Vokera Linea Plus AG User guide

Plus AG
Installation & Servicing Instructions
British Gas Service Listed G.C. No. 47 094 27 (Linea 24) G.C. No. 47 094 28 (Linea 28)
G.C. No. 47 094 29 (Linea Plus)
THESE INSTRUCTIONS TO BE RETAINED BY USER
CONTENTS Section Subject Page no
Section 1 Introduction 1
General Layout 1
Section Subject Page no
Concluding Operations 20
Section 7 Instructing The User 20
Section 2 Design Principles & Operating
Sequence 2
Schematic Diagram 2 Central Heating Mode 2 Domestic Hot Water Mode 2 Safety Devices 2 Frost Thermosat 2
Section 3 Technical Data 3
Dimensions & Contents 3 Connection Sizes 3 Installation Requirements 3 Electrical Details 3 Performance & Limitations 3 Working Pressure (H/W & C/H) 3 Flow Rates 3 Central Heating Pump Duty 4
Section 4 General Requirements 5
Related Documents 5 Location of Appliance 5 Gas Supply 5 Flue System 5 Air Supply 6 Water Circulation (C/H) 6 Pipework 6 By-Pass 6 System Design 6 Filling Point 8 Electrical Supply 8 Showers 8
Section 5 Installation 9
Delivery 9 Unpacking 9 Preparing For Mounting 9 Mounting The Appliance 10 Fitting The Flue Horizontal - Vertical Twin 10-11 Connecting Gas & Water Supplies 15 Electrical connections 15
Section 6 Commissioning 17
Gas Installation 17 Initial Flushing of Pipework 17 Initial Filling of System 17 System Design Pressure 17 Checking Electrical supply 17 Lighting The Boiler 17 Checking Burner Pressures 18 Range Rating C/H 19 Checking The Flue System 19 Checking The Heating Thermistor 19 Regulating The C/H System 19 Final Flushing The C/H System 19 Filling & Testing H/W System 19 Final Checks For Operation 20
Section 8 Servicing Instructions 21
General 21 Recommended Routine Servicing 21 Replacement Of Parts 21 To Gain General Access 22
To Remove:
Room Sealed Chamber Front Cover22 Main Burner & Electrode 23 Main Burner Injectors 23 Main Heat Exchanger 23 Fan 24 DAPS Combustion Chamber Insulation Panel Ignition PCB 25 Gas Control Valve 25 Pump 26 Domestic Flow Switch 26 Diverter Domestic Heat Exchanger 27 Diverter Valve 27 Main Expansion Vessel 27 Safety Valve 28 Pressure Switch 28 Motorised Valve 29 Printed Circuit Board 29 Display Printed Circuit Board 29 Safety Thermostat 29 Thermistor Sensors 29 Pressure Gauge 30 Setting Gas Pressures 31
Section 9 Operational Checks & Wiring 32
Sequence of Functions 32 Diagnostic Error Codes 33 Fault Finding Guides 34-43
Section 10Appendix 44
Internal Time Clock Installation 44 External Time Clock Installation 46 S & Y Plan Installations 47 Exploded Diagrams 48-52 Abling & Disabling Controls 53 Functional Flow Diagram 54 Illustrated Wiring Diagram 55 Preliminary Electrical System Checks56 LPG Instructions 57-58
Valve 26
24 24
SECTION 1 INTRODUCTION
The Vokèra Linea Plus is a combined central heating and domestic hot water appliance. By design it incorporates full sequence electronic ignition, circulating pump, expansion vessel, safety valve, temperature gauge, pressure gauge and 3 port diverter valve. The Plus also benefits from an air/gas modulation system and has low NOx emissions.
The boiler is produced as a room sealed appliance suitable for wall mounting applica­tions only. It is provided with a fan powered flue outlet with an annular co-axial combustion air intake which can be rotated through 360 degrees. A vertical & twin flue option is avail­able.
The appliance is designed for use with a sealed heating system only and is not intended for use on an open vented system.
The provision of stored domestic hot water is possible by the addition of an indirect cylinder with 'S' or 'Y' plan controls.
An automatic range-rating facility is incorpo­rated in the boiler for the central heating sys­tem in conjunction with the electronic burner modulation. The domestic hot water (dhw) service utilises a motorised control combined with a 3 port diverter valve to give hot water priority which also benefits from a preheat function.
Fig.1 General Layout
1 Flue Outlet 2 Air Intake 3 Differential analog Pressure Switch (DAPS) 4 Silicone Pressure Tube 5 Silicone Negative Pressure Tube 6 Expansion Vessel 7 Main Heat Exchanger 8 Electrode 9 Burner Temperature control 9a Transformer 10 Gas Valve 11 Modulator Coil 12 Domestic Heat Exchanger 13 Domestic Hot Water Flow Switch 14 Safety Valve 15 Pressure Switch 16 Diverter Valve Motor 17 Pump 18 Automatic Air Release Valve 19 Main Burner 20 Combustion Chamber 21 Fan Assembly 22 Air Chamber (with front removed) 23 Flue Gas Analysis Test Point 24 Hot Water Temperature Control 25 Mode Selector Switch 26 Status LED 27 Temperature Indicator 28 Central Heating Temperature Control 29 Combustion Switch 30 Timeclock Aperture (optional) 31 Pressure Gauge
Linea Plus AG
1
SECTION 2 DESIGN PRINCIPLES AND OPERATING SEQUENCE
2.1 Fig.1 illustrates the general layout of compo-
nents. Fig.2 illustrates the operating principles described below.
2.2 Central Heating Mode
2.2.1 When the various switches and controls im-
pose a demand for heat, the pump is started. If the primary pressure is sufficient, the electronic circuitry is energised. The fan is started, the gas valve is energised at an inter­mediate rate and the electronic ignition goes through an ignition attempt.
2.2.2 The burner ignition is checked by the electronic circuitry to ensure correct ignition of the burner; once successful the gas will flow at 75% of maximum heat input for a period of approximately 15 minutes and then go to maxi­mum heat input to maximise heating perform­ance, unless the boiler nears optimum temperature where it will modulate down to suit system load.
2.2.3 As water temperature increases this is sensed by the temperature sensor on the flow pipe which modulates the fan and burner to match the heat output to the heat requirement of the system.
2.2.4 Depending on the load, either a) The water temperature will continue to rise and the fan and burner will continue to modulate down; The burner will switch off at maximum tem­perature, or b) the water temperature will fall; the fan and burner
Air Intake
Flue Outlet
3
6
NOTE
Fig. 2
18
17
16
15
A
BCD
7
19
10
12
13
will return to a higher output to match de­mand.
2.3 Domestic Hot Water Mode
2.3.1 The appliance incorporates a hot water
preheat facility. The appliance will therefore ignite periodically to maintain heat within the appliance.
2.3.2 The appliance will operate in domestic hot water mode whenever the mode selector switch is on regardless of mode selector switch position and any demand for central heating.
2.3.3 The diverter valve will automatically energise into the hot water position after central heat­ing demand, or will stay in the hot water position after hot water demand. Opening a draw off tap will energise the pump and fan sending primary water to the domestic hot water heat exchanger.
2.3.4 Temperature control is transferred to the do­mestic hot water thermostat (potentiometer) which modulates the fan and burner output between high and low flame to maintain an average heat input to suit the dhw output required.
2.3.5 An overrun is incorporated in the boiler in both c/h & dhw modes. The fan overruns until the boiler water cools to approximately 80°C (176°F).
2.4 Safety Devices
2.4.1 In both central heating and hot water modes
safe operating is ensured by: A. Differential pressure unit in the primary
circuit which prevents burner operation if water pressure is too low.
B. An electronic device that checks the pri­mary pressure unit for activation. Failure re­sults in deactivation of the pump, after ap­proximately 10 minutes of operation.
C. A safety thermostat, which interrupts the control circuit shutting off the gas valve. At the same time the fan will still operate.
D. A DAPS in the flue system to check the fan's operation before allowing ignition.
2.4.2 A safety valve is provided to relieve excess pressure from the primary circuit.
2.4.3 Frost Thermostat
The appliance has a built in frost protection circuit. Should the boiler temperature sensed at the primary thermistor fall below 5°C, the boiler will operate in central heating mode and continue to operate until the primary thermistor reaches approximately 40°C.
KEY: A Central Heating Return. B Central Heating Flow. C Hot Water Outlet. D Cold Water Inlet.
2
NOTE: Pressure switch.
Senses water pressure in the primary circuit and operates the pressure switch (15)
Linea Plus AG
SECTION 3 TECHNICAL DATA
3.1 Units Dimensions and values are given in the
preferred Sl Units with Imperial units in brack­ets where applicable.
3.2 Dimensions and Contents
Plus AG
Height Width Depth Weight dry Weight full
820mm (32.3) 500mm (19.7)
355mm (14.0) 48kg (105.6lb) 51kg (112.2lb)
Water content: 3 litres (.66 gals) for further dimensions see figs 12 - 16
3.3 Connection sizes
Heating flow and return: Nut and olive for 22mm o.d. Cold water inlet: Nut and olive for 15mm o.d. Hot water outlet: Nut and tail for 15mm o.d. Gas Service: Nut and tail for 15mm o.d. Safety valve outlet: 15mm comp.or cap­illary
Flue outlet/Air inlet: nom dia 60/100mm spe­cially supplied with boiler (concentric). Flue outlet/Air inlet: nom dia 80/80mm spe­cially supplied with boiler (twin).
3.4 Installation Requirements
3.4.1 Clearances (Horizontal or Vertical Flue)
Minimum - above casing 225mm (9in) Mini­mum - below casing 200mm (8in) Minimum ­In front 600mm (24in) Minimum - At sides 12mm (1/2in) from casing
3.4.2 Maximum heating system contents approx.
76.4 litres (16.8 gals). Acceptance capacity of expansion vessel 10 litres (2.2 gals).
3.4.3 Means of filling sealed system: to accord with BS and/or local Water Authority requirements.
3.4.4 The standard concentric horizontal flue allows a maximum length of duct as follows: Rear flue: 700mm (wall thickness) Side flue: 890mm (to centre line of boiler).
Using extension tubes the flue may be ex­tended to the following lengths.
Concentric
Plus AG
Horizontal Vertical
3.0m
3.0m
Concentric Flue
Reduction in flue
Bend
45° 90°
length for each bend
0.5 m
1.0 m
Twin Flue
Reduction in flue
Bend
45° 90°
length for each bend
1.0 m
1.0 m
3.5 Electrical Details
Mains supply 230v ~ 50Hz Fused 3A Internal fuse rating F2A and T100mA Power consumption:160W
3.6 Performance and Limitations Plus AG Max. input 34.9 kW (119,080 Btu/h)(net h/w) Max. inpu 38.7 kW (132.050Btu/h)(grossh/w) Max. input 34.9 kW (119.080 Btu/h)(net c/h) Max. input 38.7 kW (132.050Btu/h)(gross c/h) Min. input 9.95 kW (34.052 Btu/h)(net)(c/h) Min. input 9.95 kW (34.052 Btu/h)(net)(h/w) Min. input 11.07 kW (37.770 Btu/h)(gross)(c/h) Min. input 11.07 kW (37.770 Btu/h)(gross)(h/w)
Max. output 32.00 kW (109,200 Btu/h)(h/w) Max. output 32.00 kW (109,200 Btu/h)(c/h) Min. output 9.0 kW (30,700 Btu/h)(h/w) Min. output 9.0 kW (30,700 Btu/h)(c/h)
Central heating output range
Max. 32.0 kW (109,200 Btu/h) Min. 9.0 kW (30,700 Btu/h)
Nominal hot water production
Temp. rise of 30°C 15.3l/min. Temp. rise of 35°C 13.1l/min.
Gas Pressures
Max. gas pressure 10.1 mbar h/w Min. gas pressure 1.1 mbar h/w
Gas Rate
Max. 3.69m3/h 138.8 ft3/h (h/w) Min. 1.05 m3/h 35.6 ft3/h (h/w) Note: Use gross input values when gas rating the appliance
Twin (+ concentric terminal)
Horizontal Vertical
The reduction in flue length for each bend used is listed opposite.
Linea Plus AG
Plus AG
14/14m 14/14m
Burner Details Main burner:
Polidoro type Main burner injectors 16 x 1.35
3.7 Working Pressure Heating System
Maximum 1.5bar/15m w.g./50ft w.g. Minimum 0.15bar/1.5m w.g./5ft w.g. Safety valve setting 3bar/30m/102ft w.g.
3.8 Flow Rates Min. waterflow (dhw) 2.0l/min. (0.45 gal/min) Min central heating flow rate through appliance 350litres/hr (1.28 gal/min)
3
3.9 Working Pressure Hot Water System
Maximum 6.0 bar/90psig Minimum 0.6 bar/ 7psig
For LPG instructions see page 62.
3.10 Central Heating Pump Duty
Fig.3 indicates the flow rate available plotted against system pressure drop.
N.B. When using this graph apply only the pressure drop of the system. The curve has been modified to allow for the pressure drop through the appliance.
Fig. 3
4
Linea Plus AG
SECTION 4 GENERAL REQUIREMENTS
4.0 General Requirements
This appliance must be installed by a compe­tent person in accordance with the Gas Safety (Installation & Use) Regulations 1998.
4.1 Related Documents
The installation of this boiler must be in ac­cordance with the relevant requirements of the Gas Safety (Installation & Use) Regula­tions 1998 the Local Building Regulations, the current l.E.E. Wiring Regulations, the by-laws of the local water undertaking, and in Scot­land, in accordance with the Building Stand­ards (Scotland) Regulation. In Ireland the lo­cal building regulations (IE).
It should be in accordance also with any rel­evant requirements of the local authority and the relevant recommendations of the follow­ing British Standard Codes of Practice:
BS 6891 1988 Low pressure installation pipes. BS 6798 1987 Boilers of rated input not exceeding 60kW. BS 5449 Part 1 1990 Forced circulation hot water systems BS 5546 1990 Installation of gas hot water supplies for domestic
BS 5440 Part 1 1990 Flues. BS 5440 Part 2 1989 Flues & Ventilation. BS 7074 Part 1 1989 Application, selection & installation of expansion
A compartment used to enclose the boiler must be designed and constructed specifi­cally for this purpose. An existing cupboard or compartment may be used provided that it is modified for this purpose.
Details of essential features of cupboard/ com­partment design including airing cupboard in­stallations are given in BS 6798:1987. This appliance is not suitable for external installa­tion.
4.3 Gas Supply
A gas meter is connected to the service pipe by the gas supplier.
An existing meter should be checked, prefer­ably by the gas supplier, to ensure that the meter is adequate to deal with the rate of gas supply required for all appliances it serves.
purposes (2nd family gases).
vessels & ancillary equipment for sealed water systems.
4.2 Location of Appliance
The combination boiler may be installed in any room or internal space, although particular attention is drawn to the requirements of the current l.E.E. Wiring Regulations, and in Scot­land, the electrical provisions of the Building Regulations applicable in Scotland, with re­spect to the installation of the combination boiler in a room or internal space containing a bath or shower.
Where a room-sealed appliance is installed in a room containing a bath or shower, any electrical switch or appliance control, utilising mains electricity, should be located in such a position that it cannot be touched by a person using the bath or shower.
The location chosen for the boiler must permit the provision of a satisfactory flue and termi­nation. The location must also permit an ad­equate air supply for combustion purposes and an adequate space for servicing and air circulation around the boiler.
Where the installation of the boiler will be in an unusual location special procedures may be necessary and BS 6798:1987 gives detailed guidance on this aspect.
Installation pipes should be fitted in accord­ance with BS 6891:1988.
Pipework from the meter to the boiler must be of adequate size. Pipes of a smaller size than the boiler inlet connection should not be used.
The complete installation must be tested for soundness as described in the above code.
N.B. If the gas supply for the boiler serves other appliances ensure that an adequate supply is available both to the boiler and the other appliance when they are in use at the same time.
4.4 Flue System
The terminal should be located where disper­sal of combustion products is not impeded and with due regard for the damage or discolora­tion that might occur to building products in the vicinity (see fig 4).
The terminal must not be located in a place where it is likely to cause a nuisance.
In cold and/or humid weather water vapour may condense on leaving the flue terminal. The effect of such ‘steaming’ must be consid­ered.
Linea Plus AG
5
For protection of combustibles, refer to BS 5440:1 where the terminal is less than 2m (6.6ft) above a pavement or platform to which people have access (including any balcony or flat roof the terminal must be protected by a guard of durable material).
A suitable guard is available from Vokera Ltd. Part No 018, G.C. No. 301 106
This guard must be fitted centrally over the terminal. Mark the positions of the fixings, drill the wall and secure using wall plugs and 3 of 1˚" No.8 plated screws.
Fig. 4
Terminal position for fan assisted boiler
(minimum distance) mm A - Directly below an open window or other 300
opening (e.g. air brick) B - Below gutters, soil pipes or drain pipes 25 C - Below eaves 25 D - Below balconies or car port roof 25 E - From vertical drain pipes and soil pipes 75 F - From internal or external corners 25 G - Above ground or below balcony level 300 H - From a surface facing a terminal 600 I - From a terminal facing a terminal 1200 J - From an opening in the car port (e.g. door
window) into dwelling. 1200 K - Vertically from a terminal on the same wall 1500 L - Horizontally from a terminal on the same wall 300 M - Horizontally from a vertical terminal to a wall 300
N - Horizontally from an opening, airbrick, openable
window, etc. 300
4.6 Water Circulation (Central Heating)
Detailed recommendations are given in S6798: 1987 and BS 5449: 1: 1990 (for smallbore and microbore central heating systems).
4.6.1 The following notes are given for general guidance.
4.6.2 Pipework
Copper tubing to BS 2871:1:1971 is recom­mended for water pipe. Jointing should be either by capillary soldered or with compres­sion fittings.
Where possible, pipes should have a gradient to ensure air is carried naturally to air release points and water flows naturally to drain taps.
It should be ensured as far as possible that the appliance heat exchanger is not a natural collecting point for air.
Except where providing useful heat, pipes should be insulated to prevent heat loss and to avoid freezing. Particular attention should be paid to pipes passing through ventilated spaces in roofs and under floors.
4.6.3 By-Pass
An automatic by-pass is incorporated in the boiler, but systems should be designed to ensure that with all radiators turned off a flow rate of at least 350 litres/hour (1.28 gals/min) is achieved through the system. See 6.9.4.
4.6.4 System Design
Figs 5 & 5a illustrates typical system layouts showing options of either, pipe connection from below as fig. 5, or pipe connection from above utilising the purpose made duct in the rear frame of the appliance.
4.6.5 Draining Taps
These must be located in accessible positions to permit the draining of the whole system. The taps must be at least 15mm nominal size and manufactured in accordance with BS 2879:
1980.
NOTE: The flue must be terminated in a place not likely
to cause a nuisance.
4.5 Air Supply
The following notes are intended for general guidance.
The room sealed fan flued boiler does not require a permanent air vent for combustion air supply.
Where installed in a cupboard or compartment ventilation is not required.
6
Linea Plus AG
Fig. 5
Fig. 5a
N.B. Vokèra Ltd recommend a 2-pipe system. Single pipe systems are more liable to be troublesome unless
carefullly designed and installed.
Linea Plus AG
7
4.6.6 Air Release Points
These must be fitted at all high points where air will naturally collect, and must be sited to facilitate complete filling of the system.
4.6.7 The appliance has an integral sealed expan­sion vessel to accommodate the increase of water volume when the system is heated. It can accept up to 10 litres of expansion water. If the appliance is connected to a system with an unusually high water content. Calculate the total expansion and add additional sealed expansion capacity as appropriate.
In general, modern systems will present no problem.
4.6.8 Filling Point
A method for filling the system and replacing water lost during servicing is provided on the appliance.
This method complies with the Water Supply (Water Fittings) Regulations 1999.
4.7 Electrical Supply
The appliance is supplied for operation on 230V ~ 50Hz electricity supply. It should be protected with a 3-amp fuse.
THIS APPLIANCE MUST BE EARTHED. The method of connection to the mains elec-
tricity must allow complete isolation from the supply.
The preferred method is by using a fused double pole switch with a contact separation of at least 3mm.
The switch must supply ONLY the appliance and immediate electrical control circuits (e.g. programmer / room thermostat)
Alternatively, use an unswitched shuttered socket outlet with a fused 3-pin plug both complying with BS 1363.
4.8 Showers
If a shower control is to be supplied from the combination unit it should be of the type which incorporates a thermostatic control and by design is suitable for use with a combination boiler. Check application with shower manu­facturer.
C/H Flow
Valve
C/H Return
Valve
Safety valve
outlet
Filling Loop
Cold water
Inlet Stopcock/
filling valve
Gas
Cock
Hot water
Outlet
Fig.6
Fig. 7
8
Linea Plus AG
SECTION 5 INSTALLATION
Fig. 8
Fig. 9
5.1 Delivery (fig. 8)
The appliance is delivered in a heavy duty cardboard carton.
Lay the carton on the floor with the writing the correct way up.
5.2 Unpacking (fig. 9) Pull both sides of the top of the carton open.
Do not use a knife. Remove the hanging bracket, literature pack and fittings pack, from the packaging. Remove the package sup­ports.
Lift the appliance from the carton and lay the appliance down with the white frame on the floor.
Remove the protective bag, and the polystyrene support from the back of the appliance.
Do not remove the insulation jacket on the domestic heat exchanger.
The fittings pack contains
Wiring harness for optional built in timer 15mm nut & olive Adjustable stopcock Safety valve outlet pipe (1) Filling loop hose (1) Various washers Flue kit supplied in separate carton.
5.3 Preparing for Mounting
5.3.1 Push to release front door panel and lower to
reveal controls. Loosen the 2 captive screws securing the front control panel to the lower part of the casing and lower to reveal inside of boiler (fig. 10).
5.3.2 Remove two screws at base of casing, slightly lift the casing and slide it gently towards the top of the appliance to disengage the case from the top suspension hooks (fig. 11).
5.3.3 Ensure the casing and screws are put to one side in a safe place.
Fig. 10
Linea Plus AG
Case Screws
Fig. 11
Case screws
(one either side)
9
5.4 Mounting the appliance
The appliance should be mounted on a smooth, vertical surface, which must be capable of supporting the full weight of the appliance. Care should be exercised when determining the position of the appliance with respect to hidden obstructions such as pipes, cables, etc.
When the position of the appliance has been decided – using the template supplied – carefully mark the position of the fixing jig/mounting bracket assembly (see fig. 7) and flue-hole (if applicable).
5.4.1 Important There are two holes on the template. The lower hole should be used with the telescopic flue kit (part no. 0225705 & 0225710). The upper hole is for use with all other horizontal flue kits.
5.4.2 Maximum flue lengths
Flue system Linea Plus AG Concentric Horizontal 3.0m
Concentric Vertical 3.0 m Twin flue 14m/14m + terminal
5.5 Fitting the flue
The top flue outlet permits both horizontal and vertical flue applications to be considered, alternatively, the Vokera twin flue system can be utilised if longer flue runs are required.
5.5.1 Concentric horizontal flue
(For concentric vertical flue, see 5.5.2) (For twin flue applications, see 5.5.3) The appliance flue outlet elbow can be rotated through 360º on its vertical axis. In addition the flue may be extended from the outlet elbow in the horizontal plane (see 5.4.2), however if the flue is to be extended or additional bends are to be fitted, the standard horizontal flue kit (part no.
2359029) must be used. A reduction must also be made to the maximum length (see table) when additional bends are used.
Horizontal flue terminals and accessories
Part No. Description Min-Max Length
0225705 Standard telescopic flue 380mm – 600mm
(Dimension ‘X’)
0225710 Extended telescopic flue 600mm – 920mm
(Dimension ‘X’)
2359029 Horizontal flue kit 833mm
For use with add. (Dimension ‘X’) Bends & extensions
2359069 750mm extension 750mm 2359079 1500mm extension 1500mm 2359049 45º bend (pair) N/A 2359059 90º bend N/A 0225760 Wall bracket (5) N/A
FITTING THE TELESCOPIC FLUE KIT (0225705 &
0225710)
Carefully measure the distance from the centre of the appliance flue outlet to the face of the outside wall (dimension ‘X’ see fig. 12). Add 50mm to dimension ‘X’ to give the overall flue length (dimension ‘Y’). Using the complete telescopic flue assembly adjust the length to suit dimension ‘Y’. Once the telescopic flue terminal has been adjusted to the correct length, secure the flue assembly with the screw supplied.
Insert the flue assembly into the previously drilled flue hole and locate the flue bend over the appliance flue outlet. Push the flue bend down over the appliance flue outlet and ensure the correct seal is made. Pull the flue assembly towards and over the flue bend – using a twisting action – ensuring the correct seal is made. Check that the terminal protrudes past the finished outside wall by the correct length (115mm).
NOTE
You must ensure that the entire flue system is properly supported and conncented.
Reduction for bends
Bend Reduction in maximum flue length
for each bend
45º bend 0.5 metre 90º bend 1.0 metre
Using the template provided (see 5.4.1), mark and drill a 125mm hole for the passage of the flue pipe. The hole should have a 1º drop from the boiler to outside, to eliminate the possibility of rainwater entering the appliance via the flue.
The fixing holes for the wall-mounting bracket & jig should now be drilled and plugged, an appropriate type and quantity of fixing should be used to ensure that the bracket is mounted securely. Once the bracket & jig has been secured to the wall, mount the appliance onto the bracket.
10
Fig. 12
Seal the flue assembly to the wall using cement or a suitable alternative that will provide satisfactory weatherproofing. The interior and exterior trim can now be fitted.
Linea Plus AG
FITTING THE STANDARD (2359029) HORIZONTAL FLUE KIT (see 5.4.1)
Carefully measure the distance from the centre of the appliance flue outlet to the face of the outside wall (dimension ‘X’ see fig. 13). Ensure the inner (60mm) pipe is fully inserted into the outer (100mm) pipe (when the inner pipe is fully inserted, it stands proud of the outer pipe by 7.5mm). Add 32mm to dimension ‘X’ to give the overall flue lenghth (dimension 'Y')standard horizontal flue kit (part no. 2359029) is suitable for a distance (dimension ‘Y’) of up to 865mm.
Fig. 13
NOTE
Dimension ‘Y’ is measured from the end of the terminal to the end of the outer (100mm) pipe. The internal trim should be fitted to the flue pipe before connection of the 90º bend.
If the horizontal flue kit (2359029) requires to be cut to the correct size (dimension ‘Y’), you must ensure that the inner (60mm) pipe stands proud of the outer (100mm) pipe by 7.5mm (see fig. 13A). Ensure any burrs are filed or removed and that any seals are located properly before assembly.
Connect the inner (60mm) pipe of the terminal assembly to the push-fit end of the 90º bend (supplied) using a twisting action. Insert the assembled flue into the previously drilled hole. Using the clips & screws supplied, connect the flue assembly to the boiler, ensuring that the terminal protrudes past the finished outside wall by the correct length (135mm).
You must ensure that the entire flue system is properly supported and connected.
EXTENDING THE HORIZONTAL FLUE
If the horizontal flue requires extension/s or additional bend/s, the horizontal flue terminal kit (2359029) must be used. Connect the bend – supplied with the terminal kit – to the top of the boiler using the clips, screws, & gaskets supplied. The additional bends & extensions have an internal push-fit connection, care should be taken to ensure that the correct seal is made when assembling the flue system. Connect the required number of flue extensions or bends (up to the maximum equivalent flue length) to the flue terminal using the clips, screws, & gaskets supplied (see fig. 13 & 13A).
NOTE
When cutting the horizontal flue terminal or an extension to the required length, you must ensure that the excess is cut from the plain end of the terminal or extension, and that the inner (60mm) pipe is 7.5mm longer than outer (100mm) pipe (see fig. 13 & 13A). Remove any burrs, and check that any seals are located properly.
You must ensure that the entire flue system is properly supported and connected.
Seal the flue assembly to the wall using cement or a suitable alternative that will provide satisfactory weatherproofing. The interior and exterior trim can now be fitted.
5.5.2 CONCENTRIC VERTICAL FLUE
The vertical flue terminal can be connected directly to the appliance flue outlet. Alternatively, an extension or bend can be connected to the appliance flue outlet if desired (see 5.4.2), however if additional bends are fitted, a reduction must be made to the maximum flue length (see table below).
Reduction for bends
Bend Reduction in maximum flue length for
each bend
45º bend 0.5 metre 90º bend 1.0 metre
Seal the flue assembly to the wall using cement or a suitable alternative that will provide satisfactory weatherproofing. The exterior trim
can now be fitted.
Linea Plus AG
Fig. 13A
Vertical flue terminal and accessories
Part No. Description Length
2359039 Vertical flue terminal 1.0 metre 0225770 Pitched roof flashing N/A
plate 0225765 Flat roof flashing plate N/A 2359069 750mm extension 750mm 2359079 1500mm extension 1500mm 2359049 45º bend (pair) N/A 2359059 90º bend N/A 0225760 Wall bracket (5) N/A
11
Using the dimensions given in fig. 14 as a reference, mark and cut a 105mm hole in the ceiling and/or roof.
Fit the appropriate flashing plate to the roof and insert the vertical flue terminal through the flashing plate from the outside, ensuring that the collar on the flue terminal fits over the flashing.
The fixing holes for the wall-mounting bracket & jig should now be drilled and plugged, an appropriate type and quantity of fixing should be used to ensure that the bracket is mounted securely. Once the bracket has been secured to the wall, mount the appliance onto the bracket & jig.
IMPORTANT
The vertical flue terminal is 1.0 metre in length and cannot be cut; therefore it may be necessary to adjust the height of the appliance to suit or use a suitable extension.
Remove or discard the flue restrictor ring from the appliance flue outlet (see fig. 1), if the total flue length – including the allowance for any additional bends – exceeds 1.0 metre.
Connect the vertical flue assembly to the boiler flue spigot using the 60mm & 100mm clips, gaskets, & screws (supplied), ensuring the correct seal is made. The flue support bracket (supplied with the vertical flue kit) can now be fitted.
If the vertical flue requires extension/s or additional bend/s, connect the required number of flue extensions or bends (up to the maximum equivalent flue length) between the boiler and vertical flue assembly (see fig. 13A).
5.5.3 TWIN FLUE SYSTEM
The Vokera twin flue system enables greater flue distances to be achieved (see 5.4.2) than that of the standard concentric flue system. It can be used for horizontal or vertical applications, however the twin flue system must be converted to the dedicated concentric flue kit for termination. It is essential that the installation of the twin flue system be carried out in strict accordance with these instructions.
GUIDANCE NOTES ON TWIN FLUE INSTALLATION
The flue must have a fall back of 1º back to the appliance to allow any condensate that may form in the flue system to drain via the condensate drain. Consideration must also be given to the fact that there is the possibility of a small amount of condensate dripping from the terminal.
Ensure that the entire flue system is adequately supported, use at least one bracket for each extension.
The entire flue system must be adequately insulated to maintain heat within the flue system thereby reducing the possibility of condensate production.
As the exhaust outlet pipe can reach very high temperatures it must be protected to prevent persons touching the hot surface.
NOTE
When cutting an extension to the required length, you must ensure that the excess is cut from the plain end of the extension and that the inner (60mm) pipe is 7.5mm longer than outer (100mm) pipe (see fig. 13A). Remove any burrs, and check that any seals are located properly.
You must ensure that the entire flue system is properly supported and connected.
Fig. 14
Reduction for bend
Bend Reduction in maximum flue length for
each bend
45º bend 1.0 metre 90º bend 1.0 metre
Twin flue accessories
Part No. Description Length
0225805 Horizontal flue terminal 1.0 metre 0225810 Vertical flue terminal 1.0 metre 300 Twin adapter kit N/A 0225770 Pitched roof flashing plate N/A 0225765 Flat roof flashing plate N/A 0225815 Condensate drain kit N/A 0225820 0.25m extension (pair) 250mm 0225825 0.5m extension (pair) 500mm 0225830 1.0m extension (pair) 1000mm 0225835 2.0m extension (pair) 2000mm 0225840 45º bend (pair) N/A 0225845 90º bend (pair) N/A 0225850 Twin bracket (5) N/A 0225855 Single bracket (5) N/A
12
Linea Plus AG
Mounting the boiler
The fixing holes for the wall-mounting bracket & jig should now be drilled and plugged, an appropriate type and quantity of fixing should be used to ensure that the bracket is mounted securely. Once the bracket has been secured to the wall, mount the appliance onto the bracket & jig.
5.5.3.1 Installation of twin adaptor kit (fig. 15)
The condensate drain kit must be fitted within 1 metre of the appliance flue outlet. It is recommended that the condensate drain kit should be fitted in the vertical plane, however it can be fitted horizontally with care.
Fit the first bend to the condensate drain kit or exhaust connection manifold by firmly pushing in to position.
Using the two holes in the exhaust connection manifold as a guide, drill a 3mm hole in each and secure using the screws provided.
Connect the air inlet pipe to the air baffle as above.
The twin flue pipes extensions and accessories can now be installed by pushing together (the plain end of each extension or bend should be pushed approximately 50mm into the female socket of the previous piece).
The condensate drain trap must be connected to the drain in accordance with Building Regulations or other rules in force
Fig. 15
5.5.3.2
Remove or discard the flue restrictor ring from the appliance flue outlet (see fig. 1).
Insert the small restrictor ring (supplied with the twin adapter kit) if the total flue length – including the allowance for any bends – is less than 8 metres.
Insert the exhaust connection manifold onto the appliance flue outlet.
Place the silicone seal (supplied with twin adapter kit) over the rim of the exhaust connection manifold.
Remove one of the blanking plates (located to the left & right of the appliance flu
Remove one of the blanking plates (located to the left & right of the appliance flue outlet) and – using the same screws – install the air baffle.
Installation of condensate drain kit (fig. 16)
5.5.3.3 Horizontal termination ( fig. 17)
The twin flue system must be converted to the dedicated concentric flue kit for termination.
The horizontal terminal is supplied with a built-in converter box and cannot be shortened.
Fig. 17
A 130mm hole is required for the passage of the concentric terminal through the wall.
Depending on site conditions it may be preferable to install the terminal assembly prior to fitting the twin flue pipes.
Fig. 16
Linea Plus AG
Mark and drill a 130mm hole for the passage of the horizontal flue terminal, ensuring that there is a 1º fall back to the boiler (17mm per 1000mm). Insert the terminal assembly into the flue hole.
Push-fit the twin flue pipes onto the concentric to twin converter ensuring that the exhaust pipe connects to the exhaust connection on the concentric to twin converter. If necessary cut the plain ends (male) of the twin flue pipes to allow connection to the
concentric to twin converter.
13
NOTE
Before cutting twin flue pipes ensure allowances have been made for connection onto the previous piece and onto the concentric to twin converter. The last twin flue pipes must be pushed 50mm onto the male spigots of the concentric to twin converter.
NOTE
You must ensure that the entire flue system is properly supported and connected.
When cutting an extension to the required length, you should ensure that the excess is cut from the plain end of the extension. Remove any burrs, and check that both seals are located properly.
Seal the flue terminal assembly to the wall using cement or a suitable alternative that will provide satisfactory weatherproofing. The interior and exterior trim can now be fitted.
5.5.3.4 Vertical termination (See fig. 18)
The twin flue system must be converted to the dedicated concentric flue kit for termination.
The vertical terminal is supplied with a built­in converter box and cannot be shortened.
A 130mm hole is required for the passage of the concentric terminal through the ceiling and/or roof.
Depending on site conditions it may be preferable to install the terminal assembly prior to fitting the twin flue pipes.
Fit the appropriate flashing plate to the roof and insert the vertical flue terminal through the flashing plate from the outside, ensuring that the collar on the flue terminal fits over the flashing.
Push-fit the twin flue pipes onto the concentric to twin converter ensuring that the exhaust pipe connects to the exhaust connection on the concentric to twin converter. If necessary cut the plain ends (male) of the twin flue pipes to allow connection to the concentric to twin converter.
Fig. 18
You must ensure that the entire flue system is properly supported and connected.
Ensure that any horizontal sections of pipe have a 1º fall towards the appliance (17mm per 1000mm).
The convertor box on the vertical terminal will have to be temporarily removed when inserting the terminal through the flashing.
The condensate trap must be primed with water prior to commissioning the boiler.
The condensate drain trap must be connected to the drain in accordance with building regulations or other rules in force.
14
NOTE
Before cutting twin flue pipes ensure allowances have been made for connection onto the previous piece and onto the concentric to twin converter. The last twin flue pipes must be pushed 50mm onto the male spigots of the concentric to twin converter.
Linea Plus AG
5.6 Connecting the Gas and Water
5.6.1 Figs. 6 and 15 show the locations of the
fittings.
5.6.2 Do not over tighten nuts, use another spanner to apply counter force to avoid damaging the appliance
5.6.3 Gas Supply
Connecting the gas supply. Connect a 15mm gas pipe to the gas service
tap and tighten the union nut securing the tap to the appliance.
Pipework from the meter to the appliance must be of adequate size.
A minimum gas pressure of 20mb (8 in. w.g.) must be available at the appliance inlet at full flow rate. See section 3.
DO NOT use pipes of a smaller size than the appliance inlet connection.
5.6.4 Central Heating
Connect the central heating pipework (22mm o.d) to the respective valves, right hand: flow, left hand: return, and tighten the nuts.
5.6.5 Hot Water
Connect a 15mm pipe to the hot water outlet connection of the appliance. Tighten the nut.
If the hot water system does not include a tap below the hot water outlet connection, provide a suitable drain tap to permit draining of the appliance hot water side during servicing.
5.6.6 Cold Water
Connect a 15mm cold water service pipe to the inlet stopcock of the appliance. Tighten the nut.
If the cold water supply is liable to high pres­sure or large pressure fluctuations, a flow/ pressure regulator should be fitted in the sup­ply pipe.
Should the appliance be subject to 'mains knock' it would be advisable to install an non return valve in the hot water outlet pipe to prevent unnecessary activation of the domes­tic flow switch.
5.6.7 Safety Valve Discharge
Connect a 15mm pipe to the discharge outlet of the appliance.
The discharge should terminate facing down­wards outside the building in a position where discharging (possibly boiling) water will not create danger or nuisance; but in an easily visible position.
5.7 Electrical Connections
5.7.1 The electricity supply must be as specified in
4.7. If controls external to the appliance are required, design of the external electrical cir­cuits should be undertaken by a competent person.
See Section 10 for further advice.
N.B. IT IS ESSENTIAL THAT ALL EXTER­NAL CONTROL CIRCUITS AND WIRING IS WIRED FROM THE SAME ELECTRICAL ISO­LATOR AS SERVES THE APPLIANCE.
Factory fitted internal wiring must not be dis­turbed when wiring external controls.
5.7.2 To gain access to the electrical terminals
Remove electrical cover by releasing four securing screws. Fig.18.
The mains input terminal block is now easily visible (see fig. 18a).
5.7.3 The electricity supply cable from the isolator and the appliance terminal block must be 3 core flexible sized 0.75mm˝ (24 x 0.2mm) to BS6500.
Wiring to the appliance should be rated for operation in contact with surfaces up to 90°C.
Electrical Cover Screws
Fig. 18
Factory Fitted Earth Screw
Fig. 18a
Link Between
= & TA
Mains Input and External Con­trols Terminal Block
Linea Plus AG
15
5.7.4 Pass the cable through one of the cord an­chorage points and connect the wires Brown to L, Blue to N, and Green/Yellow to . Arrange the cable so that should the cable slip the anchorage the current carrying conduc­tors become taut before the earthing conduc­tor.
5.7.5 Securely tighten all terminal screws and ar­range the cable with slack between the cable anchor and the terminal block. Tighten the cord anchorage screw until the cable is se­cure.
5.7.6 Neatly arrange the external cable in such a way that unrestricted opening of the controls fascia is possible without strain on the cable.
5.7.7 External controls may be wired from terminals TA to TA after removing the factory fitted link (see fig. 18 & pages 49 - 52 for further details). If a neutral is needed use the terminal marked N on the terminal strip.
DO NOT CONNECT ANY WIRES TO THE TERMINAL STRIP MARKED 'S' '-' 'POS' 'POS'
When connecting wires to the terminal strip it is possible to remove the terminal strip from the circuit board: Grasp the terminal strip firmly and slide up to clear pcb. See fig.21.
When refitting the terminal strip it is important that it is replaced correctly (with the screws facing left).
Section 10 gives details of fitment for external and internal controls (ie Vokera time clock).
If required pass the external controls cable through the spare cord anchorage and ar­range the cable so that should the cable slip the anchorage the current carrying conduc­tors become taut before the earthing conduc­tor.
Main Burner
Test Point
Incoming Gas Pressure Test
Point
Closed Position
Fig. 19
Normal Operating Position
Filling Position
16
Fig. 20
Do not connect wires to this terminal strip
Fig. 21
Controls terminal strip
Linea Plus AG
SECTION 6 COMMISSIONING
6.1 Where the text bears identifying numbers in
brackets, refer to figs. 1 and 2 unless other­wise instructed.
6.2 Gas Supply Installation
Inspect the entire installation including the meter. Test for soundness and purge, all as described in BS6891:1988.
6.3 Central Heating Systems
6.3.1 IMPORTANT DO NOT RELEASE AIR FROM
THE RED SEALED EXPANSION TANK. It is charged with air at the factory from .75 - .80 bar (11 - 12psig)
6.3.2 Initial filling of the System
6.3.2.1 See 3.4.3.
6.3.2.2 Open central heating flow and return valves.
Unscrew black cap on automatic air release valve (18) one full turn. (Leave open perma­nently).
6.3.2.3 Close all air release taps on the central heat­ing system.
6.3.2.4 Identify the filling/inlet valve found at the base of the appliance. See fig.6. The filling loop may have been disconnected from the filling/inlet valve and heating flow valve. If so reconnect unscrewing the caps as necessary. The filling/inlet valve has 3 positions. (Fig. 20) i) Vertically up - normal operating position. ii) Turn to the left to horizontal - closed posi-
tion.
iii) Vertically down - Filling position. To fill,
slowly turn the handle of the filling/inlet valve from the closed position towards the filling position. Mains water will be heard to enter the system/boiler. As the water en­ters the system/boiler the pressure gauge will be seen to rise. Pressurise to between 1bar & 1.5bar when the system is cold. DO NOT OVERPRESSURISE. Once the desired pressure is achieved turn the filling/inlet valve back to the closed position.
6.3.2.5 Starting with the lowest radiator open each air release tap in turn closing it only when clear water, free of bubbles, flows out. In the same way release air from any high points in the
pipework.
6.3.2.6 Continue filling the system until at least 1.0 bar registers on the gauge then turn the handle of the filling/inlet valve back to the closed posi­tion.
6.3.2.7 Inspect the system for water soundness and remedy any leaks discovered.
6.3.3 Initial flushing of Pipework
The whole of the heating system must be flushed both cold and later hot as detailed in
6.10. Open all radiator or heating valves and the appliance central heating valves. Drain the boiler and system from the lowest points. Open the drain valve full bore to remove any installation debris from the boiler prior to light­ing. Refill the boiler and heating system as described in 6.3.2
6.3.4 Setting the System Design Pressure
6.3.4.1 The design pressure should be a minimum of
1 bar and maximum 1.5 bar.
6.3.4.2 The actual reading should ideally be 1 bar plus the equivalent height in metres to the highest point of the system above the base of the appliance. (Up to the maximum of 1.5 bar total).
N.B. The safety valve is set to lift at 3bar/ 30m/ 45psig.
6.3.4.3 To lower the system pressure to the required value, pull lever on head of safety valve (14) a quarter turn to release water until the required figure registers on the gauge (31).
6.3.5 Filling the Hot Water System
6.3.5.1 Close all hot water draw-off taps.
6.3.5.2 Turn filling/inlet valve to the normal operating
position (vertically up). See fig. 20
6.3.5.3 Slowly open each draw-off until clear water is discharged.
6.4 Checking Electricity Supply
6.4.1 Carry out preliminary checks for continuity,
polarity, and resistance to earth (see page
61), gaining access as required according to
5.7.2 in this manual.
6.4.2 Leave the appliance with the control fascia closed and with the mains electricity switched OFF
6.5 Lighting the Boiler
6.5.1 Ensure flow and return valves are open.
(6.3.2.1) If external and/or internal controls are fitted
(e.g Timeclock and/or Room thermostat) en­sure they ‘call for heat’. The commissioning of the appliance may be easier if the external/ internal controls are disconnected and termi­nals TA & TA are linked. (For access proce­dure turn off electricity and refer to 5.7.2 for instructions).
6.5.2 Switch on the mains electricity and turn the on / off / mode switch (25) to
6.5.3 Set the c/h control knob (28) to the highest setting.
6.5.4 The appliance will go through an ignition se­quence and the burner will light.
Linea Plus AG
17
6.5.5 If during the ignition attempt period (10 secs approx.) the boiler fails to light, the ignition control circuit will go to lockout. This is indi­cated by the status LED (26) flashing red accompanied by a flashing error code 01 shown in the temperature indicator (27). The gas valve is de-energised, but leaves the fan and pump running for approximately 2 min­utes after lockout.
6.5.5 In the event of the boiler going to lockout turn the mode selector switch to the reset position for approximately 10 seconds, then back to the original position. The two main causes of the boiler going to lockout during commissioning are electrical supply polarity reversed, or air in the gas supply. Check polarity and that the gas supply is completely purged of air, and that gas is reaching the boiler, then repeat from
6.5.2.
6.6 Checking Burner Pressures
6.6.1 The heat inputs for high and low gas rates are
factory set to the maximum values given in section 3.6 for domestic hot water and central heating but it is necessary to check them when commissioning.
6.6.4 Turn off the main electricity supply. Gain ac­cess to the interior as instructed in 5.7.2.
6.6.5 Locate the main burner pressure test point (fig. 19) and slacken the screw half a turn in an anti clockwise direction. Attach a suitable U gauge tube between the test nipple and ma­nometer (see fig. 22).
IMPORTANT: Before measuring gas pres­sures it is imperitive that the protective cover over the gas valve adjustment screw is removed (fig. 31).
Turn on electricity supply and fully open a domestic hot water tap to operate boiler in dhw mode. Adjust hot water control knob to it's maximum setting.
be:
Plus AG (N/G)
10.1 mbar (plus or minus 1mbar)
If the pressure is wrong it should be adjusted as instructed in 8.23 (N.B. Whenever the maxi­mum rate is adjusted, check and adjust the minimum rate too).
6.6.7 Turn off the electricity supply and remove one of the grey wires connecting to the modulator coil on the front of the gas valve. Switch on the electricity supply. The boiler will now light at the minimum setting.
6.6.8 When low flame is established, the pressure reading should be:
Plus AG (N/G)
1.1 mbar (plus or minus 0.11 mbar)
If it is different adjustment should be made in accordance with the instructions in 8.23.
6.6.9 Turn off the electricity supply and replace the wire onto the modulator coil.
6.6.6 The pressure reading for maximum rate should
Gas Valve
Manometer
18
U Gauge Tube
Fig. 22
Linea Plus AG
6.6.10 Setting the Maximum Rate for Central Heating
The maximum heat input for the central heat­ing mode is not adjustable. When central heating is selected the appliance will light at 75% of maximum heat input for a period of approximately 15 minutes, whereupon the appliance will burn at maximum rate. Should the appliance reach temperature during the 15 minute period the burner will modulate further to suit system load.
6.7 Checking the Flue System
6.7.1 The flue system should be visually checked
for soundness. Check all clamps and fixings are secure and tight.
6.8 Checking the Heating Thermistor
6.8.1 Allow the system to warm up and manipulate
the c/h control knob to ensure that the burner modulates between ‘high’ and ‘low’ and then to ‘off’ and vice versa (scale range covers approx. 45° - 85°C).
6.9 Regulating the Central Heating System
6.9.1 Fully open all radiator and circuit valves and
run the appliance in the central heating mode until heated water is circulating. If conditions are warm, remove any thermostatic valve heads.
6.9.2 If the burner will not light, ensure that water is in fact circulating. See 4.6.3
6.9.3 Adjust radiator return valves and any branch circuit return valves until the individual return temperatures are correct and are approxi­mately equal.
6.9.4 When all is adjusted, progressively close all radiator valves to ensure that the appliance still operates when flow through the system is limited.
If the burner cuts out prematurely due to lack of water pressure through the appliance, the system should be regulated to ensure a flow rate of at least 350 litres/h (78 gals/h). This may mean the addition of a small manual by­pass being fitted to the system if a fully TRV system is used.
6.10 Final Flushing of the Heating System
6.10.1 The system should be flushed in accordance
with BS 7593: 1992.Turn on the boiler for central heating and allow the boiler and sys­tem to reach temperature. Turn off the boiler and drain the system whilst still hot.
Refill the boiler and heating system as de­scribed in 6.3.2.
Although not necessary for correct operation of the boiler, an inhibitor may be added at this point. Contact the inhibitor manufacturer for further information concerning application and dosage.
6.10.2 Inspect the system for soundness. Turn the appliance off at the mode selector switch (fig. 1, 25).
6.11 Filling, Testing and Regulating the Domestic Hot Water System
6.11.1 Start with the appliance switched on having
completed the procedures described in 6.4 to
6.10.
6.11.2 Open a domestic hot water tap (preferably the bath tap).
Ensure cold water inlet stopcock is fully open (vertically up) and the dhw control knob (24) is set at maximum.
6.11.3 Set the adjustable stopcock to restrict the maximum flow of water and achieve a tem­perature rise acceptable to the end user.
6.11.4 The flow of water should activate the domestic hot water flow switch (13) and drive the divert­ing valve (16) to its hot water position thus heating the domestic water flowing through the dhw heat exchanger. At the same time the pump and fan are activated lighting the burner on maximum rate.
6.11.5 If the burner does not light, check that the water flow rate is above the minimum re­quired to operate the domestic hot water flow switch (13) 2.0 litres/min (0.45 gals/min).
6.11.6 The temperature of the water will depend on the rate at which it flows.
The temperature of water at the tap can be varied by adjusting the water flow rate at the tap up to the maximum predetermined quantity.The hot water temperature control knob (24) will govern the maximum tempera­ture. When the appliance is being used in hot water mode the temperature indicator (27) indicates the temperature of the hot water leaving the appliance.
6.11.7 It is best to set for the lowest acceptable temperature since the user can gain higher temperatures by restricting flow at the tap.
N.B. If the cold supply is subject to large fluctuations or is above the permitted maxi­mum a suitable pressure/flow regulator should be fitted in the cold water supply to the appliance.
6.11.8 Turn the appliance mode selector switch (25) to the position.
Slowly close the tap to reduce the rate of draw to above the minimum approx. 2.0 litres/min., (0.45 gal/min.) Rotate the dhw control knob to ensure the appliance modulates at its various setting.
6.11.9 Close the draw-off tap still further. The burner should stop when the rate falls below approxi­mately 2.0 litres/min. (0.45 gal/min.).
6.11.10 The appliances incorporate a hot water preheat facility. The appliance will therefore ignite pe­riodically to maintain heat within the appliance.
Linea Plus AG
19
6.12 Final Check for Operations
Turn mode selector switch to the OFF/RESET position, disconnect pressure gauge, re-tighten screw. Relight boiler.
6.12.1 Re-check for gas soundness.
6.12.2 Re examine heating and hot water systems
and cold water supply for water soundness.
6.12.3 Check the appearance of the gas flame to assess adequacy of combustion air supply.
6.12.4 Re-check the flue system for soundness and adequacy of supports.
6.13 Concluding Operations
6.13.1 If external/internal controls have been discon-
nected and terminals TA & TA temporarily linked, remove the link and reconnect the controls circuit. Check the operation of the controls.
6.14 Refixing the boiler casing (fig. 24).
6.14.1 Offer up the front casing to the back frame in
a near vertical attitude and locate the hooks on the casing over the hooks on the frame.
Slide the casing downwards to fully engage the hooks and to align the bottom fixing holes. Replace the two case retaining screws (fig.24).
6.14.2 Hinge up the control fascia and secure using the two screws (fig.25).
6.14.3 Disconnect filling loop, fit filling loop cap. Leave filling loop in a safe and accessible place.
6.15 Supplementary Instructions for Fitting & Re­moving Optional Time Clock and for Wiring to External Controls.
Section 10 Appendices A and B at the rear of this manual provides full instruction for fitting and wiring the optional built-in time switches and for wiring to external controls.
6.16 Complete details of the boiler, controls, instal­lation and commissioning in the log book supplied with the boiler. This is an important document which must be correctly completed and handed to the user. Failure to install and commission this appliance to the manufactur­ers instructions may invalidate the warranty.
SECTION 7 INSTRUCTING THE USER
7.1 Hand over the copy of the Users Instructions
and boiler log book supplied with the appli­ance, together with these instructions. Explain how to operate the boiler correctly and how to use the timeclock and room thermostat if fitted.
7.2 Show the user how to switch off the appliance and indicate the position of the electric supply isolator.
7.3 Inform the user of the location of all drain cocks and air vents.
7.4 Explain how to turn the appliance off for both short and long periods and advise on the precautions necessary to prevent damage should the appliance be inoperative when freezing conditions may occur.
7.5 Show the user the filling loop position its function and how to repressurise the system using the filling/inlet valve.
7.6 Advise the user that, for continued safe and efficient operation, the appliance must be serv­iced by a competent person at least once a year.
Fig. 24
20
Fig. 25
Case Screws
Case screws
(one either side)
Linea Plus AG
SECTION 8 SERVICING INSTRUCTIONS
8.1 General
To ensure the continued safe and efficient operation of the appliance, it is recommended that it is checked and serviced as necessary at regular intervals.
The frequency of servicing will depend upon the particular installation conditions and us­age, but in general, once per year should be adequate.
It is the law that any servicing work is carried out by a competent person such as a Vokèra service engineer, approved service agent, British Gas or other CORGI registered per­sonnel.
The following instructions apply to the boiler and its controls, but it should be remembered that the central heating and domestic hot water systems will also require attention from time to time.
8.2 Important Notes
WARNING: having carried out preliminary
flame checks and before starting any servic­ing work, switch OFF the mains electricity supply and disconnect the plug at the main isolating switch and socket. (If a switch is used remove the fuse.)
Turn off gas supply at the gas service tap fitted to the appliance.
Always test for gas soundness after any serv­ice work and after exchanging any gas carry­ing component.
8.3 Recommended Routine Servicing
8.3.1 Annual Servicing
When servicing is required the following pro­cedures should be carried out.
1. Inspect exterior for signs of damage and deterioration, particularly of flue pipework and electrical connections.
2. Turn off mains electricity and remove front casing (see 8.4.).
3. Replace fuse if previously removed (8.2. above) and turn on electricity. Run the boiler for a few minutes in the domestic hot water mode to permit inspection of its operation. This is accomplished by opening a domestic hot water draw off tap and inspecting burner for yellowing of flame tip, flame lift off or sooting.
4. Ensure central heating valves are open. See 6.3.2.1.
Observe pressure gauge reading (fig. 1, 31 which should be approximately 1 bar when the system is cold See 6.3.4
5. Turn off mains electricity and turn off gas service tap on the appliance.
6. Gain general access as described in 8.4.
7. Remove main burner (see 8.6). Lightly clean with a soft brush and inspect for dam­age. If during initial inspection any combus­tion irregularity was suspected, remove injec­tors and clean or replace (see 8.7).
8. Place cloth below combustion chamber to catch debris. Clean heat exchanger using suitable brushes and rods if necessary.
9. Inspect combustion chamber lining. The insulating material is easily damaged. Do not scrape, but clean off lightly.
If any panels are damaged these should be replaced (see 8.11).
10. Replace all parts in reverse order but leave the controls fascia open and outer cas­ing off.
11. Undertake a complete commissioning check as detailed in section 6.
12. Close up control fascia and refix front casing.
13. Clean off casing using soft cloth and dilute detergent.
14. Complete details of service undertaken in the boiler log book.
NOTE: there is a flue gas analysis test point incorporated in the flue outlet (fig. 1, 23).
8.3.2 Replacement of Parts
1. The life of individual components varies and they will need servicing as and when faults develop. The fault finding sequence charts in section 9 will serve to locate which component is the cause of any malfunction. Instructions for removal, inspection and re­placement of the individual parts are given in the following pages.
2. The domestic hot water heat exchanger may in certain conditions become partially blocked by scale deposits. Evidence of this will be deterioration in performance.
This condition could well be treated using proprietary descalants following makers' in­structions without dismantling the appliance by circulating a fluid through the dhw coil. To do this, disconnection from hot and cold serv­ices is necessary. Reconnect only after thor­ough flushing with clean water.
3. Occasional maintenance of mechanical working parts will be necessary (three port valve, flow diaphragm). Service kits are avail­able from your local Vokèra stockists. Vokèra Service Kit No.T0019.
Linea Plus AG
21
8.4 To Gain General Access/Assembly
To remove components access to the interior is essential. Refer to figs. 10 & 11.
Ensure electricity supply is isolated before carrying out any servicing.
8.4.1 To remove front casing. Push to release front door panel and lower to
reveal controls. Loosen the 2 captive screws securing the front control panel to the lower part of the casing and lower to reveal inside of boiler (fig. 10).
Remove two screws at base of casing, slightly lift the casing and slide it gently towards the top of the appliance to disengage the case from the top suspension hooks (fig. 11).
Ensure the casing and screws are put to one side in a safe place.
8.4.2 Reassembly is always carried out in reverse order to dismantling, unless otherwise stated. Electrical connections must be remade in accordance with the wiring diagram (figs.39-
40).
8.4.3 Where gas control components are replaced, check the burner pressures and adjust if nec­essary. See 8.23.
8.5 Room Sealed Chamber Front Cover
Refer to fig. 26.
8.5.1 Gain general access as 8.4.
8.5.2 Remove room sealed cover plate by releasing
two lower retaining clips and easing cover off the top locating hooks. Inspect gasket for damage. If damaged, replace.
NOTE: when refitting the combustion cham­ber front cover it is essential to correctly seat and secure the cover in place ensuring both clips are secured in place.
Fig. 26
Flue gas analysis
test point
Fig. 27 a
Fig. 27 b
22
Fig. 28 a
Linea Plus AG
8.6 Main Burner and Electrodes
Main Burner Part No 0511 N.G. 0512 L.P.G Spark/Sense Electrode Part No 1838 Refer to figs 28a - 28c.
8.6.1 Gain general access as 8.4.
8.6.2 Remove room sealed front cover as 8.5
8.6.3 Remove front of combustion chamber by re-
leasing screws (fig. 27a&b).
8.6.4 Remove four burner retaining screws (fig. 29a&b). Ease burner forward and rest on cham­ber base (fig. 28a&b).
8.6.5 Release electrode retaining screws & carefully remove electrode(s).
8.6.6 Trace electrode and earth lead to electronic ignition control and gas valve and disconnect
Trace electrode leads, 1 to pcb and 2 to elec-
tronic ignition unit and disconnect.
8.6.7 Remove main burner.
8.6.8 Reassemble in reverse order ensuring correct
location of electrode(s). Note1. If the Ionisation electrode is replaced
the gas pressures will need resetting as in­structed in 8.23.
Note 2: If difficulty is found in relocating the burner securing screws, easier access can be gained by removing the two side panels (fig. 28a&b).
Note 3: See page 36 for electrode positioning.
8.7 Main Burner Injectors
8.7.1 Gain general access as 8.4.
8.7.2 Remove room sealed front cover plate and
combustion chamber front (8.5 & 8.6.3).
8.7.3 Remove main burner (8.6.4 to 8.6.8).
8.7.4 Unscrew injector(s) from burner bar.
8.8.8 Unscrew unions on either side of main heat
exchanger fig. 29a&b.
8.8.9 Slide out main heat exchanger, taking care not to damage insulation panels. Avoid spillage of water on boiler electrics.
8.8.10 Reassemble in reverse order using new fibre washers in unions.
Fig. 28b
Fig. 28cFig. 28c
Fig. 28c
Fig. 28cFig. 28c
8.8 Main Heat Exchanger
0513 Refer to fig. 29
8.8.1 Gain general access as 8.4.
8.8.2 Remove room sealed front cover plate (8.5).
8.8.3 Remove front of combustion chamber (8.6.3).
8.8.4 Remove two air baffle plates, 1 screw securing
each (fig. 30).
8.8.5 Remove both side panels, 2 screws each (fig. 28a&b).
8.8.6 Close heating flow and return valves by turning 1/4 turn until indicating lines are horizontal. Pull lever on head of safety valve to drain primary circuit to boiler.
8.8.7 Place cloth under heat exchanger to catch surplus water.
Linea Plus AG
Fig. 29a
23
8.9 Flue Fan
Part No. 2076.
8.9.1 Remove room sealed front cover plate (8.5) and front of combustion chamber (8.6.3).
8.9.2 Loosen maintenance clip securing screws (see fig. 30) and slide upwards to clear joint.
8.9.3 Remove silicone pipes from nozzles on inner flue bend.
8.9.4 Remove 5 flue hood retaining screws (see fig.
30). NOTE: when removing the two side screws
the two air baffle plates can be removed.
8.9.5 Carefully slide flue hood forward disconnecting electrical leads on fan in the process.
8.9.6 Unscrew 4 screws securing fan to flue hood and remove fan. Transfer aluminium manifold (two screws) to new fan.
8.9.7 Reassemble in reverse order, replacing cen­tre hood screw first.
8.10 Differential Analog Pressure Switch
Part No. 2677 Refer to Fig. 30
8.10.1 Gain general access as 8.4.
8.10.2 Remove room sealed cover (8.5).
8.10.3 Remove 2 screws holding pressure differen-
tial switch to the combustion chamber.
8.10.4 Pull off tab connectors and remove pressure switch, disconnecting the air pressure pipes in the process.
8.10.5 Reassemble in reverse order. See fig. 39&40 for correct fitting of electrical
connections. When reconnecting the pres­sure pipes the upper nozzle on the inner flue bend connects to the upper nozzle of the pressure differential switch.
8.11 Combustion Chamber Insulation Boards
8.11.1 Gain general access as 8.4.
8.11.2 Remove room sealed front cover 8.5.
Remove front of combustion chamber 8.6.3. Remove Main Heat Exchanger 8.8.
8.11.3 To remove side combustion chamber insula­tion boards, gently prise upwards and pull out.
8.11.4 To remove rear board, gently prise upwards and pull out.
8.11.5 Fourth panel (front) is replaced complete with combustion chamber front panel.
Maintenance clip
Fig. 29b
Pressure
differential switch
Air tubes
Air
baffle
plate
Fig. 30
Hood
Retaining
Screws
24
Linea Plus AG
8.12 Ignition PCB
8.12.1 Gain general access as 8.4.
8.12.2 Remove PCB cover.
8.12.3 Disconnect wires from ignition PCB.
8.12.4 Remove ignition PCB.
8.12.5 Replace in the reverse order ensuring wires
are replaced correctly.
8.13 Gas Control Valve (complete)
Part No. 2471 fig. 31.
8.13.1 Turn off gas service tap.
8.13.2 Remove Ignition control box as 8.12.
8.13.3 Pull off silicone tube from gas valve regulator.
8.13.4 Disconnect earth leads from gas valve.
8.13.5 Disconnect wires from modulator coil.
8.13.6 Unscrew gas service tap union & release from
its seating.
8.13.7 Remove 2 screws securing gas valve bracket to the base frame.
8.13.8 Undo union above the gas control valve & withdraw gas valve.
8.13.9 Transfer gas connecting pipes to the new valve using new gasket.
8.13.10 Reassemble in reverse order.
8.13.11 Test all joints for gas soundness.
8.13.12 Check burner pressures. As detailed in 6.6.
Modulator Coil
Silicone Compensation Tube Point
Fig. 31
Protective cover
Pipe Securing Clip
Pump Securing Bracket
Linea Plus AG
Fig. 32
25
8.14 Pump
Part No. 0438.
8.14.1 Gain general access as 8.4.
8.14.2 Close heating flow and return valves (fig. 6),
by turning 1/4 turn until indicating lines are horizontal. Pull lever on head of safety valve to drain primary circuit to boiler.
8.14.3 Place cloth under pump to catch surplus wa­ter.
8.14.4 HEAD ONLY Unscrew the 4 allen screws around the pump head. Pull head from base of pump and disconnect electrical leads. If re­placement required, use the head from a standard 15-60 Grundfos.
8.14.5 COMPLETE PUMP Disconnect pipe union connection at front left corner of combustion chamber. See fig. 33.
8.14.6 Disconnect push fit pipe from pump body by releasing pump securing clip and pulling pipe free from body. See fig. 32.
8.14.7 Remove screw from pump securing bracket.
8.14.8 Grasp pump and pull upwards with slight
twisting movement to release pump from manifold.
8.14.9 Disconnect electrical leads from pump.
8.14.10 Remove pump securing bracket from pump
housing and transfer to new body.
8.14.11 Reassemble in reverse order. Reconnect electrical leads Brown to L, Blue to N and Green to E.
8.15 Domestic Flow Switch
Refer to fig. 33.
8.15.1 Gain general access as 8.4.
8.15.2 Place receptacle or an absorbent pad below
appliance to catch trapped water.
8.15.3 Close cold water inlet stopcock. See fig.6 and
6.3.2.4.
8.15.4 Open lowest draw-off or drain tap on hot water system.
8.15.5 Disconnect cold water inlet valve from flow switch by undoing union.
8.15.6 Disconnect union at top of flow switch and two electrical tab connectors.
8.15.7 Undo lock nut securing flow switch to base frame and remove.
8.15.8 Reassemble in reverse order.
8.16 Combined Diverter Valve & Pressure Switch
Refer to fig. 33.
8.16.1 Gain general access as 8.4.
8.16.2 Place receptacle or an absorbent pad below
appliance to catch trapped water.
8.16.3 Remove domestic hot water heat exchanger as 8.17.
8.16.4 Remove diverter valve as 8.21.8.
8.16.5 Release pressure switch from the hydraulic
group by removing one retaining screw on bracket.
8.16.6 Remove cold water connecting pipe by undoing the unions at both ends.
8.16.7 Disconnect flow tube union where it connects onto the hydraulic group.
8.16.8 Disconnect expansion vessel pipe.
8.16.9 Unscrew pressure gauge connection retain-
ing screw and pull out pressure gauge connnection.
8.16.10 Disconnect safety valve discharge pipe and heating valve unions.
8.16.11 Remove retaining screw securing hydraulic group to frame.
8.16.12 Withdraw hydraulic group from appliance. See fig. 34 for further disassembly.
Pump Pipe Union
Diverter Valve
26
Pump
Safety
Valve
Pressure
Switch
Gas Valve & Ignition Control Box
Domestic Heat Exchanger
Domestic Hot Water Flow Switch
Fig. 33
Linea Plus AG
8.17 Removal of Domestic Hot Water Heat Ex­changer
Refer to figs. 33 and 34.
8.17.1 Gain General access 8.4.
8.17.2 Place receptacle or an absorbent pad below
appliance to catch trapped water.
8.17.3 Close cold water inlet stopcock.See fig. 6 and
6.3.2.4.
8.17.4 Open lowest draw-off or drain tap on hot water system.
8.17.5 Close heating flow and return valves (fig. 6) by turning 1/4 turn until indicating lines are hori­zontal. Pull lever on head of safety valve to drain primary circuit to boiler.
8.17.6 Remove domestic heat exchanger retaining screw (L/H) and elongated brass nut (R/H).
8.17.7 Gently release heat exchanger from O' ring seals by rocking to the rear and remove.
8.17.8 Remove insulation jacket and transfer to new domestic heat exchanger.
8.17.9 Reassemble in reverse order, using new O' rings if required.
8.18 Diverter Valve
8.18.1 Gain general access as 8.4.
8.18.2 Close heating flow and return valves (fig. 6) by
turning 1/4 turn until indicating lines are hori­zontal. Pull lever on head of safety valve to drain primary circuit to boiler.
8.18.3 Remove motorised valve. See 8.21.8.
8.18.4 Remove front of diverter valve by unscrewing
six retaining bolts.
8.18.5 See Fig.35 for further disassembly and loca­tion of components.
8.18.6 Reassemble in reverse order.
8.19 Checking/Replacing Main Expansion Vessel
8.19.1 The expansion vessel is factory pressurised
0.8 bar (12psig) and should be checked dur­ing servicing. Should it have lost pressure it can be repressurised in situ. Drain the boiler. Fit a suitable pump and gauge (i.e. car foot pump and gauge) to the nipple at the top right­hand side of the expansion vessel, and pres­surise to 0.8bar (12psig) and remove the pump.
NOTE: Access to the nipple can be improved by removing the upper vessel retaining bracket and rocking the vessel forwards.
If the vessel cannot be repressurised or if pressure loss is very frequent the expansion vessel will require changing. Alternatively, a new vessel can be fitted in the return to the appliance, and the old vessel isolated in situ.
8.19.2 Switch OFF mains electricity and gain general access. Disconnect electricity supply and wir­ing for external controls from the appliance.
8.19.3 Close heating flow and return valves (fig. 6) by turning 1/4 turn until indicating lines are hori­zontal. Pull lever on head of safety valve to drain primary circuit to boiler.
8.19.4 Remove screws on large maintenance clip/s (fig. 13) and remove. Loosen screws on the small clip/s and disconnect flue.
8.19.5 Disconnect all pipe unions at the base of the appliance.
8.19.6 Lift appliance off upper bracket.
8.19.7 Remove two screws retaining vessel securing
strap at top. Disconnect expansion pipe at base of expansion vessel and lift vessel out of the appliance.
8.19.8 Reassemble in reverse order, using new fibre washers.
Linea Plus AG
27
8.20 Safety Valve
Part No. 1806 Refer to figs.33 & 34.
8.20.1 Gain general access as 8.4.
8.20.2 Close heating flow and return valves (fig. 6) by
turning 1/4 turn until indicating lines are hori­zontal. Pull lever on head of safety valve to drain primary circuit to boiler.
8.20.3 Disconnect safety valve discharge pipe.
8.20.4 Loosen grub screw at base of safety valve and
pull forwards releasing valve from O' ring seal.
8.20.5 Replace in reverse order.
8.21 Removal of Electrical Components
8.21.1 Ensure electricity is switched off at main iso-
lator and gain general access as 8.4.
8.21.2 Pressure Microswitch
Fig. 1, no. 15.
8.21.3 Gain general access as 8.4.
8.21.4 Release microswitch from hydraulic group by
removing one securing screw.
8.21.5 Remove plastic cover.
8.21.6 Remove electrical wires.
8.21.7 Reassemble in reverse order ensuring cor-
rect location of electrical connections. (See fig. 39&40 for electrical connections).
Domestic Heat Exchanger
Diverter Valve and Flow Switch Manifold
Water Flow Regulator
Domestic Hot Water Thermistor
Domestic Hot Water Heat Exchanger Retaining Screws
Pressure Switch
Safety Valve
28
Diverter Valve Bobbin
Diverter Valve Cover
Fig. 34
Motorised Valve
Linea Plus AG
8.21.8 Diverter Valve
8.21.9 Gain general access as 8.4.
8.21.10 Release motorised valve by removing retain-
ing clip.
8.21.11 Remove electrical plug in connector.
8.21.12 Reassemble in reverse order.
8.21.13 Printed Circuit Board
Part No. 05022.
8.21.14 Gain general access as 8.4.
8.21.15 Remove printed circuit board cover by releas-
ing 5 securing screws.
8.21.16 Pull out multi plug connectors,one earth lead and one electrode lead from the printed cir­cuit board.
8.21.17 Remove 2 screws securing circuit board to front panel and remove board.
8.21.18 Reassemble in reverse order ensuring cor­rect location of electrical connections. (See fig. 39&40 for electrical connections).
NOTE: it will also be necessary to check/ adjust the c/h gas pressure as 8.23.
8.21.19 Display Printed Circuit Board
8.21.20 Remove printed circuit board as 8.21.13 to
8.21.18.
8.21.21 Remove three control knobs from front con­trol panel.
8.21.22 Remove the two screws securing the circuit board to the front panel.
8.21.23 Pull out two multi-plug connectors.
8.21.24 Replace in reverse order.
8.21.25 Safety Thermostat
Part No 8367 Refer to fig. 35.
8.21.26 Gain general access as 8.4.
8.21.27 Remove room sealed chamber front cover as
8.5 and R/H side panel (fig. 28a&b).
8.21.28 Pull off the two electrical connections on the back of the thermostat.
8.21.29 Release stat from flow pipe by unscrewing 2 retaining screws.
8.21.30 Reassemble in reverse order ensuring cor­rect location of electrical connections. (See fig. 39&40 for electrical connections).
8.21.31 Thermistor Sensors
Part No. 8484 Refer to fig.35.
8.21.32 Gain general access as 8.4.
8.21.33 Remove room sealed chamber front cover as
8.5. Remove R/H side panel as fig.28a&b.
8.21.33a PRIMARY
Close heating flow and return valves (fig. 6) by turning 1/4 turn until indicating lines are horizontal. Pull lever on head of safety valve to drain primary circuit to boiler.
8.21.33b DOMESTIC HOT WATER
Close cold water inlet stopcock. See fig.6 and
6.3.2.4.
Open lowest draw-off or drain tap on hot water system.
8.21.34 Remove ignition control box as 8.12.
8.21.35 Pull off electrical plug connection from ther-
mistor.
8.21.36 Unscrew thermistor from pocket.
8.21.37 Reassemble in reverse order.
8.22 Pressure Gauge
Part No 1857.
8.22.1 Gain general access as 8.4.
8.22.2 Close heating flow and return valves (fig.6) by
turning 1/4 turn until indicating lines are hori­zontal. Pull lever on head of safety valve to drain primary circuit to boiler.
8.22.3 Trace capillary from back of pressure gauge to connecting point on brass manifold.
8.22.4 Unscrew the retaining screw beside the capil­lary tube entry to the manifold.
8.22.5 Pull out capillary tube from manifold.
8.22.6 Squeeze plastic locking lugs behind fascia
and press gauge from aperture.
8.22.7 Reassemble in reverse order following origi­nal route for capillary tubes and ensuring lock­ing lugs are located in the grooves.
Fig. 35
Primary Thermistor
Safety Thermostat
Flow Pipe
Linea Plus AG
29
8.23 Setting Gas Pressures
ALL SETTINGS DONE WITH A SUITABLE MANOMETER CONNECTED TO GAS VALVE AS INSTRUCTED IN 6.6.5.
8.23.1 Setting Maximum Rate
Turn off electrical supply to boiler and follow instructions in section 8.4 to gain access. Refer to fig. 22 & 36.
Turn on the electricity supply and the appli­ance mode selector switch to remove gas pressure adjustment protective cover (fig. 36).
Turn on fully a domestic draw off tap. The boiler will now light at full flame. Screw the
outer nut (a) on the end of the modulator coil slowly clockwise until the burner lights.
Adjust the nut until the correct pressure is obtained on the gauge. The correct reading should be:
10.1 mbar plus or minus 1.0 mbar
8.23.2 Setting Minimum Rate
Remove one of the grey wires connecting to the modulator coil. The gas pressure will now be at the minimum rate.
Turn the inner minimum adjusting screw (b) anti clockwise to decrease the pressure, or clockwise to increase the pressure until the minimum gas pressure is achieved, (ensure when adjusting the inner screw the outer nut (a) is held in position) the correct reading should be:
1.1 mbar plus or minus 0.11 mbar
Replace the grey wire back onto the modula­tor coil together with the protective cover.
30
Fig. 36
Maximum pressure adjustment screw (a)
Gas pressure adjustment protective cover
Minimum pressure ad­justment screw (b)
Linea Plus AG
8.24 Soft Light Ignition
The Linea range incorporates a fully auto­matic soft light ignition sequence which is non adjustable.
When ignition is called for the gas valve is energised and at the same time 20 m/A is applied to the modulator coil for a period of approximately 3 seconds. During this 3 sec­onds the appliance will ignite.
After the initial 3 seconds power to the modu­lator coil is gradually increased to a maximum power of 140 m/A.
140 m/A is applied to the modulator coil for a further second. If the appliance is operating in hot water mode the maximum heat input will be automatically adjusted depending on the temperature of the appliance.
If the appliance is operating in central heating mode see 8.24.1.
8.24.1 Maximum Rate in Central Heating Mode.
The Linea range does not require any adjust­ment to maximum heat requirement of the system load.
After initial ignition the appliance will auto­matically reduce the maximum heat input to 75% of its maximum capability for a maximum period of 15 minutes.
During this 15 minutes should there be suffi­cient temperature rise of the heating system the appliance will reduce the heat input to suit the system load to a point where the maximum selected temperature is achieved, and the appliance switches off.
Alternatively should the appliance fail to achieve sufficient temperature rise within this 15 minute period, the appliance will increase its maximum heat input to further increase the temperature of the system.
Once achieved the appliance will modulate to suit system load.
8.24.2.1 To use the combustion switch it is important that the gas pressures are set accurately as described in 8.23.1- 8.23.3.
8.24.2.2 Remove combustion switch cap on front con­trol panel by turning 1/4 turn to disengage. Fig.1, 29
8.24.2.3 Unscrew flue gas analysis test point fig.1, 23. Set up flue gas analyser and insert probe into test point.
8.24.2.4 Using a screwdriver lightly press the black toggle behind the combustion switch cap once only.
The appliance will light at maximum rate. At this point the digital display will show CO to confirm the appliance is in combustion test mode.
8.24.2.5 Analyse flue gasses on analyser.
8.24.2.6 Once the analysis is complete lightly press the
black toggle once to disengage the combus­tion mode. The display will revert to showing appliance temperature on the digital display.
NOTE: the combustion switch can also be used when gas rating the appliance.
8.25 End of Servicing
Run through the general commissioning as described in Section 6 as far as they apply.
Refit casing and clean up.
8.24.2 Combustion Analysis
Incorporated on the appliance is a combus­tion switch (fig.1, 29). Once the gas pressures have been set activation of the combustion switch automatically fires the appliance at maximum rate in central heating. The appli­ance will be held at maximum rate until the maximum temperature of the appliance is achieved. The appliance will not modulate during this period.
Linea Plus AG
31
SECTION 9 OPERATIONAL CHECKS AND WIRING DIAGRAMS
9.1 On completion of any service/fault finding task
which has required the breaking and remaking of electrical connections, the checks Earth Continuity, polarity and Resistance to Earth must be repeated.
The following flow diagrams suggest the logical sequence of steps for fault finding.
They are not exhaustive but cover all that can reasonably be carried out on site by the installer.
Acquaintance with the functional sequence will prove helpful for some, and this is included for reference. As further help, the role of each part is briefly described.
Also included in this section are wiring dia­grams and schematics to assist in fault loca­tion and servicing as described in the text.
9.2 Sequence of Functions
When following this sequence, refer to figs. 39 & 40. It is assumed that the mode selector switch is in the position.
9.2.1 Rest (No demand for central heating or hot water)
With no demand for heating or hot water the appliance will periodically light to preheat the domestic hot water heat exchanger. This is done to ensure that when a demand is made for domestic hot water the appliance is not cold, thereby reducing the wait for hot water. (This function can be deactivated by a service engineer). See page 58.
Once every 19 hours the appliance will auto­matically activate and deactivate the pump and motorised valve (provided the electrical supply is on to the appliance). This will help prevent these components becoming stuck if the appliance is not used for long periods.
The temperature indicator will always display the temperature of the boiler unless domestic hot water is drawn where it will indicate the temperature of the hot water leaving the appliance.
9.2.2 Domestic Hot Water Mode
Turning on a tap will cause the domestic hot water flow switch to activate.
Activation of the domestic hot water flow switch operates the motorised valve. Operation of the motorised valve mechanically diverts the primary water to the domestic heat exchanger in stand-by mode the diverter valve is already in DHW position. The pump is started simulta­neously and with sufficient primary water pressure the fan starts which results in a voltage produced by the DAPS. Once this action has been proven the gas valve will be energised and the electrode will start to spark.
If a flame is detected during the ignition at­tempt time (8-12 seconds) the sparking will cease, the gas valve will remain energised and the appliance will produce hot water as described below.
If a flame is not detected the appliance will go to lockout (failure to detect a flame during ignition attempt time). The gas valve will be de-energised and the sparking will stop. (See self diagnostic error codes)
To reset the appliance after lockout turn the mode selector switch to the reset position for approximately 10 seconds then back to origi­nal position.
The temperature rise of primary water and domestic hot water in the appliance is sensed by thermistors on the flow tube and hot water outlet.
An increase in temperature will in turn de­crease the voltage to the fan. The difference in pressure is detected by the differential analogue pressure switch (DAPS) and alters the voltage produced from it and transmits this to the pcb. The pcb will in turn decrease the voltage reaching the modulator coil causing the gas rate to be lowered in proportion to the fan speed. If the temperature rise is too great the fan and gas valve will turn off completely.
Conversely a fall in temperature of the primary and domestic hot water will increase voltage to the fan and this in turn increases the gas rate accordingly.
Temperature of the domestic hot water leav­ing the appliance is shown at the temperature indicator whenever hot water is drawn.
Constant monitoring of the temperature of the primary and domestic hot water by the thermistors will regulate the gas rate to main­tain an average heat input.
NOTE: As the thermistor senses the tempera­ture of the primary water leaving the main heat exchanger, the amount of heat transferred from the primary water to the dhw water de­pends upon the temperature differential be­tween them.
When the dhw water draw off rate drops below the permitted minimum (2.0 l/min) the domes­tic hot water flow switch is deactivated, and the appliance either reverts to the 'Rest' mode where the fan may overrun to remove residual heat, or if there is a call for heating to the mode described below.
32
Linea Plus AG
9.2.3 Central Heating Mode
In this mode the mode selector switch must be turned to the position.
With all controls calling for heat the motorised valve returns, mechanically diverting primary water to the central heating circuit. The pump will run and with sufficient primary water pressure the fan starts which results in a voltage produced by the DAPS. This in turn will energise the electronic ignition control box. The gas valve will be energised and the electrode will start to spark.
If a flame is detected during the ignition at­tempt period, (8-12 seconds) the sparking will cease and the gas valve will remain ener­gised. The appliance will light at 75% of maxi­mum heat input for a maximum of 15 minutes then increase to maximum output if required, or will modulate during the 15 minute period if the temperature rise is sufficient.
The temperature rise of the primary water is sensed by the thermistor on the heat exchanger.
As the temperature of the primary water ap­proaches that set on the c/h temperature control, the boiler will modulate as described in domestic hot water mode.
On reaching the set temperature the gas valve is de-energised and the burner is extin­guished.
The appliance has an inbuilt delay timer and re-ignition will not be attempted for approxi­mately 3 minutes. This can be deactivated.
Constant monitoring of the temperature of the primary water by the thermistor will regulate the gas rate to maintain an average heat input. When the appliance has reached the set tem­perature and the burner is off, the pump will continue to run to circulate the primary water around the c/h system.
Temperature of the central heating is shown at the temperature indicator whenever the central heating is on.
If supply to the appliance is broken (e.g. by a
room thermostat or timeclock) the burner is extinguished the pump stops, the motorised valve is energised into the hot water mode waiting for pre-heat or demand for hot water. However, the fan will continue to run until the primary water temperature is below 80°C.
Should there be a drop in primary water pres­sure below 0,2 mbar the pressure switch could deactivate and de-energise the gas valve.
Self Diagnostic Error Codes
The temperature indicator also serves as an error code indicator. Should an error occur the status LED (which is normally green) will flash red. This will be accompanied by the temperature indicator flashing an error code of 01 - 08. Check code and proceed as follows:
01: Failure to ignite (see 6.5.5). To re-set turn mode selector switch to re-set position for approximately 10 seconds, then back to origi­nal position.
02: Overheat - Normally associated with ei­ther poor or lack of primary water circulation. Wait for appliance to cool then re-set as de­scribed for code 01.
03: Problem with fan/flue. Re-set as described for code 01.
04: Insufficient water pressure. Check pressure gauge reading, if low restore pressure (see 6.3.4) then re-set as described in code
01. Re-set as described for code 01.
05: Re-set as described for code 01. 06: Hot water thermistor open circuit. 07: Primary thermistor open circuit. 08: Burner overheat. Reset as described for
code 01.
FAULT FINDING GUIDES
On the following pages are the fault finding guides. Be sure to read the notes below before begining any fault finding
NOTES:
1. To ensure correct fault diagnosis it is important that these guides are carried out in the set order.
2. Check the electrical supply polarity is correct before carrying out fault finding (lockout will occur if the
polarity is reversed).
3. To ensure that internal/external controls (if fitted) do not interfere with fault finding, disconnect the wires from terminals TA & TA (labelling them in the process to ensure correct reconnection) and provide a solid link between TA & TA.
Linea Plus AG
33
VOKERA
LINEA PLUS AG
Rev. 1 08/03/2000
TEST A : CHECKING OPERATION OF ELECTRONIC
CONTROL BOARD AT START UP
NO
MAINS
ON 3 WAY
NO
VALVE BETWEEN
TERMINALS
M11.1 & M11.3
ON PCB
YES
CHECK &/OR REPLACE
REPLACE PCB
WIRING OR CONNECTIONS
AND 3 WAY VALVE
IS THE
3 WAY VALVE
IN DHW
POSITION?
YES
TURN ON HOT
TAP
PUMP
RUNNING
YES
SWITCH ON/OFF
SELECTOR TO
DHW POSITION
YES
START
GREEN LED
ALIGHT
NO
A2
NO
REPLACE CONTROL
BOARD
REPLACE
CONTROL
BOARD
NO
THERE 5 Vdc
BETWEEN TERMINALS
M5.5 & M5.6
ON PCB
CHECK WIRING AND
CONNECTIONS OR
DHW FLOW SWITCH
ON PUMP
CONNECTOR
NO
ON PUMP
IS
YES
MAINS
M15.1 &
M15.2
YES
MAINS
YES
NO
THERE 0 Vdc
BETWEEN TERMINALS
NO
NO
IS
M5.5 & M5.6
ON PCB
YES
NO
IS
THERE 0 - 1 Vdc
BETWEEN TERMINALS
M3.11 & M3.10
ON PCB
FAN RUNNING
NO
MAINS
ON FAN
CONNECTOR
M12.1 &
M12.2
YES
REPLACE FAN
YES
A
YES
MAINS
ON FAN
NO
CHECK &/OR
REPLACE
WIRING AND
CONNECTIONS
YES
REPLACE
WIRING OR
CONNECTIONS
34
REPLACE PUMP
CHECK FLUE GAS TUBE,
DIFFERENTIAL ANALOG
PRESSURE SWITCH AND
WIRING OR
CONNECTIONS
REPLACE
CONTROL
BOARD
Linea Plus AG
NO
CHECK WIRING
AND
CONNECTIONS
BETWEEN TERMINALS
YES
IS
THERE 24 Vdc
BETWEEN TERMINALS
M5.3 ON PCB & WHITE WIRE
ON HIGH LIMIT
THERMOSTAT
YES
A1
IS
THERE 24 Vdc M5.3 AND M3.3
ON PCB
NO
REPLACE THE
CONTROL BOARD
NO
RESET THE
HIGH LIMIT
THERMOSTAT
GREEN LED
LIGHT
YES
RESTART THE
TEST
IS
THERE 24 Vdc
BETWEEN TERMINALS
M5.3 ON PCB & RED WIRE
ON HIGH LIMIT
THERMOSTAT
YES
IS
THERE 24 Vdc
BETWEEN TERMINALS
M5.3 AND M3.4
ON PCB
NO
CHECK WIRING AND
CONNECTIONS
NO
CHECK WIRING AND
CONNECTIONS,
HIGH LIMIT
THERMOSTAT OR
PCB
YES
IS
THERE 24 Vdc
BETWEEN TERMINALS
M5.3 AND M3.5
ON PCB
NO
CHECK
COMBUSTION AND
CHECK &/OR REPLACE BURNER THERMISTOR AND
WIRING
YES
REPLACE THE
CONTROL BOARD
Linea Plus AG
35
A2
IS
RED LED
FLASHING
NOYES
SHOWING
FAULT CODE
YES
NO
5 Vdc
BETWEEN TERMINALS
M2.1 & M2.2 ON DISPLAY
BOARD
NO
5 Vdc
BETWEEN
TERMINALS
M9.1 & M9.2 ON
CONTROL
BOARD
NO
YES
REPLACE DIGITS
BOARD
YES
CHECK AND/OR
REPLACE WIRING
OR CONNECTIONS
WITH DISPLAY BOARD
FAULT
CODE 01
SHOWING
FAULT
CODE 02
SHOWING
REPLACE THE BICOULORED
LED ASSEMBLY
YES
NO
BICOULORED
LED ASSEMBLY
OK
YES
REPLACE THE
DIGITS BOARD
YES
SWITCH ON/OFF
SELECTOR TO
OFF POSITION
SWITCH MODE
SELECTOR TO
DHW POSITION
MAINS
PRESENT BETWEEN
M16.L & M16.N ON
CONTROL
BOARD
NO
RECHECK SUPPLY FUSE
& CONNECTORS TO
BOILER TERMINALS
REPLACE
CONTROL
BOARD
YES
YES
CHECK FUSES
F1 AND F2 ON CONNECTION
BOARD
FUSE OK
NO
REPLACE FUSE
NO
A4
NO
CHECK WIRING AND
CONNECTIONS ,HIGH
LIMIT THERMOST. AND
CONTROL BOARD
36
RESTART THE
HIGH LIMIT STAT
GREEN LED
LIGHT
GREEN LED
LIGHT
YES
YES
RESTART THE
TEST
NO
IGNITION
CONTROL OK
NO
REPLACE
IGNITION
CONTROL
RESTART THE
TEST
YES
REPLACE
CONTROL
BOARD
Linea Plus AG
VOKERA
LINEA PLUS AG
Rev. 1 08/03/2000
TEST B : CHECK CONTROL
IN DHW MODE
NO
START
TURN MODE
SELECTOR SWITCH TO
DHW.
DHW STAT AT MAX.
TURN ON TAP
DOES
BURNER
LIGHT
CHECK BOILER
STARTUP:
TEST A
YES
IS
THERE A
VOLTAGE >4 Vdc
BETWEEN TERMINALS
M3.10 & M3.11
ON PCB
YES
TURN DHW
THERMOSTAT AT
MIN.
NO
IS
FAN
ON?
YES
IS
D.A.P.S.
OK?
YES
CHECK FLUE
VENTURI TUBE
NO
CHECK FAN, WIRING
AND CONNECTIONS,
DIFFERENTIAL ANALOG
PRESSURE SWITCH AND
CONTROL BOARD
NO
REPLACE DIFFERENTIAL
ANALOG PRESSURE
SWITCH
Linea Plus AG
BURNER AND FAN
DO
SWITCH OFF
YES
TURN DHW
THERMOSTAT AT
MAX.
B
NO
IS
WATER FLOW
TEMPERATURE
>40 ˚C
YES
REPLACE
CONTROL
BOARD
WAIT WATER
FLOW
TEMPERATURE
>40 ˚C
NO
37
YES
START
SWITCH ON BOILER
AND SELECT MODE
TO WINTER C/H THERMOSTAT AT
MAX.
MAKE A LINK
BETWEEN PIN M16.TA
AND M16.TA ON
CONTROL BOARD
IS THE
3 WAY VALVE
ON CH
POSITION?
VOKERA
LINEA PLUS AG Rev. 1 08/03/2000
TEST C: CHECK CONTROL
IN C/H MODE
NO
DOES
BURNER
LIGHT
NO
CHECK BOILER
STARTUP
TEST A
YES NOYES
CHECK &/OR
REPLACE 3
WAY VALVE
IS
THERE A
VOLTAGE >4 Vdc
BETWEEN TERMINALS
M3.10 & M3.11
ON PCB
NO
YES
TURN CH
THERMOSTAT TO
VENTURI TUBE
MIN.
PRESENT BETWEEN
M11.1 & M11.2 ON
IS
FAN
ON?
YES
IS
D.A.P.S.
OK?
YES
CHECK FLUE
MAINS
CONTROL
BOARD
NO
CHECK FAN, WIRING
AND CONNECTIONS,
DIFFERENTIAL ANALOG
PRESSURE SWITCH AND
CONTROL BOARD
NO
REPLACE DIFFERENTIAL
ANALOG PRESSURE
SWITCH
REPLACE
CONTROL
BOARD
38
DO
BURNER AND FAN
SWITCH OFF
YES
TURN CH
THERMOSTAT AT MAX.
C
NO
WATER FLOW
TEMPERATURE
>40 ˚C
REPLACE
CONTROL
BOARD
WAIT WATER FLOW
TEMPERATURE
>40 ˚C
IS
NO
YES
Linea Plus AG
A
END
REPLACE IGNITION
CONTROL
NO
YES
SPARK AT
ELECTRODE
YES
IGNITION
YES
LOCKOUT
AFTER
IGNITION
YES
CHECK SENSING
ELECTRODE
AND LEAD
SENSING
ELECTRODE
AND LEAD
OK
NO
REPLACE SENSING
ELECTRODE
AND LEAD
NO
REPLACE
IGNITION CONTROL
NO
NO
IGNITION
CONTROL
OK
YES
IS
THERE MAIN
BETWEEN TERMINALS
M14.1 & M14.2
ON PCB
NO
IS
THERE 0 Vdc
BETWEEN TERMINALS
M5.3 & M5.4
ON PCB
YES
YES
IS
THERE MAIN
BETWEEN TERMINALS
L & N ON IGNITION
CONTROL
CHECK WIRING
YES
CONNECTIONS
CHECK SPARK
ELECTRODE AND
LEAD OR REPLACE
IGNITION CONTROL
NO
0 VDC
ON BOILER
FLOW
SWITCH
CHECK WIRING
NO
CONNECTIONS
NO
AND
YES
AND
CHECK WIRING
AND
CONNECTIONS
Linea Plus AG
NO
REPLACE GAS VALVE
IS
THERE A
VOLTAGE > 0.5 Vdc
BETWEEN TERMINALS
M3.11 ON PCB & GRAY
WIRE ON D.A .P.
SWITCH
GAS
VAL VE
OK
YES
CHECK GAS
NO
NOYES
CHECK THE FAN,
VENTURI
AND/OR D.A.P.S
IS
THERE A
VOLTAGE > 0.5 Vdc
BETWEEN TERMINALS
M3.11 & M3.10
ON PCB
YES
A1
FLOW
SWITCH
OK
NO
A3
YES
CHECK WATER
39
A4
FAULT CODE SHOWING 03
YES
A3
DOES THE
FLOW SWITCH PIN
OPERATE
NO
NO
FAULT CODE SHOWING 04
NO
FAULT CODE SHOWING 06
NO
FAULT CODE SHOWING 07
YES
REPLACE
CONTROL BOARD
YES
CHECK DHW
NTC SENSOR OR
CONNECTION
YES
YES
DO
THE BOILER
FLOW SWITCH
OPERATE
YES
CHECK THE
WIRING AND/OR
THE CONTROL
BOARD
CHECK AND/OR REPLACE THE
DIAPHRAGM.
CHECK THE CORRECT WATER DP
CHECK THE WATER CIRCUIT.
CHECK IF THE PUMP IS ON 3a SPEED
NO
CHECK/ REPLACE THE BOILER FLOW
SWITCH
NO
FAULT CODE SHOWING 08
NO
REPLACE
CONTROL BOARD
CHECK FLOW
NTC SENSOR OR
CONNECTION
YES
CHECK COMBUSTION
AND BURNER
THERMISTOR OR
CONNECTION
40
Linea Plus AG
B
END
BURNER AND FAN
TURN OFF TAP
YES
NO
BURNER , FAN
AND PUMP TURN
WATER FLOW TEMPERATURE
DHW FLOW
DO
OPERATE
YES
DO
OFF
NO
IS
>78 ˚C
NO
IS
SWITCH
OK
YES
NO
DO
BURNER AND
PUMP SWITCH
OFF
YES
IS
WATER FLOW
TEMPERATURE
>80 ˚C
NO
REPLACE
CONTROL
BOARD
NO
YES
REPLACE
CONTROL
BOARD
WAIT WATER FLOW
TEMPERATURE
< 80 ˚C
YES
IS
DHW FLOW
SWITCH
OK
REPLACE DHW
FLOW SWITCH
NO
REPLACE DHW
FLOW SWITCH
YES
IS DHW NTC OK
YES
REPLACE
CONTROL
BOARD
NO
NO
NO
REPLACE DHW
NTC
DOES
FUN
RUN
YES
IS
WATER FLOW
TEMPERATURE
< 78 ˚C
YES
DOES
FAN
SWITCH
OFF
NO
YES
IS DHW NTC OK
YES
REPLACE
CONTROL
BOARD
END
NO
REPLACE DHW
NTC
Linea Plus AG
41
C1
IS
WATER FLOW
TEMPERATURE
>78 ˚C
YES
REPLACE
CONTROL
BOARD
REPLACE FLOW
NTC
NO
NO
NO
DOES
PUMP
RUN
YES
IS FLOW
NTC OK
YES
REPLACE
CONTROL
BOARD
NO
NO
DO
BURNER AND
FAN SWITCH
OFF
YES
DOES PUMP
RUN
YES
IS
WATER FLOW
TEMPERATURE
< 78 ˚C
YES
DOES
PUMP SWITCH
OFF
NO
NO
IS FLOW NTC OK
YES
BOILER
IN LOCK OUT
STATE
YES
REPLACE
CONTROL
BOARD
NO
REPLACE
FLOW NTC
NO
REPLACE
CONTROL
BOARD
YES
END
SWITCH OFF BOILER.
WAIT ABOUT 10
SECS. AFTER
RESTART TEST
42
Linea Plus AG
C
DO
BURNER AND FAN
SWITCH ON
YES
WAIT WATER
FLOW
TEMPERATURE
< 80 ˚C
YES
NO
WAIT 3 MIN.
DO
BURNER AND FAN
SWITCH ON
NO
IS
WATER FLOW
TEMPERATURE
>80 ˚C
NO
REPLACE
CONTROL
BOARD
NO
REPLACE
CONTROL
BOARD
YES
YES
BETWEEN TERMINALS
REMOVE THE LINK
BETWEEN PIN M16.TA
AND M16.TA ON
CONTROL BOARD
TIMER JUMPER
ON
IS
THERE A
VOLTAGE < 1 Vdc
M3.10 & M3.11
ON PCB
REMOVE
JUMPER
RESTART
THE TEST
IS
YES
REMOVE
JUMPER
RESTART THE
TEST
NO
IS
THERE A
VOLTAGE >4 Vdc
BETWEEN TERMINALS
M3.10 & M3.11
ON PCB
YES
YES
IS
TIMER JUMPER
ON JP9
NO
NO
REPLACE
CONTROL
BOARD
IS
NO
FAN
ON?
Linea Plus AG
END
YES
WAIT 30 SEC.
DO
BURNER,
FAN AND PUMP
SWITCH
OFF
NO
C1
CHECK FAN, WIRING
AND CONNECTIONS,
DIFFERENTIAL ANALOG
PRESSURE SWITCH AND
CONTROL BOARD
NO
REPLACE DIFFERENTIAL
ANALOG PRESSURE
SWITCH
YES
IS
D.A.P.S.
OK?
YES
CHECK FLUE
VENTURI
43
SECTION 10 APPENDIX
Instructions for (A) Fitting Vokèra 24 Hour Time Switch (Part No. 201)
and Vokèra Digital 7 Day Time Switch (Part No. 202)
(B) Wiring to external Time Switches and Room Thermostat (C) Wiring for 'S' & 'Y' Plan Installations.
A. Installation of the Vokèra time switches (24 Hr and 7 Day)
Remove printed circuit board cover (5 screws). Remove the clock aperture blanking plate (1) fig.1 by
squeezing the 4 lugs on the rear of the plate together and push the plate out.
Remove the central circular disk from the plate (some force is necessary to break the holding nibs).
Remove the clock from its box. Wire the clock as shown in fig. 2. The wiring loom to the
clock comes complete with 4 spade connectors (for connection to the clock terminals), and a multi-plug for connection to the clock loom pre assembled on the appliance.
Replace the clock blanking plate back into the fascia of the appliance.
Insert the clock into the aperture from the back of the control panel, and secure the clock to the front control panel using the four screws provided.
Identify the internal clock wiring loom and disconnect the end plug. Push fit the multi-plug onto the multi-plug connector connected to the time clock. The multi-plug connector is polarised, it is therefore only possible to connect the multi-plugs one way.
When all electrical connections are made replace printed circuit board cover.
NO EXTERNAL OR INTERNAL CONTROLS
The loop between terminals = & TA remains when no external or internal controls are used (as fig. 5).
ROOM THERMOSTAT
Remove the loop between terminals = & TA and connect room thermostat between TA & TA (as fig. 6).
Fig. 1
Brown
Blue
Fig. 2
1
23
1
White
Red/White
Spare
45
Fig.3
44
Multiplug Connector
Clock
Vokera room
thermostat
Link 1 & 4 in r/stat
Fig. 4
1
3
2
4
5
6
Linea Plus AG
Live
Load Neutral
Fig. 5
Fig. 6
To internal timeclock multiplug connector (unused)
Room thermostat
IMPORTANT
DO NOT USE SMALLER TERMINAL BLOCK MARKED 'POS' 'POS' '-''S' WHEN CONNECTING INTERNAL OR EXTERNAL ELECTRICAL CONTROLS.
Fig. 5 Showing 230v input electrical connec­tion without room thermostat or internal time clock (Internal wiring loom for timeclock and link between = & TA remains)
Fig. 6 Showing 230v input electrical connec­tion and room thermostat connection (con­nected between TA & TA) without internal time clock. (Remove link between = & TA). Note: room thermostat contact rated at 230v. Should the room thermostat require a neu­tral or earth, connect neutral to one of the terminals marked N, and the earth to the earthing strip.
Fig. 7
Fig. 8
Internal time clock
Room thermostat
Fig. 7 Showing 230v input electrical con­nection and internal timer without room thermostat. Note: DO NOT remove link between ter­minals = & TA.
Fig. 8 showing 230v input electrical connec­tion internal timer and room thermostat. Note: i) Room thermostat contact rated at 230v.
Should the room thermostat require a neutral or earth, connect neutral to one of the terminals marked N, and the earth to the earthing strip.
ii) Terminal marked = is a spare terminal
used to connect controls. (Remove link between = & TA )
Linea Plus AG
Internal time clock
45
B. Wiring to External Time Switches and Thermostats.
(i) General Schematic Diagram.(i) General Schematic Diagram.
(i) General Schematic Diagram.
(i) General Schematic Diagram.(i) General Schematic Diagram.
Room
Thermostat
To ease wiring con­gestion at the appli­ance terminal strip, remove the wiring harness normally used for internal clock connection.
Earths have been omitted for clarity
Remove
Link between
= & TA
External
Time Switch
(ii) ACL Time Switch and Typical Room Thermostat
To ease wiring con­gestion at the appli­ance terminal strip, remove the wiring harness normally used for internal clock connection.
LOADLOAD
LOAD
LOADLOAD
COMMON
Appliance
Terminal
Block
Earths have been omitted for clarity
ACL Lifestyle
LP111 or LP711
Do not link L & 1
Appliance
Terminal
Block
Remove link between = & TA
(iii) Randall Time Switch and Vokera Room Thermostat.
To ease wiring con­gestion at the appli­ance terminal strip, remove the wiring harness normally used for internal clock connection.
Room
Thermostat
Earths have been omitted for clarity
Randall Time switches 103 103E 103E7
Do not link terminals 3 & 6 in time switch
Room
Thermostat
LOAD
COMMON
46
Appliance Terminal Block
Remove link between = & TA
Linea Plus AG
MODE SELECTOR SWITCH MUST BE IN THE POSITION.
To ease wiring conjestion at the appliance terminal strip, remove the wiring harness normally used for internal clock connection.
Wiring for 'Y' Plan Installations.
NOTE: WHEN USING A 'Y' PLAN INSTALLATION THE MODE SELECTOR
SWITCH WILL BE OVERRIDEN BY THE CONTROL CIRCUIT.
To ease wiring conjestion at the appliance terminal strip, remove the wiring harness normally used for internal clock connection.
Linea Plus AG
47
EXPLODED DIAGRAMS
1
46
13
44
44
14
45
6
41
50
51
KEY DESCRIPTION PLUS AG
1 Frame 01005212 6 Guard 1913 9 Case 2062 13 Plastic Trade Mark Label 1781 14 3A fuse 3478 15 2A fuse 8968 16 100 mA fuse 1947 17 Cover 10021849 20 Printed Circuit Board 1847 21 Led Light Guide 1858 22 Printed Circuit Board 10020477 25 Instrumental panel 10022029 27 Door panel 1996 28 Quick primer pressure gauge 1857 29 Hole cap 8654 30 Pin 1867
15 16
17
20
22
52
26
27
36
21
47
42
43
25
30
28 29
31 Film for display 1865 32 Push-push cover 1864 33 Hole cap 1861 34 Protection film 1866 36 O ring 1869 41 Screw 5080 42 Selector knob kit 01005072 43 Control knob kit 01005073 44 Edge clip 5128 45 Nut 5230 46 Transformer 10022659 47 Ignition module 10021848 50 Wiring harness 10021117 51 Wiring harness 1980 52 Wiring harness 1780
34
33
32
31
48
Linea Plus AG
KEY DESCRIPTION PLUS AG
1 Expansion vessel 2573 2 Flexible pipe 2164 3 Heating distributor manifold 10020439 4 Pipe 10023211 5 DHW actuator 10020330 6 Clip 2165 7 Water supply stop cock 10023567 8 Flexible pipe 10023570 9 Non return valve 10023569 10 Connection 1790 11 Heating cock 10023566
12 Heating cock 1789 13 Pipe 10023643 14 Nipple 1793 16 Water supply stop cock 1749 17 Water supply stop cock 10023568 22 Washer 5208 23 Washer 5026 28 Clip 1820 30 Nut 1824 32 Nut 1823 34 Clip 1890
Linea Plus AG
49
1
44
43
44
3
4
24
44
2
23
23
50
19
22
17
6
5
11
43
26
7
13
45
15
45
45
44
18
11
12
44
8
44
9
51
KEY DESCRIPTION PLUS AG
1 Heat exchanger 10020513 2 Pipe 10023209 3 Pipe 2051 4 Pump 10020438 5 Wiring harness 1845 6 Domestic water heat exchanger 1957 7 Connection 9807 8 Non return valve 2908 9 Pipe 10023208 10 Hight limit thermostat 2258 11 NTC sensor 8484 12 Pipe 10020519 13 Pipe 10023210 15 Flow governor 9430 16 Connection 2903 17 Bracket 2940 18 By-pass valve 1552 19 Pump lock key 9263 20 Venting plugs kit 01005137
16
20
39
38
33
32
31
30
29
43
21
27
28
21 Pressure switch 2044 22 Heat insulator 1988 23 O ring 6898 24 Automatic air vent bottle 0439 26 O ring 7999 27 Safety valve 1806 28 Motorized valve 2905 29 O ring connection 6919 30 Three way valve cover 2904 31 Fixing fork wrench 2906 32 Seating plate 7134 33 Three way valve overhault kit 01005127 38 Spring 6862 39 Screw 6903 43 Washer 5041 44 Washer 5023 45 Washer 5026 50 Wiring harness 10020530 51 Wiring harness 1873
50
Linea Plus AG
31
25
30
25
29
3
33
6
1
4
11
13
19
26
28
17
19
12
14
16
15
5
50
51
32
8
7
KEY DESCRIPTION PLUS AG
1 Air box bottom 10022390 4 NG Burner NP 10020511 4 LPG burner NP 10020512 5 Spark electrode 10022027 6 Air box clip 0442 7 Cover 2058 8 Washer 5072 9 Glass 3139 10 Glass flange 4007 12 Gas valve solenoid 10020838 13 Gas pipe 1839 14 Gas valve 10021021
Linea Plus AG
16 Gas pipe 1840 17 Gas cock 1787 19 Washer 5023 25 Washer 5905 26 Nut 1823 28 Clip 1890 30 Air box side 2060 31 Air box side 2059 32 Burner thermostat 2600 33 Bracket 2762 50 Wiring harness 10021947 51 Wiring harness 10022112
51
4
8
6
7
14
32
31
12
17
33
19
23
5
50
51
20
24
25
27
KEY DESCRIPTION PLUS AG
4 Pressure differential switch 2677 5 Silicone tube 1457 6 Brass cap 8086 7 Block with combustion analysis check 8085 8 Fan flue connection 8083 12 Clamp for 60 diam. tube 5916 14 Washer clamp 5917 17 Fan to flue connector 7280 19 Fan 2076 20 Hood assembly 1968 23 Combustion chamber assembly 10020514 24 Combustion chamber back panel 10020518
52
30
24 Combustion chamber lateral panel 5271 27 Combustion chamber front panel 10020517 30 Self tapping screw 5080 31 Depressure tube 6985 32 Pressure tube 7948 33 1/8" lock nut 4807 50 Wiring harness 1870 51 Wiring harness 10020529
Linea Plus AG
ABLING AND DISABLING ELECTRONIC FUNCTIONS
Certain electronic functions on the Linea range of appliances can be abled or disabled ac­cording to customer preference. The selec­tions can be made by the addition or removal of jumper tags situated on the printed circuit board. Refer to fig. 40 for jumper positions on printed circuit board.
Hot Water Preheat Function:
To disable remove jumper JP6 To able add jumper to JP6
C/H Delay Timer:
To disable add jumper to JP9 To able remove jumper from JP9
Natural Gas / LPG
For Nat gas add jumper to JP8 For LPG remove jumper from JP8
Jumpers JP1, JP2, JP3, JP4, JP5 and JP7 also exist on the printed circuit board DO NOT under any circumstances add or remove jump­ers at these points.
Spare jumpers are available from Vokera stockists. Part no. 7232.
Linea Plus AG
53
FUNCTIONAL FLOW DIAGRAM
Fig. 39
NOTE: L-N-E CONNECTION IS ADVISABLE
Key F1 Fuse 100 mA F (on 240V circuit)
F2 Fuse 2A F (on 230V circuit) R.T. Room Thermostat TSH Heat Time Switch S.F.S. H/W Flow Switch P.S. Pressure Switch H.L. Hight limit thermostat S.R. Heat Thermistor S.S. H/W Thermistor MOD Modulator Coil F Fan P Pump 3W Motorised Valve SP/SE E. Spark/sense ectrode OPE Solenoid Operators B.C.B. Burner Control Board B.E.B. Boiler control board S.B. Secondary board
JP8 Natural gas or L.P.G. selector JP9 Timer on-off selector JP7 Room thermostat or remote control jumper PT2 C/H Temperature Control PT3 D/H/W Temperature Control PT1 (S.B.) Selection of 0-reset / winter-summer DS1-DS2 Temperature/alarm display TA1 Combustion analysis switch TRF1 Transformer RL1 Ignition Relay RL2 Pump Relay RL3 3 Way Relay ISO1 Fan triac L1 Led OK (green) L2 Led alarm (blink red) TRF1 Transformer PAD Differential Analogue Pressure Switch
54
Linea Plus AG
white-red
white
brown
blue
blue
brown
blue
brown
red
blue
brown
black
white-light blue
white-brown
white-purple
GREEN
RED
red
white
white
purple
purple
brown
brown
white
red
balck
black
orange
blue
grey
grey
grey
blue
blue
brown
brown
black
red
red
GENERAL LAYOUT & ILLUSTRATED WIRING DIAGRAM
Fig. 40
NOTE: L-N-E CONNECTION IS ADVISABLE
CONTROL SWITCHING OF TIME CLOCK AND ROOM THERMOSTAT IS 230 V.a.c.
Linea Plus AG
55
PRELIMINARY ELECTRICAL SYSTEM CHECKS
A. EARTH CONTINUITY CHECK - appliance must be
electrically disconnected - meter set on (ohms) x 1 scale and adjust zero if necessary.
a) Test leads from any appliance earth point to earth pin on plug - resistance should be less than 1 (ohm). If the resistance is greater than 1 (ohm) check all earth wires for continuity and all contacts clean and tight.
B. SHORT CIRCUIT CHECK - appliance electrically disconnected, all switches ON (including stats) ­a) meter set on (ohms) x 1 scale. Test leads from L to N in appliance terminal strip/block
- if meter reads 0 then there is a short circuit. b) meter set on (ohms) x 100 scale
Repeat test with leads from L to E. If meter reads less than (infinity) there is a fault.
NOTE - Should it be found that the fuse has failed but no fault is indicated, a detailed continuity check (i.e. by disconnecting and checking each component) is re­quired to trace the faulty component. It is possible that a fault could occur as a result of local burning/arcing but no fault could be found under test. However, a detailed visual inspection should reveal evidence of burning around the fault.
D. RESISTANCE TO EARTH CHECK
Appliance must be disconnected from mains supply and meter set on (ohms) x 100 scale. All switches, including stats, ON - Test leads from L to E - if meter reads other than infinity () there is a fault which should be isolated. A detailed continuity check is required to trace the faulty component.
IMPORTANT - This series of checks are the first electrical checks to be carried out during a fault finding procedure. On completion of the service/fault finding task which has required the breaking and remaking of electrical connections then the checks - A. Earth Conti­nuity. C. Polarity and D. Resistance to Earth - must be repeated.
C. POLARITY CHECK
Appliance connected to mains supply and meter set on 300V ac scale. Test at appliance terminal strip:-
a) Test leads from L to N - meter reads approx 230V ac b) Test leads from L to E ( ) - meter reads approx
230 V ac
c) Test leads from N to E ( ) - meter reads from O-15V
ac*
Thus the terminal marked L is the live terminal. If the low* V ac reading is given on terminals other than N to E ( ) there is an electrical fault.
Repeat the test at the appliance plug/inlet spur to check the wiring system up to the appliance and rectify any fault. If necessary repeat the test at the supply system socket/spur - if the fault also occurs at this stage then there is a house system fault which requires attention by the ELECTRICITY AUTHORITY. The customer should be warned not to use the appliance until this examina­tion has been carried out.
Linea Plus AG
56
SECTION 11 L.P.G. INSTRUCTIONS
11.1 Gas Rates (LPG)
Min. Gas Rate
Max. Gas Rate
11.2 Burner Details (LPG)
Main Burner Main Burner Injectors Burner Pressure Max. Rate
Burner Pressure Min. C/H Burner Pressure Min. DHW
11.3 RELATED DOCUMENTS
BS 6798 1987 Boilers of rated input not exceeding 60kW BS 5449 Part 1 1990 Forced circulation hot water systems BS 5546 1990 Installation of gas hot water supplies for
BS 5440 Part 1 1990 Flues BS 5482 Part 1 1994 Domestic Butane & Propane Gas burners in
Plus AG
410
1430
Plus AG
POLIDORO NP16
16X0,77 36,0 mbar 3,70 mbar 3,70 mbar
domestic purposes.
permanent dwellings
11.4 GAS SUPPLY
A gas supply should be connected to the boiler by a competent L.P.G. installer and should be of sufficient size to supply the boiler at its maximum output.
An existing supply should be checked by the installer or L.P.G. supplier to ensure that it can deal with the rate of gas supply required for all the appliances when they are in use at the same time.
11.5 GAS SUPPLY INSTALLATION
11.5.1 Inspect the entire installation including the
meter, test for soundness and purge.
11.6 CHECK BURNER PRESSURE
11.6.1 The heat inputs for high and low gas rates are
factory set to the maximum values given in section 11.2 but it is necessary to check/ adjust this when commissioning the appli­ance.
11.6.2 Turn off the main electrical supply. Gain access to the interior as instructed in 5.3.1 -
5.3.2.
11.6.3 Gain access to the electrical terminals as
5.7.2. Ensure the Jumper at point JP8 is removed.
57
11.6.4 Locate the main burner pressure test point (fig. 19) and slacken the screw half a turn in an anti clockwise direction. Attach a suitable pressure gauge as described at 6.6.5.
IMPORTANT: Before measuring gas pres­sures it is imperative that the protective cover over the gas valve adjustment screw is removed (fig. 36). Turn on electricity supply. Turn mode selector switch to the position and fully open a domestic hot water tap to operate boiler in dhw mode. Adjust hot water control knob to it’s maximum setting.
11.6.5 The pressure reading for maximum output should be :
Plus AG (LPG)
36.0 mbar (Plus or minus 3.6 mbar)
If the pressure is wrong it should be adjusted as instructed in 8.23. (N.B. Whenever the maximum rate is adjusted, check and adjust the minimum rate too).
Linea Plus AG
11.6.6 Reduce the domestic water flow rate to ap­proximately 3-4 litres/min. Turn the domestic control knob slowly to minimum the boiler output will reduce to the minimum setting. If low flame cannot be established in this way, turn off the electricity supply, and disconnect a grey wire from the modulator coil. Switch on the electricity supply, the boiler will now light at the minimum setting.
11.6.7 When low flame is established the pressure reading should be :
Plus AG (LPG)
3.7 mbar (Plus or minus 0.37 mbar)
If it is different adjustment should be made in accordance with the instructions in 8.23.
11.6.8 If a grey wire was disconnected from the modulator coil to check the minimum setting, turn off the electricity supply and reconnect the wire.
11.7 Maximum Rate in Central Heating Mode
The Linea range does not require any adjust­ment to the maximum heat requirement of the system load.
11.8 Setting the Minimum Rate for Central Heat­ing
The Linea range does not require any adjust­ment to the minimum heat requirement of the system load.
11.9 Soft light ignition and range rating for central heating is fully automatic, no adjustment is necessary.
11.10 Turn mode selector to the OFF position, dis­connect pressure gauge, re-tighten screw. Relight boiler.
11.11 Re- check for gas soundness.
11.12 Replace electrical controls panel.
11.13 Refix the boiler casing (fig. 24).
11.14 Hinge up controls facia and secure using the
2 screws (fig. 25).
Linea Plus AG
58
Linea Plus AG
Linea Plus AG
Linea Plus AG
energizing home heating
Vokèra Ltd.
Catherine House, Boundary Way, Hemel Hempstead, Herts, HP2 7RP
Cod. 10023217 - 20/02 - Ed. 3
Email: enquiries@vokera.co.uk Web: www.vokera.co.uk
General Enquiries - Tel: 01442 281400 Fax: 01442 281460
Technical Advice - Tel: 0870 333 0520
Spare Parts - Tel: 0141 945 6820
After Sales Service - Tel: 0870 333 0220
Vokèra Ireland
West Court, Callan, Co Kilkenny
Tel: 056 55057 Fax: 056 55060
Vokèra Ltd. reserve the right to change the specifications without prior notice. Consumers’ statutory rights are not affected.
A Riello Group Company
COLLECTIVE MARK
“Vokèra”
supports Benchmark
Loading...