7.2.2Selector switch in the hot water only position27
7.2.3Selector switch in the heating & hot water position27
7.2.4Appliance functions27
7.2.5Heating mode27
7.2.6DHW mode28
7.3Checking and adjusting burner pressure28
7.3.1Setting the maximum burner pressure28
7.3.2Setting the minimum burner pressure28
7.4Combustion analysis test28
7.5Checking the expansion vessel29
7.6External faults29
7.6.1Installation faults29
7.7Electrical checks29
7.7.1Earth continuity test29
7.7.2Short circuit test29
7.7.3Polarity check29
7.7.4Reversed polarity or supply fault29
7.7.5Resistance to earth check30
7.8Fault finding30
7.9Fault codes31-38
Wiring diagramsPage
8.1External wiring39
8.2Typical control applications39
8.3Vokera time clock39
8.4Vokera remote control39
8.5Vokera room thermostat39
8.6Other controls39
Exploded diagramsPage
Table 1 - 543 - 48
L.P .G. instructionsPage
10.1Related documents49
10.2Technical data49
10.3Converting the appliance gas type49
10.4Gas supply49
10.5Gas supply installation49
10.6Checking and adjusting burner pressure49
10.6.1Setting the maximum burner pressure49
10.6.2Setting the minimum burner pressure49
Supplied By www.heating spares.co Tel. 0161 620 6677
INTRODUCTION
The Syntesi range of appliances is comprised of 3 models
of high-efficiency combination boiler with outputs to
heating & DHW of 24, 28, & 34kW respectively. Each
appliance – by design – incorporates electronic ignition,
circulating pump, expansion vessel, safety valve, pressure
gauge, and automatic by-pass.
The Syntesi range is produced as room sealed, category
II2H3+ appliances, suitable for internal wall mounting
applications only . They are provided with a fan powered
flue outlet with an annular co-axial combustion air intake
14
9
8
7
10
3
11
6
5
4
2
1
12
272830 312932
13
that can be rotated – horizontally – through 360 degrees
for various horizontal or vertical applications. The Syntesi
range can also be used with the Vokera twin flue system.
The Syntesi range is approved for use with C12 & C32
type flue applications.
These appliances are designed for use with a sealed
system only; consequently they are not intended for use
on open vented systems.
10Latent Heat Collector
11Condense Sensor
12Flue Gas Analysis Test Point
13Flue Outlet
14Air Intake
15Differential Analog Pressure Switch
20
16Silicone Pressure T ube
17Silicone Negative Pressure T ube
21
18Fan Assembly
19Combustion Chamber
22
23
20Burner Temperature Control
21Expansion Vessel
22Transformer
24
23Gas V alve
24Modulator Coil
25
25Condense Trap
26Domestic Hot Water Flow Switch
26
27Hot Water Temperature Control
28Mode Selector Switch
29Status LED
30Temperature Indicator
31DHW Request LED
32Central Heating Temperature Control
33Combustion Switch
34Timeclock Aperture (optional)
35Pressure Gauge
353433
Fig. 1
1
Supplied By www.heating spares.co Tel. 0161 620 6677
SECTION 1DESIGN PRINCIPLES AND OPERATING SEQUENCE
1.1PRINCIPLE COMPONENTS
● A fully integrated electronic control board
featuring electronic temperature control, anticycle control, pump over-run, self-diagnostic
fault indicator, full air/gas modulation.
● Low-water-content, copper heat exchanger.
● Electronic ignition with flame supervision
● Integral high-head pump
● Fan
● Expansion vessel
● Analogue pressure switch (P AD)
● Water pressure switch
● Two-stage gas valve
● Pressure gauge
● Safety valve
1.2MODE OF OPERATION (at rest)
When the appliance is at rest and there are no
requests for heating or DHW, the following functions are active:
● pre-heat function – the pre-heat function ena-
bles the appliance to periodically light and maintain the temperature of the DHW heat exchanger. This “keep-hot” facility enables the
appliance to provide an instantaneous response to DHW requests.
● 2-stage frost-protection system – the frost-pro-
tection system protects the appliance against
the risk of frost damage. The first stage enables activation of the pump should the temperature of the appliance fall to 7°C. The second
stage becomes active when the temperature
has dropped to 3°C. Should the second stage
become active, the appliance will function on
minimum power until it reaches 30°C.
● anti-block function – the anti-block function ena-
bles the pump and divertor valve actuator, to
be energised for short periods, when the appliance has been inactive for more than 19hours.
1.3MODE OF OPERA TION (Heating)
When there is a request for heat via the
programmer/time clock and/or any external
control, the pump and fan are started, the fan
speed will modulate until the correct signal
voltage is received at the control PCB. At this
point an ignition sequence is enabled.
Ignition is sensed by the electronic circuitry to
ensure flame stability at the burner. Once
successful ignition has been achieved, the
electronic circuitry increases the gas rate to 75%
for a period of 15 minutes. Thereafter, the boiler’s
output will either be increase to maximum or
modulate to suit the set requirement. When the
appliance reaches the desired temperature the
burner will shut down and the boiler will perform
a three-minute anti-cycle (timer delay).
When the request for heat has been satisfied the
appliance pump and fan may continue to operate
to dissipate any residual heat within the
appliance.
1.4MODE OF OPERATION (DHW)
When there is a request for DHW via a hot water
outlet or tap, the pump and fan are started, the
fan speed will modulate until the correct signal
voltage is received at the control PCB. At this
point an ignition sequence is enabled.
During DHW request LED (31, fig. 1) is ON.
Ignition is sensed by the electronic circuitry to
ensure flame stability at the burner. Once
successful ignition has been achieved, the
electronic circuitry increases the gas rate to
maximum or will modulate output to stabilise the
temperature. In the event of the appliance
exceeding the desired temperature the burner will
shut down until the temperature drops.
When the request for DHW has been satisfied
the appliance pump and fan may continue to
operate to dissipate any residual heat within the
appliance.
1.5SAFETY DEVICES
When the appliance is in use, safe operation is
ensured by:
● a water pressure switch that monitors system
water pressure and will de-activate the pump,
fan and burner should the system water
pressure drop below the rated tolerance.
● a high limit thermostat that over-rides the
temperature control circuit to prevent or
interrupt the operation of the burner.
● an analogue pressure switch (PAD) that
checks the operation of the fan and flue thereby
allowing safe operation of the burner.
● a sensor that interrupts the operation of the
appliance if the condense pipe becomes
blocked.
● a safety valve which releases excess pressure
from the primary circuit.
1.6OPTIONAL ACCESSORIES
The Syntesi is suitable for use with a range of
optional accessories that enable enhanced
operation and/or applications. These include:
● RC05 remote control – the RC05 remote
control enables the appliance to be controlled,
adjusted, and monitored from another location
or room. The RC05 can also be used as a room
thermostat or programmable room thermostat.
● external sensor – used in conjunction with the
RC05 the external sensor enables the
appliance to automatically adjust its outlet flow
temperature in response to the outside
Expansion
vessel
AARV
Pump
Fig. 2
temperature.
Flue Outlet
Latent Heat
Collector
Diverter
Valve Motor
Pressure
Switch
ABCD
Air Intake
PAD
Main Heat
Exchanger
Main
Burner
Gas Valve
Domestic
Heat
Exchanger
DHW Flow
Switch
2
Supplied By www.heating spares.co Tel. 0161 620 6677
SECTION 2TECHNICAL DATA
2.1 Central heatingSyntesi 25Syntesi 29Syntesi 35
Heat input25.0 kW29.0 kW35.0 kW
Max heat output 60/80°C (return & flow temp.)24.1 kW28.0 kW33.9 kW
Max heat output 30/50°C (return & flow temp.)25.9 kW29.7 kW36.2 kW
Min heat output 60/80°C (return & flow temp.)9.5 kW9.5 kW 9.4 kW
Min heat output 30/50°C (return & flow temp.)10.1 kW10.2 kW 10.2 kW
Minimum working pressure0.45 bar
Maximum working pressure3.0 bar
Minimum flow rate350 l/h
2.2 Domestic hot water
Maximum input25.0 kW29.0 kW35.0 kW
Maximum output24.1 kW28.0 kW33.9 kW
Minimum output9.5 kW9.5 kW9.4 kW
Flow rate (35oC rise)9.9 kW11.5 kW13.9 kW
Maximum inlet pressure 6.0 bar
Minimum inlet pressure0.15 bar
Minimum flow rate 2.0 l/min
2.3 Gas pressures
Inlet pressure (G20) 20.0 mbar
Burner pressure maximum8.8 mbar9.3 mbar10.1 mbar
Burner pressure minimum1.5 mbar1.25 mbar1.00 mbar
Maximum gas rate2.65 Sm3/h3.07 Sm3/h3.75 Sm3/h
Minimum gas rate1.05 Sm3/h1.05 Sm3/h1.05 Sm3/h
Injector size (quantity)12 x 1.35 mm14 x 1.35 mm16 x 1.35 mm
2.4 Expansion vessel
Capacity 8-litres10-litres
Maximum system volume 76-litres91-litres
Pre-charge pressure 1.0 bar
Voltage (V/Hz)230/50
Power consumption 174W174W194W
Internal fuse2A
External fuse3A
2.9 Flue details (concentric)
Maximum horizontal flue length (60/100mm)5.75m4.90m0.75m
Maximum vertical flue length (60/100mm)6.55m5.70m1.55m
Maximum horizontal flue length (80/125mm)13.80m11.80m6.75m
Maximum vertical flue length (80/125mm)15.30m13.30m8.25m
2.9A Flue Details (twin pipes)
Maximum horizontal flue length (80mm + 80mm)25m+25m20m+20m10m+10m
Maximum vertical flue length (80mm + 80mm)25m+25m20m+20m10m+10m
2.10 Efficiency
SEDBUK (%)87.487.588.1
3
Supplied By www.heating spares.co Tel. 0161 620 6677
SECTION 2TECHNICAL DATA
2.1 1PUMP DUTY
Fig. 3 shows the flow-rate available – after allowing for pressure loss through the
appliance – for system requirements.
When using this graph, apply only the
pressure loss of the system. The graph
is based on a 20°C temperature differential.
Fig. 3
7
6,5
6
5,5
5
4,5
4
3,5
3
2,5
2
1,5
1
Water pressure (mbar)
0,5
0
0100200300400500600 700800900 1000 1100 1200 1300
Syntesi 25 & 29
Syntesi 35
Litres Per Hour
2.12 Emissions
Appliance
Syntesi 25Syntesi 29
Syntesi 35
NOx max/min160/140180/120160/110
CO max/min70/20100/6090/80
CO2 max/min6.5/4.86.60/4.156.5/3.7
CO/CO2 ratio max/min0.00108 to 1/0.00044 to 10.00152 to 1/0.00145 to 1 0.00138 to 1/0.00216 to 1
Fig. 4
H
H
KeyLocationMinimum distance
ABelow an opening (window, air-brik, etc.)300 mm
BAbove an opening (window, air-brik, etc.)300 mm
CTo the side of an opening (window, air-brik, etc.)300 mm
DBelow gutter, drain-pipe, etc.75 mm
EBelow eaves200 mm
FBelow balcony, car-port roof, etc.200 mm
GTo the side of a soil/drain-pipe, etc.150 mm
HFrom internal/external corner or boundary300 mm
IAbove ground, roof, or balcony level300 mm
JFrom a surface or boundary facing the terminal600 mm
KFrom a terminal facing a terminal1200 mm
LFrom an opening in the car-port into the building1200 mm
MVertically from a terminal on the same wall1500 mm
NHorizontally from a terminal on the same wall300 mm
PFrom a structure to the side of the vertical terminal300 mm
QFrom the top of the vertical terminal to the roof flashingAs determined by the fixed collar
of the vertical terminal
4
Supplied By www.heating spares.co Tel. 0161 620 6677
SECTION 3GENERAL REQUIREMENTS (UK)
This appliance must be installed by a competent
person in accordance with the Gas Safety
(Installation & Use) Regulations.
3.1RELATED DOCUMENTS
The installation of this boiler must be in
accordance with the relevant requirements of the
Gas Safety (Installation & Use) Regulations, the
local building regulations, the current I.E.E. wiring
regulations, the bylaws of the local water
undertaking, the Building Standards (Scotland)
Regulation, and Building Standards (Northern
Ireland) Regulations.
It should be in accordance also with any relevant
requirements of the local authority and the
relevant recommendations of the following British
Standard Codes of Practice.
3.2LOCATION OF APPLIANCE
The appliance may be installed in any room or
internal space, although particular attention is
drawn to the requirements of the current I.E.E.
wiring regulations, and in Scotland, the electrical
provisions of the Building Regulations, with respect
to the installation of the appliance in a room or
internal space containing a bath or shower.
3.3GAS SUPPL Y
The gas meter – as supplied by the gas supplier
– must be checked to ensure that it is of adequate
size to deal with the maximum rated input of all
the appliances that it serves. Installation pipes
must be fitted in accordance with BS 6891.
Pipe work from the meter to the appliance must
be of adequate size. Pipes of a smaller size than
the appliance gas inlet connection must not be
used. The installation must be tested for
soundness in accordance with BS6891.
If the gas supply serves more than one appliance,
it must be ensured that an adequate supply is
maintained to each appliance when they are in
use at the same time.
3.4FLUE SYSTEM
The terminal should be located where the
dispersal of combustion products is not impeded
and with due regard for the damage and
discoloration that may occur to building products
located nearby . The terminal must not be located
in a place where it is likely to cause a nuisance
(see fig. 4).
BS 5440P ART 1FLUES
BS 5440P ART 2FLUES & VENTILA TION
BS 5449P ART 1FORCED CIRCULA TION HOT W ATER SYSTEMS
BS 5546INSTALLATION OF GAS HOT WATER SUPPLIES FOR DOMESTIC PURPOSES
(2nd FAMILY GASES)
BS 6798INSTALLATION OF BOILERS OF RATED INPUT NOT EXCEEDING 60kW
BS 6891LOW PRESSURE INSTALLATION PIPES
BS 7074P AR T 1APPLICA TION, SELECTION AND INSTALLTION OF EXPANSION VESSELS AND
ANCILLARY EQUIPMENT FOR SEALED WATER SYSTEMS
When an appliance is installed in a room or internal
space containing a bath or shower, the appliance
or any control pertaining to it must not be within
reach of a person using the bath or shower.
The location chosen for the appliance must permit the provision of a safe and satisfactory flue
and termination. The location must also permit
an adequate air supply for combustion purposes
and an adequate space for servicing and air circulation around the appliance. Where the installation of the appliance will be in an unusual location special procedures may be necessary, BS
6798 gives detailed guidance on this aspect. A
compartment used to enclose the appliance must
be designed and constructed specifically for this
purpose. An existing compartment/cupboard may
be utilised provided that it is modified to suit.
Details of essential features of compartment/cupboard design including airing cupboard installations are given in BS 6798. This appliance is not
suitable for external installation.
3.4FLUE SYSTEM (Cont’d.)
In cold and/or humid weather, water vapour will
condense on leaving the terminal; the effect of
such pluming must be considered.
If installed less than 2m above a pavement or
platform to which people have access (including
balconies or flat roofs) the terminal must be
protected by a guard of durable material. The
guard must be fitted centrally over the terminal.
Refer to BS 5440 Part 1, when the terminal is
0.5 metres (or less) below plastic guttering or 1
metre (or less) below painted eaves.
3.5AIR SUPPL Y
The following notes are intended for general
guidance only .
This appliance is a room-sealed, fan-flued boiler,
consequently it does not require a permanent
air vent for combustion air supply . When installed
in a cupboard or compartment, ventilation for
cooling purposes is also not required.
5
Supplied By www.heating spares.co Tel. 0161 620 6677
3.6WATER CIRCULATION
Detailed recommendations are given in BS 5449
Part 1 and BS 6798. The following notes are for
general guidance only .
3.6.1PIPEWORK
It is recommended that copper tubing to BS 2871
Part 1 is used in conjunction with soldered
capillary joints.
Where possible pipes should have a gradient to
ensure air is carried naturally to air release points
and that water flows naturally to drain cocks.
Except where providing useful heat, pipes should
be insulated to avoid heat loss and in particular
to avoid the possibility of freezing. Particular
attention should be paid to pipes passing through
ventilated areas such as under floors, loft space,
and void areas.
3.6.2AUTOMA TIC BY-PASS
The appliance has a built-in automatic by-pass,
consequently there is no requirement for an
external by-pass, however the design of the
system should be such that it prevents boiler
‘cycling’.
The cold feed from the make-up vessel or tank
must be fitted with an approved non-return valve
and stopcock for isolation purposes. The feed pipe
should be connected to the return pipe as close
to the boiler as possible.
3.6.8FREQUENT FILLING
Frequent filling or venting of the system may be
indicative of a leak. Care should be taken during
the installation of the appliance to ensure all
aspects of the system are capable of withstanding
pressures up to at least 3 bar.
Automatic
air-vent
Non-return
valve
Stopcock
Make-up vessel
or tank
5.0 metres minimum
3.6.3DRAIN COCKS
These must be located in accessible positions to
facilitate draining of the appliance and all water
pipes connected to the appliance. The drain cocks
must be manufactured in accordance with BS
2879.
3.6.4AIR RELEASE POINTS
These must be positioned at the highest points
in the system where air is likely to be trapped.
They should be used to expel trapped air and
allow complete filling of the system.
3.6.5EXPANSION VESSEL
The appliance has an integral expansion vessel
to accommodate the increased volume of water
when the system is heated. It can accept up to 8
litres (25/29) or 10 litres (35) of expansion from
within the system, generally this is sufficient,
however if the system has an unusually high
water content, it may be necessary to provide
additional expansion capacity (see 6.19).
3.6.6FILLING POINT
A method for initial filling of the system and
replacing water lost during servicing etc. has been
provided. This method of filling complies with the
current Water Supply (Water Fittings) Regulations
1999 and Water Bylaws 2000 (Scotland).
3.6.7LOW PRESSURE SEALED SYSTEM
An alternative method of filling the system would
be from an independent make-up vessel or tank
mounted in a position at least 1 metre above the
highest point in the system and at least 5 metres
above the boiler (see fig. 5).
Fig. 5
Heating
return
3.7ELECTRICAL SUPPLY
The appliance is supplied for operation on 230V
@ 50Hz electrical supply; it must be protected
with a 3-amp fuse. The method of connection to
the mains electricity supply must allow for
complete isolation from the supply . The preferred
method is by using a double-pole switch with a
contact separation of at least 3mm. The switch
must only supply the appliance and its
corresponding controls, i.e. time clock, room
thermostat, etc. Alternatively an un-switched
shuttered socket with a fused 3-pin plug both
complying with BS 1363 is acceptable.
3.8SHOWERS
If the appliance is intended for use with a shower,
the shower must be thermostatically controlled
and be suitable for use with a combination boiler.
3.9MOUNTING ON A COMBUSTIBLESURFACE
If the appliance is to be fitted on a wall of combustible material, a sheet of fireproof material
must protect the wall.
6
Supplied By www.heating spares.co Tel. 0161 620 6677
3.10TIMBER FRAMED BUILDINGS
If the appliance is to be fitted in a timber framed
building, it should be fitted in accordance with the
Institute of Gas Engineers publication (IGE/UP/
7) ‘Guide for Gas Installations in Timber Frame
Buildings’.
3.11INHIBITORS
Vokera recommend that a inhibitor – suitable for
use with low water-content, copper heat exchangers – is used to protect the boiler and system
SECTION 3AGENERAL REQUIREMENTS (EIRE)
from the effects of corrosion and/or electrolytic
action. The inhibitor must be administered in strict
accordance with the manufacturers* instructions.
*Fernox and Sentinel manufacture products that
have proved suitable for use with Vokera appliances. Vokera Ltd. cannot comment on the suitability of any other such product with our
appliances.
This appliance must be installed by a competent
person in accordance with and defined by, the
Standard Specification (Domestic Gas
Installations) Declaration (I.S. 813).
3A.1RELATED DOCUMENTS
The installation of this boiler must be in
accordance with the relevant requirements of the
local building regulations, the current ETCI
National Rules for Electrical Installations, and the
bylaws of the local water undertaking.
It should be in accordance also with any relevant
requirements of the local and/or district authority .
3A.2LOCATION OF APPLIANCE
The appliance may be installed in any room or
internal space, although particular attention is
drawn to the requirements of the current ETCI
National Rules for Electrical Installations, and I.S.
813, Annex K.
When an appliance is installed in a room or internal
space containing a bath or shower, the appliance
or any control pertaining to it must not be within
reach of a person using the bath or shower.
The location chosen for the appliance must permit
the provision of a safe and satisfactory flue and
termination. The location must also permit an
adequate air supply for combustion purposes and
an adequate space for servicing and air circulation
around the appliance. Where the installation of the
appliance will be in an unusual location special
procedures may be necessary , refer to I.S. 813 for
detailed guidance on this aspect.
A compartment used to enclose the appliance
must be designed and constructed specifically
for this purpose. An existing compartment/
cupboard may be utilised provided that it is
modified to suit.
This appliance is not suitable for external
installation.
3A.3GAS SUPPLY
The gas meter – as supplied by the gas supplier
– must be checked to ensure that it is of adequate
size to deal with the maximum rated input of all
the appliances that it serves. Installation pipes
must be fitted in accordance with I.S. 813.
Pipe work from the meter to the appliance must
be of adequate size. Pipes of a smaller size than
the appliance gas inlet connection must not be
used. The installation must be tested for
soundness in accordance with I.S. 813.
If the gas supply serves more than one appliance,
it must be ensured that an adequate supply is
maintained to each appliance when they are in
use at the same time.
3A.4FLUE SYSTEM
The terminal should be located where the
dispersal of combustion products is not impeded
and with due regard for the damage and
discoloration that may occur to building products
located nearby . The terminal must not be located
in a place where it is likely to cause a nuisance
(see I.S. 813).
In cold and/or humid weather, water vapour will
condense on leaving the terminal; the effect of
such pluming must be considered.
If installed less than 2m above a pavement or
platform to which people have access (including
balconies or flat roofs) the terminal must be
protected by a guard of durable material. The
guard must be fitted centrally over the terminal.
Refer to I.S. 813, when the terminal is 0.5 metres
(or less) below plastic guttering or 1 metre (or
less) below painted eaves.
3A.5AIR SUPPLY
The following notes are intended for general
guidance only .
This appliance is a room-sealed, fan-flued boiler,
consequently it does not require a permanent air
vent for combustion air supply .
When installed in a cupboard or compartment,
ventilation for cooling purposes is also not
required.
3A.6W ATER CIRCULATION
Specific recommendations are given in I.S. 813.
The following notes are for general guidance only .
7
Supplied By www.heating spares.co Tel. 0161 620 6677
3A.6.1 PIPEWORK
It is recommended that copper tubing be used in
conjunction with soldered capillary joints.
Where possible pipes should have a gradient to
ensure air is carried naturally to air release points
and that water flows naturally to drain cocks.
Except where providing useful heat, pipes should
be insulated to avoid heat loss and in particular
to avoid the possibility of freezing. Particular
attention should be paid to pipes passing through
ventilated areas such as under floors, loft space,
and void areas.
3A.6.2 AUTOMA TIC BY -P ASS
The appliance has a built-in automatic by-pass,
consequently there is no requirement for an
external by-pass, however the design of the
system should be such that it prevents boiler
‘cycling’.
3A.6.3 DRAIN COCKS
These must be located in accessible positions to
facilitate draining of the appliance and all water
pipes connected to the appliance.
3A.6.4 AIR RELEASE POINTS
These must be positioned at the highest points
in the system where air is likely to be trapped.
They should be used to expel trapped air and
allow complete filling of the system.
3A.6.5 EXP ANSION VESSEL
The appliance has an integral expansion vessel
to accommodate the increased volume of water
when the system is heated. It can accept up to 8
litres (25/29) or 10 litres (35) of expansion from
within the system, generally this is sufficient,
however if the system has an unusually high
water content, it may be necessary to provide
additional expansion capacity (see 6.19).
3A.6.6 FILLING POINT
A method for initial filling of the system and
replacing water lost during servicing etc. has been
provided. Y ou should ensure this method of filling
complies with the local water authority
regulations.
3A.6.7 LOW PRESSURE SEALED SYSTEM
An alternative method of filling the system would
be from an independent make-up vessel or tank
mounted in a position at least 1 metre above the
highest point in the system and at least 5 metres
above the boiler (see fig. 5).
The cold feed from the make-up vessel or tank
must be fitted with an approved non-return valve
and stopcock for isolation purposes. The feed
pipe should be connected to the return pipe as
close to the boiler as possible.
the installation of the appliance to ensure all
aspects of the system are capable of withstanding
pressures up to at least 3 bar.
3A.7ELECTRICAL SUPPLY
The appliance is supplied for operation on 230V
@ 50Hz electrical supply; it must be protected
with a 3-amp fuse. The method of connection to
the mains electricity supply must allow for
complete isolation from the supply . The preferred
method is by using a double-pole switch with a
contact separation of at least 3mm. The switch
must only supply the appliance and its
corresponding controls, i.e. time clock, room
thermostat, etc.
3A.8SHOWERS
If the appliance is intended for use with a shower,
the shower must be thermostatically controlled
and be suitable for use with a combination boiler.
3A.9MOUNTING ON A COMBUSTIBLESURFACE
If the appliance is to be fitted on a wall of
combustible material, a sheet of fireproof material
must protect the wall.
3A.10 TIMBER FRAMED BUILDINGS
If the appliance is to be fitted in a timber framed
building, it should be fitted in accordance with
I.S. 813 and local Building Regulations.
The Institute of Gas Engineers publication (IGE/
UP/7) ‘Guide for Gas Installations in Timber
Frame Buildings’ gives specific advice on this type
of installation.
3A.11 INHIBITORS
Vokera recommend that a inhibitor – suitable for
use with low water-content, copper heat
exchangers – is used to protect the boiler and
system from the effects of corrosion and/or
electrolytic action. The inhibitor must be
administered in strict accordance with the
manufacturers* instructions.
Fernox and Sentinel manufacture products that
have proved suitable for use with Vokera
appliances. Vokera Ltd. cannot comment on the
suitability of any other such product with our
appliances.
3A.12 DECLARATION OF CONFORMITY
A Declaration of Conformity (as defined in I.S.
813) must be provided on completion of the
installation.
A copy of the declaration must be given to the
responsible person and also to the gas supplier
if required.
3A.6.8 FREQUENT FILLING
Frequent filling or venting of the system may be
indicative of a leak. Care should be taken during
8
Supplied By www.heating spares.co Tel. 0161 620 6677
SECTION 4INSTALLATION
4.1DELIVERY
Due to the weight of the appliance it may be
necessary for two people to lift and attach the
appliance to its mounting. The appliance is
contained within a heavy-duty cardboard carton.
Lay the carton on the floor with the writing the
correct way up.
4.2CONTENTS
Contained within the carton is:
● the boiler
● the fixing jig and wall bracket
● template
● an accessories pack containing appliance
service connections and washers
● the instruction pack containing the installation
& servicing instructions, user instructions,
Benchmark logbook, guarantee registration
card, and a 3-amp fuse
4.3UNPACKING (see fig. 6)
At the top of the carton pull both sides open – do
not use a knife – unfold the rest of the carton
from around the appliance, carefully remove all
protective packaging from the appliance, and lay
the accessories etc. to one side. Protective gloves
should be used to lift the appliance, the appliance
back-frame should be used for lifting points.
Fig. 6A
Fig. 6
4.4PREPARATION FOR MOUNTING THE
APPLIANCE (see fig. 6A)
The appliance should be mounted on a smooth,
vertical, non-combustible surface, which must be
capable of supporting the full weight of the
appliance. Care should be exercised when
determining the position of the appliance with
respect to hidden obstructions such as pipes,
cables, etc.
When the position of the appliance has been
decided, carefully mark the position of the
combined fixing jig and wall- mounting bracket
(see fig. 6A), and – using the template supplied
– mark the position of the flue-hole (if applicable).
4.5FITTING THE FLUE
The top flue outlet permits both horizontal and
vertical flue applications to be considered,
alternatively , the V okera twin flue system can be
utilised if longer flue runs are required.
4.5.1CONCENTRIC HORIZONTAL FLUE
(For concentric vertical flue, see 4.5.2)
(For twin flue applications, see 4.5.3)
The appliance can be used with either the Vokera
condensing 60/100mm concentric flue system or
the optional 80/125mm concentric flue system.
NOTE
These instructions relate only to the Vokera
condensing 60/100mm concentric flue system.
For specific details on the installation of the 80/
125mm concentric flue system please refer to
the instructions supplied.
The appliance flue outlet elbow can be rotated
through 360° on its vertical axis. In addition the
flue may be extended from the outlet elbow in
the horizontal plane (see 2.9). A reduction must
also be made to the maximum length (see table
below) when additional bends are used.
9
Supplied By www.heating spares.co Tel. 0161 620 6677
Reduction for additional bends
BendReduction in maximum flue length for each bend
Using the template provided, mark and drill a
1 15mm hole for the passage of the flue pipe. The
hole should have a 1° rise from the boiler to
outside, to ensure any condense fluid that forms,
is allowed to drain back to the appliance.
The fixing holes for the wall-mounting bracket/
fixing jig should now be drilled and plugged, an
appropriate type and quantity of fixing should be
used to ensure that the bracket/jig is mounted
securely . Once the bracket/jig has been secured
to the wall, mount the appliance onto the bracket.
Push-fit connection
Terminal or
extension
NOTE
Fit the internal trim to the flue assembly prior to
connecting the flue pipe to the bend.
You must ensure that the entire flue system is
properly supported and connected.
Seal the flue assembly to the wall using cement
or a suitable alternative that will provide
satisfactory weatherproofing.
The exterior trim can now be fitted.
Fig. 7A
“Y” = “X” + 45mm
4.5.1.1 EXTENDING THE FLUE
Connect the bend – supplied with the terminal
kit – to the top of the boiler using clamp (supplied)
see fig. 7. The additional bends & extensions have
push-fit connections, care should be taken to
ensure that the correct seal is made when
assembling the flue system. Connect the required
number of flue extensions or bends (up to the
maximum equivalent flue length) to the flue
terminal (see fig. 7 & 8).
125mm
outer
clamp
Boiler
Fig. 7
FITTING THE HORIZONT AL FLUE KIT
Carefully measure the distance from the centre
of the appliance flue outlet to the edge of the
finished outside wall (dimension X). Add 45mm
to dimension X to give you Dimension Y (see fig
7A). Measure dimension Y from the terminal end
of the concentric flue pipe and cut off the excess
ensuring any burrs are removed. Pass the
concentric flue pipe through the previously drilled
hole. Fit the flue bend to the boiler flue outlet and
insert the concentric flue pipe into the flue bend
ensuring the correct seal is made. Using the
clamp, gasket, and screws supplied, secure the
flue bend to the appliance flue spigot. The 60mm
M & F adaptor (supplied with the flue kit) should
be discarded.
The hole should have a 1° rise from the boiler to
outside, to ensure any condense fluid that forms,
is allowed to drain back to the appliance.
NOTE
When cutting an extension to the required length,
you must ensure that the excess is cut from the
plain end of the extension (see fig. 7 & 8).
Remove any burrs, and check that all seals are
located properly.
You must ensure that the entire flue system is
properly supported and connected.
Seal the flue assembly to the wall using cement
or a suitable alternative that will provide
satisfactory weatherproofing. The interior and
exterior trim can now be fitted.
10
Supplied By www.heating spares.co Tel. 0161 620 6677
Fig. 8
4.5.2CONCENTRIC VERTICAL FLUE
The appliance can be used with either the Vokera
condensing 60/100mm concentric flue system or
the optional 80/125mm concentric flue system.
NOTE
These instructions relate only to the Vokera
condensing 60/100mm concentric flue system.
For specific details on the installation of the 80/
125mm concentric flue system please refer to
the instructions supplied.
The vertical flue terminal can be connected
directly to the appliance flue outlet. Alternatively,
an extension or bend can be connected to the
appliance flue outlet if desired (see 4.4.2),
however if additional bends are fitted, a reduction
must be made to the maximum flue length (see
table below).
Reduction for bends
BendReduction in maximum flue length for each bend
Using the dimensions given in fig. 9 as a reference, mark
and cut a 115mm hole in the ceiling and/or roof.
Fit the appropriate flashing plate to the roof and insert
the vertical flue terminal through the flashing plate from
the outside, ensuring that the collar on the flue terminal
fits over the flashing.
The fixing holes for the wall-mounting bracket should now
be drilled and plugged, an appropriate type and quantity
of fixing should be used to ensure that the bracket is
mounted securely. Once the bracket has been secured
to the wall, mount the appliance onto the bracket.
Fig. 9
IMPORTANT
The vertical flue terminal is 1.0 metre in length
and cannot be cut; therefore it may be necessary
to adjust the height of the appliance to suit or
use a suitable extension.
Connect the vertical flue assembly to the boiler
flue spigot using the 60mm & 100mm clips,
gaskets, & screws (supplied), ensuring the correct
seal is made. The flue support bracket (supplied
with the vertical flue kit) can now be fitted.
If the vertical flue requires extension/s or
additional bend/s, connect the required number
of flue extensions or bends (up to the maximum
equivalent flue length) between the boiler and
vertical flue assembly (see fig. 8).
Ensure that any horizontal sections of the flue
system have a 1° fall back to the boiler (17mm
per 1000mm).
11
Supplied By www.heating spares.co Tel. 0161 620 6677
NOTE
When cutting an extension to the required length,
you must ensure that the excess is cut from the
plain end of the extension (see fig. 8). Remove
any burrs, and check that any seals are located
properly.
You must ensure that the entire flue system is
properly supported and connected.
4.5.3TWIN FLUE SYSTEM
The Vokera twin flue system enables greater flue
distances to be achieved (see 4.4.2) than that of
a concentric flue system. It can be used for
horizontal or vertical applications, however the
twin flue system must be converted to the
dedicated concentric flue kit for termination. It is
essential that the installation of the twin flue
system be carried out in strict accordance with
these instructions.
GUIDANCE NOTES ON TWIN FLUE INSTALLATION
● The flue must have a fall back of 1° back to
the appliance to allow any condensate that
may form in the flue system to drain via the
condensate drain. Consideration must also be
given to the fact that there is the possibility of
a small amount of condensate dripping from
the terminal.
● Ensure that the entire flue system is
adequately supported, use at least one bracket
for each extension.
● The entire flue system must be adequately
insulated to maintain heat within the flue
system thereby reducing the possibility of
condensate production.
● As the exhaust outlet pipe can reach very high
temperatures it must be protected to prevent
persons touching the hot surface.
● The condensate drain pipe must be connected
in accordance with building regulations.
MOUNTING THE BOILER
The fixing holes for the wall-mounting bracket should now
be drilled and plugged, an appropriate type and quantity
of fixing should be used to ensure that the bracket is
mounted securely. Once the bracket has been secured
to the wall, mount the appliance onto the bracket.
Pay attention to condense trap!
4.5.3.1 INST ALLATION OF TWIN ADAPTOR KIT (see
fig. 10 & 11)
● Insert the exhaust connection manifold (A)
onto the appliance flue outlet.
● Remove the blanking plate (located to the right
of the appliance flue outlet) and – using the
same screws – install the air inlet plate (B).
● Using the hole in the exhaust connection
manifold as a guide, drill a 3mm hole in the
appliance flue spigot and secure the exhaust
manifold connection to the flue spigot using
the screw provided (C).
● Using the two holes in the air inlet plate as a
guide, drill a 3mm hole in each and secure the
air inlet pipe/bend using the screws provided.
● The twin flue pipes extensions and accessories
can now be installed by pushing together (the
plain end of each extension or bend should
be pushed approximately 50mm into the
female socket of the previous piece).
C
A
B
Reduction for bends
BendReduction in maximum flue length for each bend
Supplied By www.heating spares.co Tel. 0161 620 6677
Fig. 12
4.5.3.2 HORIZONTAL TERMINATION (see fig. 12)
The twin flue system must be converted to the
dedicated concentric flue kit for termination.
● The horizontal terminal is supplied with a built-
in converter box and cannot be shortened.
● A 130mm hole is required for the passage of
the concentric terminal through the wall.
● The air inlet pipe must always be level with or
below, that of the exhaust pipe.
Depending on site conditions it may be preferable
to install the terminal assembly prior to fitting the
twin flue pipes.
Mark and drill a 130mm hole for the passage of
the horizontal flue terminal, ensuring that there
is a 1° fall back to the boiler (17mm per 1000mm).
Insert the terminal assembly into the flue hole.
Push-fit the twin flue pipes onto the concentric to
twin converter box ensuring that the exhaust pipe
connects to the exhaust connection on the
concentric to twin converter.
If necessary cut the plain ends (male) of the twin
flue pipes to allow connection to the concentric
to twin converter
NOTE
Before cutting twin flue pipes ensure allowances
have been made for connection onto the previous
piece and onto the concentric to twin converter.
The last twin Flue pipes must be pushed 50mm
onto the male spigots of the concentric to twin
converter.
NOTE
You must ensure that the entire flue system is
properly supported and connected.
Seal the flue terminal assembly to the wall using
cement or a suitable alternative that will provide
satisfactory weatherproofing. The interior and
exterior trim can now be fitted.
1-deg. = 17mm
1.0-metre
4.5.3.3 VERTICAL TERMINA TION (see fig. 13)
The twin flue system must be converted to the
dedicated concentric flue kit for termination.
● The vertical terminal is supplied with a built-in
converter box and cannot be shortened.
● A 130mm hole is required for the passage of
the concentric terminal through the ceiling and/
or roof.
Depending on site conditions it may be preferable
to install the terminal assembly prior to fitting the
twin flue pipes.
Fit the appropriate flashing plate to the roof and
insert the vertical flue terminal through the
flashing plate from the outside, ensuring that the
collar on the flue terminal fits over the flashing.
Push-fit the twin flue pipes onto the concentric to
twin converter ensuring that the exhaust pipe
connects to the exhaust connection on the
concentric to twin converter.
If necessary cut the plain ends (male) of the twin
flue pipes to allow connection to the concentric
to twin converter.
NOTE
● Before cutting twin flue pipes ensure
allowances have been made for connection
onto the previous piece and onto the
concentric to twin converter. The last twin flue
pipes must be pushed 50mm onto the male
spigots of the concentric to twin converter.
● Y ou must ensure that the entire flue system is
properly supported and connected.
● Ensure that any horizontal sections of pipe
have a 1° fall towards the appliance (17mm
per 1000mm).
13
Supplied By www.heating spares.co Tel. 0161 620 6677
C/H flow
valve
Fig. 14
C/H return
valve
Safety valve
outlet
4.6.1GAS (see fig. 6A & 14)
The appliance is supplied with a 15mm service
valve, connect a 15mm pipe to the inlet of the
valve and tighten both nuts.
NOTE
It will be necessary to calculate the diameter of
the gas supply pipe to ensure the appliance has
an adequate supply of gas.
Hot water
Outlet
Cold water Inlet
Stopcock/filling
valve
Filling Loop
Gas
Cock
Fig. 13
4.6CONNECTING THE GAS AND W ATER
The appliance is supplied with a fixing jig that
includes service valves (fig. 14). The service
valves are of the compression type. The
accessories pack contains sealing washers etc,
for use with the service valves.
When connecting pipe work to the valves, tighten
the compression end first then insert the sealing
washers before tightening the valve to the
appliance.
NOTE
It will be necessary to hold the valve with one
spanner whilst tightening with another.
4.6.2FLOW & RETURN (see fig. 6A & 14)
The appliance is supplied with 22mm service
valves for the flow and return connections,
connect a 22mm pipe to the inlet of each valve
and tighten both nuts.
NOTE
Depending on system requirements, it may
necessary to increase the size of the flow & return
pipe work after the service valve connections.
4.6.3COLD WATER INLET (see fig. 6A & 14)
The appliance is supplied with a 15mm combined
stopcock and double check-valve, connect a
15mm pipe to the inlet of the stopcock and tighten
both nuts.
4.6.4HOT WATER OUTLET (see fig. 6A & 14)
The appliance is supplied with a 15mm outlet
connection, connect a 15mm pipe to the outlet
connection and tighten both nuts.
4.6.5SAFETY VALVE (see fig. 6A & 14)
Connect the safety valve connection pipe
between the safety valve outlet and the fixing jig.
14
Loading...
+ 36 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.