before installation. If you have any doubts about the installation procedure, please consult a professional technician. Determine the best location for the sensor. Install the sensor at least 1 metre away from any light fittings and HVAC ducts or vents. The sensor is to be mounted on ceiling. (Figure 2)
(IP43 from below, as installed)
Connection to the power supply:
1. Note: This sensor
must be installed according to local Wiring Regulations and Code of
Practice.
2. Note: Make sure that the power wiring comes from an external 10A miniature circuit breaker for short circuit protection.
3. Ensure the supply is disconnected at the distribution board before doing with the electrical wiring. If any doubt, check the wire with a voltage tester.
4. Study the wiring diagram below before making any electrical connections. Incorrect wiring of the unit could destroy the sensor.
5. Strip the cable and connect the wires to terminal block. (Figure 3)
6. Connect Brown wire from the supply circuit (incoming active/phase) to the active terminal
(L).
7.
8.
9. Contact T1 and T2 are Dry contacts.
10. Switch on the power and the detector will commence a 60 second warm-up period.
Connect Blue wires (neutrals) from the supply circuit and lamp circuit to the Neutral terminal (N).
Connect the lighting load ("Time 1" Output) to terminal. ( ).
Wire according to Figure 4, for 240 V output on "Time 2" Output
© Voltex Electrical 2016. All Rights Reserved.
®
Cable Size - Min: 1.0mm² Max: 4.0mm²
Loading...
+ 2 hidden pages