VOKERA ProCombi 85 HE, ProCombi 100 HE Installation And Service Instructions Manual

Supplied By www.heating spares.co Tel. 0161 620 6677
Installation & Servicing Instructions
THESE INSTRUCTIONS TO BE RETAINED BY USER
0694
Supplied By www.heating spares.co Tel. 0161 620 6677
Design principles and operating sequence Page
1.1 Principle components 4
1.2 Mode of operation (at rest) 4
1.3 Mode of operation (heating) 4
1.4 Mode of operation (DHW) 4
1.5 Safety devices 4
Technical data Page
2.1 Central heating 5
2.2 Domestic hot water 5
2.3 Gas pressure 5
2.4 Expansion vessel 5
2.5 Dimensions 5
2.6 Clearances 5
2.7 Connections 5
2.8 Electrical 5
2.9 Flue details 5
2.10 Efficiency 5
2.11 Pump duty 6
2.12 Appliance 6
General requirements (UK) Page
3.1 Related documents 7
3.2 Location of appliance 7
3.3 Gas supply 7
3.4 Flue system 7
3.5 Air supply 7
3.6 Water circulation 7
3.6.1 Pipework 8
3.6.2 Automatic by-pass 8
3.6.3 Drain cocks 8
3.6.4 Air release points 8
3.6.5 Expansion vessel 8
3.6.6 Filling point 8
3.6.7 Low pressure sealed system 8
3.6.8 Frequent filling 8
3.7 Electrical supply 8
3.8 Showers 8
3.9 Mounting on a combustible surface 9
3.10 Timber framed building 9
3.11 Inhibitors 9
Installation Page
4.1 Delivery 10
4.2 Contents 10
4.3 Unpacking 10
4.4 Preparation for mounting the appliance 10
4.5 Fitting the flue 10
4.5.1 Concentric horizontal flue 10
4.5.2 Concentric vertical flue 11
4.6 Connecting the gas and water 12
4.6.1 Gas 12
4.6.2 Flow and return 12
4.6.3 Cold water inlet 12
4.6.4 Hot water outlet 12
4.6.5 Safety valve 12
4.6.6 Condense pipe 12
4.7 Electrical connections 13
4.7.1 Casing removal 13
4.7.2 Appliance terminal block 13
4.7.3 Connecting the mains (230V) input 13
Commissioning Page
5.1 Gas supply installation 14
5.2 The heating system 14
5.3 Initial filling of the system 14
5.4 Initial flushing 14
5.5 Filling the hot water system 14
5.6 Pre-operation checks 14
5.7 Initial lighting 14
5.7.1 Checking burner pressures 14
5.8 Final flushing of the heating system 14
5.8.1 Inhibitors 14
5.9 Setting the boiler operating temperature 14
5.9.1 Setting the DHW temperature 15
5.10 Setting the system design pressure 15
5.11 Regulating the hot water 15
5.11.1 Changing the flow restrictor 15
5.11.2 Regulating the central heating system 15
5.12 Final checks 15
5.13 Instructing the user 15
5.14 Technical assistance 15
Servicing instructions Page
6.1 General 16
6.2 Routine annual servicing 16
6.3 Replacement of components 16
6.4 Component removal procedure 16
6.5 Pump assembly 16
6.6 Safety valve 16
6.7 Automatic air release valve 16
6.8 Water pressure switch 17
6.9 Pressure gauge 17
6.10 Primary thermistor 17
6.11 High limit thermostat 17
6.12 PCB 17
6.13 Gas valve 17
6.14 Integral time switch 18
6.15 Electrode, burner thermostat, burner & injectors 18
6.16 Flue fan 18
6.17 Main heat exchanger 19
6.18 Air pressure switch 19
6.19 Flow restrictor 19
6.20 DHW flow switch 19
6.21 DHW heat exchanger 20
6.22 Valve actuator 20
6.23 Divertor valve cartridge 20
6.24 DHW thermistor 20
6.25 Automatic by-pass 20
6.26 DHW non-return valve 2 0
6.27 Expansion vessel 20
6.27.1 Expansion
6.27.2 Expansion vessel removal
6.28.1 Latent heat collector 21
6.28.2 Dismantling the latent heat collector 21
6.29 Condense trap removal 21
Checks, adjustments and fault finding page
7.1 Checking appliance operation 22
7.2 Appliance mode of operation 22
7.2.1 Selector switch in the OFF position 22
7.2.2 Selector switch in the hot water only position 22
7.2.3 Selector switch in the heating & hot water position 22
7.2.4 Appliance functions 22
7.2.5 DHW mode 22
7.2.6 Heating mode 23
7.3 Checking & adjusting burner pressure 24
7.3.1 Setting the maximum burner pressure 24
7.3.2 Setting the minimum burner pressure 24
7.3.3 Setting the minimum CH output 24
7.4 Combustion analysis test 24
7.5 Checking the expansion vessel 25
7.6 External faults 25
7.6.1 Installation faults 25
7.7 Electrical checks 25
7.7.1 Earth continuity test 25
7.7.2 Short circuit check 25
7.7.3 Polarity check 25
7.7.4 Reversed polarity or supply fault 26
7.7.5 Resistance to earth check 26
7.8 Fault finding 26
7.8.1 Replacing the main PCB 26
7.9 Fault codes 26
7.10 Fault finding 27-32
Wiring diagrams Page
8.1 External wiring 33
8.2 Typical control applications 33
8.3 Room thermostat 33
8.4 Other controls 33 Functional diagram 3 4
L.P.G. instructions Page
10.1 Related documents 35
10.2 Technical data 35
10.3 Converting the appliance gas supply 35
10.4 Gas supply 35
10.5 Gas supply installation 35
10.6 Checking & adjusting burner pressure 35
10.6.1 Setting the maximum burner pressure 35
10.6.2 Setting the minimum burner pressure 3 5
vessel removal (with sufficient clearance above)
(with insufficient clearance above)
21
20
2
Supplied By www.heating spares.co Tel. 0161 620 6677
INTRODUCTION
The PRO Combi HE range of appliances is comprised of 2 models of high-efficiency combination boiler with inputs to heating & DHW of 25, 29 kW respectively. Each appli­ance - by design - incorporates electronic ignition, circu­lating pump, expansion vessel, safety valve, pressure gauge and automatic by-pass.
The PRO Combi HE range is produced as room sealed, category II2H3P appliances, suitable for internal wall mounting applications only. They are provided with a fan
powered flue outlet with an annular coaxial combustion air intake that can be rotated - horizontally - through 360 degrees for various horizontal or vertical applications. The PRO Combi HE range is approved for use with C12 & C32 type flue applications. These appliances are designed for use with a sealed system only; consequently they are not intended for use on open vented systems
Fig.1 General Layout
1 Discharge valve 2 Gas valve 3 Modulator coil 4 Pressure switch 5 Condense trap 6 Ignition transformer 7 Expansion vessel 8 Electrode 9 Main burner 1 0 Main heat exchanger 1 1 Latent heat collector 1 2 Flue gas analysis test point 1 3 Flue outlet 1 4 Air intake 1 5 Differential pressure switch 1 6 Silicone pressure tube (-) 1 7 Silicone pressure tube (+) 1 8 Fan assembly 1 9 CH NTC sensor 2 0 High limit thermostat 21 Combustion chamber 22 Condensate pressure switch 2 3 Auto air vent (AAV) 24 Pump 2 5 DHW flow switch 26 DHW sensor 2 7 Domestic hot water heat exchanger 2 8 Diverter valve motor 29 Pressure gauge 30 DHW position 3 1 Mode selector switch 3 2 Fault indicator led 33 CH position 34 Timeclock
Fig. 1
29 30 31 33
32
34
3
Supplied By www.heating spares.co Tel. 0161 620 6677
SECTION 1 DESIGN PRINCIPLES AND OPERATING SEQUENCE
1.1 PRINCIPLE COMPONENTS
A fully integrated electronic control board fea-
turing electronic temperature control, anti-cy­cle control, pump over-run, LED fault indicator, full gas modulation.
Low-water-content, copper heat exchanger.
Electronic ignition with flame supervision.
Integral high-head pump.
Fan.
Air pressure switch.
Expansion vessel.
Water pressure switch.
Two-stage gas valve.
Pressure gauge.
Safety valve.
Condense switch.
1.2 MODE OF OPERATION (at rest)
When the appliance is at rest and there are no requests for heating or DHW, the following func­tions are active:
Frost-protection system: the frost-protection
system protects the appliance against the risk of frost damage. Should the temperature of the appliance fall to 5 °C, the boiler will function in the heating mode at minimum power until it reaches 35 °C.
Anti-block function: the anti-block function ena-
bles the pump and divertor valve actuator, to be energised for short periods, when the appli­ance has been inactive for more than 19-hours.
DHW
temperature
sensor
DHW non
return valve
Water
pressure
switch
Automatic
by-pass
Safety valve
Fig. 2
CH
flow
latent heat
collector
DHW
outlet
Flue
outlet
Gas valve
DHW heat exchanger
Air
intake
Pressure
switch
Main heat
exchanger
return
CH NTC
sensor
Main
burner
CH
Expansion
vessel
AAV
Pump
Diverter
valve motor
DHW
flow switch
Domestic cold water inlet
1.3 MODE OF OPERATION (Heating)
When there is a request for heat via the time clock and/or any external control, the pump and fan are started, the fan will then prove the air pressure switch. At this point an ignition sequence is enabled.
Ignition is sensed by the electronic circuitry to ensure flame stability at the burner. Once suc­cessful ignition has been achieved, the electronic circuitry increases the gas rate to 75% for a period of 15 minutes. Thereafter, the boiler’s output will either be increase to maximum or modulate to suit the set requirement.
When the appliance reaches the desired tem­perature the burner will shut down and the boiler will perform a three-minute anti-cycle (timer de­lay).
When the request for heat has been satisfied the appliance pump and fan may continue to operate to dissipate any residual heat within the appli­ance.
1.4 MODE OF OPERATION (DHW)
When there is a request for DHW via a hot water outlet or tap, the pump and fan are started, the fan will then prove the air pressure switch. At this point an ignition sequence is enabled.
Ignition is sensed by the electronic circuitry to ensure flame stability at the burner. Once suc­cessful ignition has been achieved, the electronic circuitry increases the gas rate to maximum or will modulate output to stabilise the temperature.
In the event of the appliance exceeding the desired temperature the burner will shut down until the temperature drops.
When the request for DHW has been satisfied the appliance pump and fan may continue to operate to dissipate any residual heat within the appli­ance.
1.5 SAFETY DEVICES
When the appliance is in use, safe operation is ensured by:
A water pressure switch that monitors system
water pressure and will deactivate the pump, fan and burner should the system water pres­sure drop below the rated tolerance.
A high limit thermostat that over-rides the tem-
perature control circuit to prevent or interrupt the operation of the burner.
An air pressure switch that requires the fan to
prove operation before the gas valve is ener­gised.
A pressure switch that interrupts the operation
of the appliance if the condense pipe becomes blocked.
A safety valve which releases excess pressure
from the primary circuit.
4
Supplied By www.heating spares.co Tel. 0161 620 6677
SECTION 2 TECHNICAL DATA
85 HE
2.1 Central heating
Heat input (kW) 25.00 29.00 Maximum heat output@ 80/60 °C (kW) 24.35 28.30 Minimum heat output@ 80/60 °C (kW) 14.25 14.28 Maximum heat output@ 50/30 °C (kW) 25.90 29.93 Minimum heat output@ 50/30 °C (kW) 14.85 14.75 Minimum working pressure 0.5 bar 0.5 bar Maximum working pressure 2.7 bar 2.7 bar Minimum flow rate 350 l/h 350 l/h
2.2 Domestic hot water
Minimum output (kW) 9.50 9.90 Flow rate (35 °C rise) 10.2 l/min 11.9 l/min Maximum inlet pressure 6.0 bar 6.0 bar Minimum inlet working pressure 0.15 bar 0.15 bar Minimum flow rate 2 l/min. 2 l/min.
2.3 Gas pressures
Inlet pressure G20 20.0 mbar 20.0 mbar Maximum burner pressure 9.40 mbar 9.20 mbar Minimum burner pressure (central heating) 3.50 mbar 2.70 mbar Minimum burner pressure (domestic hot water) 1.50 mbar 1.20 mbar Gross rate (central heating, max - min) 2.64 - 1.59 m3/h 3.07 - 1.59 m3/h Injectors size 12 x 1.35 mm 14 x 1.35 mm
100 HE
2.4 Expansion vessel
Capacity 8 litres 10 litres Maximum system volume 76 litres 91 litres Pre-charge pressure 1.0 bar 1.0 bar
2.5 Dimensions
Height 780 mm 780 mm Width 400 mm 450 mm Depth 332 mm 332 mm Dry weight 40 kg 44 kg
2.6 Clearances
Sides 12 mm 12 mm Top 150 mm from casing or 25 mm above flue elbow, whichever is applicable Bottom 150 mm 150 mm Front 600 mm 600 mm
2.7 Connections
Flow & return 22 mm 22 mm Hot & cold water connections 15 mm 15 mm Gas 15 mm 15 mm Safety valve 15 mm 15 mm Condense 21 mm 21 mm
2.8 Electrical
Voltage 230V/~ 50hz 230V/~ 50hz Power consumption 153 W 153 W Internal fuse 2 A 2 A External fuse 3 A 3 A
2.9 Flue details (concentric)
Maximum horizontal flue length (60/100mm) 4.5 m 4.0 m Maximum vertical flue length (60/100mm) 5.5 m 5.0 m
2.10 Efficiency
SEDBUK 86.9 Band “B” 86.7 Band “B”
Ref. Condition 15 °C , 1013,25 mbar, dry gas NOTE: L.P.G. data refer to section 10
5
Supplied By www.heating spares.co Tel. 0161 620 6677
2.11 PUMP DUTY
Fig. 3 shows the flow rate available - after allowing for pressure loss through the appliance - for system requirements. When using this graph, apply only the pressure loss of the system. The graph is based on a 20 ºC temperature differential.
85 HE - 100 HE
5,0
4,5
4,0
3,5
3,0
2,5
2,0
1,5
1,0
0,5
0,0
0 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300
first speed
second speed
85 HE 100 HE
2.12 Appliance
NOx 94 ppm - 166 mg/kWh 92 ppm - 162 mg/kWh CO (max-min) 80 ppm - 80 ppm 100 ppm - 60 ppm CO2 (max-min) 6.75 - 3.90 % 7.05 - 3.50 % CO/CO2 ratio (max) 0.001 to 1 0.001 to 1 CO/CO
ratio (min) 0.002 to 1 0.002 to 1
2
third speed
SECTION 3 GENERAL REQUIREMENTS
Fig. 4
Key Location Minimum distance
A Below an opening (window, air-brick, etc.) 300 mm
B Above an opening (window, air-brick, etc.) 300 mm C To the side of an opening (window, air-brick, etc.) 300 mm D Below gutter, drain-pipe, etc. 25 mm E Below eaves 25mm F Below balcony, car-port roof, etc. 25 mm
G To the side of a soil/drain-pipe, etc. 25 mm
H From internal/external corner or boundary 300 mm
I Above ground, roof, or balcony level 300 mm
J From a surface or boundary facing the terminal 1200 mm K From a terminal facing a terminal 1200 mm
L From an opening in the car-port into the building 1200 mm
M Vertically from a terminal on the same wall 1500 mm
N Horizontally from a terminal on the same wall 300 mm P From a structure to the side of the vertical terminal 500 mm
Q From the top of the vertical terminal to the roof flashing As determined by the fixed collar
of the vertical terminal
6
Supplied By www.heating spares.co Tel. 0161 620 6677
This appliance must be installed by a competent person in accordance with the Gas Safety (Instal­lation & Use) Regulations.
3.1 RELATED DOCUMENTS
The installation of this boiler must be in accord­ance with the relevant requirements of the Gas Safety (Installation & Use) Regulations, the local building regulations, the current I.E.E. wiring regulations, the bylaws of the local water under­taking, the Building Standards (Scotland) Regu­lation and Building Standards (Northern Ireland) Regulations.
It should be in accordance also with any relevant requirements of the local authority and the rel­evant recommendations of the following British Standard Codes of Practice.
3.2 LOCATION OF APPLIANCE
The appliance may be installed in any room or internal space, although particular attention is drawn to the requirements of the current I.E.E. wiring regulations and in Scotland, the electrical provisions of the Building Regulations, with re­spect to the installation of the appliance in a room or internal space containing a bath or shower.
3. 3 GAS SUPPLY
The gas meter - as supplied by the gas supplier
- must be checked to ensure that it is of adequate size to deal with the maximum rated input of all the appliances that it serves. Installation pipes must be fitted in accordance with BS 6891.
Pipe work from the meter to the appliance must be of adequate size. Pipes of a smaller size than the appliance gas inlet connection must not be used. The installation must be tested for sound­ness in accordance with BS6891.
If the gas supply serves more than one appliance, it must be ensured that an adequate supply is maintained to each appliance when they are in use at the same time.
3.4 FLUE SYSTEM
The terminal should be located where the disper­sal of combustion products is not impeded and with due regard for the damage and discoloration that may occur to building products located nearby. The terminal must not be located in a place where it is likely to cause a nuisance (see fig. 4).
Water vapour will condense on leaving the termi­nal and the effect of such pluming must be considered.
BS 5440 PART 1 FLUES BS 5440 PART 2 FLUES & VENTILATION BS 5449 PART 1 FORCED CIRCULATION HOT WATER SYSTEMS BS 5546 INSTALLATION OF GAS HOT WATER SUPPLIES FOR DOMESTIC PURPOSES
(2ND FAMILY GASES) BS 6798 INSTALLATION OF BOILERS OF RATED INPUT NOT EXCEEDING 60kW BS 6891 LOW PRESSURE INSTALLATION PIPES BS 7074 PART 1 APPLICATION, SELECTION AND INSTALLATION OF EXPANSION VESSELS AND
ANCILLARY EQUIPMENT FOR SEALED WATER SYSTEMS
When an appliance is installed in a room or internal space containing a bath or shower, the appliance or any control pertaining to it must not be within reach of a person using the bath or shower.
The location chosen for the appliance must permit the provision of a safe and satisfactory flue and termination. The location must also permit an adequate air supply for combustion purposes and an adequate space for servicing and air circulation around the appliance. Where the in­stallation of the appliance will be in an unusual location special procedures may be necessary, BS 6798 gives detailed guidance on this aspect.
A compartment used to enclose the appliance must be designed and constructed specifically for this purpose. An existing compartment/cup­board may be utilised provided that it is modified to suit.
Details of essential features of compartment/ cupboard design including airing cupboard instal­lations are given in BS 6798. This appliance is not suitable for external installation.
3.5 AIR SUPPLY
3.6 WATER CIRCULATION
If installed less than 2m above a pavement or platform to which people have access (including balconies or flat roofs) the terminal must be protected by a guard of durable material. The guard must be fitted centrally over the terminal. Refer to BS 5440 Part 1, when a terminal is sited less than 1m below a plastic gutter, or less than 500mm below a painted surface, a suitable one metre long heat shield should be fitted.
The following notes are intended for general guidance only.
This appliance is a room-sealed, fan-flued boiler, consequently it does not require a permanent air vent for combustion air supply.
When installed in a cupboard or compartment, ventilation for cooling purposes is also not re­quired.
Detailed recommendations are given in BS 5449 Part 1 and BS 6798. The following notes are for general guidance only.
7
Supplied By www.heating spares.co Tel. 0161 620 6677
3.6.1 PIPEWORK
It is recommended that copper tubing to BS 2871 Part 1 is used in conjunction with soldered capil­lary joints.
Where possible pipes should have a gradient to ensure air is carried naturally to air release points and that water flows naturally to drain cocks.
Except where providing useful heat, pipes should be insulated to avoid heat loss and in particular to avoid the possibility of freezing. Particular atten­tion should be paid to pipes passing through ventilated areas such as under floors, loft space and void areas.
3.6.2 AUTOMATIC BY-PASS
The appliance has a built-in automatic by-pass. However it may be necessary to fit an external bypass should the design of the heating system require such. In any case, the design of the system should be such that it prevents boiler ‘cycling’.
3.6.3 DRAIN COCKS
These must be located in accessible positions to facilitate draining of the appliance and all water pipes connected to the appliance. The drain cocks must be manufactured in accordance with BS 2879.
3.6.7 LOW PRESSURE SEALED SYSTEM
An alternative method of filling the system would be from an independent make-up vessel or tank mounted in a position at least 1 metre above the highest point in the system and at least 5 metres above the boiler (see fig. 5a).
The cold feed from the make-up vessel or tank must be fitted with an approved non-return valve and stopcock for isolation purposes. The feed pipe should be connected to the return pipe as close to the boiler as possible.
Make-up vessel or tank
Automatic air-vent
Non-return
valve
Stopcock
5.0 metres minimum
3.6.4 AIR RELEASE POINTS
These must be positioned at the highest points in the system where air is likely to be trapped. They should be used to expel trapped air and allow complete filling of the system.
3.6.5 EXPANSION VESSEL
The appliance has an integral expansion vessel to accommodate the increased volume of water when the system is heated. It can accept up to 8 litres (25kW) or 10 litres (29 kW) of expansion from within the system, generally this is sufficient, however if the system has an unusually high water content, it may be necessary to provide additional expansion capacity (see 6.19).
3.6.6 FILLING POINT
An approved method for initial filling of the system and replacing water lost during servicing etc. is required (see fig. 5). This method of filling must comply with the current Water Supply (Water Fittings) Regulations 1999 and Water Bylaws 2000 (Scotland).
control valve
temporary
connection
control valve
Fig. 5a
Heating return
3.6.8 FREQUENT FILLING
Frequent filling or venting of the system may be indicative of a leak. Care should be taken during the installation of the appliance to ensure all aspects of the system are capable of withstand­ing pressures up to at least 3 bar.
3.7 ELECTRICAL SUPPLY
The appliance is supplied for operation on 230V @ 50Hz electrical supply; it must be protected with a 3-amp fuse. The method of connection to the mains electricity supply must allow for com­plete isolation from the supply. The preferred method is by using a double-pole switch with a contact separation of at least 3mm. The switch must only supply the appliance and its corre­sponding controls, i.e. time clock, room thermo­stat, etc. Alternatively an un-switched shuttered socket with a fused 3-pin plug both complying with BS 1363 is acceptable.
flow/return
pipe
Fig. 5
8
double check
valve
supply pipe
3.8 SHOWERS
If the appliance is intended for use with a shower, the shower must be thermostatically controlled and be suitable for use with a combination boiler.
Supplied By www.heating spares.co Tel. 0161 620 6677
3.9 MOUNTING ON A COMBUSTIBLE SURFACE
If the appliance is to be fitted on a wall of combustible material, a sheet of fireproof mate­rial must protect the wall.
3.10 TIMBER FRAMED BUILDING
If the appliance is to be fitted in a timber framed building, it should be fitted in accordance with the Institute of Gas Engineers publication (IGE/UP/
7) ‘Guide for Gas Installations in Timber Frame Buildings’.
3.11 INHIBITORS
It is recommend that an inhibitor - suitable for use with copper and aluminium heat exchangers - is used to protect the boiler and system from the effects of corrosion and/or electrolytic action. The inhibitor must be administered in strict ac­cordance with the manufacturers instructions*.
*Water treatment of the complete heating system
- including the boiler - should be carried out in accordance with BS 7593 and the Domestic Water Treatment Association’s (DWTA) code of practice.
Fig. 6a
Fig. 6
9
Supplied By www.heating spares.co Tel. 0161 620 6677
SECTION 4 INSTALLATION
4.1 DELIVERY
Due to the weight of the appliance it may be necessary for two people to lift and attach the appliance to its mounting. The appliance is contained within a heavy­duty cardboard carton. Lay the carton on the floor with the writing the correct way up.
4.2 CONTENTS
Contained within the carton is:
the boiler
the wall bracket
appliance template
an accessories pack containing appliance serv-
ice connections and washers
the instruction pack containing the installation
& servicing instructions, user instructions, Benchmark logbook, guarantee registration card and a 3-amp fuse.
4.3 UNPACKING
At the top of the carton pull both sides open - do not use a knife - unfold the rest of the carton from around the appliance, carefully remove all pro­tective packaging from the appliance and lay the accessories etc. to one side. Protective gloves should be used to lift the appliance, the appliance back-frame should be used for lifting points.
Horizontal flue terminals and accessories
Part No. Description Min-Max Length
489 Telescopic flue terminal kit 350/500mm 491 Horizontal flue kit for use with 1000 mm
add. bends & extensions 492 0.5m extension 500 mm 493 1.0m extension 1000 mm 494 2.0m extension 2000 mm 495 45º bend (pair) N/A 496 90º bend N/A 499 Wall bracket N/A
Using the template provided, mark and drill a 115mm hole for the passage of the flue pipe. The hole should be drilled level to ensure any con­dense fluid that forms will drain back to the boiler.
The fixing holes for the wall-mounting bracket should now be drilled and plugged, an appropri­ate type and quantity of fixing should be used to ensure that the bracket is mounted securely. Once the bracket has been secured to the wall, mount the appliance onto the bracket.
Terminal or
extension
4.4 PREPARATION FOR MOUNTING THE APPLI­ANCE
The appliance should be mounted on a smooth, vertical, non-combustible surface, which must be capable of supporting the full weight of the appli­ance. Care should be exercised when determin­ing the position of the appliance with respect to hidden obstructions such as pipes, cables, etc.
When the position of the appliance has been decided - using the template supplied - carefully mark the position of the wall- mounting bracket (see fig. 6) and flue-hole (if applicable).
4.5 FITTING THE FLUE
The top flue outlet permits both horizontal and vertical flue applications to be considered.
4.5.1 CONCENTRIC HORIZONTAL FLUE
(For concentric vertical flue, see section 4.5.2). The appliance flue outlet elbow can be rotated
through 360º on its vertical axis. In addition the flue may be extended from the outlet elbow in the horizontal plane (see 2.9). A reduction must also be made to the maximum length (see table below) when additional bends are used.
Reduction for additional bends
Bend Reduction in maximum flue length for each bend
45º bend 0.5 metre 90º bend 1.0 metre
outer
clamp
Boiler
Fig. 7
FITTING THE HORIZONTAL FLUE KIT
Carefully measure the distance from the centre of the appliance flue outlet to the edge of the fin­ished outside wall (dimension X). Add 65mm to dimension X to give you dimension Y (see fig 7A). Measure dimension Y from the terminal end of the concentric flue pipe and cut off the excess from the 100mm pipe ensuring any burrs are removed. Using the cut-off piece of 100mm pipe as a guide, mark and cut the same length of pipe from the inner 60mm pipe (the 60mm should always project past the 100mm pipe by 30mm). Pass the concentric flue pipe through the previ­ously drilled hole. Fit the flue bend to the boiler flue outlet and insert the concentric flue pipe into the flue bend ensuring the correct seal is made.
Using the clamps, gaskets, and screws supplied, secure the flue bend to the appliance flue spigot and the flue terminal.
NOTE
Fit the internal (White) trim to the flue assembly prior to connecting the flue pipe to the bend.
10
Supplied By www.heating spares.co Tel. 0161 620 6677
Fig. 7a
an extension or bend can be connected to the appliance flue outlet if desired (see 4.4.2), how­ever if additional bends are fitted, a reduction must be made to the maximum flue length (see table below).
Reduction for bends
Bend Reduction in maximum flue length for each bend
45º bend 0.5 metre 90º bend 1.0 metre
FLUE RESTRICTOR RING (horizontal flue)
To ensure maximum efficiency of the appliance, it may be necessary to fit one of the supplied flue restrictor rings to the appliance flue outlet (see tables below).
85 HE
Total flue length Restrictor required
Less than 1.2 metre 82.5mm diameter (fitted) Less than 3.0 metres 88mm diameter Less than 4.5 metres not required
100 HE
Total flue length Restrictor required
Less than 2.0 metres 84mm diameter (fitted) Less than 4.0 metres not required
4.5.1.1 EXTENDING THE FLUE
Connect the bend - supplied with the terminal kit
- to the top of the boiler using clamp (supplied) see fig. 7. The additional bends & extensions hav e push-fit connections, care should be taken to ensure that the correct seal is made when as­sembling the flue system. Connect the required number of flue extensions or bends (up to the maximum equivalent flue length) to the flue ter­minal (see fig. 7 & 8).
The hole should be drilled level to ensure that any condense fluid drains back to the appliance.
NOTE
When cutting an extension to the required length, you must ensure that the excess is cut from the plain end of the extension (see fig. 7 & 8). Re­move any burrs, and check that all seals are lo­cated properly. You must ensure that the entire flue system is properly supported and connected. Seal the flue assembly to the wall using cement or a suitable alternative that will provide satisfac­tory weatherproofing.
4.5.2 CONCENTRIC VERTICAL FLUE
The vertical flue terminal can be connected di­rectly to the appliance flue outlet. Alternatively,
Vertical flue ter minal and accessories
Part No. Description Min-Max Length
490 Vertical flue terminal 497 Pitched roof flashing plate N/ A 498 Flat roof flashing plate N/A
492 0.5m extension 500 mm 493 1.0m extension 1000 mm 494 2.0m extension 2000 mm 495 45º bend (pair) N/ A 496 90º bend N/A 499 Wall bracket N/A
Using the dimensions given in fig. 9 as a refer­ence, mark and cut a 107mm hole in the ceiling and/or roof.
Fig. 9
145
FLUE RESTRICTOR RING (vertical flue)
To ensure maximum efficiency of the appliance, it may be necessary to fit one of the supplied flue restrictor rings to the appliance flue outlet (see tables below).
85 HE
Total flue length Restrictor required
Less than 2.0 metre 82.5mm diameter (fitted) Less than 4.0 metres 88mm diameter Less than 5.5 metres not required
100 HE
Total flue length Restrictor required
Less than 2.8 metres 84mm diameter (fitted) Less than 5.0 metres not required
Fig. 8
11
Supplied By www.heating spares.co Tel. 0161 620 6677
Fit the appropriate flashing plate to the roof and insert the vertical flue terminal through the flash­ing plate from the outside, ensuring that the collar on the flue terminal fits over the flashing. The fixing holes for the wall-mounting bracket should now be drilled and plugged, an appropri­ate type and quantity of fixing should be used to ensure that the bracket is mounted securely. Once the bracket has been secured to the wall, mount the appliance onto the bracket.
IMPORTANT
The vertical flue terminal cannot be cut; therefore it may be necessary to adjust the height of the appliance to suit or use a suitable extension.
Connect the vertical flue assembly to the boiler flue spigot using the 60mm & 100mm clips, gaskets & screws (supplied), ensuring the correct seal is made. The flue support bracket (supplied with the vertical flue kit) can now be fitted.
If the vertical flue requires extension/s or addi­tional bend/s, connect the required number of flue extensions or bends (up to the maximum equivalent flue length) between the boiler and vertical flue assembly (see fig. 8).
Ensure that any horizontal sections of the flue system have a minimum 1º fall back to the boiler (17mm per 1000mm).
NOTE
When cutting an extension to the required length, you must ensure that the excess is cut from the plain end of the extension (see fig. 8). Remove any burrs, and check that any seals are located properly. You must ensure that the entire flue system is properly supported and connected.
4.6 CONNECTING THE GAS AND WATER
The appliance is supplied with an accessory pack that includes service valves. The service valves are of the compression type. The accessory pack contains sealing washers’ etc, for use with the service valves. When connecting pipe work to the valves, tighten the compression end first then insert the sealing washers before tightening the valve to the appliance.
NOTE
It will be necessary to hold the valve with one spanner whilst tightening with another
NOTE
Depending on system requirements, it may nec­essary to increase the size of the flow & return pipe work after the service valve connections.
4.6.3 COLD WATER INLET (fig. 6 & 10)
The appliance is supplied with a 15mm stopcock, connect a 15mm pipe to the inlet of the stopcock and tighten both nuts.
4.6.4 HOT WATER OUTLET (fig. 6 & 10)
The appliance is supplied with a 15mm outlet connection, connect a 15mm pipe to the outlet connection and tighten both nuts.
4.6.5 SAFETY VALVE (fig. 6 & 10)
Connect the safety valve pipe to the safety valve outlet and tighten. The discharge pipe must have a continuous fall away from the appliance to outside and allow any water to drain away thereby eliminating the possibility of freezing. The dis­charge pipe must terminate in a position where any water - possibly boiling - discharges safely without causing damage or injury, but is still visible.
4.6.6 CONDENSE PIPE (fig. 6 & 10)
During normal operation the boiler produces con­dense which is collected in a trap located in the lower part of the boiler. A flexible pipe (condense outlet pipe) is connected to the outlet of the trap. The flexible pipe must be connected to a plastic waste pipe only. The plastic waste pipe must have a minimum of a 3º fall towards the drain. Any external run of pipe should be insulated to prevent the risk of freezing.
CONNECTING THE CONDENSATE OUTLET
Gently pull the condense outlet pipe down from its location inside the boiler until approximately it protrudes from the underside of the boiler. Con­nect a suitable plastic (not copper) pipe (no less than 21mm diameter) to the outlet pipe and ensure it discharges in accordance with local building regulations or other rules in force.
condense
4.6.1 GAS (fig. 6 & 10)
The appliance is supplied with a 15mm service valve, connect a 15mm pipe to the inlet of the valve and tighten both nuts.
NOTE
It will be necessary to calculate the diameter of the gas supply pipe to ensure the appliance has an adequate supply of gas.
4.6.2 FLOW & RETURN (fig. 6 & 10)
The appliance is supplied with 22mm service valves for the flow and return connections, con­nect a 22mm pipe to the inlet of each valve and
Fig. 10
tighten both nuts.
12
flow
DHW outlet
gas
return
DHW
inlet
Supplied By www.heating spares.co Tel. 0161 620 6677
4.7 ELECTRICAL CONNECTIONS
The boiler is supplied with a 2-metre fly-lead. This lead can be used for connection to the electrical supply. Connect the fly-lead to a fused plug or fused isolator in the following way:
brown wire to LIVE supply
blue wire to NEUTRAL supply
green/yellow to EARTH connection.
Insert the supplied 3-AMP fuse into the fused isolator or fused plug.
Should the fly-lead be unsuitable, refer to 4.7.3 for details on how to connect the electrical supply directly to the boiler.
The electrical supply must be as specified in section 3/3A. A qualified electrician should con­nect the appliance to the electrical supply. If controls - external to the appliance - are required, a competent person must undertake the design of any external electrical circuits, please refer to section 8 for detailed instructions. ANY EXTER­NAL CONTROL OR WIRING MUST BE SERVED FROM THE SAME ISOLATOR AS THAT OF THE APPLIANCE. The supply cable from the isolator to the appliance must be 3-core flexible sized 0.75mm to BS 6500 or equivalent. Wiring to the appliance must be rated for operation in contact with surfaces up to 90 ºC.
Control panel screws and casing screws
A
Fig. 12
thermostat - will be required please refer to the wiring diagrams in section 8 for more detailed information.
4.7.3 CONNECTING THE MAINS (230V) INPUT (see fig. 12)
Lift the terminal block cover as described in 4.7.2. Pass the cable through the cab le anchorage point. At the terminal block on the extreme left, there are 3 terminals from left to right they are:
LIVE - NEUTRAL - EARTH Connect the supply cable wires (LIVE, NEUTRAL
& EARTH) to their corresponding terminals on the appliance terminal block (see fig. 13). Ensure that the EARTH wire is left slightly longer than the others, this will prevent strain on the EARTH wire should the cable become taut.
Fig. 11
4.7.1 CASING REMO V AL
T o gain internal access to the appliance you must first remove the casing, proceed as outlined below:
locate and unscrew the 3-screws (A) that se-
cure the outer casing to the appliance (see fig.
11)
lift the casing upward to disengage it from the
top locating hooks and then remove
store the casing and screws safely until re-
quired. Re-fit in the reverse order
gently lower the control fascia until it rests.
4.7.2 APPLIANCE TERMINAL BLOCK
The appliance terminal block is located on the left side of the control fascia (see fig. 11). Locate and remove the screw that secures the terminal block cover.
NOTE
The appliance comes with a factory fitted clock to allow basic operation of the boiler. If it is antici­pated that additional controls - such as a room
The securing screw on the cable anchorage should now be tightened. This must be done before the control fascia is re-fitted in the upright position. The appliance casing and screws can now be re-fitted.
Fig. 13
13
Supplied By www.heating spares.co Tel. 0161 620 6677
SECTION 5 COMMISSIONING
5.1 GAS SUPPLY INSTALLATION
Inspect the entire installation including the gas meter, test for soundness and purge. Refer to BS 6891 for specific instruction.
5.2 THE HEATING SYSTEM
The appliance contains components that may become damaged or rendered inoperable by oils and/or debris that are residual from the installa­tion of the system, consequently it is essential that the system be flushed in accordance with the following instructions.
5.3 INITIAL FILLING OF THE SYSTEM
Ensure both flow and return service valves are open, remove appliance casing as described in
4.7.1, identify the automatic air release valve and loosen the dust cap by turning the cap anti­clockwise one full turn. IMPORTANT, THERE ARE NO MANUAL AIR RELEASE VALVES LO­CATED ON THE APPLIANCE. Ensure all manual air release valves located on the heating system are closed. Connect the filling loop (not supplied) and slowly proceed to fill the system. As water enters the system the pressure gauge will begin to rise. Once the gauge has reached 1 BAR close the filling loop and begin venting all manual air release valves, starting at the lowest first. It may be necessary to go back and top-up the pressure until the entire system has been filled. Inspect the system for water soundness, rectifying any leaks.
5.4 INITIAL FLUSHING
The whole of the heating system must be flushed both cold and hot as detailed in 5.8. Open all radiator or heating valves and the appliance flow & return service valves. Drain the boiler and system from the lowest points. Open the drain valve full bore to remove any installation debris from the boiler prior to lighting. Refill the boiler and heating system as described in 5.3.
5.5 FILLING THE HOT WATER SYSTEM
Close all hot water outlets, turn appliance stop­cock to the normal operating position (fully coun­ter clockwise), slowly open each outlet until air has been expelled and clear water is discharged. Check pipe-work etc. for water soundness.
5.6 PRE-OPERATION CHECKS
Before attempting the initial lighting of the appli­ance, the following checks must be carried out:
ensure all gas service valves from the meter to
the appliance are open and the supply pipe has been properly purged
ensure the proper electrical checks have been
carried out, (see 7.7) particularly continuity, polarity and resistance to earth
ensure the 3 AMP fuse - supplied with the
appliance - has been fitted
ensure the system has been filled, vented and
the pressure set to 1 BAR
ensure the flue system has been fitted properly
and in accordance with the instructions
ensure all appliance service valves are open.
5.7 INITIAL LIGHTING
Ensure the electrical supply to the appliance is switched on. Move the selector switch to the Heating & Hot Water position, ensure the time clock is switched to an ‘ON’ position and ensure any other external controls (room thermostat for example) are also calling for heat. The appliance will now operate in the mode as described in 1.2. Should the appliance fail to ignite, refer to 5.6 and/or section 7 (faultfinding).
5.7.1 CHECKING THE BURNER PRESSURE
Although the burner pressure is factory set, it is necessary to check it during commissioning. Isolate the appliance from the electrical supply and attach a suitable manometer to the gas valve outlet test­point (see fig. 14). Light the boiler as described in
5.7, turn the Hot Water temperature selector to maximum, and open fully a DHW outlet (preferably the bath), allowing the appliance to stabilise. Compare the reading on the manometer with the value described in 2.3. If adjustment is required, follow the detailed instructions in section 7 (7.3). Once the burner pressure has been checked, close
Outlet
test-point
Protective
cap
Inlet
Fig. 14
test-point
the DHW outlet, isolate the appliance from the electrical supply, remove the manometer and tighten the gas valve outlet test nipple.
5.8 FINAL FLUSHING OF THE HEATING SYSTEM
The system shall be flushed in accordance with BS 7593. Should a cleanser be used, it must be suitable for Copper and Aluminium heat exchang­ers. It shall be from a reputable manufacturer and shall be administered in strict accordance with the manufacturers’ instructions and the DWTA code of practice.
5.8.1 INHIBITORS
See section 3 “General requirements”.
5.9 SETTING THE BOILER OPERATING TEMPERA­TURE
The flow outlet temperature can be adjusted be­tween 40 ºC - 80 ºC via the Heating thermostat knob (see fig.1).
14
Supplied By www.heating spares.co Tel. 0161 620 6677
5.9.1 SETTING THE DOMESTIC HOT WATER TEM­PERATURE
The DHW outlet temperature can be adjusted between 40 ºC - 65 ºC via the Hot Water thermo­stat knob (see fig.1).
5.10 SETTING THE SYSTEM DESIGN PRESSURE
The design pressure should be a minimum of 1 BAR and a maximum of 1.5 BAR.
The actual reading should ideally be 1BAR plus the equivalent height in metres (0.1 BAR = 1 metre) to the highest point in the system above the base of the appliance (up to the maximum of
1.5 BAR total). N.B. The safety valve is set to lift at 3 BAR/30
metres/45 psig.). To lower the system pressure to the required
value, water can be drained from the heating system drain cock or from the boiler drain cock.
5.11 REGULATING THE HOT WATER
The appliance is fitted with a flow rate restrictor that limits the maximum flow rate that can be drawn through the appliance.
85 HE
8-litre (White) 9-litre (Orange) 10-litre (Blue)
Fitted Spare Spare
100 HE
9-litre (Orange) 10-litre (Blue) 11-litre (Beige)
Spare Fitted Spare
The restrictor eliminates the need to manually adjust the DHW flow rate. However if it is felt necessary to further increase or decrease the available flow rate, spare restrictors are included in the accessory pack.
The spare flow rate restrictors can be fitted to either increase or decrease the maximum flow rate. The tables above denote the size of restrictor fitted and the spare restrictors supplied in the accessory pack. Each restrictor is colour-coded to enable identification.
AND CHECKED FOR SOUNDNESS.
ENSURE THE APPLIANCE FLUE SYSTEM
IS FITTED CORRECTLY AND IS PROPERLY SECURED.
ENSURE ALL PIPE WORK IS RE-CHECKED
FOR SOUNDNESS.
RE-FIT APPLIANCE CASING.
COMPLETE BENCHMARK CHECKLIST.
Complete details of the boiler, controls, installa­tion and commissioning in the Benchmark check­list at the back of this book. It is important that the Benchmark checklist is correctly completed and handed to the user. Failure to install and commission the appliance to the manufacturers instructions may invalidate the warranty.
5.13 INSTRUCTING THE USER
Hand over all documentation supplied with this appliance - including these instructions - and explain the importance of keeping them in a safe place.
Explain to the user how to isolate the appliance from the gas, water and electricity supplies, and the locations of all drain points.
Show the user how to operate the appliance and any associated controls correctly.
Show the user the location of the filling valve and how to top-up the system pressure correctly, and show the location of all manual air release points.
Explain to the user how to turn off the appliance for both long and short periods and advise on the necessary precautions to prevent frost damage.
Explain to the user that for continued safe and efficient operation, the appliance must be serv­iced annually by a competent person.
5.14 TECHNICAL ASSISTANCE
Should you require technical advice or assistance on this product, please contact ‘Heating Services’ on 0870 264 1220 or Heating Services, PO BOX
167, BRADFORD, BD19 4WL.
5.11.1 CHANGING THE FLOW RESTRICTOR
Refer to 6.19 for detailed instruction on changing the flow restrictor.
5.11.2 REGULATING THE CENTRAL HEATING SYS­TEM
Fully open all radiator and circuit valves and run the appliance for both heating and hot water until heated water is circulating. If conditions are warm remove any thermostatic heads. Adjust radiator return valves and any branch circuit return valves until the individual return temperatures are cor­rect and are approximately equal.
5.12 FINAL CHECKS
ENSURE ALL TEST NIPPLES ON THE APPLI-
ANCE GAS VALVE HAVE BEN TIGHTENED
15
Supplied By www.heating spares.co Tel. 0161 620 6677
SECTION 6 SERVICING INSTRUCTIONS
6.1 GENERAL
To ensure the continued safe and efficient opera­tion of the appliance, it is recommended that it is checked and serviced at regular intervals.
To ensure correct and safe operation of the appliance, it is essential that any worn or failed component be replaced only with a genuine spare part.
The frequency of servicing will depend upon the particular installation conditions, but in general, once per year should be adequate.
It is the law that any servicing work is carried out by competent person such as an engineer, an approv ed service agent, British Gas, CORGI registered per­sonnel or other suitably qualified personnel.
The following instructions apply to the appliance and its controls, but it should be remembered that the central heating and the domestic hot water systems would also require attention from time to time.
6.2 ROUTINE ANNUAL SERVICING
Check the operation of the appliance and ensure it functions as described in section 7. Compare the performance of the appliance with its design specification. The cause of any noticeable dete­rioration should be identified and rectified without delay.
Thoroughly inspect the appliance for signs of damage or deterioration especially the flue sys­tem and the electrical apparatus.
Check and adjust - if necessary - all burner pressure settings (see section 7.3).
Check and adjust - if necessary - the system design pressure (see section 5.10).
Carry out an analysis of the flue gases (see 7.4) and visually check the condition of the entire flue assembly. Compare the results with the appli­ance design specification. Any deterioration in performance must be identified and rectified with­out delay.
Ensure both flue venturis are clean and free from any debris or obstruction.
Ensure the burner, main heat exchanger and latent heat collector are clean and free from any debris or obstruction.
the appliance, remove the appliance casing as described in section 4.7.1 and drain the water content from the appliance via the drain valve located at the front of the hydraulic section using the tube provided. Ensure some water absorbent cloths are available to catch any residual water that may drip from the appliance or removed component. Undertake a complete commission­ing check as detailed in section 5, after replacing any component. ALWAYS TEST FOR GAS
SOUNDNESS IF ANY GAS CARRYING COM­PONENTS HAVE BEEN REMOVED OR DIS­TURBED.
6.5 PUMP ASSEMBLY fig. 15
Carry out component removal procedure as de­scribed in 6.4. The pump head can be replaced by disconnecting the electrical connection at the pump and removing the 4-Allen screws that secure the head to the pump base. Alternatively, the complete pump assembly can be removed as follows:
disconnect the electrical connection from the
pump control box
locate and remove the pressure gauge securing pin and disconnect the pressure gauge from the pump assembly
Refer to fig. 15 and remove items A & B
Locate and remove the pump locking pin ‘G’ (it
may be necessary to remove the valve actuator F to facilitate this) and lift the pump assembly clear of the hydraulic manifold.
Locate and remove the expansion pipe locking pin, and disconnect the expansion pipe from the pump assembly
Replace in the reverse order.
A
B
AAV
G
F
6.3 REPLACEMENT OF COMPONENTS
Although it is anticipated that this appliance will give years of reliable, trouble free service, the life span of components will be determined by factors such as operating conditions and usage. Should
Fig. 15
6.6 AUTOMATIC AIR RELEASE VALVE fig. 15 (AAV)
the appliance develop a fault, the fault finding section will assist in determining which compo­nent is malfunctioning.
6.4 COMPONENT REMOVAL PROCEDURE
To remove a component, access to the interior of the appliance is essential. Isolate the appliance from the electrical supply and remove the fuse. And when necessary, close all service valves on
16
Carry out component removal procedure as de­scribed in 6.4. Locate and remove the pressure gauge pipe securing pin and disconnect the pipe from the pump assembly. Locate and remove the AAV securing pin (G) and lift the AAV free from the pump assembly. Replace in the reverse order.
Supplied By www.heating spares.co Tel. 0161 620 6677
the flow pipe from the heat exchanger to facilitate this. Replace in the reverse order.
6.11 HIGH LIMIT THERMOSTAT fig. 18
Carry out component removal procedure as de-
B
scribed in 6.4. Unclip and remove the air chamber cover.
Fig. 16
E
6.7 SAFETY VALVE fig. 16
Carry out component removal procedure as de­scribed in 6.4. Disconnect and remove the safety valve outlet pipe. Locate and remove the safety valve securing pin (B). The safety valve can now be removed. Replace in the reverse order. Check and clean (if necessary) the condense trap (see 6.29).
6.8 WATER PRESSURE SWITCH fig. 1
Carry out component removal procedure as de­scribed in 6.4. Disconnect the 2-wires from the water pressure switch, taking note of their locations. Locate and remove the pin that secures the water pressure switch to the hydraulic assembly. Remove the water pressure switch from the hydraulic assembly. Replace in the reverse order.
6.9 PRESSURE/TEMPERATURE GAUGE fig. 1
Carry out component removal procedure as de­scribed in 6.4. Locate and remove the pressure gauge securing pin and disconnect the pressure gauge from the pump assembly. Locate the spring tabs on the pressure gauge body, push and hold tabs in, to enable extraction of the gauge from its location on the control panel. Replace in the reverse order.
6.10 PRIMARY THERMISTOR fig. 17
Carry out component removal procedure as de­scribed in 6.4. Unclip and remove the air chamber cover and remove the right side air baffle.
Disconnect thermistor electrical plug. Using a 13mm spanner slacken and remove the
thermistor and sealing washer (1,2) from the main heat exchanger.
NB, it may be necessary to disconnect or remove
Fig. 18
Pull off electrical connections from the high limit thermostat (2), slacken and remove retaining screws (3).
Replace in reverse order.
6.12 PRINTED CIRCUIT BOARD fig. 19
Carry out component removal procedure as de­scribed in 6.4. Locate and remove the screws that secure the PCB cover, then remove cover. After carefully taking note of all wiring connections, disconnect all wiring from the PCB, locate and remove the PCB securing screws (2,3,), remove the required PCB (Main or ignition control). Replace in the reverse order.
NOTE
Ensure that any replacement PCB has the correct jumper tag configuration, and that the relevant gas pressures are correctly set/adjusted (see 7.8.1).
6.13 GAS VALVE fig. 20
Carry out component removal procedure as de­scribed in 6.4. The gas valve must be changed as complete unit. Disconnect the electrical plug and leads from the gas valve. Slacken and unscrew gas valve inlet and outlet connections (3). Please note, the sealing wash­ers (2) must be discarded and replaced with new sealing washers (2). Locate and remove gas valve retaining screws on the underside of the boiler if required. The gas valve can now be removed. Replace in the reverse order. Check and adjust burner pressure settings. WARNING, A GAS
SOUNDNESS CHECK MUST BE CARRIED OUT.
Fig. 17
17
Supplied By www.heating spares.co Tel. 0161 620 6677
Fig. 20
6.14 INTEGRAL TIME SWITCH (if fitted)
Carry out component removal procedure as de­scribed in 6.4. Locate and remove the PCB cover and securing screws (fig. 19/19A), locate and remove the time clock retaining screws, remove time clock. Dis­connect wiring after carefully taking note of all electrical connections. Replace in the reverse order.
M
CLK-1 CLK-4
M
Fig. 19a
6.15 ELECTRODE, BURNER & INJECTORS fig. 21
Carry out component removal procedure as de­scribed in 6.4. Unclip and remove the air chamber cover (2). Locate and remove the 6 screws securing the front combustion cover (3), pull the cover towards you before lifting and disengaging. Disconnect the electrode lead. Ease the electrode sealing grommet from its seating (4).
FIG. 22: locate and remove the four screws which secure the burner in position (1), gently ease the burner out of its location. Once the burner has been removed, the electrode retaining screw can be removed. Locate the burner injectors (2) and remove (if necessary). Replace in the reverse order. Please note, the injector sealing washers (3) must be replaced if the injectors have been removed, ensure all seals are in good condition, taking care to ensure they are replaced correctly. Replace in the reverse order.
6.16 FLUE FAN fig. 23
Carry out component removal procedure as de­scribed in 6.4. Unclip and remove the air chamber cover, gently
Fig. 21 Fig. 22
18
Supplied By www.heating spares.co Tel. 0161 620 6677
6
4
5
Fig. 23
pull the cover towards you before lifting and disengaging. Locate and remove the six screws that secure the front combustion cover, then remove the cover. Disconnect the electrical con­nections and silicone tubes attached to the fan, noting their positions. Locate and remove the screws (6) that secure the air pressure switch assembly (4 & 5). Locate and remove the screws that secure the flue hood and air baffle, disconnect the flue clip (1) from the fan-flue elbow, and gently ease the fan (3) & flue hood assembly (2) from its location. Locate and remove the four screws that secure the fan to the flue hood. Remove the fan to flue elbow. Replace in the reverse order. Ensure all seals are in good condition, taking care to ensure they are replaced correctly.
6.17 MAIN HEAT EXCHANGER fig. 23/24
Carry out component removal procedure as de­scribed in 6.4. Unclip and remove the air chamber cover, gently pull the cover towards you before lifting and disengaging. Locate and remove the six screws
8
9
2
3
7
1
6.18 AIR PRESSURE SWITCH fig. 23
Carry out component removal procedure as de­scribed in 6.4. Unclip and remove the air chamber cover, gently pull the cover towards you before lifting and disengaging. Locate and remove the two screws (6) holding the air pressure switch to the air chamber. Disconnect the electrical connections and silicone tubes (10) attached to the air pressure switch, noting their connections/positions. Replace in the reverse order. Ensure all seals are in good condition, taking care to ensure they are replaced correctly.
6.19 FLOW RESTRICTOR fig. 25
Carry out the component removal procedure as described in 6.4. Slacken the cold water outlet pipe (A) at the DHW flow switch and disconnect. Ease the flow restrictor (B) from its seating. Replace in the reverse order. Ensure all seals are in good condition, taking care to ensure they are replaced correctly.
6.20 DHW FLOW SWITCH fig. 25
Carry out component removal procedure as de­scribed in 6.4. Disconnect the cold water inlet/outlet pipes (A) from the DHW flow switch. Disconnect the wiring to the DHW flow switch. Lift the DHW flow switch from its location. Replace in the reverse order. Ensure all seals are in good condition, taking care to ensure they are replaced correctly.
10
Fig. 24
that secure the front combustion cover, then remove the cover. Remove the air chamber side panels if necessary by unscrewing the securing screws. Disconnect the flow and return connec­tions (4,5, fig. 24) and the primary thermistor on the heat exchanger. The heat exchanger can now be withdrawn from the appliance. Replace in the reverse order. Ensure all seals are in good condition, taking care to ensure they are replaced correctly.
Fig. 25
A
B
C
19
Supplied By www.heating spares.co Tel. 0161 620 6677
6.21 DHW HEAT EXCHANGER fig. 16/16A
Carry out component removal procedure as described in 6.4. Before removing the DHW heat e xchanger, it will be necessary to remove the gas valve (see 6.13). Locate and remove the DHW outlet pipe (A) from the LH (left hand) DHW manifold and DHW outlet connection. Locate and remove the locking pins (1) that secure the flexible pipe (B) that connects both hydraulic manifolds and then remove the pipe. Locate and remove the 2-screws (C) that secure the DHW heat exchanger to the LH and RH DHW manifolds and gently ease the DHW heat exchanger from its location. Locate and remove the locking pin (2) that secures the LH DHW manifold to the LH hydraulic manifold and then remove the manifold. Gently ease the LH DHW manifold away from the LH hydraulic manifold and disconnect the wiring to the secondary (DHW) thermistor. Replace in the reverse order ensuring all seals are correctly positioned and in good condition. Replace the gas valve in accordance with the instructions detailed in 6.13.
Replace in the reverse order ensuring that the seating cam inserts into the locating groove correctly (see fig. 26a). Ensure all seals are in good condition, taking care to ensure they are replaced correctly.
6.24 DHW THERMISTOR fig. 27
Carry out component removal procedure as de-
E
E
C
D
scribed in 6.4. Disconnect the electrical plug. Using a suitable pair of pliers, remove the thermistor locking pin (E) and ease the thermistor (F) from its seating. Replace in the reverse order ensuring the sealing ring is in good condition.
Fig. 26
Fig. 26a
6.22 VALVE ACTUATOR fig. 26
Carry out component removal procedure as de­scribed in 6.4. Remove the locking pin (A) that secures the actuator (B) to the hydraulic manifold. Disconnect the electrical plug from the actuator. Replace in the reverse order.
6.23 DIVERTOR VALVE CARTRIDGE fig. 26
Carry out component removal procedure as de­scribed in 6.4. Remove the valve actuator as described in 6.22. Remove the cartridge locking pin (C) and - using a suitable pair of pliers - withdraw the cartridge assembly. The cartridge assembly is a non­serviceable item and therefore needs to be re­placed if it’s suspected as being damaged or worn.
6.25 AUTO BY-PASS VALVE fig. 27
Carry out component removal procedure as de­scribed in 6.4. Locate and remove the hydraulic cover locking pin (A) and remove the cover. Using a suitable hooked wire or screwdriver, gently ease the valve (C) from its seating. Ensure all seals are in good condition, taking care to ensure they are replaced correctly. Replace in the reverse order ensuring the cartridge is facing the correct way.
6.26 DHW NON-RETURN VALVE fig. 27
Carry out component removal procedure as de­scribed in 6.4. Locate and remove the hydraulic cover locking pin (A) and remove the cover. Using a suitable hooked wire or screwdriver, gently ease the non-return valve (D) from its seating. Ensure all seals are in good condition, taking care to ensure they are replaced correctly. Replace in the reverse order ensuring the cartridge is facing the correct way.
6.27 EXPANSION VESSEL fig. 1
Should the removal and replacement of the expan­sion vessel be deemed impractical, an external expansion vessel may be fitted to the return pipe as close to the appliance as possible.
6.27.1 EXPANSION VESSEL REMOVAL (with suffi­cient clearance above)
Carry out component removal procedure as de­scribed in 6.4. Disconnect the flue from the appliance. Disconnect the flexible expansion pipe from the vessel. Locate and remove the four screws (A) that secure the vessel top holding plate (B), remove the plate (fig. 28). The expansion vessel
20
Supplied By www.heating spares.co Tel. 0161 620 6677
can now be removed. Replace in the reverse order. Ensure all seals are in good condition, taking care to ensure they are replaced correctly.
6.27.2 EXPANSION VESSEL REMOVAL (with insuffi­cient clearance above)
Carry out component removal procedure as de­scribed in 6.4. Disconnect the flexible expansion pipe from the vessel.
A
B
6.28.2 DISMANTLING THE LATENT HEAT COLLEC­TOR
Apart from routine cleaning of the coil, the latent heat collector is a non-serviceable component, therefore, there is no requirement to disassemble the collector.
6.29 CONDENSE TRAP REMOVAL fig. 31
Carry out component removal procedure as de­scribed in 6.4. Disconnect the flexible condense pipe (1) from the condense trap. Locate and remove the condense pipe locking pin and disconnect the condense pipe (2) from the condense trap. Locate and disconnect the condense pressure switch pipe from the con­dense trap (3). Carefully remove the condense trap. Replace in the reverse order.
Fig. 28
Disconnect the flue elbow or pipe from the appli­ance flue outlet. Unclip and remove the air cham­ber cover, gently pull the cover towards you before lifting and disengaging. Remove the RH side panel of the air chamber. Disconnect the wiring to the fan, pressure switch, primary thermistor, overheat thermostat, condense switch & spark electrode, taking note of their locations. Carefully unclip the wires from the air chamber and withdraw the wiring & grommet from the air chamber.
Disconnect the outlet gas pipe, the flow & return pipes and the condense pipe from the air chamber.
Locate and remove the 2-screws that secure the lower section of the air chamber. Locate and remove the 2-screws that secure the upper sec­tion of the air chamber. The complete air cham­ber assembly can now be lifted clear from the appliance.
Locate and remove the 4-screws that secure the vessel (see fig. 28). The expansion vessel can now be removed. Replace in the reverse order. Take extreme care when refitting the wiring to the air chamber. Ensure all seals are in good condi­tion, taking care to ensure they are replaced correctly.
Fig. 29
Fig. 30
6.28.1 LATENT HEAT COLLECTOR fig. 29/30
Carry out component removal procedure as de­scribed in 6.4. Remove the flue hood and fan assembly as detailed in 6.16. Disconnect and remove the inlet, outlet and condense pipes from the collector. Unscrew and remove the 3 screws that secure the
Fig. 31
collector to the air chamber and disconnect the collector from the flue connection. Replace in the reverse order ensuring all seals are intact and located correctly.
21
Supplied By www.heating spares.co Tel. 0161 620 6677
SECTION 7 CHECKS, ADJUSTMENTS AND FAULT FINDING
7.1 CHECKING APPLIANCE OPERATION
When carrying out any repairs or servicing to the appliance, the relevant commissioning proce­dure must be undertaken to ensure the continued safe operation of the appliance. Particular atten­tion should be made to ensure gas soundness, water soundness and the electrical integrity of the appliance.
7.2 APPLIANCE MODE OF OPERATION NOTE
There must be sufficient system water pressure (min. 0.5 bar) to ensure the water pressure switch is activated. If there is insufficient system pres­sure the pump and fan will be prevented from operating.
7.2.1 SELECTOR SWITCH IN THE OFF POSITION
When the selector switch is in the OFF position, the Green LED status indicator will flash every 6­seconds to confirm the appliance is in standby mode. The divertor valve is in the DHW position. The appliance will not respond to any DHW or heating requests.
Active functions:
●●
frost-protection system
●●
●●
pump anti-block
●●
●●
valve actuator anti-block
●●
fan over-run.
7.2.2 SELECTOR SWITCH IN THE HOT WATER ONLY POSITION
When the selector switch is in the HW only position, the Green LED is illuminated:
●●
flashing every 6-seconds if no DHW request is
●●
active
●●
constant during a DHW request.
●●
The divertor valve is in the DHW position. The appliance will respond to any DHW requests.
Active functions:
●●
frost-protection system
●●
●●
pump anti-block
●●
●●
valve actuator anti-block
●●
●●
fan over-run.
●●
7.2.4 APPLIANCE FUNCTIONS
●●
Frost-protection: this function is only active
●●
when there are no requests for heating or HW. When the temperature of the primary thermis­tor drops below 5 °C, the valve actuator will motor to the heating position, whereupon the boiler will operate on minimum power until the temperature of the primary thermistor reaches 35 °C. Thereafter the pump will over-run for 30­seconds.
●●
Anti-block cycle: when there has been no
●●
heating or HW request for 19-hours, the anti­block cycle is activated. The valve actuator will motor from the DHW position to the heating position and then motor back to the DHW position. Thereafter the pump will be activated for a period of 30-seconds.
●●
Fan over-run: should the temperature of the
●●
primary thermistor exceed 78 °C after a heating or DHW request, the pump and/or fan will run for a period of 30-seconds.
●●
AUTO function: the AUTO function permits the
●●
boiler (when the set-point is within the AUTO range) to automatically adjust (raise) the heating flow outlet temperature should the room thermo­stat contacts remain closed for more that 20­minutes.
7.2.5 DHW MODE fig. 32
With the selector switch in the Heating & HW position, or HW only position and a DHW outlet is opened, the appliance will operate in the HW mode. The valve actuator will motor to the HW position (if a heating request was active) and the pump and fan will be active. The operation of the fan causes the air pressure switch (APS) to deliver a signal voltage to the control PCB. A slow ignition sequence is enabled, whereby the current sup­plied to the gas valve modulating coil is progres­sively increased from minimum to maximum over a period of 8-seconds. During this period the ignition electrode sparks continuously even if the burner has ignited.
7.2.3 SELECTOR SWITCH IN THE HEATING & HOT WATER POSITION
When the selector switch is in the heating & HW position, the Green LED is illuminated:
●●
flashing every 6-seconds if no Heat or DHW
●●
request is active
●●
constant during a heat or DHW request.
●●
The divertor valve remains in the DHW position if no heat request is active. The appliance will respond to any heating or DHW requests.
Active functions:
●●
frost-protection system
●●
●●
pump anti-block
●●
●●
valve actuator anti-block
●●
●●
fan/pump over-run.
●●
22
Supplied By www.heating spares.co Tel. 0161 620 6677
of the fan causes the air pressure switch (APS) to deliver a signal voltage to the control PCB. A slow ignition sequence is enabled, whereby the current supplied to the gas valve modulating coil is pro­gressively increased from minimum to maximum over a period of 8-seconds. During this period the ignition electrode sparks continuously even if the burner has ignited.
Fig. 32
NOTE
If the spark/sensing electrode does not sense ignition the appliance will then go to lockout.
Ignition is sensed by the electronic circuitry to ensure flame stability at the burner. Once suc­cessful ignition has been achieved, the electronic circuitry modulates the appliance output in order to achieve the DHW set-point (the position of the DHW temperature selector) as measured at the secondary thermistor.
When the set-point has been reached, the appli­ance will begin the modulation phase whereby the fan and gas valve will continuously modulate to maintain the set-point.
If the temperature continues to rise and exceeds the set-point by 5 °C, the burner will shut down until the temperature drops to set-point + 4 °C, whereby a new ignition sequence will be enabled.
When the request for DHW has been satisfied, the appliance fan may continue to operate to dissipate any residual heat from within the appliance.
7.2.5.1 DHW PARAMETERS
RANGE MINIMUM MAXIMUM
Temperature (°C) 37.5 60 DHW NTC fault ON at 50 °C OFF at 55 °C
7.2.6 HEATING MODE fig. 33
With the selector switch in the Heating & HW position and the relevant controls (time clock, room thermostat, etc,) are calling for heat, the appliance will operate in the heating mode. The valve actuator will motor to the heating position and the pump and fan will be active. The operation
Fig. 33
NOTE
If the spark/sensing electrode does not sense ignition the appliance will then go to lockout. Ignition is sensed by the electronic circuitry to ensure flame stability at the burner. Once suc­cessful ignition has been achieved, the electronic circuitry allows 75% of the full gas rate through the appliance. After 15 minutes the gas rate is increased to maximum (100%).
When the set-point has been reached (the position of the heating temperature selector) as measured at the primary thermistor, the appliance will begin the modulation phase whereby the fan and gas valve will continuously modulate to maintain the set-point.
If the temperature continues to rise and exceeds the set-point by 6 °C, the burner will shut down and the boiler will perform a three-minute anti-cycle (timer delay).
A new ignition sequence will be enabled when the 3-minute anti-cycle has been performed and the temperature at the primary thermistor has dropped 6 °C below the set-point.
NOTES
The timer delay can be de-activated by the inser­tion of a ‘jumper’ on the PCB at JP1 or by isolating the appliance from the electrical supply for 30 seconds. Any DHW requests will always have priority over a heating request.
When the request for heating has been satisfied, the appliance pump and fan may continue to circulate to dissipate any residual heat within the appliance.
23
Supplied By www.heating spares.co Tel. 0161 620 6677
7.2.6.1 HEATING PARAMETERS
RANGE MINIMUM MAXIMUM
Temperature (°C) 40 80
ST
1
sector 40 55
AUTO sector 55 65
ND
sector 65 80
2
When the boiler is operating in the AUTO range, the Green LED flashes rapidly to signify the AUTO function is active.
AUTO sector
1st sector
40 °C
3rd sector
80 °C
AUTO FUNCTION
When the heating temperature selector is set within the AUTO range (AUTO sector) the boiler will automatically raise the heating flow outlet temperature by 5 °C every 20-minutes that the room thermostat contacts remain in the closed position or until the boiler reaches the maximum operating temperature.
7.3 CHECKING AND ADJUSTING BURNER PRES­SURE (see fig. 15)
Although the burner pressure is factory set, it is necessary to check it during servicing or if the gas valve has been removed. Isolate the appliance from the electrical supply and attach a suitable manometer to the gas valve outlet test nipple.
Fig. 34
Fig. 35
7.3.1 SETTING THE MAXIMUM BURNER PRESSURE fig. 39
Light the boiler as described in 5.7 and compare the reading on the manometer with the value described in 2.3. If adjustment is required, re­move the protective cap from the gas valve modulating coil assembly and turn the outer (10mm) nut clockwise to increase, or counter­clockwise to decrease the burner pressure.
NOTE
Always check and/or adjust the minimum and maximum gas pressures whilst the appliance is in the HW only mode. Ensure a DHW outlet (pref­erably the bath) is fully open, and that the HW temperature selector is at maximum.
7.3.2 SETTING THE MIMIMUM BURNER PRES­SURE fig. 34
Once the maximum burner pressure has been checked and/or adjusted, remove one of the grey wires from the modulating coil. Compare the reading on the manometer with the value de­scribed in 2.3. If adjustment is required, turn the inner (red) crosshead screw clockwise to in­crease, or counter-clockwise to decrease the burner pressure, whilst ensuring that the outer (10mm) nut does not move. When checking and/ or adjustment has been completed, isolate the appliance from the electrical supply, replace the protective cap, refit the grey wire to the modulat­ing coil, remove the manometer and tighten the outlet test nipple.
IMPORTANT, A GAS SOUNDNESS CHECK MUST BE CARRIED OUT.
7.3.3 SETTING THE MINIMUM CENTRAL HEATING OUTPUT THIS CAN ONLY BE CARRIED OUT AFTER THE MAXIMUM AND MINIMUM GAS PRES­SURES HAVE BEEN SET.
Isolate the appliance from the electrical supply.
Attach a manometer to the gas valve outlet test
nipple.
Insert a jumper tag at JP2.
Switch the appliance ON in the heating mode.
Turn potentiometer P5 to the minimum position
Adjust potentiometer P4 to the required value
shown in section2.3 (section 10.2 for LPG), i.e. minimum burner pressure (central heating).
Turn potentiometer P5 back to the maximum
position.
Isolate the appliance from the electrical supply.
Remove the manometer, tighten the outlet test
nipple, and check for soundness.
7.4 COMBUSTION ANALYSIS TEST
A combustion analysis check (see 2.12 Nat. Gas or 10.2 LPG) can easily be carried out on the appliance via the test points located on the top of the appliance, however you must check that the burner pressures are set correctly (see 7.3).
Isolate the appliance from the electrical supply
and turn the mode selector switch to the OFF/ RESET position.
Locate and remove the CO test point sealing
screw (see fig. 36).
Insert the flue gas analyser probe into the test
point.
Restore the electrical supply to the appliance
Remove the mode selector knob and turn the
shaft fully clockwise (see fig. 37).
24
Supplied By www.heating spares.co Tel. 0161 620 6677
The boiler will now enter the combustion analy-
sis mode (CO mode) for a period of 15 minutes, signified by the LED flashing Yellow. During this time, the boiler will remain on full gas.
Once the flue gas analysis has been made, turn
the shaft back to the required position and replace the mode selector knob.
Remove the probe and replace the sealing screw.
GREEN LED
Frequency Faults/Status
ON every 6-secs At stand-by with no faults
Flashing 8-times a second AUTO function active
ON every 0.5-secs Temporary fault, e.g.:
Solid Active for heat/DHW request
●●
APS fault
●●
●●
low water pressure
●●
Air analysis
outlet
Fumes analysis
outlet
Fig. 36
Rotate shaft fully clock wise
Fig. 37
7.5 CHECKING THE EXPANSION VESSEL
Carry out the component removal procedure as described in 6.4. You must ensure that the boiler is completely drained of water.
Using a suitable pressure gauge, remove dust cap on expansion vessel and check the charge pressure. The correct charge pressure should be
1.0 bar ± 0.1 bar. If the charge pressure is less, use a suitable pump to increase the charge.
NOTE
You must ensure the drain valve is in the open position whilst re-charging takes place. Replace the dust cap and carry out the relevant commis­sioning procedure (section 5).
7.6 EXTERNAL FAULTS
Before carrying out any faultfinding or component replacement, ensure the fault is not attributable to any aspect of the installation.
Symptom Possible causes
No ignition Check wiring
No hot water Check hot/cold pipe
No central heating Check wiring of room thermostat
Check electrical supply
work is not reversed
and/or other external controls
YELLOW LED
Frequency Faults/Status
ON every 0.5-secs CO function active
Solid DHW thermistor fault (see 7.2.5.2)
RED LED
Frequency Faults/Status
ON every 0.5-secs Final fault, e.g.:
Solid
●●
water pressure switch
●●
●●
condense pressure switch
●●
●●
fan/flue problem
●●
●●
limit thermostat
●●
●●
primary NTC open/short circuit
●●
7.6.1 INSTALLATION FAULTS
7.7 ELECTRICAL CHECKS
Any electrical checks must be carried out by a suitably qualified person.
7.7.1 EARTH CONTINUITY TEST
Isolate the appliance from the electrical supply, and using a suitable multi-meter carry out a resistance test. Connect test leads between an appliance earth point and the earth wire of the appliance supply cable. The resistance should be less than 1 OHM. If the resistance is greater than 1 OHM check all earth wires and connectors for continuity and integrity.
7.7.2 SHORT CIRCUIT CHECK
Isolate the appliance from the electrical supply, and using a suitable multi-meter, carry out a short circuit test between the Live & Neutral connec­tions at the appliance terminal strip (fig.12).
Repeat above test on the Live & Earth connec­tions at the appliance terminal strip (fig.12).
NOTE
Should it be found that the fuse has failed but no fault is indicated, a detailed continuity. Check will be required to trace the fault. A visual inspection of components may also assist in locating the fault.
7.7.3 POLARITY CHECK
With the appliance connected to the electrical supply and using a suitable multimeter, carry out the following voltage tests:
●●
Connect test leads between the Live & Neutral
●●
connections at the appliance terminal strip (fig.12). The meter should read approximately 230V ac. If so proceed to next stage. If not, see
7.7.4.
●●
Connect test leads between the Live & Earth
●●
connections at the appliance terminal strip (fig.12). The meter should read approximately 230V ac. If so proceed to next stage. If not, see
7.7.4.
●●
Connect test leads between the Neutral &
●●
Earth connections at the appliance terminal strip (fig.12). The meter should read approximately 0
- 15Vac. If so polarity is correct. If not, see 7.7.4.
25
Supplied By www.heating spares.co Tel. 0161 620 6677
7.7.4 REVERSED POLARITY OR SUPPLY FAULT
Repeat the above tests at the appliance isolator, if testing reveals correct polarity and/or supply at the isolator, re-check wiring and connections be­tween the isolator and the appliance. If tests on the isolator also reveal reversed polar­ity or a supply fault, consult the local electricity supplier for advice.
mode selector switch to the reset position (0) for 2-minutes’ then back to the relevant mode of operation.
If the boiler does not reset, refer to the following section and the detailed faultfinding flowcharts overleaf.
7.7.5 RESISTANCE TO EARTH CHECK
Isolate the appliance from the electrical supply and using a suitable multi-meter carry out a resistance test. Connect test leads between the Live & Earth connections at the appliance termi­nal strip (fig.12). If the meter reads other than infinity there is a fault that must be isolated, carry out a detailed continuity check to identify the location of the fault.
IMPORTANT
These series of checks must be carried out before attempting any faultfinding procedures on the appliance. On completion of any task that required the disconnection and re-connection of any electrical wiring or component, these checks must be repeated.
7.8 FAULT FINDING
Before attempting any faultfinding, the electrical checks as detailed in 7.7 must be carried out. Isolate the appliance from the electrical supply. Disconnect any external controls such as room thermostats etc. from the boiler.
7.8.1 REPLACING THE MAIN PCB
When replacing the main PCB it’s essential that the potentiometers are set as follows:
It’s essential that the minimum - central heating
- gas pressure is checked/adjusted as de­scribed in 7.3.3
P4 - to be used to set/adjust the minimum
heating output
P5 - set at maximum.
YELLOW LED
Frequency Faults/Status
ON every 0.5-secs CO function active
Solid DHW* thermistor fault (see 7.2.5.2)
* When there is a fault condition with the DHW thermistor, the
appliance will still operate and produce limited hot water. The Primary thermistor will control the temperature of the DHW during this period and the outlet temperature is fixed at 50­55oC.
RED LED
Frequency Faults/Status
ON every 0.5-secs Final fault, e.g.:
Solid
●●
water pressure switch
●●
●●
condense pressure switch
●●
●●
fan/flue problem
●●
●●
limit thermostat
●●
●●
primary NTC open/short circuit
●●
EFFECT OF JUMPER TAGS (part code 7232) FITTED TO THE MAIN PCB AT:
JP1 - disables DHW function
JP2 - cancels anti-cycle function and initial
heating output (75% of maximum at start up)
JP3 - for LPG boilers only
JP4 - enables DHW temperature stabiliser
function (boiler modulates at set point and remains on minimum power, even if the set point is exceeded).
Restore the electrical supply to the boiler and turn the selector switch to the on position. The boiler should now function as described in sec­tion 7.2. Should the boiler fail to respond, the in­ternal fuses and connectors should be checked to ensure integrity and continuity . If the boiler still fails to respond, refer to the detailed faultfinding flowcharts overleaf.
7.9 FAULT CODES
When the boiler is in a fault condition, the LED is displayed in a colour and/or frequency that is relevant to the fault. To reset the boiler, turn the
26
Supplied By www.heating spares.co Tel. 0161 620 6677
7.10.1 FAULT FINDING TEST ‘A’: CHECKING OPERATION OF ELECTRONIC CONTROL BOARD AT START UP
START
SWITCH ON BOILER AND
SELECT MODE TO
WINTER C/H
THERMOSTAT AT MAX.
NO
YES
REST AR T THE
TEST
IS
THERE 24dc
BETWEEN TERMINALS
CN9.1 & CN9.2
ON PCB
YES
CONTROL BOARD
WATER
PRESSURE SWITCH
IS OK
NO
CHECK WIRING AND
CONNECTIONS OR
WATER PRESSURE
SWITCH
MAINS ON
PUMP CONNECTOR
CN2.1 & CN2.2
ON PCB
LOOSE THE PUMP
ACTING WITH A
SCREWDRIVER ON
THE IMPELLER
PUMP RUNNING
NO
NO
REPLACE
CHECK IDRAULIC
CIRCUIT
YES
REPLACE
PUMP
MAINS
BETWEEN PIN
CN1.4 & CN1.5
ON PCB
YES
MADE A LINK BETWEEN BLACK &
BLACK WIRES AT BOILER
TERMINAL STRIP AND CLOSE THE
NO
YES
MAINS
ON PUMP
REPLACE WIRING
OR CONNECTIONS
NO
CHECK &/OR
REPLACE WIRING
AND
CONNECTIONS
YES
IS ROOM
THERMOST AT
INPUT LINKED
YES
CHECK WIRING OR
CONNECTIONS BETWEEN TERMINAL STRIP AND CONTROL
BOARD
TIMER CONTACT
PUMP
RUNNING
NO
YES
BETWEEN TERMINALS
CN8.3 & CN8.5
CONTROL BOARD
NO
MADE A LINK
BETWEEN THE ROOM
THERMOSTAT INPUT
REST AR T THE
ON FAN
CONNECTOR
CN4.1 & CN4.2
ON PCB
IS
THERE 24dc
ON PCB
REPLACE
TEST
NO
MAINS
NO
YES
YES
FAN RUNNING
NO
MAINS
ON FAN
NO
REPLACE WIRING
OR CONNECTIONS
BETWEEN TERMINALS
YES
AIR FLOW
SWITCH
OFF?
YES
GREEN LED
BLINKS
NO
A1
YES
YES
REPLACE FAN
NO
IS
THERE 0 VCC
CN8.3 & CN8.5
ON PCB
YES
REPLACE
CONTROL BOARD
NO
REPLACE AIR FLOW SWITCH OR CHECK FLUE GAS
TUBE
A
27
Supplied By www.heating spares.co Tel. 0161 620 6677
7.10.2 FAULT FINDING TEST ‘A’
A
NO
END
NO
REPLACE
SENSING/SPARK
ELECTRODE AND
LEAD
IS
THERE 0 Vdc
BETWEEN TERMINALS
CN8.7 & CN8.8
ON PCB
NO
SPARK AT
ELECTRODE
YES
IGNITION
YES
LOCKOUT
AFTER
IGNITION
YES
CHEK
SENSING/SPARK
ELECTRODE AND
LEAD
SENSING
SPARK ELECTRODE
AND LEAD
OK
YES
REPLACE PCB
NO
YES
REPLACE THE
CONTROL BOARD
NO
NO
NO
CHECK AND/OR
REPLACE PCB
CHECK WIRING AND
CONNECTIONS OR
THERMOSTAT
IS
THERE 230 Vac
BETWEEN TERMINALS
CN5.1 & CN5.2
ON PCB
NO
IS
THERE 24 Vdc
BETWEEN TERMINALS
CN8.4 & CN8.5
ON PCB
NO
IS
THERE 24 Vdc
BETWEEN TERMINALS
CN8.4 & CN8.8
ON PCB
NO
HIGH LIMIT
CHECK WIRING AND
CONNECTIONS, AIR FLOW
SWITCH AND CONTROL
YES
MAINS
ON E.V.G.
YES
YES
CHECK AND/OR
REPLACE PCB
YES
IS
THERE 24 Vdc
BETWEEN TERMINALS
CN8.4 & CN8.7
ON PCB
YES
BOARD
NO
CHECK/CLEAN THE
VENTURI TUBE AND
SILICONE AIR
TUBES
YES
CHECK REPLACE
AIR FLOW SWITCH
IS
THERE 230 Vac
BETWEEN TERMINALS
CN6.1 & CN6.2
ON PCB
CHECK
SENSING/SPARK
ELECTRODE AND
LEAD
NO
DO THE
AIR FLOW SWTCH
TURN ON
NO
ARE THE
VENTURI TUBE
AND THE SILICONE
AIR TUBES
CLEAN
YES
IS
THE AIR DP >
11 mmCH2O
NO
CHECK WIRING AND
CONNECTIONS OR
HIGH LIMIT THERMOSTAT
28
CHECK WIRING
AND
CONNECTIONS
NO
REPLACE EVG
EVG OK
YES
CHECK GAS
CHECK THE FAN
AND/OR FLUE GAS
TUBE
Supplied By www.heating spares.co Tel. 0161 620 6677
7.10.3 FAULT FINDING TEST ‘A1’
A1
YES
REPLACE CONTROL
BOARD
YES
REST AR T THE
TEST
RED LED
BLINKS
YES
SWITCH ON/OFF
SELECTOR ON OFF
POSITION
SWITCH ON/OFF
SELECTOR TO
WINTER POSITION
GREEN LED
BLINKS
NO
NO
RED LED
LIGHT
CHECK CH NTC
SENSOR OR WIRING
AND CONNECTIONS
PRESENT BETWEEN
YES
BLUE & BROWN WIRES AT
REPLACE WIRING OR
CONNECTIONS
TERMINAL STRIP AND
CONTROL BOARD
NO
YES
BOILER TERMINAL
YELLOW
LED
LIGHT
YES
CHIMNEY
SWEEPER CYCLE.
RESET AND
REST AR T TEST
MAINS
STRIP
NO
YELLOW LED
BLINKS
NO
NO
RECHECK SUPPLY
FUSE &
CONNECTORS TO
BOILER
TERMINALS
NO
MAINS
PRESENT BETWEEN
TERMINALS CN1.2
&CN1.3 M2.2 ON
CONTROL
BOARD
YES
CHECK FUSE F1
ON CONTROL
BOARD
YES
IS
THERE 24 Vdc
BETWEEN TERMINALS
CN8.4 & CN8.6
ON PCB
YES
THERE 24 Vdc
BETWEEN TERMINALS
CN8.4 & CN8.5
ON PCB
CHECK WIRING AND
CONNECTIONS OR
AIR PRESSURE SWITCH
BETWEEN TERMINALS
CONTROL BOARD
IS
NO
IS
THERE 24 Vdc
CN8.4 & CN8.7
ON PCB
NO
REPLACE
YES
NO
THERE 24 Vdc
BETWEEN TERMINALS
CN8.4 & CN8.8
ON PCB
YES
CHECK WIRING AND
CONNECTIONS OR
HIGH LIMIT THERMOSTAT
YES
REPLACE
CONTROL BOARD
IS
IS
THERE 0 VCC
BETWEEN TERMINALS
CN9.1 & CN9.2
ON PCB
REPLACE
CONTROL BOARD
NO
REPLACE
CONTROL BOARD
NO
CHECK WIRING AND
CONNECTIONS, WATER
PRESSURE SWITCH AND
HYDRAULIC CIRCUIT
YES
FUSE OK
NO
REPLACE FUSE
REST AR T THE
TEST
29
Supplied By www.heating spares.co Tel. 0161 620 6677
7.10.4 FAULT FINDING TEST ‘B2’: CHECK CONTROL IN DHW MODE
START
SWITCH ON BOILER AND
SELECT MODE TO
SUMMER. DHW
THERMOSTAT AT MAX.
IS
YES
THERE A
VOLTAGE >10 VDC
BETWEEN TERMINALS
CN9.7 & CN9.8
ON PCB
NO
IS THE
RESISTENCE OF
MODULATOR COIL
ABOUT 70/80
OHM
NO
REPLACE
MODULATOR COIL
YES
NO
REPLACE
CONTROL BOARD
TURN ON TAP
DOES
BURNER LIGHT
YES
IS
VOLT AGE
ACROSS TERMINALS
OF MODULATOR
COIL > 10 VDC
YES
NO
IS
THERE 24 Vdc
BETWEEN TERMINALS
CN9.7 & CN9.8
ON PCB
CHECK BOILER
YES
IS
THERE 0 Vdc
BETWEEN TERMINALS
CN9.7 & CN9.8
ON PCB
NO
CHECK WIRING AND
CONNECTIONS OR
DHW SWITCH
NO
STARTUP: TEST A
YES
REPLACE
CONTROL
BOARD
REPLACE WIRE
AND
CONNECTIONS
WAIT D.H.W.
TEMPERATURE
>40 ûC
NO
IS
D.H.W.
TEMPERATURE
>40 ûC
YES
WAIT TILL THE
VOLTAGE BETWEEN
TERMINAL CN9.3 & CN9.4
ON PCB IS < 1.2 Vdc
IS THE
VOLTAGE BETWEEN
TERMINAL CN9.3 &
CN9.4 ON PCB IS
< 1.2 Vdc
YES
SWITCH DHW
THERMOSTAT AT MIN.
NO
DO
BURNER AND FAN
SWITCH OFF
YES
NO
IS
D.H.W.
TEMPERATURE
>60 ûC
YES
IS
D.H.W. NTC
OK
NO
REPLACE D.H.W. NTC
WAIT D.H.W.
TEMPERATURE
>60 ûC
NO
YES
REPLACE
CONTROL BOARD
REPLACE
CONTROL BOARD
30
B
Supplied By www.heating spares.co Tel. 0161 620 6677
7.10.5 FAULT FINDING TEST ‘C’: CHECK CONTROL IN C/H MODE
SWITCH ON BOILER
AND SELECT MODE
TO WINTER C/H
THERMOSTAT AT
MADE A LINK BETWEEN
BLACK & BLACK WIRES AT
BOILER TERMINAL
STRIP AND CLOSE THE
TIMER CONTACT
START
MAX.
IS
ACROSS TERMINALS OF
VOLT AGE
MODULATOR COIL
>10 VDC
NO
CONTROL BOARD
IS
THERE A
VOLTAGE <8 VDC
BETWEEN TERMINALS
CN9.3 & CN9.4
ON PCB
REPLACE
NO
YES
YES NO
IS
VOLT AGE
ACROSS TERMINALS OF
MODULATOR COIL
< 8 VDC
YES
NO
IS
TIMER JUMPER
ON
YES
REMOVE JUMPER
REST AR T THE
TEST
DOES
BURNER
LIGHT
YES
ACROSS TERMINALS OF
MODULATOR COIL
YES
WAIT TILL THE
VOLTAGE BETWEEN
TERMINAL CN9.3 & CN9.4
ON PCB IS < 1.2 Vdc
CHECK BOILER
ST AR TUP TEST A
SET TIMER
JUMPER ON
IS
VOLT AGE
>10 VDC
CONTROL BOARD
NO
REPLACE
REPLACE WIRE
NO
IS THE
RESISTENCE OF
MODULATOR COIL
ABOUT 70/80
OHM
NO
REPLACE
MODULATOR COIL
AND
CONNECTIONS
SWITCH CH
THERMOSTAT AT MIN.
YES
REPLACE
CONTROL BOARD
YES
C
NO
REPLACE
C.H. NTC
IS THE
VOLTAGE BETWEEN
TERMINAL CN9.3 &
CN9.4 ON PCB IS
< 1.2 Vdc
NO
IS
D.H.W.
TEMPERATURE
>80 ûC
YES
IS
C.H. NTC
OK
WAIT D.H.W.
TEMPERATURE
>80 ûC
NO
YES
REPLACE
CONTROL BOARD
31
Supplied By www.heating spares.co Tel. 0161 620 6677
7.10.6 TEST ‘C’ CONT’D
C
SWITCH CH
THERMOSTAT AT MAX.
BURNER AND FAN
SWITCH ON
WAIT 3 MIN.
YES
BURNER AND FAN
SWITCH ON
DO
DO
NO
YES
DO
BURNER AND FAN
SWITCH OFF
REPLACE
CONTROL BOARD
YES
REPLACE
CONTROL BOARD
NO
NO
YES
NO
WAIT WATER FLOW
IS
WATER FLOW
TEMPERATURE
>40 ûC
IS
TIMER JUMPER
ON
TEMPERATURE
< 80 ûC
WAIT W ATER FLOW
TEMPERATURE
>40 ûC
NO
YES
REMOVE JUMPER
REST AR T THE
TEST
OPEN THE TIMER
CONTACT
DO
BURNER
AND FAN
SWITCH
OFF
YES
WAIT
30 SECS.
DO
PUMP SWITCH
OFF
YES
END
NO
REPLACE
CONTROL BOARD
NO
REPLACE
CONTROL BOARD
IS WATER FLOW TEMPERATURE
>80 ûC
NO
IS
C.H. NTC
OK
NO
REPLACE C.H. NTC
YES
YES
REPLACE
CONTROL BOARD
32
Supplied By www.heating spares.co Tel. 0161 620 6677
SECTION 8 WIRING DIAGRAMS
8.1 EXTERNAL WIRING
The appliance comes with a factory fitted clock to allow basic operation of the boiler (fig. 38). If external controls are to be added to the system, they must be connected to the appliance as shown in the following diagrams. For advice on controls that are not featured in this book, please contact the Service & Technical Helpline on 0870-264-1220.
factory configuration
8.3 ROOM THERMOSTAT
Should a room thermostat be required, it must be of the ‘voltage-free’ type, and should be con­nected to the appliance as shown in fig. 39.
8.4 OTHER CONTROLS
Contact the controls manufacturer and/or the technical help line should you require more spe­cific information on the suitability of a particular control. Further guidance on the recommended practice for the installation of external controls, can be found in CHeSS - HC5/HC6 (www.energy­efficiency.gov.uk).
Fig. 38
8.2 TYPICAL CONTROL APPLICATIONS
The appliance can be used with the following controls:
external single-channel, voltage-free time clocks
programmable room thermostats.
In addition, the appliance can be used in con­junction with a typical ‘S’-Plan system, please contact the technical help line (0870 264 1220) for further detailed instruction.
NOTE
This appliance is not suitable for use with ‘Y’-Plan systems.
Fig. 39
33
Supplied By www.heating spares.co Tel. 0161 620 6677
FUNCTIONAL DIAGRAM
NOTE: L-N-E CONNECTION IS ADVISABLE
JP4 Jumper disable/enable DHW absolut thermostat
P1 Domestic hot water temperature control
P2 Central heating temperature control
P3 Off/summer/winter/combustion test
P4 Minimum heating regulation
P5 Heating potentiometer (must be set to max)
F1-F2 Fuse 2 AF
S.S.E. Spark\Sense electrode
CP04X Control board
CN1-CN9 Connectors
RL1 Pump relay
RL2 Fan relay
RL3 Diverter valve motor relay
RL4 Ignition relay
TRF1 Trasformer
TRX Ignition trasformer
Led alarm (red)
Combustion test (blink orange)
ACF01X Ignition control board
M3-M6 External connections block
LED Led OK (green)
Fig. 40
34
F2 = fuse 2AF
Key
D.H.W.F.S. Domestic hot water flow switch
P.S. Pressure switch
P.D.S. Differential pressure switch
H.L.T. High limit thermostat
H.T. Heat thermistor
D.H.W.T. Domestic hot water thermistor
C.P.S. Condense pressure switch
MOD Modulator
F Fan
P Pump
3 W 3 way motor
OPE Gas valve solenoids
JP1 C.H. only selector
JP2 Setting timer
JP3 Natural gas or L.P.G. selector
Supplied By www.heating spares.co Tel. 0161 620 6677
SECTION 10 L.P.G. INSTRUCTIONS
10.1 RELATED DOCUMENTS
BS 6798 INSTALLATION OF BOILERS OF RATED NOT EXCEEDING 60kW BS 5449 PART 1 FORCED CIRCULATION HOT WATER SYSTEMS BS 5546 INSTALLATION OF GAS HOT WATER SUPPLIES FOR DOMESTIC PURPOSES BS 5440 PART 1 FLUES BS 5482 PART 1 DOMESTIC BUTANE & PROPANE GAS BURNERS IN PERMAMENT DWELLINGS
10.2 TECHNICAL DATA
GAS PRESSURES 85 HE 100 HE
Inlet pressure 37 mbar 37 mbar Burner pressure maximum 35.70 mbar 35.50 mbar Burner pressure minimum (heating) 12.80 mbar 10.00 mbar Burner pressure minimum (DHW) 4.90 mbar 4.50 mbar Maximum gas rate 1.94 Kg/h 2.25 Kg/h Minimum gas rate 1.16 Kg/h 1.16 Kg/h Injectot size (quantity) 12 x 0.76 14 x 0.76 SEDBUK (%) 87.7 Band “B” 87.9 Band “B” NOx (max - min) PPM 200 - 120 250 - 180 CO (max - min) PPM 90 - 100 100 - 190 CO2 (%) 7.60 - 4.35 8.20 - 4.00 CO/CO
ratio (max - min) 0.001 to 1 - 0.002 to 1 0.001 to 1 - 0.005 to 1
2
10.3 CONVERTING THE APPLIANCE GAS TYPE
To convert the appliance to another gas type it is necessary to change the burner injectors and adjust the gas pressures. It is also necessary to ensure the jumper tag at JP3 is enabled or disa­bled according to the gas type used.
To change the injectors see section 6.
For correct jumper tag configuration see 7.8.
Ensure you have the correct gas conversion
kit, part code: 01005407
10.4 GAS SUPPLY
The gas supply must be connected to the appli­ance by a competent LPG installer and must be of sufficient size to supply the appliance at its maximum output.
An existing supply must be checked to ensure that it is of adequate size to deal with the maxi­mum rated input of this and any other appliances that it serves.
10.5 GAS SUPPLY INSTALLATION
The entire installation including the meter must be purged and checked for gas soundness.
remove the protective cap from the gas valve modulating coil assembly and turn the outer (10mm) nut clockwise to increase, or counter-clockwise to decrease the burner pressure.
10.6.2 SETTING THE MINIMUM BURNER PRESSURE fig. 34
Once the maximum burner pressure has been checked and/or adjusted, remove one of the grey wires from the modulating coil. Compare the reading on the manometer with the value de­scribed in 10.2.
If adjustment is required, turn the inner (red) crosshead screw clockwise to increase, or coun­ter-clockwise to decrease the burner pressure, whilst ensuring that the outer (10mm) nut does not move. When checking and/or adjustment and/or adjustment has been completed, isolate the appliance from the electrical supply, close the DHW outlet, replace the protective cap, refit the grey wire to the modulating coil, remove the manometer, and tighten the outlet test point.
IMPORTANT, A GAS SOUNDNESS CHECK MUST BE CARRIED OUT.
10.6 CHECKING AND ADJUSTING BURNER PRES­SURE (see fig. 22)
Isolate the appliance from the electrical supply and attach a suitable manometer to the gas valve outlet test point.
10.6.1 SETTING THE MAXIMUM BURNER PRES­SURE fig. 35
Light the boiler as described in 5.7, fully open a DHW outlet (preferably the bath) and ensure the HW temperature selector is set at maximum. Allow the appliance to stabilise.
Compare the reading on the manometer with the value described in 10.2. If adjustment is required,
35
Supplied By www.heating spares.co Tel. 0161 620 6677
BENCHMARK No.
COLLECTIVE MARK
GAS BOILER COMMISSIONING CHECKLIST
BOILER SERIAL No. NOTIFICATION No.
CONTROLS To comply with the Building Regulations, each section must have a tick in one or other of the boxes
TIME & TEMPERATURE CONTROL TO HEATING ROOM T/STAT & PROGRAMMER/TIMER PROGRAMMABLE ROOMSTAT
TIME & TEMPERATURE CONTROL TO HOT WATER CYLINDER T/STAT & PROGRAMMER/TIMER
HEATING ZONE VALVES FITTED NOT REQUIRED
HOT WATER ZONE VALVES FITTED NOT REQUIRED
THERMOSTATIC RADIATOR VALVES FITTED
AUTOMATIC BYPASS TO SYSTEM FITTED NOT REQUIRED
COMBI BOILER
FOR ALL BOILERS CONFIRM THE FOLLOWING
THE SYSTEM HAS BEEN FLUSHED IN ACCORDANCE WITH THE BOILER MANUFACTURERS INSTRUCTIONS?
THE SYSTEM CLEANER USED
THE INHIBITOR USED
FOR THE CENTRAL HEATING MODE, MEASURE & RECORD
N/A
3
/hr
GAS RATE
BURNER OPERATING PRESSURE (IF APPLICABLE)
CENTRAL HEATING FLOW TEMPERATURE °C
CENTRAL HEATING RETURN TEMPERATURE °C
3
/hr
FOR COMBINATION BOILERS ONLY
HAS A WATER SCALE REDUCER BEEN FITTED? YES NO
WHAT TYPE OF SCALE REDUCER HAS BEEN FITTED?
FOR THE DOMESTIC HOT WATER MODE, MEASURE & RECORD
N/A
3
/hr
GAS RATE
MAXIMUM BURNER OPERATING PRESSURE (IF APPLICABLE) mbar
COLD WATER INLET TEMPERATURE °C
HOT WATER OUTLET TEMPERATURE °C
WATER FLOW RATE
FOR CONDENSING BOILERS ONLY CONFIRM THE FOLLOWING
THE CONDENSATE DRAIN HAS BEEN INSTALLED IN ACCORDANCE WITH THE MANUFACTURERS INSTRUCTIONS? YES
FOR ALL INSTALLATIONS CONFIRM THE FOLLOWING
THE HEATING AND HOT WATER SYSTEM COMPLIES WITH CURRENT BUILDING REGULATIONS
THE APPLIANCE AND ASSOCIATED EQUIPMENT HAS BEEN INSTALLED AND COMMISSIONED IN ACCORDANCE WITH THE MANUFACTURERS INSTRUCTIONS
IF REQUIRED BY THE MANUFACTURER, HAVE YOU RECORDED A CO/CO2RATIO READING? N/A YES CO/CO2RATIO
THE OPERATION OF THE APPLIANCE AND SYSTEM CONTROLS HAVE BEEN DEMONSTRATED TO THE CUSTOMER
THE MANUFACTURERS LITERATURE HAS BEEN LEFT WITH THE CUSTOMER
3
/hr
lts/min
COMMISSIONING ENGS NAME
PRINT CORGI ID No.
SIGN DATE
Supplied By www.heating spares.co Tel. 0161 620 6677
SERVICE INTERVAL RECORD
It is recommended that your heating system is serviced regularly
and that you complete the appropriate Service Interval Record Below.
Service Provider. Before completing the appropriate Service Interval Record below, please ensure you have carried out the service
as described in the boiler manufacturers instructions. Always use the manufacturers specified spare part when replacing all controls
SERVICE 1
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
SERVICE 3
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
SERVICE 5
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
DATE
DATE
DATE
SERVICE 2
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
SERVICE 4
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
SERVICE 6
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
DATE
DATE
DATE
SIGNATURE
SERVICE 7
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
SERVICE 9
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
DATE
DATE
SIGNATURE
SERVICE 8
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
SERVICE 10
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
DATE
DATE
Supplied By www.heating spares.co Tel. 0161 620 6677
Supplied By www.heating spares.co Tel. 0161 620 6677
Supplied By www.heating spares.co Tel. 0161 620 6677
Heating Services provides after-sales assistance and Tec hnical ad vice for
Procombi HE Boilers
Service & Technical Helpline: 0870-264-1220
Heating Services, PO BOX 167, BRADFORD, BD19 4WL.
Cod. 10028499 - 03/06 - Ed. 1
COLLECTIVE MARK
We reserve the right to change the specifications without prior notice. Consumers’ statutory rights are not affected
Loading...