Vollrath Modular Drop-In Auto-Fill User Manual

ENGLISH
Operator’s Manual
MODULAR DROP-IN AUTO-FILL
Item Description
26806 Modular Drop-In Auto-Fill 80 PSI 120 16 5-15P
Thank you for purchasing this Vollrath equipment. Before operating the equipment, read and familiarize yourself with the following operating and safety instructions. SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE. Save the original box and packaging. Use this packaging to ship the equipment if repairs are needed.
Pressure
Voltage Watts Plug
Item No. 2350072-1 Rev 10/12
Countertop Warming and display
Safety precaUtionS
To ensure safe operation, read the following statements and understand their meaning. Please read carefully.
WARNING
Warning is used to indicate the presence of a hazard that can cause severe personal injury, death, or substantial property damage if the
warning is ignored.
CAUTION
Caution is used to indicate the presence of a hazard that will or can cause minor personal injury or property damage if the caution is ignored.
NOTE
Note is used to notify people of installation, operation, or maintenance information that is important but not hazard-related.
For Your Safety!
These precautions should be followed at all times. Failure to follow these precautions could result in injury to yourself and others.
To reduce risk of injury or damage to the equipment:
Read and understand all installation and operation instructions before
installing or operating equipment. Have this equipment installed by qualied service personnel. Use only grounded electrical outlets matching the nameplate rated
voltage. Do not spray controls or outside of equipment with liquids or cleaning
agents. The control box must be installed in a dry location. Do not use an extension cord with this equipment. Do not plug this
equipment into a power strip or multi-outlet power cord. Do not operate without water. Keep equipment and power cord away from open ames, electric
burners or excessive heat. Do not operate unattended. Do not operate if equipment has been damaged or is malfunctioning in
any way.
fUnction and pUrpoSe
This product is intended to maintain the water level in a hot food unit at a predetermined level.
This equipment is not intended for household, industrial or laboratory use.
operational Statement
This Auto-ll unit operates by lling a water reservoir that represents an additional well. This reservoir has a oat switch installed that is closed when the tank is empty. When the Auto-Fill system is turned on, the closed oat switch allows power to ow to the solenoid valve, opening the solenoid valve and allowing water to ow into the drain system through a check valve.
As water lls the drain line, it will ll each well and the Auto-Fill reservoir at approximately the same rate. When the water reaches the oat switch, the switch will open, stopping the power supply to the solenoid valve and the solenoid valve will return to its normally closed position stopping the ow of water into the system.
Unpacking the eqUipment and initial SetUp
When no longer needed, dispose of all packaging and materials in an environmentally responsible manner. Have the unit installed only by qualied service personnel. This unit must be installed in accordance with any local and national plumbing codes.
A shut-off valve to control the fresh water supply to this product is
required. This unit requires a 120Volt 15Amp electrical outlet. Units using this auto-ll unit MUST NOT SHARE A DRAIN LINE with
any other units that do not have the same well depth. Multiple units with the same well depth may share a drain line provided
they are level to each other within ¼”. Maximum water pressure is 80 PSI.
NOTE: A water lter to remove particles that may clog the solenoid valve is
strongly recommended.
1. Remove all packing material and tape, as well as any protective plastic from the equipment.
2. Clean any glue residue left over from the plastic or tape.
3. If installing this Auto-ll on a Vollrath drain manifold, cut off the pipe cap from the end of the drain manifold assembly that is on the opposite end of the main drain valve.
4. Solder the Auto-Fill manifold assembly (A) to the open end of the drain line (B) from step 2 making sure the auto ll manifold is level with the existing drain manifold. Figure 1.
Figure 1. Drain Line and Manifold Assembly .
5. For installation with Rectangular Drop-In For initial setup, mount the
Auto-Fill main body water reservoir (B) level to the bottom of any full size Vollrath hot well (C) unit outer skin. Mark and use appropriate length fasteners to mount reservoir (B) assembly in a level position (D) to the bottom of the well assembly (A). See Figure 2.
6. For use with Round Soup Drop-In: Install the reservoir (B) 5/8” (15 mm) below the bottom of a Vollrath round soup drop in unit outer skin. See Figure 2.
1. The adjustment procedure above should be used with soup pots with the understanding that the water level the unit will maintain is the water level when there is a soup pot in use. The recommended 5/8” (15 mm)” placement of the reservoir below the soup warmer (In the installation section above) will maintain water at the water level mark in the well. However at this level, if a soup insert is placed into the soup warmer that has water lled to this mark without an insert in place, when inserted the insert will displace some of the water up the sides of the soup warmer. Because the water will level out in the entire system, this may cause the reservoir tank of the auto-ll unit to overow.
B
C
A
D
2
OperatOrs Manual
Countertop Warming and display
C
B
A
D
Figure 4. Solenoid Valve, Flexible Hose, and Fittings.
Figure 2. Water Reservoir and Well Assembly.
10. Using the section of the exible hose (D) coming from the “O” side of the
7. Mount the auto-ll control box (A) at any convenient dry location close to an access door. See Figure 3.
solenoid (C) connect this hose to the ant-siphon valve (E).
11. Using the section of the exible hose (F) coming from the reservoir tting (G) to the tting (H).
Start Up and teSting
A
B
C
Figure 3. Control Box, Switch and Light.
WARNING
Water Contamination Hazard.
The overow drain line must not be connected to any drain. It must be routed to an open drain leaving a air gap separating the overow drain line from the top of the open drain reservoir.
8. Using the section of the exible hose marked and/or coming from outlet (E) side of the water tank, route this line to an OPEN FLOOR DRAIN. This drain MUST not be directly plumbed to the auto ll unit. This is done to prevent contamination of the fresh water supply. See Figure 4.
9. Using the section of the exible hose (A) coming from the “IN” or “I” side of the solenoid (B) connect this hose to your fresh water source. See Figure 4.
1. Plug the auto-ll control box into a grounded 120 Volt 15 Amp electrical outlet.
2. Verify the main drain valve is in the CLOSED position to prevent water from draining out. Be sure the individual well drains are in the OPEN position to allow water to ll the wells from the drain manifold.
3. Turn the fresh water supply valve on. Start with the valve in the full open position.
4. Turn on the Auto-ll system using the switch on the control assembly. The red indicator light should come on indicating power is supplied to the unit and water should ow into the system.
NOTE: If a continuous stream of water begins to ow out of the overow tube when lling the unit, stop lling and drain the unit. Close the water supply valve from step 3 part way to reduce water ow. Rell unit. Continue this process until water does not ow out of the overow when lling the unit. It is normal to have small amounts of water ow out the overow while the unit is lling.
5. The auto-ll system may cycle on and off a few times, with delays, before the water level is stabilized. The number of cycles and delays are dependant on water pressure, number of wells lling, etc. Do not attempt to adjust the water level until the system has fully stabilized. When the system does not cycle on or off after a full minute, the system should be stabilized.
6. When the system is stabilized, check the water level in each of the wells. For proper water level control it is important the hot food unit be level. Each well should have approximately the same amount of water.
7. If the water level is too low, loosen (do not remove) the screws used to mount the reservoir assembly. Lift the reservoir assembly up approximately 1/8”. Retighten the screws. There may again be a delay before the system begins to ll. Allow the system to stabilize again and re-check the water level.
8. Continue the adjustment until you have the water level adjusted to the desired level. The water level should not be adjusted above 1/2” of water.
9. For most efcient heating and performance, use approximately 1/4” of water in each well.
C
G
F
D
E
H
B
A
ENGLISH
OperatOrs Manual
3
Loading...
+ 5 hidden pages