VOKERA Mynute 12HE, Mynute 15HE, Mynute 35HE, Mynute 20HE, Mynute 25HE Installation And Servicing Instructions

...
Supplied By www.heating spares.co Tel. 0161 620 6677
Installation & Servicing Instructions
0694BR1207
THESE INSTRUCTIONS TO BE RETAINED BY USER
Supplied By www.heating spares.co Tel. 0161 620 6677
Contents
Design principles & operating sequence Page
1.1 Principle components 3
1.2 Mode of operation (at rest) 3
1.3 Mode of operation 3
1.4 Safety devices 3
Technical data Page
2.1 Central heating 4
2.2 Gas pressures 4
2.3 Expansion vessel 4
2.4 Dimensions 4
2.5 Clearances 4
2.6 Connections 4
2.7 Electrical 4
2.8 Flue details (concentric) 4
2.8A Flue details (twin pipes) 4
2.8B Flue details (80/125) 4
2.9 Efficiency 4
2.10 Emissions 4
2.11 Pump duty 5
General requirements (UK) Page
3.1 Related documents 6
3.2 Location of appliance 6
3.3 Gas supply 6
3.4 Flue system 6
3.5 Air supply 6
3.6 Water circulation 6
3.7 Electrical supply 7
3.8 Mounting on a combustible surface 7
3.9 Timber framed buildings 7
3.10 Inhibitors 7
General requirements (EIRE) Page
3A.1 Related documents 8 3A.2 Location of appliance 8 3A.3 Gas supply 8 3A.4 Flue system 8 3A.5 Air supply 8 3A.6 Water circulation 8 3A.7 Electrical supply 9 3A.8 Mounting on a combustible surface 9 3A.9 Timber framed buildings 9 3A.10Inhibitors 9 3A.11 Declaration of conformity 9
Installation Page
4.1 Delivery 10
4.2 Contents 10
4.3 Unpacking 10
4.4 Preparation for mounting the appliance 10
4.5 Fitting the flue 10
4.6 Connecting the gas & water 14
4.7 Electrical connections 14
6.8 Water pressure switch 19
6.9 Primary thermistor 19
6.10 Return thermistor 19
6.11 Printed circuit board 19
6.12 Gas valve 19
6.13 Electrodes and condense sensor 20
6.14 Flue fan & mixer 20
6.15 Burner 20
6.16 Main heat exchanger 20
6.17 Automatic by-pass 21
6.18 Expansion vessel 21
6.19 Condense trap removal 21
6.20 Flue collector removal 22
Checks, adjustments and fault finding Page
7.1 Checking appliance operation 22
7.2 Appliance modes of operation 22
7.3 Appliance fan speed 23
7.4 Checking the CO2 & adjusting the valve 24
7.5 Combustion analysis test 24
7.6 Checking the expansion vessel 24
7.7 External faults 24
7.8 Electrical checks 24
7.9 Fault finding 25
7.10 Component values & characteristics 25
7.11 Boiler configuration 27
7.12 Final fault codes 26
Wiring diagrams Page
8.1 External wiring 27
8.2 Typical control applications 27
8.3 Other devices 27
8.4 Vokera twin-channel programmer 27
Exploded diagrams Page
9.1 Table 1 31
9.2 Table 2 32
9.3 Table 3 33
9.4 Table 4 34
9.5 Table 5 35
L.P.G. instructions Page
10.1 Related documents 36
10.2 Technical data 36
10.3 Converting the appliance gas type 36
10.4 Gas supply 36
10.5 Gas supply installation 36
10.6 Adjusting the gas valve 36
10.7 Appliance fan speed 3 7
Benchmark 38-39
Commissioning Page
5.1 Gas supply installation 16
5.2 The heating system 16
5.3 Initial filling of the system 16
5.4 Initial flushing of the system 16
5.5 Pre-operation checks 16
5.6 Initial lighting 16
5.7 Checking gas pressure & combustion analysis 16
5.8 Final flushing of the heating system 17
5.9 Setting the boiler operating temperature 17
5.10 Setting the system design pressure 17
5.11 Regulating the central heating system 17
5.12 Final checks 17
5.13 Instructing the user 17
Servicing Page
6.1 General 18
6.2 Routine annual servicing 18
6.3 Replacement of components 18
6.4 Component removal procedure 18
6.5 Pump assembly 18
6.6 Safety valve 18
6.7 Lower automatic air release valves 19
Supplied By www.heating spares.co Tel. 0161 620 6677
INTRODUCTION
The Mynute HE comprises a range of high-efficiency system boilers with outputs ranging from 12 to 35kW. These appliances – by design – incorporate electronic ignition, circulating pump, expansion vessel, safety val­ve, pressure gauge, and automatic by-pass.
The Mynute HE range are produced as room sealed, category II2H3P appliances, suitable for internal wall mounting applications only. Each appliance is provided with a fan powered flue outlet with an annular co-axial combustion air intake that can be rotated – horizontally – through 360 degrees for various horizontal or vertical
Mynute
12-15-20-25 HE
Fig. 1
R
F
G
Mynute
30-35 HE
applications. The Mynute HE can also be used with the V okera twin flue system. The Myn ute HE is approv ed f or use with C13 & C33 type flue applications.
These appliances are designed for use with a sealed system only; consequently they are not intended for use on open vented systems.
This booklet is an integral part of the appliance. It is therefore necessary to ensure that the booklet is handed to the person responsible for the property in which the appliance is located/installed. A replacement copy can be obtained from Voker a customer services.
General layout (fig. 1)
1 Safety valve 2 Pressure switch 3 Pump 4 Bottom auto air vent (AAV) 5 Injector 6 Condense trap 7 Return sensor 8 Flue gas analysis test point 9 Flue outlet & air intake 10 Ignition transformer 11 Top AAV 12 Flow sensor 13 High limit thermostat 14 Limit thermostat 15 Sensing Electrode 16 Spark Electrode 17 Cylindric Burner 18 Condensate level sensor 19 Main heat exchanger 20 Top AAV pipe 21 Fan assembly 22 Mixer 23 Expansion vessel 24 Hydraulic manifold 25 Gas valve 26 Condensing drain
R
GF
R Heating return connection F Heating flow connection G Gas connection
1
Supplied By www.heating spares.co Tel. 0161 620 6677
HYDROMETRE
GREEN LED
2-digit LED
display
MODE SELECTOR
RED LED
SWITCH
TEMPERATURE SELECTOR
Fig. 1A
Boiler at reset/standby Select this position if/when the boiler requires to be reset Boiler switched OFF Select this position if you w ant the boiler to remain OFF (this will over-ride any
heating/hot water request from the time-clock/programmer)
Boiler switched ON Select this position when you want the boiler to respond to a heating/hot water
request from the time-clock/programmer
°C
T emperature selector Move the temperature selector clockwise to increase the boiler outlet temperature, or
counter-clockwise to reduce the outlet flow temperature
2-digit LED display Displays the current outlet temperature of the boiler . During a fault condition, the
appropriate fault code will be display ed (refer to the users handbook for instructions
regarding fault codes) Green LED lit Boiler is working/responding to a heating/hot water request Red LED lit Boiler has identified a fault and has failed-saf e. Ref er to users handbook for
instructions on how to reset Pressure gauge Ensure the system pressure is set correctly (minimum 0.5-bar)
2
Supplied By www.heating spares.co Tel. 0161 620 6677
SECTION 1 DESIGN PRINCIPLES AND OPERATING SEQUENCE
1.1 PRINCIPLE COMPONENTS
A fully integrated electronic control board featuring electronic temperature control, anti-cycle control, pump over-run, self-diagnostic fault indicator, full air/gas modulation.
●●
Radial aluminium heat exchanger.
●●
●●
Electronic ignition with flame supervision
●●
●●
Integral high-head pump
●●
●●
Fan
●●
●●
Expansion vessel
●●
●●
Water pressure switch
●●
●●
Condensate level sensor
●●
●●
Pressure gauge
●●
●●
Safety valve
●●
1.2 MODE OF OPERATION (at rest)
When the appliance is at rest and there are no requests for heating or hot water, the following functions are active:
●●
2-stage frost-protection system – the frost-
●●
protection system protects the appliance against the risk of frost damage. The first stage enables activation of the pump should the temperature of the appliance fall to 6oC. Should the first stage become active, the appliance will function on minimum +25% power until it reaches 35oC.
●●
Anti-block function – the anti-block function
●●
enables the pump to be energised for short periods, when the appliance has been inactive for more than 24-hours.
●●
fan speed sensor to ensure safe operation of the
●●
burner;
●●
a high limit thermostat that over-rides the tem-
●●
perature control circuit to prevent or interrupt the operation of the burner;
●●
flame sensor that will shut down the burner when
●●
no flame signal is detected;
●●
a sensor that interrupts the operation of the
●●
appliance if the condense pipe becomes blocked;
●●
a safety valve which releases excess pressure
●●
from the primary circuit.
1.3 MODE OF OPERATION
When there is a request for heat and/or hot water, via the programmer/time clock and/or any external control, the pump and fan are started, the fan speed will modulate until the correct signal voltage is received at the control PCB. At this point an ignition sequence is enabled. Ignition is sensed by the electronic circuitry to ensure flame stability at the burner. Once successful ignition has been achieved, the electronic circuitry increases the gas rate to 75% of the MAX Heating (set by the corresponding HTG trimmer) for a period of 15 minutes. Thereafter, the boiler’s output will either be increase to maximum or modulate to suit the set requirement. When the appliance reaches the desired temperature the burner will shut down and the boiler will perform a three-minute anti-cycle (timer delay). When the request for heat has been satisfied the appliance pump and fan may continue to operate to dissipate any residual heat within the appliance.
1.4 SAFETY DEVICES
When the appliance is in use, safe operation is
ensured by:
●●
a water pressure switch that monitors system
●●
water pressure and will de-activate the pump (when lockout condition is reached), fan and burner should the system water pressure drop below the rated tolerance;
Fig. 2
expansion
vessel
safety valve
pump
return
temperature
sensor
bottom
CH
return
AAV
automatic
by-pass
CH
flow
pressure
switch
drain valve
main heat
exchanger
3
Supplied By www.heating spares.co Tel. 0161 620 6677
SECTION 2 TECHNICAL DATA
2.1 Central Heating 12HE 15HE 20HE 25HE 30HE 35HE
Heat input (kW) 12 15 20 25 30 34.6 Maximum heat output (kW) 60/80°C 11.84 14.81 19.68 24.53 29.31 33.67 Minimum heat output (kW) 60/80°C 3.5 3.5 5 6 7 7 Maximum heat output (kW) 30/50°C 12.74 15.90 21.16 26.30 6.84 36.54 Minimum heat output (kW) 30/50°C 3.7 3.71 5.30 6.37 7.41 7.41 Minimum working pressure 0.5 bar Maximum working pressure 2.7 bar Minimum flow rate 350 l/h
2.2 Gas Pressures 12HE 15HE 20HE 25HE 30HE 35HE
Inlet pressure (G20) 20.0 mbar Maximum gas rate (m3/hr) 1.27 1.59 2.12 2.64 3.17 3.66 Minimum gas rate (m3/hr) 0.37 0.37 0.53 0.63 0.74 0.74 Injector size 4.6mm 4.6mm 4.6mm 6.7mm 7.0mm 7.0mm
2.3 Expansion Vessel 12HE 15HE 20HE 25HE 30HE 35HE
Capacity 6-litres 8-litres 10-litres Maximum system volume 63-litres 76-litres 91-litres Pre-charge pressure 1.0 bar
2.4 Dimensions 12HE 15HE 20HE 25HE 30HE 35HE
Height 740mm 780mm 780mm Width 400mm 400mm 450mm Depth 340mm 358mm 358mm Dry weight (kg)
2.5 Clearances Mynute HE Range
Sides 12mm Top 150mm from casing or 25mm above flue elbow (whichever is applicable) Bottom 150mm Front 600mm
2.6 Connections Mynute HE Range
Flow & return 22mm Gas 15mm Safety valve 15mm Condense 21mm
2.7 Electrical 12HE 15HE 20HE 25HE 30HE 35HE
Power consumption (Watts) 150 150 150 150 165 165 Supply (V/Hz) 230/50 Internal fuse 3.15A T (for PCB) - 3.15A F (for connections block) External fuse 3A
2.8 Flue Details (concentric - 60/100) 12HE 15HE 20HE 25HE 30HE 35HE
Maximum horizontal flue length (60/100mm) 7.8m 7.8m 7.8m 7.8m 7.8m 7.8m Maximum vertical flue length (60/100mm) 8.8m 8.8m 8.8m 8.8m 8.8m 8.8m
2.8A Flue Details (concentric 80/125mm) 12HE 15HE 20HE 25HE 30HE 35HE
Maximum horizontal flue length (80/125mm) 20m 20m 20m 20m 20m 20m Maximum vertical flue length (80/125mm) 25m 25m 25m 25m 25m 25m
2.8A Flue Details (twin pipes) 12HE 15HE 20HE 25HE 30HE 35HE
Maximum horizontal flue length (80mm/80mm) 40m/40m 40m/40m 40m/40m 40m/40m 40m/40m 40m/40m Maximum vertical flue length (80mm/80mm) 40m/40m 40m/40m 40m/40m 40m/40m 40m/40m 40m/40m
2.9 Efficiency 12HE 15HE 20HE 25HE 30HE 35HE
SEDBUK (%) 90.7 90.7 90.5 90.4 90.2 90.0
2.10 Emissions 12HE 15HE 20HE 25HE 30HE 35HE
CO2 @ maximum output (%) 9.0 9.0 9.0 9.0 9.0 9.0 CO2 @ minimum output (%) 9.0 9.0 9.0 9.0 9.0 9.0 CO/CO2 ratio @ maximum output 0.001 to 1 0.001 to 1 0.001 to 1 0.0002 to 1 0.0002 to 1 0.0002 to 1 CO/CO2 ratio @ minimum output 0.0002 to 1 0.0002 to 1 0.0004 to 1 0.0003 to 1 0.0003 to 1 0.0003 to 1 CO @ maximum output (mg/kWh) 107.5 129.0 161.3 204.3 215 268.8 CO @ minimum output (mg/kWh) 21.5 21.5 43.0 32.3 32.3 32.3 NOx @ maximum output mg/kWh) 88.3 88.3 79.4 88.3 88.3 88.3 NOx @ minimum output (mg/kWh) 35.3 35.5 53.0 61.8 70.6 70.6 NOx rating class 5 class 5 class 5 class 5 class 5 class 5
Band ‘A’ Band ‘A’ Band ‘A’ Band ‘A’ Band ‘A’ Band ‘A’
Ref. Condition 15 °C, 1013,25 mbar, dry gas NOTE: L.P.G. data refer to section 10
4
Supplied By www.heating spares.co Tel. 0161 620 6677
2.11 PUMP DUTY
Fig. 3 shows the flow-rate available – after allow­ing for pressure loss through the appliance – for system requirements. When using this graph, apply only the pressure loss of the system. The graph is based on a 20 °C temperature differential.
Mynute
12-15-20-25 HE
5,0 4,8 4,6 4,4 4,2 4,0 3,8 3,6 3,4 3,2 3,0 2,8 2,6 2,4 2,2 2,0 1,8 1,6 1,4 1,2 1,0 0,8
Residual head (x 100 mbar)
0,6 0,4 0,2 0,0
0 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500
1st speed
2nd speed
Flow rate (l/h)
Fig. 3
Fig. 4
3rd speed
Mynute
30-35 HE
6,0 5,8 5,6 5,4 5,2 5,0 4,8 4,6 4,4 4,2 4,0 3,8 3,6 3,4 3,2 3,0 2,8 2,6 2,4 2,2 2,0 1,8 1,6 1,4 1,2 1,0 0,8
Residual head (x 100 mbar)
0,6 0,4 0,2 0,0
0 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500
1st speed
2nd speed
Flow rate (l/h)
3rd speed
Key Location Minimum distance
A Below an opening (window, air-brick, etc.) 300 mm B Above an opening (window, air-brick, etc.) 300 mm C To the side of an opening (window, air-brick, etc.) 300 mm D Below gutter, drain-pipe, etc. 25 mm E Below eaves 25 mm
F Below balcony, car-port roof, etc. 25 mm G To the side of a soil/drain-pipe, etc. 25 mm H From internal/external corner or boundary 300 mm
I Above ground, roof, or balcony level 300 mm J From a surface or boundary facing the terminal 1200 mm K From a terminal facing a terminal 1200 mm L From an opening in the car-port into the building 1200 mm
M Vertically from a terminal on the same wall 1500 mm N Horizontally from a terminal on the same wall 300 mm
P From a structure to the side of the vertical terminal 500 mm
Q From the top of the vertical terminal to the roof flashing As determined by the fixed collar
of the vertical terminal
5
Supplied By www.heating spares.co Tel. 0161 620 6677
SECTION 3 GENERAL REQUIREMENTS (UK)
This appliance must be installed by a competent person in accordance with the Gas Safety (Installation & Use) Regulations.
3.1 RELATED DOCUMENTS
The installation of this boiler must be in accord­ance with the relevant requirements of the Gas Safety (Installation & Use) Regulations, the local building regulations, the current I.E.E. wiring regu­lations, the bylaws of the local water undertaking, the Building Standards (Scotland) Regulation, and Building Standards (Northern Ireland) Regulations.
It should be in accordance also with any relevant requirements of the local authority and the rel­evant recommendations of the following British Standard Codes of Practice.
3.2 LOCATION OF APPLIANCE
The appliance may be installed in any room or internal space, although particular attention is drawn to the requirements of the current I.E.E. wiring regulations, and in Scotland, the electrical provisions of the Building Regulations, with re­spect to the installation of the appliance in a room or internal space containing a bath or shower. When an appliance is installed in a room or internal space containing a bath or shower, the appliance or any control pertaining to it must not be within reach of a person using the bath or shower.
the appliance gas inlet connection must not be used. The installation must be tested for sound­ness in accordance with BS6891. If the gas supply serves more than one appliance, it must be ensured that an adequate supply is maintained to each appliance when they are in use at the same time.
3.4 FLUE SYSTEM
The terminal should be located where the disper­sal of combustion products is not impeded and with due regard for the damage and discoloration that may occur to building products located nearby. The terminal must not be located in a place where it is likely to cause a nuisance (see fig. 4). In cold and/or humid weather, water vapour will condense on leaving the terminal; the effect of such pluming must be considered. If installed less than 2m above a pavement or platform to which people have access (including balconies or flat roofs) the terminal must be protected by a guard of durable material. The guard must be fitted centrally over the terminal. Refer to BS 5440 Part 1, when the terminal is 0.5 metres (or less) below plastic guttering or 1 metre (or less) below painted eaves.
BS 5440 BS 5449 BS 6798 BS 6891 BS 7074
PART 2 PART 1
PART 1
The location chosen for the appliance must permit the provision of a safe and satisfactory flue and termination. The location must also permit an adequate air supply for combustion purposes and an adequate space for servicing and air circulation around the appliance. Where the installation of the appliance will be in an unusual location special procedures may be necessary, BS 6798 gives detailed guidance on this aspect. A compartment used to enclose the appliance must be designed and constructed specifically for this purpose. An existing compartment/cupboard may be utilised provided that it is modified to suit. Details of essential features of compartment/ cupboard design including airing cupboard instal­lations are given in BS 6798. This appliance is not suitable for external installation.
3.3 GAS SUPPLY
The gas meter – as supplied by the gas supplier – must be checked to ensure that it is of adequate size to deal with the maximum rated input of all the appliances that it serves. Installation pipes must be fitted in accordance with BS 6891. Pipe work from the meter to the appliance must be of adequate size. Pipes of a smaller size than
FLUES & VENTILATION FORCED CIRCULATION HOT WATER SYSTEMS INSTALLATION OF BOILERS OF RATED INPUT NOT EXCEEDING 60kW LOW PRESSURE INSTALLATION PIPES APPLICATION, SELECTION, AND INSTALLTION OF EXPANSION VESSELS AND ANCIL-
LARY EQUIPMENT FOR SEALED WATER SYSTEMS
3.5 AIR SUPPLY
The following notes are intended for general guid­ance only. This appliance is a room-sealed, fan-flued boiler, consequently it does not require a permanent air vent for combustion air supply. When installed in a cupboard or compartment, ventilation for cooling purposes is also not re­quired.
3.6 WATER CIRCULATION
Detailed recommendations are given in BS 5449 Part 1 and BS 6798. The following notes are for general guidance only.
3.6.1 PIPEWORK
It is recommended that copper tubing to BS 2871 Part 1 is used in conjunction with soldered capil­lary joints. Where possible pipes should have a gradient to ensure air is carried naturally to air release points and that water flows naturally to drain cocks. Except where providing useful heat, pipes should be insulated to avoid heat loss and in particular to avoid the possibility of freezing. Particular atten­tion should be paid to pipes passing through
6
Supplied By www.heating spares.co Tel. 0161 620 6677
ventilated areas such as under floors, loft space, and void areas.
3.6.2 AUTOMATIC BY-PASS
The appliance has a built-in automatic by-pass, consequently there is no requirement for an exter­nal by-pass, however the design of the system should be such that it prevents boiler ‘cycling’.
3.6.3 DRAIN COCKS
These must be located in accessible positions to facilitate draining of the appliance and all water pipes connected to the appliance. The drain cocks must be manufactured in accordance with BS
2879.
3.6.4 AIR RELEASE POINTS
These must be positioned at the highest points in the system where air is likely to be trapped. They should be used to expel trapped air and allow complete filling of the system.
3.6.5 EXPANSION VESSEL
The appliance has an integral expansion vessel to accommodate the increased volume of water when the system is heated. It can accept up to 6 litres (12-15-20HE), 8 (25HE) and 10 litres (30­35HE) of expansion from within the system, gen­erally this is sufficient, however if the system has an unusually high water content, it may be neces­sary to provide additional expansion capacity (see
6.19).
3.6.6 FILLING POINT
A method for initial filling of the system and re­placing water lost during servicing etc. is required (see fig. 5). This method of filling must comply with the current Water Supply (Water Fittings) Regulations 1999 and W ater Bylaws 2000 (Scot­land).
control
valve
temporary
connection
control
valve
Make-up vessel or tank
Automatic air-vent
Non-return
valve
Fig. 5A
Stopcock
5.0 metres minimum
Heating return
3.6.8 FREQUENT FILLING
Frequent filling or venting of the system may be indicative of a leak. Care should be taken during the installation of the appliance to ensure all aspects of the system are capable of withstanding pressures up to at least 3 bar.
3.7 ELECTRICAL SUPPLY
The appliance is supplied for operation on 230V @ 50Hz electrical supply; it must be protected with a 3-amp fuse. The method of connection to the mains electricity supply must allow for complete isolation from the supply. The preferred method is by using a double-pole switch with a contact separation of at least 3,5mm (3° high-voltage category). The switch must only supply the appli­ance and its corresponding controls, i.e. time clock, room thermostat, etc. Alternatively an un­switched shuttered socket with a fused 3-pin plug both complying with BS 1363 is acceptable.
3.8 MOUNTING ON A COMBUSTIBLE SURFACE If the appliance is to be fitted on a wall of combus­tible material, a sheet of fireproof material must protect the wall.
3.9 TIMBER FRAMED BUILDINGS
flow/return
pipe
Fig. 5
3.6.7 LOW PRESSURE SEALED SYSTEM
double
check valve
supply
pipe
3.10 INHIBITORS
An alternative method of filling the system would be from an independent make-up vessel or tank mounted in a position at least 1 metre above the highest point in the system and at least 5 metres above the boiler (see fig. 5A). The cold feed from the make-up vessel or tank must be fitted with an approved non-return valve and stopcock for isolation purposes. The feed pipe should be connected to the return pipe as close to the boiler as possible.
If the appliance is to be fitted in a timber framed building, it should be fitted in accordance with the Institute of Gas Engineers publication (IGE/UP/7) ‘Guide for Gas Installations in Timber Frame Buildings’.
V okera recommend that an inhibitor - suitab le for use with copper and aluminium heat exchangers
- is used to protect the boiler and system from the effects of corrosion and/or electrolytic action. The inhibitor must be administered in strict ac­cordance with the manufacturers instructions*.
*Water treatment of the complete heating system
- including the boiler - should be carried out in accordance with BS 7593 and the Domestic Water Treatment Association’s (DWTA) code of prac­tice.
7
Supplied By www.heating spares.co Tel. 0161 620 6677
SECTION 3A GENERAL REQUIREMENTS (EIRE)
This appliance must be installed by a competent person in accordance with and defined by, the Standard Specification (Domestic Gas Installa­tions) Declaration (I.S. 813).
3A.1 RELATED DOCUMENTS
The installation of this boiler must be in accord­ance with the relevant requirements of the local building regulations, the current ETCI National Rules for Electrical Installations and the bylaws of the local water undertaking. It should be in accordance also with any relevant requirements of the local and/or district authority .
3A.2 LOCATION OF APPLIANCE
The appliance may be installed in any room or internal space, although particular attention is drawn to the requirements of the current ETCI National Rules for Electrical Installations, and I.S. 813, Annex K. When an appliance is installed in a room or internal space containing a bath or shower, the appliance or any control pertaining to it must not be within reach of a person using the bath or shower. The location chosen for the appliance must permit the provision of a safe and satisfactory flue and termination. The location must also permit an adequate air supply for combustion purposes and an adequate space for servicing and air circulation around the appliance. Where the installation of the appliance will be in an unusual location special procedures may be necessary, refer to I.S. 813 for detailed guidance on this aspect. A compartment used to enclose the appliance must be designed and constructed specifically for this purpose. An existing compartment/cupboard may be utilised provided that it is modified to suit.
This appliance is not suitable for external installa­tion.
3A.3 GAS SUPPLY
The gas meter – as supplied by the gas supplier – must be checked to ensure that it is of adequate size to deal with the maximum rated input of all the appliances that it serves. Installation pipes must be fitted in accordance with I.S. 813. Pipe work from the meter to the appliance must be of adequate size. Pipes of a smaller size than the appliance gas inlet connection must not be used. The installation must be tested for sound­ness in accordance with I.S. 813. If the gas supply serves more than one appliance, it must be ensured that an adequate supply is maintained to each appliance when they are in use at the same time.
3A.4 FLUE SYSTEM
The terminal should be located where the disper­sal of combustion products is not impeded and with due regard for the damage and discoloration that may occur to building products located nearby. The terminal must not be located in a place where it is likely to cause a nuisance (see I.S. 813).
In cold and/or humid weather, water vapour will condense on leaving the terminal; the effect of such pluming must be considered. If installed less than 2m above a pavement or platform to which people have access (including balconies or flat roofs) the terminal must be protected by a guard of durable material. The guard must be fitted centrally over the terminal. Refer to I.S. 813, when the terminal is 0.5 metres (or less) below plastic guttering or 1 metre (or less) below painted eaves.
3A.5 AIR SUPPLY
The following notes are intended for general guid­ance only. This appliance is a room-sealed, fan-flued boiler, consequently it does not require a permanent air vent for combustion air supply. When installed in a cupboard or compartment, ventilation for cooling purposes is also not re­quired.
3A.6 WATER CIRCULATION
Specific recommendations are given in I.S. 813. The following notes are for general guidance only.
3A.6.1 PIPEWORK
It is recommended that copper tubing be used in conjunction with soldered capillary joints. Where possible pipes should have a gradient to ensure air is carried naturally to air release points and that water flows naturally to drain cocks. Except where providing useful heat, pipes should be insulated to avoid heat loss and in particular to avoid the possibility of freezing. Particular atten­tion should be paid to pipes passing through ventilated areas such as under floors, loft space, and void areas.
3A.6.2AUTOMATIC BY-PASS
The appliance has a built-in automatic by-pass, consequently there is no requirement for an exter­nal by-pass, however the design of the system should be such that it prevents boiler ‘cycling’.
3A.6.3 DRAIN COCKS
These must be located in accessible positions to facilitate draining of the appliance and all water pipes connected to the appliance.
3A.6.4 AIR RELEASE POINTS
These must be positioned at the highest points in the system where air is likely to be trapped. They should be used to expel trapped air and allow complete filling of the system.
3A.6.5 EXPANSION VESSEL
The appliance has an integral expansion vessel to accommodate the increased volume of water when the system is heated. It can accept up to 6 litres (12-15-20HE), 8 (25HE) and 10 litres (30­35HE) of expansion from within the system, gen­erally this is sufficient, however if the system has an unusually high water content, it may be neces­sary to provide additional expansion capacity (see
6.19).
8
Supplied By www.heating spares.co Tel. 0161 620 6677
3A.6.6 FILLING POINT
A method for initial filling of the system and replacing water lost during servicing etc. is required. You should ensure this method of filling complies with the local water authority regulations.
3A.6.7 LOW PRESSURE SEALED SYSTEM
An alternative method of filling the system would be from an independent make-up vessel or tank mounted in a position at least 1 metre above the highest point in the system and at least 5 metres above the boiler (see fig. 5). The cold feed from the make-up vessel or tank must be fitted with an approved non-return valve and stopcock for isolation purposes. The feed pipe should be connected to the return pipe as close to the boiler as possible.
3A.6.8 FREQUENT FILLING
Frequent filling or venting of the system may be indicative of a leak. Care should be taken during the installation of the appliance to ensure all aspects of the system are capable of withstanding pressures up to at least 3 bar.
3A.7 ELECTRICAL SUPPLY
The appliance is supplied for operation on 230V @ 50Hz electrical supply; it must be protected with a 3-amp fuse. The method of connection to the mains electricity supply must allow for complete isolation from the supply. The preferred method is by using a double-pole switch with a contact separation of at least 3,5mm (3° high-voltage category). The switch must only supply the appli­ance and its corresponding controls, i.e. time clock, room thermostat, etc.
3A.8 MOUNTING ON A COMBUSTIBLE SURFACE
If the appliance is to be fitted on a wall of combus­tible material, a sheet of fireproof material must protect the wall.
Mynute
12-15-20 HE
Mynute
25-30-35 HE
3A.9 TIMBER FRAMED BUILDINGS
If the appliance is to be fitted in a timber framed building, it should be fitted in accordance with I.S. 813 and local Building Regulations. The Institute of Gas Engineers publication (IGE/ UP/7) ‘Guide for Gas Installations in Timber Frame Buildings’ gives specific advice on this type of installation.
3A.10 INHIBITORS
V okera recommend that an inhibitor - suitab le for use with aluminium heat exchangers - is used to protect the boiler and system from the effects of corrosion and/or electrolytic action. The inhibitor must be administered in strict accordance with the manufacturers instructions*.
*Water treatment of the complete heating system ­including the boiler - should be carried out in accord­ance with I.S. 813 and the Domestic Water Treat­ment Association’s (DWTA) code of practice.
3A.11 DECLARA TION OF CONFORMITY
A Declaration of Conformity (as defined in I.S. 813) must be provided on completion of the installation. A copy of the declaration must be given to the responsible person and also to the gas supplier if required.
Fig. 6
9
Supplied By www.heating spares.co Tel. 0161 620 6677
SECTION 4 INSTALLATION
4.1 DELIVERY
Due to the weight of the appliance it may be necessary for two people to lift and attach the appliance to its mounting. The appliance is con­tained within a heavy-duty cardboard carton. Lay the carton on the floor with the writing the correct way up.
4.2 CONTENTS
Contained within the carton is:
the boiler
the wall bracket
template
an accessories pack containing appliance serv-
ice connections and washers
the instruction pack containing the installation & servicing instructions, user instructions, guar­antee registration card, and a 3-amp fuse.
4.3 UNPACKING
At the top of the carton pull both sides open – do not use a knife – unfold the rest of the carton from around the appliance, carefully remove all protec­tive packaging from the appliance, and lay the accessories etc. to one side. Protective gloves should be used to lift the appliance, the appliance back-frame should be used for lifting points.
4.4 PREPARATION FOR MOUNTING THE APPLI­ANCE
The appliance should be mounted on a smooth, vertical, non-combustible surface, which must be capable of supporting the full weight of the appli­ance. Care should be exercised when determining the position of the appliance with respect to hidden obstructions such as pipes, cables, etc. When the position of the appliance has been decided – using the template supplied – carefully mark the position of the wall- mounting bracket (see fig. 6) and flue-hole (if applicable).
Reduction for additional bends
Bend Reduction in maximum flue length for each bend 45° bend
90° bend
Horizontal flue terminals and accessories
Part No. 520
521 522 523 524 525 526 527 528 529
0.5 metre
1.0 metre
Description Horizontal flue kit
Telescopic flue kit Plume management kit 90-degree bend 45-degree bends (pair) 500mm extension 1000mm extension 2000m extension Telescopic extension Wall bracket pack (5)
Length 900 mm
350 /530 mm 1370 mm N/A N/A 500mm 1000 mm 2000 mm 350 /730 mm 208mm
Using the template provided, mark and drill a 115mm hole for the passage of the flue pipe. The hole should be drilled to ensure any condense fluid that forms, is allowed to drain back to the appliance (see fig. 7A). The fixing holes for the wall-mounting bracket should now be drilled and plugged, an appropriate type and quantity of fixing should be used to ensure that the bracket is mounted securely. Once the bracket has been secured to the wall, mount the appliance onto the bracket.
4.5 FITTING THE FLUE
The top flue outlet permits both horizontal and vertical flue applications to be considered, alterna­tively, the Vokera twin flue system can be utilised if longer flue runs are required.
4.5.1 CONCENTRIC HORIZONT AL FLUE
(For concentric vertical flue, see 4.5.2) (For twin flue applications, see 4.5.3) The appliance can be used with either the Vokera condensing 60/100mm concentric flue system or the optional 80/125mm concentric flue system.
NOTE
These instructions relate only to the Vokera condensing 60/100mm concentric flue system. For specific details on the installation of the 80/ 125mm concentric flue system please refer to the instructions supplied.
The appliance flue outlet elbow can be rotated through 360º on its vertical axis. In addition the flue may be extended from the outlet elbow in the horizontal plane (see 2.8). A reduction must also be made to the maximum length (see table below) when additional bends are used.
Fig. 7
10
Supplied By www.heating spares.co Tel. 0161 620 6677
FITTING THE HORIZONT AL FLUE KIT
Carefully measure the distance from the centre of the appliance flue outlet to the edge of the finished outside wall (dimension X). Add 65mm to dimension X to give you Dimension Y (see fig 7A). Measure dimension Y from the terminal end of the concentric flue pipe and cut off the excess ensuring any burrs are removed. Pass the concentric flue pipe through the previously drilled hole. Fit the flue bend to the boiler flue outlet and insert the concentric flue pipe into the flue bend ensuring the correct seal is made. Using the clamp, gasket, and screws supplied, secure the flue bend to the appliance flue spigot.
NOTE
Fit the internal (white) trim to the flue assembly prior to connecting the flue pipe to the bend. You must ensure that the entire flue system is properly supported and connected. Seal the flue assembly to the wall using cement or a suitable alternative that will provide satisfactory weatherproofing. The exterior trim can now be fitted.
4.5.1.1 EXTENDING THE FLUE
Connect the bend – supplied with the terminal kit – to the top of the boiler using clamp (supplied) see fig. 7. The additional bends & extensions hav e push-fit connections, care should be taken to ensure that the correct seal is made when assembling the flue system. Connect the required number of flue extensions or bends (up to the maximum equivalent flue length) to the flue terminal (see fig. 7 & 8). The flue system should have a minimum of 1º; maximum of 3° rise from the boiler to outside, to ensure any condense fluid that forms, is allowed to drain back to the appliance.
NOTE
When cutting an extension to the required length, you must ensure that the excess is cut from the plain end of the extension (see fig. 7 & 8). Remove any burrs, and check that all seals are located properly. You must ensure that the entire flue system is properly supported and connected.
Seal the flue assembly to the wall using cement or a suitable alternative that will provide satisfactory weatherproofing. The interior and exterior trim can now be fitted.
“X”
30mm
“X” + 65mm = “Y”
Fig. 7A
“Y”
1-3 degree
4.5.2 CONCENTRIC VERTICAL FLUE
The appliance can be used with either the V ok era condensing 60/100mm concentric flue system or the optional 80/125mm concentric flue system.
NOTE
These instructions relate only to the Vokera condensing 60/100mm concentric flue system. For specific details on the installation of the 80/ 125mm concentric flue system please refer to the instructions supplied. The vertical flue terminal can be connected directly to the appliance flue outlet. Alternatively, an extension or bend can be connected to the appliance flue outlet if desired (see 4.4.2), however if additional bends are fitted, a reduction must be made to the maximum flue length (see table in the next page).
Fig. 8
11
Supplied By www.heating spares.co Tel. 0161 620 6677
Reduction for bends
Bend 45° bend
90° bend
Ve rtical flue terminal and accessories
Part No.
530 531 532 523 524 525 526 527 528 529
Reduction in maximum flue length for each bend
0.5 metre
1.0 metre
Description
V ertical flue terminal Pitched roof flashing plate Flat roof flashing plate 90-degree bend 45-degree bends (pair) 500mm extension 1000mm extension 2000mm extension T elescopic e xtension Wall brac ket pack (5)
Using the dimensions given in fig. 9 as a reference, mark and cut a 115mm hole in the ceiling and/or roof.
“X”
12/15/20HE = 202mm 25/30/35HE = 218mm
“X”
Fig. 9
Fit the appropriate flashing plate to the roof and insert the vertical flue terminal through the flashing plate from the outside, ensuring that the collar on the flue terminal fits over the flashing. The fixing holes for the wall-mounting bracket should now be drilled and plugged, an appropriate type and quantity of fixing should be used to ensure that the bracket is mounted securely. Once the bracket has been secured to the wall, mount the appliance onto the bracket.
IMPORTANT
The vertical flue terminal is 1.0 metre in length and cannot be cut; therefore it may be necessary to adjust the height of the appliance to suit or use a suitable extension.
Min-Max length 1000 mm
N/A N/A N/A N/A 500mm 1000 mm 2000 mm 350/730mm 208mm
Connect the vertical flue assembly to the boiler flue spigot using the 100mm clip, gasket, & screws (supplied), ensuring the correct seal is made. The flue support bracket (supplied with the vertical flue kit) can now be fitted. If the vertical flue requires extension/s or additional bend/s, connect the required number of flue extensions or bends (up to the maximum equivalent flue length) between the boiler and vertical flue assembly (see fig. 8). Ensure that any horizontal sections of the flue system have a minimum 1º; maximum 3º fall back to the boiler (1º = 17mm per 1000mm)
NOTE
When cutting an extension to the required length, you must ensure that the excess is cut from the plain end of the extension (see fig. 8). Remove any burrs, and check that any seals are located properly. You must ensure that the entire flue system is properly supported and connected.
4.5.3 TWIN FLUE SYSTEM
The Voker a twin flue system enables greater flue distances to be achieved (see 4.4.2) than that of a concentric flue system. It can be used for horizontal or vertical applications, howev er the twin flue system must be converted to the dedicated concentric flue kit for termination. It is essential that the installation of the twin flue system be carried out in strict accordance with these instructions.
GUIDANCE NOTES ON TWIN FLUE INSTALLA TION
The flue must have a minimum 1º; maximum 3º (1º = 17mm per 1000mm) fall back to the appliance to allow any condensate that may form in the flue system to drain via the condensate drain. Consideration must also be given to the fact that there is the possibility of a small amount of condensate dripping from the terminal.
Ensure that the entire flue system is adequately supported, use at least one bracket for each extension.
The entire flue system must be adequately insulated to maintain heat within the flue system thereby reducing the possibility of condensate production.
As the exhaust outlet pipe can reach very high temperatures it must be protected to prevent persons touching the hot surface.
The condensate drain pipe must be connected in accordance with building regulations
Reduction for bends
Bend 45° bend 90° bend
Reduction in maximum flue length for each bend
1.0 metre
1.0 metre
12
Loading...
+ 30 hidden pages