Related Documents5
Location of Appliance5
Gas Supply5
Flue System5
Air Supply6
Water Circulation (C/H)6
Pipework6
By-Pass6
System Design6
Draining Taps6
Air Release Points7
Filling Point7
Electrical Supply7
Showers7
Section 5Installation8
Delivery8
Unpacking8
Siting the Appliance9
Connecting the Gas & Water9-10
Fitting The Flue (Horizontal)13
Fitting The Flue (Vertical)14
Electrical connections22
Section 6Commissioning17
Gas Installation17
Initial Flushing of Pipework17
Initial Filling of System17
System Design Pressure17
Filling the Hot Water System17
Checking Electrical supply17
Lighting The Boiler17
Checking Burner Pressures18
Range Rating C/H19
Checking The Flue System19
Checking The Heating Thermistor19
Regulating The C/H System19
Final Flushing The C/H System19
Filling & Testing H/W System19
Final Checks For Operation20
Concluding Operations20
SectionSubjectPage no
Section 7Instructing The User20
Section 8Servicing Instructions20
General20
Recommended Routine Servicing20
Annual Servicing20
Replacement Of Parts21
To Gain General Access21
To Remove:
Room Sealed Chamber Front Cover21
Main Burner & Electrode22
Main Burner Injectors22
Main Heat Exchanger22
Flue Fan23
Pressure Differential Switch23
Combustion Chamber Insulation Panel23
Ignition Control Box24
Gas Control Valve24
Pump25
Domestic Flow Switch25
Diverter Valve & Flow Switch Manifold25
Domestic H/W Heat Exchanger26
Diverter Valve26
Main Expansion Vessel26
Safety Valve26
Flow Microswitch26
Motorised Valve26
Printed Circuit Board26
Display Printed Circuit Board26
Safety Thermostat26
Thermistor Sensors26
Pressure Gauge26
Setting Gas Pressures27
Combustion Analysis27
Section 9Operational Checks & Wiring28
Sequence of Functions28
Diagnostic Error Codes29
Fault Finding Guides30-40
Section 10Appendix41
Internal Time Clock Installation41-42
External Time Clock Installation42
S & Y Plan Installations43
Exploded Diagrams45-51
Short Spare Parts List52
Abling & Disabling Controls52
Functional Flow Diagram53
Illustrated Wiring Diagram54
Preliminary Electrical System Checks55
LPG Instructions56-57
Linea Max
Supplied By www.heating spares.co Tel. 0161 620 6677
Supplied By www.heating spares.co Tel. 0161 620 6677
SECTION 1 INTRODUCTION
26
25
24
23
22
21
The Vokèra Linea Max is a combined central heating and domestic hot
water appliance. By design it incorporates
full sequence electronic ignition, circulating
pump, expansion vessel, safety valve,
temperature gauge, pressure gauge, 3 port
diverter valve and filling loop.
It is produced as a room sealed appliance
suitable for floor mounting only. It is provided with a fan powered flue outlet with an
annular co-axial combustion air intake, twin
flue option is also available.
Fig. 1
1413
35
This appliance is designed for use with a
sealed heating system only and is not
intended for use on an open vented system.
An automatic range-rating facility is incorporated in the boiler for the central heating
system in conjunction with the electronic
burner modulation. The domestic hot water
(dhw) service utilises a motorised valve
combined with a 3 port diverter valve to give
hot water priority which also benefits from a
heatbank having a nominal capacity of 58
litres of circulating primary hot water positioned at the rear of the appliance.
17Hot Water Outlet
18Safety Valve Outlet
19Central Heating Flow
6
20Central Heating Return
7
21Motorised Valve
22Pump
8
23Sensing Electrode
24Expansion Vessel
9
25Fan
10
26Automatic Air Vent
27Timeclock Aperture (Optional)
11
28Front Door Panel
29Pressure Gauge
30Status LED
31Central Heating Temperature Control
12161718201915
32Mode Selector Switch
33Hot Water Temperature Control
34Temperature Indicator
35Combustion Switch
34
Linea Max
31
2928303233
27
1
Supplied By www.heating spares.co Tel. 0161 620 6677
SECTION 2DESIGN PRINCIPLES AND OPERATING SEQUENCE
2.1Fig.1 illustrates the general layout of components. Fig.2 illustrates the operating principles described below.
2.2Central Heating Mode
2.2.1When the various switches and controls
impose a demand for heat, the pump is
started. The flow of water from the pump
operates a flow switch. This in turn energises the electronic circuitry. The fan is
started, the gas valve is energised at an
intermediate rate and the electronic ignition
goes through an ignition attempt.
2.2.2The burner ignition is checked by the electronic circuitry to ensure correct ignition of
the burner.
2.2.3As water temperature increases this is
sensed by the temperature sensor on the
flow pipe which modulates the burner to
match the heat output to the heat requirement of the system.
2.2.4Depending on the load, either a) the water
temperature will continue to rise and the
burner will continue to modulate down until
the maximum setting is reached at which
point the burner is switched off, or b) the
water temperature will fall and the burner
will return to a higher output to match the
demand.
flue outletair intake
26
24
22
21
2.3Domestic Hot Water Mode
2.3.1The appliances incorporate a hot water
preheat facility. The appliance will therefore
ignite periodically to maintain heat within the
appliance.
2.3.2The appliance will operate in domestic hot
water mode whenever the mode selector
switch is on regardless of mode selector
switch position and any demand for central
heating.
2.3.3The diverter valve will automatically energise into the hot water position after central
heating demand, or will stay in the hot water
position after hot water demand. Opening a
draw off tap will energise the pump and fan
sending primary water to the domestic hot
water heat exchanger.
2.3.4Temperature control is transferred to the
domestic hot water thermostat
(potentiometer) which modulates the burner
output between high and low flame to
maintain an average heat input to suit the
dhw output required.
2.3.5An overrun is incorporated in the boiler in
both c/h & dhw modes. The fan overruns
until the boiler water cools to approximately
80°C (176°F).
2.4Safety Devices
2.4.1In both central heating and hot water modes
safe operating is ensured by:
A. Differential pressure unit in the primary
circuit which prevents burner operation if
water flow rates are too low.
B. An electronic device that checks the
primary pressure unit for activation. Failure
2
4
7
11
results in deactivation of the pump, after
approximately 10 minutes of operation.
C. A safety thermostat, which interrupts the
control circuit shutting off the gas valve. At
the same time the fan will still operate.
D. A Pressure differential switch in the flue
system to check the fan's operation before
9
allowing ignition.
2.4.2A safety valve is provided to relieve excess
16
pressure from the primary circuit.
2.4.3Frost Thermostat
The appliance has a built in frost protection
circuit. Should the boiler temperature sensed
at the primary thermistor fall below 5°C, the
boiler will operate in central heating mode and
continue to operate until the primary thermistor reaches approximately 40°C.
A
B
KEY:
AGas
BHot Water Outlet
DE
C
Fig. 2
This drawing is indicative only and does
not accurately represent pipe positioning.
CCold Water Inlet
DCentral Heating Flow
ECentral Heating Return
2
Linea Max
Supplied By www.heating spares.co Tel. 0161 620 6677
SECTION 3TECHNICAL DATA
3.1Units Dimensions and values are given in
the preferred Sl Units with Imperial units in
brackets where applicable.
Water content: 65 litres (14.3 gals)
For further dimensions see fig.13
3.3Connection sizes
Heating flow and return: Nut and olive for
22mm o.d.Cold water inlet: Nut and olive for
15mm o.d.Hot water outlet: Nut and olive for
15mm o.d. Gas Service: Nut and olive for
15mm o.d. Safety valve outlet: Nut and olive
for 15mm o.d.
Flue outlet/Air inlet: nom dia 60/100mm
specially supplied with boiler (concentric).
Flue outlet/Air inlet: nom dia 80/80mm
specially supplied with boiler (twin).
3.4Installation Requirements
3.4.1Clearances (Horizontal or Vertical Flue)
Minimum - above casing 20mm (3/4in)
Minimum - In front 600mm (24in)
Minimum - At sides 12mm (½in) from casing
3.4.2Maximum heating system contents approx.
100 litres (21.9 gals). Acceptance capacity
of expansion vessel 10 litres (2.2 gals).
3.4.3Means of filling sealed system: To accord
with BS and/or local Water Authority requirements.
3.4.4Maximum flue lengths
Using extension tubes the flue may be
extended to the following lengths.
Concentric
Horizontal: 1.8 metres max.
Vertical: 4.4 metres max.
Twin: 6m/6m + concentric terminal.
(Horizontal termination only)
The reduction in flue length for each bend
used is:
Concentric Flue
Reduction in flue lenght
Bend
90°850 mm
45°425 mm
Offset850 mm
for each bend
3.5Electrical Details
Mains supply 230v ~ 50Hz Fused 3A
Internal fuse rating F2A and T100mA
Power consumption: 150W
3.6Performance and Limitations
Max. input 31.0 kW (105,802 Btu/h)(net)
Min. input 11.9 kW (40,614 Btu/h)(net)(c/h)
Min. input 10.5 kW (35,836 Btu/h)(net)(h/w)
Max. input 34.4 kW (117,406 Btu/h)(gross)
Min. input 13.2 kW (45,051 Btu/h)(gross)(c/h)
Min. input 11.6 kW (39,590 Btu/h)(gross)(h/w)
Max. output 28.0 kW (95,563 Btu/h)
Min. output 9.9 kW (33,788 Btu/h)(c/h)
Min. output 8.7 kW (29,692 Btu/h)(h/w)
Central Heating output range
Max. 28.0 kW (95,563 Btu/h)
Min. 9.9 kW (33,788 Btu/h)
Designed temp rise 20°C
Max. flow temperature 85°C
Nominal hot water production
Max.water flow at temp rise of 25°C
16.1l/min Max.water flow at temp rise of
35°C 11.5l/min
Nominal hot water production (For first 10
minutes) (Inlet temp 12°C)
Water flow at 18 l/min - average water
temperature 43°C.
Gas Pressures
Max. gas pressure 10.1mbar
Min. gas pressure C/H 1.6mbar
Min. gas pressure H/W 1.3mbar
Gas Rate
Max. 3.27 m3/h 115.8 ft3/h
Min. 1.10 m3/h 39.0 ft3/h
Note: Use gross input values when gas
rating the appliance
Burner Details Main burner:
Polidoro type NP14
Main burner injectors 14 x 1.35
Min. water flow (dhw) 2.0l/min. (0.45 gal/
min) Min central heating flow rate through
appliance 350litres/hr (1.28 gal/min)
3.9Working Pressure Hot Water System
Maximum 6.0 bar/90psig
Minimum 0.6 bar/7psig
For LPG instructions see page 62
Twin Flue
Reduction in flue lenght
Bend
90°850 mm
45°850 mm
Linea Max
for each bend
3
Supplied By www.heating spares.co Tel. 0161 620 6677
3.10Central Heating Pump Duty
Water
pressure
mbar
700
600
500
400
300
200
100
0
123456789101112131415
X 100
Water flow
l/h
Fig. 3
4
Linea Max
Supplied By www.heating spares.co Tel. 0161 620 6677
SECTION 4 GENERAL REQUIREMENTS
4.0General Requirements
This appliance must be installed by a
competent person in accordance with the
Gas Safety (Installation & Use) Regulations
1998.
4.1Related Documents
The installation of this boiler must be in
accordance with the relevant requirements
of the Gas Safety (Installation & Use)
Regulations 1998 the Local Building Regulations, the current l.E.E. Wiring Regulations,
the by-laws of the local water undertaking,
and in Scotland, in accordance with the
Building Standards (Scotland) Regulation. In
Ireland the local building regulations (IE).
It should be in accordance also with any
relevant requirements of the local authority
and the relevant recommendations of the
following British Standard Codes of Practice:
BS 68911988Low pressure installation pipes
BS 67981987Boilers of rated input not exceeding 60kW.
BS 5449Part 11990Forced circulation hot water systems
BS 55461990Installation of gas hot water supplies
A compartment used to enclose the boiler
must be designed and constructed specifically for this purpose. An existing cupboard
or compartment may be used provided that
it is modified for this purpose.
Details of essential features of cupboard/
compartment design including airing cupboard installations are given in BS
6798:1987. This appliance is not suitable for
external installation.
4.3Gas Supply
A gas meter is connected to the service pipe
by the gas supplier.
An existing meter should be checked,
preferably by the gas supplier, to ensure that
the meter is adequate to deal with the rate of
gas supply required for all appliances it
serves.
Installation pipes should be fitted in accordance with BS 6891:1988.
for domestic purposes (2nd family gases).
vessels & ancillary equipment for sealed water
systems.
4.2Location of Appliance
The combination boiler may be installed in
any room or internal space, although particular attention is drawn to the requirements
of the current l.E.E. Wiring Regulations, and
in Scotland, the electrical provisions of the
Building Regulations applicable in Scotland,
with respect to the installation of the combination boiler in a room or internal space
containing a bath or shower.
Where a room-sealed appliance is installed
in a room containing a bath or shower, any
electrical switch or appliance control, utilising mains electricity, should be located in
such a position that it cannot be touched by
a person using the bath or shower.
The location chosen for the boiler must
permit the provision of a satisfactory flue
and termination. The location must also
permit an adequate air supply for combustion purposes and an adequate space for
servicing and air circulation around the
boiler.
Where the installation of the boiler will be in
an unusual location special procedures may
be necessary and BS 6798:1987 gives
detailed guidance on this aspect.
Pipework from the meter to the boiler must
be of adequate size. Pipes of a smaller size
than the boiler inlet connection must not be
used.
The complete installation must be tested for
soundness as described in the above code.
N.B. If the gas supply for the boiler serves
other appliances ensure that an adequate
supply is available both to the boiler and the
other appliance when they are in use at the
same time.
4.4Flue System
The terminal should be located where
dispersal of combustion products is not
impeded and with due regard for the damage or discoloration that might occur to
building products in the vicinity (see fig 4).
The terminal must not be located in a place
where it is likely to cause a nuisance.
In cold and/or humid weather water vapour
may condense on leaving the flue terminal.
The effect of such steaming must be
considered.
Linea Max
5
Supplied By www.heating spares.co Tel. 0161 620 6677
For protection of combustibles, refer to BS
5440:1 where the terminal is less than 2m
(6.6ft) above a pavement or platform to
which people have access (including any
balcony or flat roof the terminal must be
protected by a guard of durable material).
A suitable guard is available from Vokéra
Ltd. Part No 018, G.C. No. 301 106
This guard must be fitted centrally over the
terminal. Mark the positions of the fixings,
drill the wall and secure using wall plugs and
3 of 1½" No.8 plated screws.
Fig. 4
Terminal position for fan assisted boiler
(minimum distance) mm
A-Directly below an open window or other300
opening (e.g. air brick)
B-Below gutters, soil pipes or drain pipes25
C-Below eaves25
D-Below balconies or car port roof25
E-From vertical drain pipes and soil pipes75
F-From internal or external corners25
G-Above ground or below balcony level300
H-From a surface facing a terminal600
I-From a terminal facing a terminal1200
J-From an opening in the car port (e.g. door
window) into dwelling.1200
K-Vertically from a terminal on the same wall1500
L-Horizontally from a terminal on the same wall300
M-Horizontally from a vertical terminal to a wall300
NOTE: The flue must be terminated in a place not likely
to cause a nuisance.
4.5Air Supply
The following notes are intended for general
guidance.
The room sealed fan flued boiler does not
require a permanent air vent for combustion
air supply.
Where installed in a cupboard or compartment ventilation is required for cooling.
The table following gives the recommended
minimum effective areas of such air vents.
Air Vent areas
Positions
of
Air Vents
High
Level
Low
Level
Air From
Room or
Internal
Spaces
310 cm
2
48 in
310 cm
2
48 in
2
2
Air Direct
From
Outside
155 cm
2
24 in
155 cm
2
24 in
2
2
4.6Water Circulation (Central Heating)
Detailed recommendations are given in
BS 6798:1987 and BS 5449:1:1990 (for
smallbore and microbore central heating
systems).
4.6.1The following notes are given for general
guidance.
4.6.2Pipework
Copper tubing to BS 2871:1:1971 is recommended for water pipe. Jointing should be
either by capillary soldered or with compression fittings.
Where possible, pipes should have a gradient to ensure air is carried naturally to air
release points and water flows naturally to
drain taps.
It should be ensured as far as possible that
the appliance heat exchanger is not a
natural collecting point for air.
Except where providing useful heat, pipes
should be insulated to prevent heat loss and
to avoid freezing. Particular attention should
be paid to pipes passing through ventilated
spaces in roofs and under floors.
4.6.3By-Pass
An automatic by-pass is incorporated in the
boiler, but systems should be designed to
ensure that with all radiators turned off a
flow rate of at least 350 litres/hour (1.28
gals/min) is achieved through the system.
See 6.9.4
4.6.4System Design
Vokèra Ltd recommend a 2-pipe system. Single pipe systems are more liable to be troublesome unless carefullly designed and installed.
4.6.5Draining Taps
These must be located in accessible positions to permit the draining of the whole
system. The taps must be at least 15mm
nominal size and manufactured in accordance with BS 2879:1980.
6
Linea Max
Supplied By www.heating spares.co Tel. 0161 620 6677
4.6.6Air Release Points
These must be fitted at all high points where air
will naturally collect, and must be sited to
facilitate complete filling of the system.
4.6.7The appliance has an integral sealed expansion vessel to accommodate the increase of
water volume when the system is heated. It
can accept up to 10 litres (2.2gals) of expansion water. If the appliance is connected to a
system with an unusually high water content.
Calculate the total expansion and add additional sealed expansion capacity as appropriate.
In general, modern systems will present no
problem.
4.6.8Filling Point
A method for initially filling the system and
replacing water lost during servicing is provided on the appliance.
In the event that this method is not suitable in
a particular area, contact the local authority for
preferred methods.
4.7Electrical Supply
The appliance is supplied for operation on
230V ~ 50Hz electricity supply. It should be
protected with a 3-amp fuse.
THIS APPLIANCE MUST BE EARTHED.
The method of connection to the mains electricity must allow complete isolation from the
supply.
The preferred method is by using a fused
double pole switch with a contact separation of
at least 3mm.
The switch must supply ONLY the appliance
and immediate electrical control circuits (e.g.
programmer / room thermostat)
Alternatively, use an unswitched shuttered
socket outlet with a fused 3-pin plug both
complying with BS 1363.
4.8Showers
If a shower control is to be supplied from the
combination unit it should be of the type which
incorporates a thermostatic control and by
design is suitable for use with a combination
boiler. Check application with shower manufacturer.
4.9Timber framed buildings
If the appliance is to be fitted in a timber framed
Building, it should be fitted in accordance with
the Institute of Gas Engineers publication (IGE/
UP/7) Guide for Gas Installations in Timber
Frame Buildings.
C/H Return
Valve
C/H Flow
Valve
Hot Water
Outlet
Safety Valve
Outlet
Cold Water
Inlet Stopcock/
filling valve
Gas
Cock
Linea Max
Base Tray
Fig. 5
7
Supplied By www.heating spares.co Tel. 0161 620 6677
SECTION 5 INSTALLATION
Fig. 6
Fig. 7
5.1Delivery (fig. 6)
The appliance is delivered in a crated heavy
duty cardboard carton.
5.2Unpacking (fig. 6 & 7)
Stand the boiler the correct way up and remove the surrounding timber frame.Slide the
protecting packaging from around the appliance. Remove appliance from base pallet.
The appliance comes complete with a base
tray which can easily be removed. The purpose of the base tray is that it can be used as
a template to preplumb the appliance before
final fitting.
To remove the base plate from the appliance,
push to release the control panel door, locate
the small tool inside and undo the two screws
securing the front panel to the appliance and
remove. Loosen and undo the Central heating
flow and return unions, cold water inlet union,
hot water outlet union, gas union and safety
valve union.See figs 5 & 9.
Ensure the filling inlet tap is in a horizontal
position. Either slide the base plate out from
the rear of the appliance or slide the appliance
forwards off the base plate. The appliance is
on wheels easing this operation.
The Base Tray Contains:
Central heating valves (2)
Gas service tap (1)
Cold water Filling/Inlet (1)
Hot water outlet Connection (1)
Found packed inside the appliance:
Safety valve outlet pipe (1)
Filling loop hose (1)
Various washers
Base plate screws (2)
Spare front panel door tool (1)
Restrictor ring (1)
Fig. 8
8
Flue kit supplied in separate carton.
Fig. 9
Linea Max
Supplied By www.heating spares.co Tel. 0161 620 6677
Fig. 10
Fig. 11a
Rear pipework
reference bar.
Base tray securing screws
Fig. 11
5.3Siting the Appliance
5.3.1The appliance is floor standing. Place the
base plate on a smooth firm and level surface.
The back of the base tray can be pushed flush
against the back wall if necessary (this will still
allow piping behind the appliance see figs 5
&10). Special floor protection is not required
and the floor must be capable of supporting
the weight of the appliance See section 3..
If the appliance is to be fitted in a timber
framed building it should be fitted in accordance with the Institute of Gas Engineers publication (IGE/UP/7) 'Guide for Gas Installations in Timber Frame Buildings'.
5.3.2If necessary drill holes through the wall to
allow passage of pipework before final base
plate fixture see fig 10.
5.3.3Drill and plug the floor for 4 - 1" No. 10 screws
and screw the base tray firmly into position
using rust proof countersunk screws.
5.3.4Refer to figs.13 for relevant dimensions for
locating the flue hole: Where it is remote from
the boiler take special care to ensure hole is at
the correct level. Drill a 105mm hole through
the wall to allow passage of the flue pipe.
5.3.5Connecting the Gas and Water
5.3.6Figs. 5 and 13 show the locations of the
fittings.
5.3.7When connecting pipework to valves do not
over tighten nuts, use another spanner to
apply counter force to avoid damaging/
moving the valves/baseplate.
5.3.8Gas Supply
Connecting the gas supply.
Connect a 15mm gas pipe to the gas
service tap and tighten the union nut securing the tap to the appliance.
Pipework from the meter to the appliance
must be of adequate size.
A minimum gas pressure of 20mb (8 in.
w.g.) must be available at the appliance
inlet at full flow rate. See section 3.
DO NOT use pipes of a smaller size than
the appliance inlet connection.
5.3.9Central Heating
Connect the central heating pipework
(22mm o.d) to the respective valves, right
hand: flow, left hand: return, and tighten the
nuts.
5.3.10Hot Water
Connect a 15mm pipe to the hot water
outlet connection of the appliance. Tighten
the nut.
If the hot water system does not include a
tap below the hot water outlet connection,
provide a suitable drain tap to permit
draining of the appliance hot water side
during servicing.
Fig. 12
Linea Max
9
Supplied By www.heating spares.co Tel. 0161 620 6677
5.3.11Cold Water
Connect a 15mm cold water service pipe to
the inlet stopcock of the appliance. Tighten
the nut.
If the cold water supply is liable to high
pressure or large pressure fluctuations, a
flow/pressure regulator should be fitted in
the supply pipe.
Should the appliance be subject to 'mains
knock' it would be advisable to install a non
return valve in the hot water outlet pipe to
prevent unnecessary activation of the
domestic flow switch.
5.3.12Safety Valve Discharge
Connect a 15mm pipe to the discharge
outlet of the appliance.
The discharge should terminate facing
downwards outside the building in a position
where discharging (possibly boiling) water
will not create danger or nuisance; but in an
easily visible position.
5.3.13Once all relevant pipework has been installed
and the flue hole has been cut,the appliance
can be slid into position.
If the filling inlet valve is in the off position
(verticaly up) remove the handle from the
valve (this will allow the appliance to slide into
position without fouling the component).
Stand the appliance in front of the base tray
See fig.11. and gently slide into position.
Tighten the nuts from the valves on the base
plate to the corresponding inlet/outlet connections on the appliance using the fibre washers
supplied.
Finally secure the appliance to the base tray
using the 2 screws provided. See fig.11a.
Fit the filling loop hose and safety valve outlet
pipe and replace the filling/inlet valve handle.
Alternatively before the appliance is positioned
the system and supplies can be filled and
pressure tested using the Vokèra pressure
test kit (part no. 401). Pressure test kit instructions supplied with kit.
Note: All pipework can be installed to run up
behind the appliance. Ensure that the pipes
pass behind the reference bar to prevent the
pipes fouling the appliance when it is pushed
into position. See fig. 10.
Remove the knock out panel in the top panel
for pipe clearance See fig.17.
Fig. 13
Fig. 14
10
Linea Max
Supplied By www.heating spares.co Tel. 0161 620 6677
5.4Installing the flue system
Care should be exercised when determining
the position of the appliance and route of the
flue system with respect to hidden obstructions such as pipes, cables, etc.
5.5Fitting the flue
The top flue outlet permits both horizontal and
vertical flue applications to be considered,
alternatively, the Vokera twin flue system can
be utilised if longer flue runs are required.
5.5.1Concentric horizontal flue
(For concentric vertical flue, see 5.5.2)
(For twin flue applications, see 5.5.3)
The appliance flue outlet elbow can be rotated
at 90º intervals on its vertical axis allowing the
flue system to exit the appliance casing at the
rear, to the left, & to the right. In addition the
flue may be extended from the outlet elbow in
the horizontal plane (see 3.4.4), however if the
flue is to be extended and/or additional bends
are to be fitted, a reduction must be made to
the maximum flue length (see table below).
Reductio n i n maximum flue
Bend
lenght for each bend
45°0,5 metre
90°1,0 metre
Discard the bend & inner (small) flue clip
supplied with the flue terminal.
Carefully measure the distance from the centre of the appliance flue outlet to the face of the
outside wall (dimension X) and add 34mm to
give you dimension Y (see fig. 15).
Measure from the terminal end of the concentric flue pipe and mark off dimension Y. Cut
only the outer flue pipe at this mark.
Mark dimension Y on the inner flue pipe then
add 10mm and cut at the new mark.
This results in the inner flue pipe being 10mm
longer than the outer flue pipe.
Horizontal flue terminal and accessoires
Part No.Descrip tionMin-Max Length
0225700 Horizontal flue kit
For use with add.
Bends & exte nsio ns
0225755 Telescopic extension35 0 - 500 m m
0225740 0,5 m extension5 00 mm
0225745 1,0 m extension1000 mm
0225730 45° bend (pair)N/A
0225735 901° bendN/A
0225760 Wall bracket (5)N/A
900 mm
Using the fig. 13 as a reference, mark and drill
a 115mm hole for the passage of the flue pipe.
The hole should have a 1º drop from the boiler
to outside, to eliminate the possibility of rainwater entering the appliance via the flue.
5.5.1.1Standard horizontal flue (See 5.5.1.2 for
extending the horizontal flue)
The flue terminal (part no. 0225700) is suitable
for the following wall thickness:
RouteMaximum wall thickness
Terminating to the rear573mm (boiler hard
against rear wall)
Terminating to the left509mm (boiler with
minimum clea ra nce a t
left hand side )
Terminating to the right 617mm (boiler with
minimum clea ra nce a t
right ha nd si de)
Insert the flue pipe into the previously drilled
flue hole.
Pull it towards the appliance flue bend and
insert the inner flue pipe into the push-fit socket
of the bend until the outer flue pipe butts
against the edge of the appliance flue bend.
Take the outer flue clip, seal, & screws (supplied with the flue terminal kit) and secure the
flue pipe to the appliance flue bend.
You must ensure that the entire flue system is
properly connected.
Check that the terminal protrudes past the
finished wall by the correct length (115mm).
Seal the flue assembly to the wall using cement or a suitable alternative that will provide
satisfactory weatherproofing. The exterior
trim can now be fitted.
5.5.1.2Extended horizontal flue
(see fig. 15a)
Discard the bend & inner (small) flue clip
supplied with the flue terminal.
Insert the flue terminal into the previously
drilled flue hole.
Connect the required bends and/or extensions
to the flue terminal working back towards the
boiler whilst maintaining a 1°fall (17mm per
1000mm) away from the boiler.
All bends and extensions are push-fit and
require no clips or screws, however care should
be taken to ensure that the correct seal is
made when assembling the flue system.
Linea Max
11
Supplied By www.heating spares.co Tel. 0161 620 6677
Carefully measure the distance between the
appliance flue outlet bend and the 2nd last
extension or bend (dimension X). Add 40mm
to dimension X to give dimension Y (see fig.
15a).
Measuring from the socket end of the last
extension, mark and cut both pipes to suit
dimension Y.
Remove the appliance flue bend from the flue
outlet and insert the inner flue pipe of the
extension into the push-fit socket of the bend
until the outer flue pipe butts against the edge
of the appliance flue bend.
Take the outer flue clip, seal, & screws (supplied with the flue terminal kit) and secure the
flue pipe to the appliance flue bend.
Connect the assembled bend and extension to
the 2nd last extension or bend and ensure the
correct seal is made.
Finally connect the appliance flue outlet bend
to the appliance flue outlet.
NOTE
When cutting an extension to the required
length, you should ensure that the excess is
cut from the plain end of the extension. Remove any burrs, and check that both seals are
located properly.
You must ensure that the entire flue system is
properly supported and connected.
Seal the flue assembly to the wall using cement or a suitable alternative that will provide
satisfactory weatherproofing. The exterior
trim can now be fitted
Optional
knock-out
panels
Fig.16
5.5.2Concentric vertical flue
(see fig. 16 & 16a)
The vertical flue terminal should be connected
directly to the appliance flue outlet. If additional bends and/or extensions are fitted, a
reduction must be made to the maximum flue
length (see table below & 3.4.4).
The vertical flue terminal is 1.0 metre in length
and cannot be cut; therefore it may be necessary to adjust the position of the appliance to
suit or use a suitable extension.
Remove and discard the appliance flue outlet
bend.
Remove the knockout panel on the appliance
casing (directly above the appliance flue outlet).
Using the dimensions given in fig. 16a as a
reference, mark and cut a 105mm hole in the
ceiling and/or roof.
Fit the appropriate flashing plate to the roof
and insert the vertical flue terminal through the
flashing plate from the outside, ensuring that
the collar on the flue terminal fits over the
flashing.
Insert the boiler top adapter (supplied with the
vertical flue terminal) into the appliance flue
outlet ensuring the correct seal is made. Insert
the vertical flue assembly into the boiler top
adapter ensuring the correct seal is made. The
flue support bracket (supplied with the vertical
flue kit) can now be fitted.
If the vertical flue requires extension/s or additional bend/s, connect the required number of
flue extensions or bends (up to the maximum
equivalent flue length) between the boiler top
adapter and vertical flue assembly.
1.0 metre
N/A
N/A
N/A
350mm –500mm
12
Linea Max
Supplied By www.heating spares.co Tel. 0161 620 6677
1 5
NOTE;
You must ensure that the entire flue system is
properly supported and connected.
When cutting an extension to the required
length, you should ensure that the excess is
cut from the plain end of the extension. Remove any burrs, and check that both seals are
located properly.
Fig. 16a
Y = 302 mm
Flashing Plate
Flue Outlet
Spigot
â
â
Collar
●Ensure that the entire flue system is ad-
equately supported, use at least one bracket
for each extension
●The entire flue system must be adequately
insulated to maintain heat within the flue
system thereby reducing the possibility of
condensate production.
●As the exhaust outlet pipe can reach very
high temperatures it must be protected to
prevent persons touching the hot surface.
B endR eduction in maximum flu e le ngth for
each bend
45º bend 1.0 metre
90º bend 1.0 metre
Twin flue accessories
Part No. DescriptionLength
0225805 Horizontal flue terminal 1.0 metre
0225835 2.0m extension (pair)2000mm
0225840 45º bend (pair)N/A
Y
0225845 90º bend (pair)N/A
0225850 Twin bracket (5)N/A
0225855 S i ngle bracket (5)N/A
Air Inlet
Spigot
5.5.3Twin flue system
The Vokera twin flue system enables greater
flue distances to be achieved (see 3.4.4) than
that of the standard concentric flue system,
however the twin flue system must be converted to the dedicated concentric flue kit for
termination. It is essential that the installation
of the twin flue system be carried out in strict
accordance with these instructions.
GUIDANCE NOTES ON TWIN FLUE INSTALLATION
●The flue must have a fall back of 1º back to
the appliance to allow any condensate that
may form in the flue system to drain via the
condensate drain. Consideration must also
be given to the fact that there is the possibility of a small amount of condensate dripping
from the terminal.
5.5.3.1Installation of twin adaptor kit (fig. 17)
●Insert the exhaust connection manifold onto
the appliance flue outlet.
●Place the silicone seal (supplied with twin
adapter kit) over the rim of the exhaust
connection manifold.
●Remove one of the blanking plates (located
to the left & right of the appliance flue outlet)
and using the same screws install the air
baffle.
Linea Max
13
Supplied By www.heating spares.co Tel. 0161 620 6677
5.5.3.2Installation of condensate drain kit (fig. 17a)
The condensate drain kit must be fitted within
1 metre of the appliance flue outlet. It is
recommended that the condensate drain kit
should be fitted in the vertical plane, however
it can be fitted horizontally with care.
●Fit the first bend to the condensate drain kit
or exhaust connection manifold by firmly
pushing in to position.
●Using the two holes in the exhaust connec-
tion manifold as a guide, drill a 3mm hole in
each and secure using the screws provided.
●Connect the air inlet pipe to the air baffle as
above.
●The twin flue pipes extensions and accesso-
ries can now be installed by pushing together (the plain end of each extension or
bend should be pushed approximately
50mm into the female socket of the previous
piece).
5.5.3.3Horizontal termination (See fig. 17c)
The twin flue system must be converted to the
dedicated concentric flue kit for termination.
●The horizontal terminal is supplied with a
built-in converter box and cannot be shortened.
●A 130mm hole is required for the passage of
the concentric terminal through the wall.
Depending on site conditions it may be preferable to install the terminal assembly prior to
fitting the twin flue pipes.
Mark and drill a 130mm hole for the passage of
the horizontal flue terminal, ensuring that there
is a 1º fall back to the boiler (17mm per
1000mm). Insert the terminal assembly into
the flue hole.
Push-fit the twin flue pipes onto the concentric
to twin converter box ensuring that the exhaust
pipe connects to the exhaust connection on
the concentric to twin converter.
If necessary cut the plain ends (male) of the
twin flue pipes to allow connection to the
concentric to twin converter.
NOTE; before cutting twin flue pipes ensure
allowances have been made for connection
onto the previous piece and onto the concentric to twin converter. The last twin flue pipes
must be pushed 50mm onto the male spigots
of the concentric to twin converter.
NOTE;
You must ensure that the entire flue system is
properly supported and connected.
The condensate drain trap must be connected
to the drain in accordance with building Regulations or other rules in force.
When cutting an extension to the required
length, you should ensure that the excess is
cut from the plain end of the extension. Remove any burrs, and check that both seals are
located properly.
Seal the flue terminal assembly to the wall
using cement or a suitable alternative that will
provide satisfactory weatherproofing. The interior and exterior trim can now be fitted.
Twin Flue system
Boiler
Fig. 17c
Concentric to Twin Converter
(Part no 310)
Horizontal
Flue Terminal
Condensate drain kit
Condensate trap
14
Linea Max
Supplied By www.heating spares.co Tel. 0161 620 6677
5.5Electrical Connections
5.5.1The electricity supply must be as specified
in clause 4.7. If controls external to the
appliance are required, design of the external electrical circuits should be undertaken
by a competent person.
See Section 10 for further advice.
N.B. IT IS ESSENTIAL THAT ALL EXTERNAL CONTROL CIRCUITS AND WIRING IS
WIRED FROM THE SAME ELECTRICAL
ISOLATOR AS SERVES THE APPLIANCE.
Factory fitted internal wiring must not be
disturbed when wiring external controls.
5.5.2To gain access to the electrical terminals
Reposition front control panel by first pulling
it free from 4 locating lugs. Rotate the panel
through 90° degrees and relocate it into the
lower position using the locating hooks as
shown in fig.18 & 19.
Remove electrical cover by releasing nine
securing screws. Fig.19.
The mains input terminal block is now easily
visible (marked 1 - 6).
5.5.3The electricity supply cable from the isolator
and the appliance terminal block must be 3
core flexible sized 0.75mm² (24 x 0.2mm) to
table 15-16, BS6500.
Wiring to the appliance should be rated for
operation in contact with surfaces up to
90°C.
Fig. 18
Locating hook
Linea Max
Locating hook
Fig. 19
15
Supplied By www.heating spares.co Tel. 0161 620 6677
5.5.4Pass the cable through one of the cord
anchorage points and connect the wires
Brown to L1, Blue to N, and Green/Yellow to
W of the terminal strip. Arrange the cable so
that should the cable slip the anchorage the
current carrying conductors become taut
before the earthing conductor.
5.5.5Securely tighten all terminal screws and
arrange the cable with slack between the
cable anchor and the terminal block. Tighten
the cord anchorage screw until the cable is
secure.
5.5.6Neatly arrange the external cable in such a
way that unrestricted opening of the controls
fascia and repositioning is possible without
strain on the cable.
5.5.7External controls may be wired from terminals 1 & 2 or 2 & 3 after removing the
factory fitted link (between 2 & 3) depending
on wiring configuration (see pages 48 - 51
for further details). If a neutral is needed use
the terminal marked N on the terminal strip.
DO NOT CONNECT ANY WIRES TO THE
PRINTED CIRCUIT BOARD TERMINALS.
Section 10 gives details of fitment for external and internal controls (ie Vokèra time
clock).
If required pass the external controls cable
through the spare cord anchorage and
arrange the cable so that should the cable
slip the anchorage the current carrying
conductors become taut before the earthing
conductor.
Main Burner
Test Point
Incoming Gas
Pressure Test
Point
Fig. 20
Filling
Position
16
Closed
Position
Normal
Operating
Position
Fig. 21
Linea Max
Loading...
+ 44 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.