4
Mynute
GETTING STARTED
2.1 BEFORE SWITCHING ON
Before switching the appliance on, please
familiarise yourself with:
● how to isolate the appliance from the gas,
water and electricity supplies;
● how to check and top-up - if necessary - the
system water pressure;
● the time clock or programmer;
● any external thermostats and their functions;
● the appliance controls.
2.2 APPLIANCE CONTROLS (see fig. 1)
The appliance controls are concealed behind the
front flap. To gain access to the controls simply
press the top centre of the flap, release, and pull
downward. The appliance has a mode switch,
variable thermostat, system pressure gauge, and
an aperture for an integral clock or programmer.
The mode switch has three positions:
● RESET
● OFF
● ON
The variable thermostat allows you to set the
temperature of the water to your radiators and hot
water cylinder (not the hot water to your taps!)
between 40°C (min) and 80°C (max).
The pressure gauge shows the current pressure
of the system, the gauge should be set between
1 and 1.5 bar. When the appliance is operating
the gauge may rise or fall slightly, this is quite
normal. The minimum permissible level for the
safe and efficient operation of the appliance is 0.5
bar. Should the pressure fall below 0.5 bar, the
boiler shuts off automatically.
Depending on the type of controls specified by
your installer you may have an integral Vokera
time clock or programmer fitted to the appliance,
if so, instructions can be found on page 6. If an
external time clock or programmer has been
fitted, please refer to the instructions supplied
with such.
2.3 LIGHTING THE BOILER
Ensure the gas and electrical supply to the boiler
are turned on.
Turn the mode switch to the “on” position. The
status indicator should be “green” if the status
indicator is flashing “red” refer to 3.2.
Refer to the particular instructions for the type of
programmer or time clock fitted and ensure there is
a demand for heating and/or hot water. If there is a
room thermostat and/or hot water cylinder
thermostat you should ensure these are also calling
for heat.
When there is a demand for heating and/or hot
water via the above controls, the boiler will go
through an ignition sequence, whereby the burner
will light.
If the appliance fails to ignite during the ignition
sequence, allow a period of two minutes before
re-setting.
To adjust the output temperature of the appliance
turn the thermostat knob clockwise to increase or
anti-clockwise to decrease.
When the appliance reaches the set temperature,
the burner will go off for minimum period of
approximately 3 minutes.
When the programmer/time clock or external
thermostats heating request has been satisfied,
the appliance will switch off automatically.
HOW TO...
3.1 HOW TO TOP-UP THE SYSTEM PRESSURE
(see fig. 2)
The system pressure must be checked periodically
to ensure the correct operation of the boiler. The
needle on the gauge should be reading between
1 and 1.5 bar when the boiler is in an off position
and has cooled to room temperature.If the
pressure requires ‘topping-up’ use the following
instructions as a guide.
● Locate the filling valve connections (external to
the boiler).
● Attach the filling loop to both connections.
● Open the filling valve slowly until you hear
water entering the system.
● Close the filling valve when the pressure gauge
(on the boiler) reads between 1 and 1.5 bar.
● Remove the filling loop from the connections.
3.2 HOW TO RESET THE APPLIANCE
When the led status indicator is flashing red, the
appliance will require to be reset manually. Using
the mode switch, turn it two clicks to the left (reset
position) then turn it back to the “on” position (see
also 3.3). Allow a period of two minutes to elapse
before turning the mode switch to the reset
position.
IMPORTANT
If the appliance requires to be reset frequently,
it may be indicative of a fault, please contact
your installer or Vokera Customer Services for
further advice.