Volison ADM-5850G User Manual

Modbus Gateway User's Manual
ADM-5850G
Functional introduction
The Modbus protocol is the most widely used protocol in the electronic industrial equipment, and now it has become a general industrial standard. Through this protocol, Modbus devices (such as PLC, DCS, HMI, and instruments) can communicate with each other through a network or serial port. But the Modbus protocol used in the serial port and the Ethernet network is different, so a gateway is needed to complete the communication conversion between the two protocols. ADM-5850G is a modbus gateway product dedicated to connecting Modbus TCP devices and Modbus RTU/ASCII devices.
ADM-5850G has Modbus RTU/ASCII and Modbus TCP protocol conversion functions, it integrates Modbus TCP, Modbus RTU and Modbus ASCII protocol, and the device's serial port can be configured by software of RS-232, RS-485 or RS-422, you can easily achieve Modbus Ethernet devices with Modbus serial devices connected.
Product features
1, 32 bit ARM Cortex-m3 CPU
2, 1 Port 10/100M Ethernet interface
3, Support RS-232, RS-422, RS-485 serial port mode
4. Baud rate, Data bit, Stop bit, Parity bit can be set
5. Integrated ARP, IP, ICMP, IGMP, UDP, TCP, DHCP, DNS,MODBUS TCP, MODBUS RTU, MODBUS ASCII protocol
6. Provide 4 mode of work:
RTU_ Master--TCP_ Slaver, TCP_ Master--RTU_ Slaver ASCII_ Master--TCP_ Slaver, TCP_ Master--ASCII_ Slaver
7. Maximum support for 32 Modbus TCP master stations and 4 Modbus TCP slave stations
8. The automatic adaptive function of the time interval of the character
9, Provide ID mapping function to realize the management of host ID number
10. The local port, the target IP address, and the target port number can be set
11, Can be configured through Web Server, Telnet, MG Configuration tools 12, MG Configuration tools support
Windows98/me/NT/2000/XP/WIN7/WIN8/WIN10 operating system
13, Industrial design, can run steadily in bad environment
Product specification
Ethernet
Standard: 10/100Mbps adaptive Ethernet port Communication mode: full duplex / half duplex adaptive Transmission distance: less than 100 meters Interface type: RJ-45
Serial port
RS-232 signals: TXD, RXD, RTS, CTS, GND RS-422 signals: T+, T-, R+, R­RS-485 signal: D+, D­Parity bit: None\Even\Odd\space\mark Data bits: 6bit, 7bit, 8bit Baud rate: 300BPS to 230400bps Direction control: RS-485 uses data flow direction automatic control technology
Load capability: RS-485/422 terminal support maximum 32 node polling Transmission distance: RS-485/422 is 1000 meters, RS-232 is 10 meters Interface protection: 1500W surge protection, 15KV ESD protection Interface type: RS-232 terminal DB-9 male, RS-485/422 terminal
Power Supply
Power input: DC9~48V power supply Power consumption: 120mA @ 24V (Max)
Environmental
Working temperature: -20 C ~ 70 C Storage temperature: -40 C ~ 95 C Storage humidity: 5 ~ 95% RH
Package size
Long x wide x high: 103x72x27 (mm)
Interface definition
RS-232:DB9 male head (TXD, RXD, RTS, CTS, GND) RS-422: terminal (T+, T-, R+, R-) RS-485: terminal (D+, D-) Network interface: RJ45 (Ethernet) Power interface: terminal VS+, VS-
Restore the default settings
Hardware recovery: Setup and GND short connection, the gateway reboot, and then disconnect Setup and GND, to restore the default settings. Software recovery: Search the device through the MG Configuration tool software and click to restore the factory settings button.
LED instructions
Power indication: "PWR" bright red is the normal power supply Modbus TCP connection success indication: "Active" is bright green Serial data sending and receiving indication: "TX/RX" is Flash
Typical application
Configuration instructions
There are three configurations of ADM-5850G, which are the Telnet console, the Web
server console, and the MG Configuration PC software configuration.
Web server console configuration instructions
1. Open the IE browser
Enter the IP address of the ADM-5850G Modbus gateway in the address bar (default: 192.168.10.245)
2. Set the basic parameters
Gateway nameDevice name (less than 11 characters). Gateway addressThe location of the device (less than 11 characters). Web console"Enable" enables Web console, and "Disable" closes Web console. Telnet console "Enable" enables Telnet console, and "Disable" closes the Telnet
console.
3. Network parameter configuration MAC addressThe MAC address of the ADM-5850G device can not be changed. IP addressThe IP address of the ADM-5850G device in the network. Net maskSubnet mask. GatewayGateway address. IP configurationThe type of IP address, DHCP: dynamic IP automatic acquisition,
Static: static IP address. DNS serverWhen the target IP is a domain name, DNS server is the IP address of the domain name resolution server.
4, Serial port configuration
Baud RateSerial baud rate, 300~230400 can be selected. Data BitsSerial data bit, 6,7,8 bit can be selected. Stop BitsThe stop bit of the serial port can be selected as 1, 1.5, and 2 bits. ParityParity bit, None\Even\Odd\space\mark can be selected, default is None TimeoutCharacter timeout time. When the device uses Modbus RTU protocol, it can
encapsulate data frames by judging the character interval. If the character timeout time is not accurate, it may cause CRC error. This value can be set (0~15000) milliseconds. When set to 0, it automatically adapts to wait for 3.5 characters.
InterfaceSerial interface type, can choose RS-232, RS-485, RS-422 three formats.
5, Modbus gateway operation mode configuration
ADM-5850G Modbus Gateway provides 4 work mode: (1), TCP_ Master-RTU_ Slaver:
Network end connection Modbus TCP master station, serial connects Modbus RTU slave station (2), TCP_ Master-ASCII_ Slaver:
Network end connection Modbus TCP master station, serial port connects Modbus ASCII slave station
Max connectionThe maximum number of connections allowed by Modbus TCP master station is 32. Users can adjust this parameter according to the actual application. When users do not need 32 connections, they can be reduced to improve performance. The effective range of the maximum number of connections is 1~32.
Local TCP port The default port number of the standard Modbus TCP protocol is 502, and the user can modify it according to the actual application. Message Timeout Message timeout time (milliseconds), Modbus is the M/S structure protocol. When master station communicates with slave station, it needs to wait for the slave station to respond. This time is "message timeout time", the effective range is (100~32000) ms, and the default value of the parameter is 200 milliseconds.
ID MappingID mapping capabilities, optional AUTO and Fixed. AUTO When Auto ID is selected, the ID number in the Modbus TCP master station
request frame is not modified and will be sent directly to the serial port slave station device. Fixed When Fixed ID is selected, the ID number in the Modbus TCP master station request frame is replaced with a fixed ID number and then sent to the serial port slave station device. The serial port slave station device returns the frame, it's ID number is converted to before the change, and then to the Modbus TCP master station. Fixed ID Value Fixed ID number, when selecting Fixed, Modbus Gateway uses this fixed ID number to access the serial port slave device, the range is 1~247.
(3), RTU_ Master-TCP_ Slaver:
Network end connection Modbus TCP slave station, serial port connection Modbus RTU master station (4), ASCII_ Master-TCP_ Slaver:
Network end connection Modbus TCP slave station, serial port connection Modbus ASCII master station
Destination IP addressWhen Modbus Gateway works in TCP_ Slaver mode, it can support 4 Modbus TCP slave connections. Users can set IP address of target host to connect Modbus TCP slave station. When the target connection is not used, the IP address should be modified to 0.0.0.0. Otherwise, the Modbus Gateway device will continuously send the connection request, so that it will affect the network performance.When the target host address is a domain name, "/" is added before the domain name, and "/" represents the domain name. The length must be less than 20 characters PortThe port number of the target host, the default port number of the standard Modbus TCP protocol is 502, and the user can modify it.
ID mapping: Min ID/Max IDThe minimum value of ID and the maximum value of ID, and its range
is 0~247. When the serial Modbus master station connects TCP slave station, the Modbus Gateway device will check whether the target is within the range, and if it is not in the
range, it will not be sent. Max ID can't be less than Min ID, otherwise it is treated as Min ID. When Max ID<=Min ID, the Modbus Gateway device uses Min ID, and the ID range of the 4 connections cannot be repeated, otherwise the error will occur. ID offsetID offset, the Modbus protocol stipulates that all slave station devices must have a unique ID number (1~247), which is used to identify the slave station address. The ID number of Modbus slave station device can be modified. When the Modbus serial master station access the TCP slave station, the target ID will add the offset and then sent to the Modbus TCP slave station. When the Modbus TCP slave station returns the data, the offset is subtracted from the ID number and then sent to the serial port MODBUS master station.
Technical support
Email: liuchangshandx@126.com QQ 513409265 Websitewww.volison.com