Supplied By www.heating spares.co Tel. 0161 620 6677
Installation
& Servicing
Instructions
0694
0694BR1207
THESE INSTRUCTIONS
TO BE RETAINED
BY USER
Supplied By www.heating spares.co Tel. 0161 620 6677
Contents
Design principles & operating sequencePage
1.1Principle components3
1.2Mode of operation (at rest)3
1.3Mode of operation3
1.4Safety devices3
Technical dataPage
2.1Central heating4
2.2Gas pressures4
2.3Expansion vessel4
2.4Dimensions4
2.5Clearances4
2.6Connections4
2.7Electrical4
2.8Flue details (concentric)4
2.8A Flue details (twin pipes)4
2.8B Flue details (80/125)4
2.9Efficiency4
2.10 Emissions4
2.11 Pump duty5
General requirements (UK)Page
3.1Related documents6
3.2Location of appliance6
3.3Gas supply6
3.4Flue system6
3.5Air supply6
3.6Water circulation6
3.7Electrical supply7
3.8Mounting on a combustible surface7
3.9Timber framed buildings7
3.10 Inhibitors7
General requirements (EIRE)Page
3A.1 Related documents8
3A.2 Location of appliance8
3A.3 Gas supply8
3A.4 Flue system8
3A.5 Air supply8
3A.6 Water circulation8
3A.7 Electrical supply9
3A.8 Mounting on a combustible surface9
3A.9 Timber framed buildings9
3A.10Inhibitors9
3A.11 Declaration of conformity9
InstallationPage
4.1Delivery10
4.2Contents10
4.3Unpacking10
4.4Preparation for mounting the appliance10
4.5Fitting the flue10
4.6Connecting the gas & water14
4.7Electrical connections14
6.8Water pressure switch19
6.9Primary thermistor19
6.10 Return thermistor19
6.11 Printed circuit board19
6.12 Gas valve19
6.13 Electrodes and condense sensor20
6.14 Flue fan & mixer20
6.15 Burner20
6.16 Main heat exchanger20
6.17 Automatic by-pass21
6.18 Expansion vessel21
6.19 Condense trap removal21
6.20 Flue collector removal22
Checks, adjustments and fault findingPage
7.1Checking appliance operation22
7.2Appliance modes of operation22
7.3Appliance fan speed23
7.4Checking the CO2 & adjusting the valve24
7.5Combustion analysis test24
7.6Checking the expansion vessel24
7.7External faults24
7.8Electrical checks24
7.9Fault finding25
7.10 Component values & characteristics25
7.11 Boiler configuration27
7.12 Final fault codes26
Wiring diagramsPage
8.1External wiring27
8.2Typical control applications27
8.3Other devices27
8.4Vokera twin-channel programmer27
Exploded diagramsPage
9.1Table 131
9.2Table 232
9.3Table 333
9.4Table 434
9.5Table 535
L.P.G. instructionsPage
10.1 Related documents36
10.2 Technical data36
10.3 Converting the appliance gas type36
10.4 Gas supply36
10.5 Gas supply installation36
10.6 Adjusting the gas valve36
10.7 Appliance fan speed3 7
Benchmark38-39
Commissioning Page
5.1Gas supply installation16
5.2The heating system16
5.3Initial filling of the system16
5.4Initial flushing of the system16
5.5Pre-operation checks16
5.6Initial lighting16
5.7Checking gas pressure & combustion analysis16
5.8Final flushing of the heating system17
5.9Setting the boiler operating temperature17
5.10 Setting the system design pressure17
5.11 Regulating the central heating system17
5.12 Final checks17
5.13 Instructing the user17
ServicingPage
6.1General18
6.2Routine annual servicing18
6.3Replacement of components18
6.4Component removal procedure18
6.5Pump assembly18
6.6Safety valve18
6.7Lower automatic air release valves19
Supplied By www.heating spares.co Tel. 0161 620 6677
INTRODUCTION
The Mynute HE comprises a range of high-efficiency
system boilers with outputs ranging from 12 to 35kW.
These appliances – by design – incorporate electronic
ignition, circulating pump, expansion vessel, safety valve, pressure gauge, and automatic by-pass.
The Mynute HE range are produced as room sealed,
category II2H3P appliances, suitable for internal wall
mounting applications only. Each appliance is provided
with a fan powered flue outlet with an annular co-axial
combustion air intake that can be rotated – horizontally –
through 360 degrees for various horizontal or vertical
Mynute
12-15-20-25 HE
Fig. 1
R
F
G
Mynute
30-35 HE
applications. The Mynute HE can also be used with the
V okera twin flue system. The Myn ute HE is approv ed f or
use with C13 & C33 type flue applications.
These appliances are designed for use with a sealed
system only; consequently they are not intended for use
on open vented systems.
This booklet is an integral part of the appliance. It is
therefore necessary to ensure that the booklet is handed
to the person responsible for the property in which the
appliance is located/installed. A replacement copy can
be obtained from Voker a customer services.
Supplied By www.heating spares.co Tel. 0161 620 6677
HYDROMETRE
GREEN LED
2-digit LED
display
MODE SELECTOR
RED LED
SWITCH
TEMPERATURE SELECTOR
Fig. 1A
Boiler at reset/standbySelect this position if/when the boiler requires to be reset
Boiler switched OFFSelect this position if you w ant the boiler to remain OFF (this will over-ride any
heating/hot water request from the time-clock/programmer)
Boiler switched ONSelect this position when you want the boiler to respond to a heating/hot water
request from the time-clock/programmer
°C
T emperature selectorMove the temperature selector clockwise to increase the boiler outlet temperature, or
counter-clockwise to reduce the outlet flow temperature
2-digit LED displayDisplays the current outlet temperature of the boiler . During a fault condition, the
appropriate fault code will be display ed (refer to the users handbook for instructions
regarding fault codes)
Green LED litBoiler is working/responding to a heating/hot water request
Red LED litBoiler has identified a fault and has failed-saf e. Ref er to users handbook for
instructions on how to reset
Pressure gaugeEnsure the system pressure is set correctly (minimum 0.5-bar)
2
Supplied By www.heating spares.co Tel. 0161 620 6677
SECTION 1DESIGN PRINCIPLES AND OPERATING SEQUENCE
1.1PRINCIPLE COMPONENTS
A fully integrated electronic control board featuring
electronic temperature control, anti-cycle control,
pump over-run, self-diagnostic fault indicator, full
air/gas modulation.
●●
● Radial aluminium heat exchanger.
●●
●●
● Electronic ignition with flame supervision
●●
●●
● Integral high-head pump
●●
●●
● Fan
●●
●●
● Expansion vessel
●●
●●
● Water pressure switch
●●
●●
● Condensate level sensor
●●
●●
● Pressure gauge
●●
●●
● Safety valve
●●
1.2MODE OF OPERATION (at rest)
When the appliance is at rest and there are no
requests for heating or hot water, the following
functions are active:
●●
● 2-stage frost-protection system – the frost-
●●
protection system protects the appliance against
the risk of frost damage. The first stage enables
activation of the pump should the temperature
of the appliance fall to 6oC. Should the first stage
become active, the appliance will function on
minimum +25% power until it reaches 35oC.
●●
● Anti-block function – the anti-block function
●●
enables the pump to be energised for short
periods, when the appliance has been inactive
for more than 24-hours.
●●
● fan speed sensor to ensure safe operation of the
●●
burner;
●●
● a high limit thermostat that over-rides the tem-
●●
perature control circuit to prevent or interrupt the
operation of the burner;
●●
● flame sensor that will shut down the burner when
●●
no flame signal is detected;
●●
● a sensor that interrupts the operation of the
●●
appliance if the condense pipe becomes blocked;
●●
● a safety valve which releases excess pressure
●●
from the primary circuit.
1.3MODE OF OPERATION
When there is a request for heat and/or hot water,
via the programmer/time clock and/or any external
control, the pump and fan are started, the fan
speed will modulate until the correct signal voltage
is received at the control PCB. At this point an
ignition sequence is enabled.
Ignition is sensed by the electronic circuitry to
ensure flame stability at the burner. Once
successful ignition has been achieved, the
electronic circuitry increases the gas rate to 75%
of the MAX Heating (set by the corresponding HTG
trimmer) for a period of 15 minutes. Thereafter,
the boiler’s output will either be increase to
maximum or modulate to suit the set requirement.
When the appliance reaches the desired
temperature the burner will shut down and the
boiler will perform a three-minute anti-cycle (timer
delay).
When the request for heat has been satisfied the
appliance pump and fan may continue to operate
to dissipate any residual heat within the appliance.
1.4SAFETY DEVICES
When the appliance is in use, safe operation is
ensured by:
●●
● a water pressure switch that monitors system
●●
water pressure and will de-activate the pump
(when lockout condition is reached), fan and
burner should the system water pressure drop
below the rated tolerance;
Fig. 2
expansion
vessel
safety
valve
pump
return
temperature
sensor
bottom
CH
return
AAV
automatic
by-pass
CH
flow
pressure
switch
drain
valve
main heat
exchanger
3
Supplied By www.heating spares.co Tel. 0161 620 6677
SECTION 2TECHNICAL DATA
2.1 Central Heating12HE15HE20HE25HE30HE35HE
Heat input (kW)121520253034.6
Maximum heat output (kW) 60/80°C11.8414.8119.6824.5329.3133.67
Minimum heat output (kW) 60/80°C3.53.55677
Maximum heat output (kW) 30/50°C12.7415.9021.1626.306.8436.54
Minimum heat output (kW) 30/50°C3.73.715.306.377.417.41
Minimum working pressure0.5 bar
Maximum working pressure2.7 bar
Minimum flow rate350 l/h
2.2 Gas Pressures12HE15HE20HE25HE30HE35HE
Inlet pressure (G20)20.0 mbar
Maximum gas rate (m3/hr)1.271.592.122.643.173.66
Minimum gas rate (m3/hr)0.370.370.530.630.740.74
Injector size4.6mm4.6mm4.6mm6.7mm7.0mm7.0mm
2.3 Expansion Vessel12HE15HE20HE25HE30HE35HE
Capacity6-litres8-litres10-litres
Maximum system volume63-litres76-litres91-litres
Pre-charge pressure1.0 bar
Maximum horizontal flue length (80mm/80mm)40m/40m40m/40m40m/40m40m/40m40m/40m40m/40m
Maximum vertical flue length (80mm/80mm)40m/40m40m/40m40m/40m40m/40m40m/40m40m/40m
2.9 Efficiency12HE15HE20HE25HE30HE35HE
SEDBUK (%) 90.790.790.590.490.290.0
2.10 Emissions12HE15HE20HE25HE30HE35HE
CO2 @ maximum output (%)9.09.09.09.09.09.0
CO2 @ minimum output (%)9.09.09.09.09.09.0
CO/CO2 ratio @ maximum output0.001 to 10.001 to 10.001 to 10.0002 to 10.0002 to 10.0002 to 1
CO/CO2 ratio @ minimum output0.0002 to 10.0002 to 10.0004 to 10.0003 to 10.0003 to 10.0003 to 1
CO @ maximum output (mg/kWh)107.5129.0161.3204.3215268.8
CO @ minimum output (mg/kWh)21.521.543.032.332.332.3
NOx @ maximum output mg/kWh)88.388.379.488.388.388.3
NOx @ minimum output (mg/kWh)35.335.553.061.870.670.6
NOx ratingclass 5class 5class 5class 5class 5class 5
Band ‘A’Band ‘A’Band ‘A’Band ‘A’Band ‘A’Band ‘A’
Ref. Condition 15 °C, 1013,25 mbar, dry gas
NOTE: L.P.G. data refer to section 10
4
Supplied By www.heating spares.co Tel. 0161 620 6677
2.11PUMP DUTY
Fig. 3 shows the flow-rate available – after allowing for pressure loss through the appliance – for
system requirements. When using this graph,
apply only the pressure loss of the system. The
graph is based on a 20 °C temperature differential.
ABelow an opening (window, air-brick, etc.)300 mm
BAbove an opening (window, air-brick, etc.)300 mm
CTo the side of an opening (window, air-brick, etc.)300 mm
DBelow gutter, drain-pipe, etc.25 mm
EBelow eaves25 mm
FBelow balcony, car-port roof, etc.25 mm
GTo the side of a soil/drain-pipe, etc.25 mm
HFrom internal/external corner or boundary300 mm
IAbove ground, roof, or balcony level300 mm
JFrom a surface or boundary facing the terminal1200 mm
KFrom a terminal facing a terminal1200 mm
LFrom an opening in the car-port into the building1200 mm
MVertically from a terminal on the same wall1500 mm
NHorizontally from a terminal on the same wall300 mm
PFrom a structure to the side of the vertical terminal500 mm
QFrom the top of the vertical terminal to the roof flashingAs determined by the fixed collar
of the vertical terminal
5
Supplied By www.heating spares.co Tel. 0161 620 6677
SECTION 3GENERAL REQUIREMENTS (UK)
This appliance must be installed by a competent person
in accordance with the Gas Safety (Installation & Use)
Regulations.
3.1RELATED DOCUMENTS
The installation of this boiler must be in accordance with the relevant requirements of the Gas
Safety (Installation & Use) Regulations, the local
building regulations, the current I.E.E. wiring regulations, the bylaws of the local water undertaking,
the Building Standards (Scotland) Regulation, and
Building Standards (Northern Ireland) Regulations.
It should be in accordance also with any relevant
requirements of the local authority and the relevant recommendations of the following British
Standard Codes of Practice.
3.2LOCATION OF APPLIANCE
The appliance may be installed in any room or
internal space, although particular attention is
drawn to the requirements of the current I.E.E.
wiring regulations, and in Scotland, the electrical
provisions of the Building Regulations, with respect to the installation of the appliance in a room
or internal space containing a bath or shower.
When an appliance is installed in a room or internal
space containing a bath or shower, the appliance
or any control pertaining to it must not be within
reach of a person using the bath or shower.
the appliance gas inlet connection must not be
used. The installation must be tested for soundness in accordance with BS6891.
If the gas supply serves more than one appliance,
it must be ensured that an adequate supply is
maintained to each appliance when they are in
use at the same time.
3.4FLUE SYSTEM
The terminal should be located where the dispersal of combustion products is not impeded and
with due regard for the damage and discoloration
that may occur to building products located nearby.
The terminal must not be located in a place where
it is likely to cause a nuisance (see fig. 4).
In cold and/or humid weather, water vapour will
condense on leaving the terminal; the effect of
such pluming must be considered.
If installed less than 2m above a pavement or
platform to which people have access (including
balconies or flat roofs) the terminal must be
protected by a guard of durable material. The
guard must be fitted centrally over the terminal.
Refer to BS 5440 Part 1, when the terminal is 0.5
metres (or less) below plastic guttering or 1 metre
(or less) below painted eaves.
BS 5440
BS 5449
BS 6798
BS 6891
BS 7074
PART 2
PART 1
PART 1
The location chosen for the appliance must permit
the provision of a safe and satisfactory flue and
termination. The location must also permit an
adequate air supply for combustion purposes and
an adequate space for servicing and air circulation
around the appliance. Where the installation of the
appliance will be in an unusual location special
procedures may be necessary, BS 6798 gives
detailed guidance on this aspect.
A compartment used to enclose the appliance
must be designed and constructed specifically for
this purpose. An existing compartment/cupboard
may be utilised provided that it is modified to suit.
Details of essential features of compartment/
cupboard design including airing cupboard installations are given in BS 6798. This appliance is not
suitable for external installation.
3.3GAS SUPPLY
The gas meter – as supplied by the gas supplier –
must be checked to ensure that it is of adequate
size to deal with the maximum rated input of all the
appliances that it serves. Installation pipes must
be fitted in accordance with BS 6891.
Pipe work from the meter to the appliance must
be of adequate size. Pipes of a smaller size than
FLUES & VENTILATION
FORCED CIRCULATION HOT WATER SYSTEMS
INSTALLATION OF BOILERS OF RATED INPUT NOT EXCEEDING 60kW
LOW PRESSURE INSTALLATION PIPES
APPLICATION, SELECTION, AND INSTALLTION OF EXPANSION VESSELS AND ANCIL-
LARY EQUIPMENT FOR SEALED WATER SYSTEMS
3.5AIR SUPPLY
The following notes are intended for general guidance only.
This appliance is a room-sealed, fan-flued boiler,
consequently it does not require a permanent air
vent for combustion air supply.
When installed in a cupboard or compartment,
ventilation for cooling purposes is also not required.
3.6WATER CIRCULATION
Detailed recommendations are given in BS 5449
Part 1 and BS 6798. The following notes are for
general guidance only.
3.6.1PIPEWORK
It is recommended that copper tubing to BS 2871
Part 1 is used in conjunction with soldered capillary joints.
Where possible pipes should have a gradient to
ensure air is carried naturally to air release points
and that water flows naturally to drain cocks.
Except where providing useful heat, pipes should
be insulated to avoid heat loss and in particular to
avoid the possibility of freezing. Particular attention should be paid to pipes passing through
6
Supplied By www.heating spares.co Tel. 0161 620 6677
ventilated areas such as under floors, loft space,
and void areas.
3.6.2AUTOMATIC BY-PASS
The appliance has a built-in automatic by-pass,
consequently there is no requirement for an external by-pass, however the design of the system
should be such that it prevents boiler ‘cycling’.
3.6.3DRAIN COCKS
These must be located in accessible positions to
facilitate draining of the appliance and all water
pipes connected to the appliance. The drain cocks
must be manufactured in accordance with BS
2879.
3.6.4AIR RELEASE POINTS
These must be positioned at the highest points in
the system where air is likely to be trapped. They
should be used to expel trapped air and allow
complete filling of the system.
3.6.5EXPANSION VESSEL
The appliance has an integral expansion vessel to
accommodate the increased volume of water
when the system is heated. It can accept up to 6
litres (12-15-20HE), 8 (25HE) and 10 litres (3035HE) of expansion from within the system, generally this is sufficient, however if the system has
an unusually high water content, it may be necessary to provide additional expansion capacity (see
6.19).
3.6.6FILLING POINT
A method for initial filling of the system and replacing water lost during servicing etc. is required
(see fig. 5). This method of filling must comply
with the current Water Supply (Water Fittings)
Regulations 1999 and W ater Bylaws 2000 (Scotland).
control
valve
temporary
connection
control
valve
Make-up vessel
or tank
Automatic
air-vent
Non-return
valve
Fig. 5A
Stopcock
5.0 metres minimum
Heating
return
3.6.8FREQUENT FILLING
Frequent filling or venting of the system may be
indicative of a leak. Care should be taken during
the installation of the appliance to ensure all
aspects of the system are capable of withstanding
pressures up to at least 3 bar.
3.7ELECTRICAL SUPPLY
The appliance is supplied for operation on 230V @
50Hz electrical supply; it must be protected with a
3-amp fuse. The method of connection to the
mains electricity supply must allow for complete
isolation from the supply. The preferred method is
by using a double-pole switch with a contact
separation of at least 3,5mm (3° high-voltage
category). The switch must only supply the appliance and its corresponding controls, i.e. time
clock, room thermostat, etc. Alternatively an unswitched shuttered socket with a fused 3-pin plug
both complying with BS 1363 is acceptable.
3.8MOUNTING ON A COMBUSTIBLESURFACE
If the appliance is to be fitted on a wall of combustible material, a sheet of fireproof material must
protect the wall.
3.9TIMBER FRAMED BUILDINGS
flow/return
pipe
Fig. 5
3.6.7LOW PRESSURE SEALED SYSTEM
double
check valve
supply
pipe
3.10INHIBITORS
An alternative method of filling the system would
be from an independent make-up vessel or tank
mounted in a position at least 1 metre above the
highest point in the system and at least 5 metres
above the boiler (see fig. 5A).
The cold feed from the make-up vessel or tank
must be fitted with an approved non-return valve
and stopcock for isolation purposes. The feed pipe
should be connected to the return pipe as close to
the boiler as possible.
If the appliance is to be fitted in a timber framed
building, it should be fitted in accordance with the
Institute of Gas Engineers publication (IGE/UP/7)
‘Guide for Gas Installations in Timber Frame
Buildings’.
V okera recommend that an inhibitor - suitab le for
use with copper and aluminium heat exchangers
- is used to protect the boiler and system from
the effects of corrosion and/or electrolytic action.
The inhibitor must be administered in strict accordance with the manufacturers instructions*.
*Water treatment of the complete heating system
- including the boiler - should be carried out in
accordance with BS 7593 and the Domestic Water
Treatment Association’s (DWTA) code of practice.
7
Supplied By www.heating spares.co Tel. 0161 620 6677
SECTION 3AGENERAL REQUIREMENTS (EIRE)
This appliance must be installed by a competent
person in accordance with and defined by, the
Standard Specification (Domestic Gas Installations) Declaration (I.S. 813).
3A.1RELATED DOCUMENTS
The installation of this boiler must be in accordance with the relevant requirements of the local
building regulations, the current ETCI National
Rules for Electrical Installations and the bylaws of
the local water undertaking.
It should be in accordance also with any relevant
requirements of the local and/or district authority .
3A.2LOCATION OF APPLIANCE
The appliance may be installed in any room or
internal space, although particular attention is
drawn to the requirements of the current ETCI
National Rules for Electrical Installations, and I.S.
813, Annex K.
When an appliance is installed in a room or internal
space containing a bath or shower, the appliance
or any control pertaining to it must not be within
reach of a person using the bath or shower.
The location chosen for the appliance must permit
the provision of a safe and satisfactory flue and
termination. The location must also permit an
adequate air supply for combustion purposes and
an adequate space for servicing and air circulation
around the appliance. Where the installation of the
appliance will be in an unusual location special
procedures may be necessary, refer to I.S. 813 for
detailed guidance on this aspect.
A compartment used to enclose the appliance
must be designed and constructed specifically for
this purpose. An existing compartment/cupboard
may be utilised provided that it is modified to suit.
This appliance is not suitable for external installation.
3A.3GAS SUPPLY
The gas meter – as supplied by the gas supplier –
must be checked to ensure that it is of adequate
size to deal with the maximum rated input of all the
appliances that it serves. Installation pipes must
be fitted in accordance with I.S. 813.
Pipe work from the meter to the appliance must
be of adequate size. Pipes of a smaller size than
the appliance gas inlet connection must not be
used. The installation must be tested for soundness in accordance with I.S. 813.
If the gas supply serves more than one appliance,
it must be ensured that an adequate supply is
maintained to each appliance when they are in
use at the same time.
3A.4FLUE SYSTEM
The terminal should be located where the dispersal of combustion products is not impeded and
with due regard for the damage and discoloration
that may occur to building products located nearby.
The terminal must not be located in a place where
it is likely to cause a nuisance (see I.S. 813).
In cold and/or humid weather, water vapour will
condense on leaving the terminal; the effect of
such pluming must be considered.
If installed less than 2m above a pavement or
platform to which people have access (including
balconies or flat roofs) the terminal must be
protected by a guard of durable material. The
guard must be fitted centrally over the terminal.
Refer to I.S. 813, when the terminal is 0.5 metres
(or less) below plastic guttering or 1 metre (or less)
below painted eaves.
3A.5AIR SUPPLY
The following notes are intended for general guidance only.
This appliance is a room-sealed, fan-flued boiler,
consequently it does not require a permanent air
vent for combustion air supply.
When installed in a cupboard or compartment,
ventilation for cooling purposes is also not required.
3A.6WATER CIRCULATION
Specific recommendations are given in I.S. 813.
The following notes are for general guidance only.
3A.6.1 PIPEWORK
It is recommended that copper tubing be used in
conjunction with soldered capillary joints.
Where possible pipes should have a gradient to
ensure air is carried naturally to air release points
and that water flows naturally to drain cocks.
Except where providing useful heat, pipes should
be insulated to avoid heat loss and in particular to
avoid the possibility of freezing. Particular attention should be paid to pipes passing through
ventilated areas such as under floors, loft space,
and void areas.
3A.6.2AUTOMATIC BY-PASS
The appliance has a built-in automatic by-pass,
consequently there is no requirement for an external by-pass, however the design of the system
should be such that it prevents boiler ‘cycling’.
3A.6.3 DRAIN COCKS
These must be located in accessible positions to
facilitate draining of the appliance and all water
pipes connected to the appliance.
3A.6.4 AIR RELEASE POINTS
These must be positioned at the highest points in
the system where air is likely to be trapped. They
should be used to expel trapped air and allow
complete filling of the system.
3A.6.5 EXPANSION VESSEL
The appliance has an integral expansion vessel to
accommodate the increased volume of water
when the system is heated. It can accept up to 6
litres (12-15-20HE), 8 (25HE) and 10 litres (3035HE) of expansion from within the system, generally this is sufficient, however if the system has
an unusually high water content, it may be necessary to provide additional expansion capacity (see
6.19).
8
Supplied By www.heating spares.co Tel. 0161 620 6677
3A.6.6 FILLING POINT
A method for initial filling of the system and replacing
water lost during servicing etc. is required. You
should ensure this method of filling complies with
the local water authority regulations.
3A.6.7 LOW PRESSURE SEALED SYSTEM
An alternative method of filling the system would
be from an independent make-up vessel or tank
mounted in a position at least 1 metre above the
highest point in the system and at least 5 metres
above the boiler (see fig. 5).
The cold feed from the make-up vessel or tank
must be fitted with an approved non-return valve
and stopcock for isolation purposes. The feed pipe
should be connected to the return pipe as close to
the boiler as possible.
3A.6.8 FREQUENT FILLING
Frequent filling or venting of the system may be
indicative of a leak. Care should be taken during
the installation of the appliance to ensure all
aspects of the system are capable of withstanding
pressures up to at least 3 bar.
3A.7ELECTRICAL SUPPLY
The appliance is supplied for operation on 230V @
50Hz electrical supply; it must be protected with a
3-amp fuse. The method of connection to the
mains electricity supply must allow for complete
isolation from the supply. The preferred method is
by using a double-pole switch with a contact
separation of at least 3,5mm (3° high-voltage
category). The switch must only supply the appliance and its corresponding controls, i.e. time
clock, room thermostat, etc.
3A.8MOUNTING ON A COMBUSTIBLESURFACE
If the appliance is to be fitted on a wall of combustible material, a sheet of fireproof material must
protect the wall.
Mynute
12-15-20 HE
Mynute
25-30-35 HE
3A.9TIMBER FRAMED BUILDINGS
If the appliance is to be fitted in a timber framed
building, it should be fitted in accordance with I.S.
813 and local Building Regulations.
The Institute of Gas Engineers publication (IGE/
UP/7) ‘Guide for Gas Installations in Timber Frame
Buildings’ gives specific advice on this type of
installation.
3A.10 INHIBITORS
V okera recommend that an inhibitor - suitab le for
use with aluminium heat exchangers - is used to
protect the boiler and system from the effects of
corrosion and/or electrolytic action. The inhibitor
must be administered in strict accordance with
the manufacturers instructions*.
*Water treatment of the complete heating system including the boiler - should be carried out in accordance with I.S. 813 and the Domestic Water Treatment Association’s (DWTA) code of practice.
3A.11 DECLARA TION OF CONFORMITY
A Declaration of Conformity (as defined in I.S. 813)
must be provided on completion of the installation.
A copy of the declaration must be given to the
responsible person and also to the gas supplier if
required.
Fig. 6
9
Supplied By www.heating spares.co Tel. 0161 620 6677
SECTION 4INSTALLATION
4.1DELIVERY
Due to the weight of the appliance it may be
necessary for two people to lift and attach the
appliance to its mounting. The appliance is contained within a heavy-duty cardboard carton. Lay the
carton on the floor with the writing the correct way up.
4.2CONTENTS
Contained within the carton is:
• the boiler
• the wall bracket
• template
• an accessories pack containing appliance serv-
ice connections and washers
• the instruction pack containing the installation &
servicing instructions, user instructions, guarantee registration card, and a 3-amp fuse.
4.3UNPACKING
At the top of the carton pull both sides open – do
not use a knife – unfold the rest of the carton from
around the appliance, carefully remove all protective packaging from the appliance, and lay the
accessories etc. to one side. Protective gloves
should be used to lift the appliance, the appliance
back-frame should be used for lifting points.
4.4PREPARATION FOR MOUNTING THE APPLIANCE
The appliance should be mounted on a smooth,
vertical, non-combustible surface, which must be
capable of supporting the full weight of the appliance. Care should be exercised when determining
the position of the appliance with respect to hidden
obstructions such as pipes, cables, etc.
When the position of the appliance has been
decided – using the template supplied – carefully
mark the position of the wall- mounting bracket
(see fig. 6) and flue-hole (if applicable).
Reduction for additional bends
BendReduction in maximum flue length for each bend
45° bend
350 /530 mm
1370 mm
N/A
N/A
500mm
1000 mm
2000 mm
350 /730 mm
208mm
Using the template provided, mark and drill a
115mm hole for the passage of the flue pipe. The
hole should be drilled to ensure any condense fluid
that forms, is allowed to drain back to the appliance
(see fig. 7A).
The fixing holes for the wall-mounting bracket
should now be drilled and plugged, an appropriate
type and quantity of fixing should be used to
ensure that the bracket is mounted securely. Once
the bracket has been secured to the wall, mount
the appliance onto the bracket.
4.5FITTING THE FLUE
The top flue outlet permits both horizontal and
vertical flue applications to be considered, alternatively, the Vokera twin flue system can be utilised
if longer flue runs are required.
4.5.1CONCENTRIC HORIZONT AL FLUE
(For concentric vertical flue, see 4.5.2)
(For twin flue applications, see 4.5.3)
The appliance can be used with either the Vokera
condensing 60/100mm concentric flue system or
the optional 80/125mm concentric flue system.
NOTE
These instructions relate only to the Vokera
condensing 60/100mm concentric flue system.
For specific details on the installation of the 80/
125mm concentric flue system please refer to the
instructions supplied.
The appliance flue outlet elbow can be rotated
through 360º on its vertical axis. In addition the
flue may be extended from the outlet elbow in the
horizontal plane (see 2.8). A reduction must also
be made to the maximum length (see table below)
when additional bends are used.
Fig. 7
10
Supplied By www.heating spares.co Tel. 0161 620 6677
FITTING THE HORIZONT AL FLUE KIT
Carefully measure the distance from the centre of
the appliance flue outlet to the edge of the finished
outside wall (dimension X). Add 65mm to
dimension X to give you Dimension Y (see fig 7A).
Measure dimension Y from the terminal end of
the concentric flue pipe and cut off the excess
ensuring any burrs are removed. Pass the
concentric flue pipe through the previously drilled
hole. Fit the flue bend to the boiler flue outlet and
insert the concentric flue pipe into the flue bend
ensuring the correct seal is made.
Using the clamp, gasket, and screws supplied,
secure the flue bend to the appliance flue spigot.
NOTE
Fit the internal (white) trim to the flue assembly
prior to connecting the flue pipe to the bend.
You must ensure that the entire flue system is
properly supported and connected.
Seal the flue assembly to the wall using cement
or a suitable alternative that will provide
satisfactory weatherproofing. The exterior trim can
now be fitted.
4.5.1.1 EXTENDING THE FLUE
Connect the bend – supplied with the terminal kit
– to the top of the boiler using clamp (supplied)
see fig. 7. The additional bends & extensions hav e
push-fit connections, care should be taken to
ensure that the correct seal is made when
assembling the flue system. Connect the required
number of flue extensions or bends (up to the
maximum equivalent flue length) to the flue terminal
(see fig. 7 & 8).
The flue system should have a minimum of 1º;
maximum of 3° rise from the boiler to outside, to
ensure any condense fluid that forms, is allowed
to drain back to the appliance.
NOTE
When cutting an extension to the required length,
you must ensure that the excess is cut from the
plain end of the extension (see fig. 7 & 8). Remove
any burrs, and check that all seals are located
properly.
You must ensure that the entire flue system is
properly supported and connected.
Seal the flue assembly to the wall using cement
or a suitable alternative that will provide
satisfactory weatherproofing. The interior and
exterior trim can now be fitted.
“X”
30mm
“X” + 65mm = “Y”
Fig. 7A
“Y”
1-3 degree
4.5.2CONCENTRIC VERTICAL FLUE
The appliance can be used with either the V ok era
condensing 60/100mm concentric flue system or
the optional 80/125mm concentric flue system.
NOTE
These instructions relate only to the Vokera
condensing 60/100mm concentric flue system.
For specific details on the installation of the 80/
125mm concentric flue system please refer to the
instructions supplied.
The vertical flue terminal can be connected directly
to the appliance flue outlet. Alternatively, an
extension or bend can be connected to the
appliance flue outlet if desired (see 4.4.2), however
if additional bends are fitted, a reduction must be
made to the maximum flue length (see table in
the next page).
Fig. 8
11
Supplied By www.heating spares.co Tel. 0161 620 6677
Reduction for bends
Bend
45° bend
90° bend
Ve rtical flue terminal and accessories
Part No.
530
531
532
523
524
525
526
527
528
529
Reduction in maximum flue length for each bend
0.5 metre
1.0 metre
Description
V ertical flue terminal
Pitched roof flashing plate
Flat roof flashing plate
90-degree bend
45-degree bends (pair)
500mm extension
1000mm extension
2000mm extension
T elescopic e xtension
Wall brac ket pack (5)
Using the dimensions given in fig. 9 as a reference,
mark and cut a 115mm hole in the ceiling and/or
roof.
“X”
12/15/20HE = 202mm
25/30/35HE = 218mm
“X”
Fig. 9
Fit the appropriate flashing plate to the roof and
insert the vertical flue terminal through the flashing
plate from the outside, ensuring that the collar on
the flue terminal fits over the flashing.
The fixing holes for the wall-mounting bracket
should now be drilled and plugged, an appropriate
type and quantity of fixing should be used to
ensure that the bracket is mounted securely. Once
the bracket has been secured to the wall, mount
the appliance onto the bracket.
IMPORTANT
The vertical flue terminal is 1.0 metre in length
and cannot be cut; therefore it may be necessary
to adjust the height of the appliance to suit or use
a suitable extension.
Min-Max length
1000 mm
N/A
N/A
N/A
N/A
500mm
1000 mm
2000 mm
350/730mm
208mm
Connect the vertical flue assembly to the boiler
flue spigot using the 100mm clip, gasket, & screws
(supplied), ensuring the correct seal is made. The
flue support bracket (supplied with the vertical
flue kit) can now be fitted.
If the vertical flue requires extension/s or
additional bend/s, connect the required number
of flue extensions or bends (up to the maximum
equivalent flue length) between the boiler and
vertical flue assembly (see fig. 8).
Ensure that any horizontal sections of the flue
system have a minimum 1º; maximum 3º fall back
to the boiler (1º = 17mm per 1000mm)
NOTE
When cutting an extension to the required length,
you must ensure that the excess is cut from the
plain end of the extension (see fig. 8). Remove
any burrs, and check that any seals are located
properly.
You must ensure that the entire flue system is
properly supported and connected.
4.5.3TWIN FLUE SYSTEM
The Voker a twin flue system enables greater flue
distances to be achieved (see 4.4.2) than that of
a concentric flue system. It can be used for
horizontal or vertical applications, howev er the twin
flue system must be converted to the dedicated
concentric flue kit for termination. It is essential
that the installation of the twin flue system be
carried out in strict accordance with these
instructions.
GUIDANCE NOTES ON TWIN FLUE
INSTALLA TION
• The flue must have a minimum 1º; maximum 3º
(1º = 17mm per 1000mm) fall back to the
appliance to allow any condensate that may form
in the flue system to drain via the condensate
drain. Consideration must also be given to the
fact that there is the possibility of a small
amount of condensate dripping from the terminal.
• Ensure that the entire flue system is adequately
supported, use at least one bracket for each
extension.
• The entire flue system must be adequately
insulated to maintain heat within the flue system
thereby reducing the possibility of condensate
production.
• As the exhaust outlet pipe can reach very high
temperatures it must be protected to prevent
persons touching the hot surface.
• The condensate drain pipe must be connected
in accordance with building regulations
Reduction for bends
Bend
45° bend
90° bend
Reduction in maximum flue length for each bend
1.0 metre
1.0 metre
12
Loading...
+ 30 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.