VOKERA Eclipse ESC Installation & Servicing Instructions Manual

Page 1
Supplied By www.heating spares.co Tel. 0161 620 6677
Installation & Servicing Instructions
THESE INSTRUCTIONS TO BE RETAINED BY USER
Page 2
Supplied By www.heating spares.co Tel. 0161 620 6677
Contents
Design principles & operating sequence Page
1.1 Principle components 2
1.2 Mode of operation (at rest) 2
1.3 Domestic hot water mode 2
1.4 Central heating mode 2
1.5 Safety devices 2
Technical data Page
2.1 Central heating 3
2.2 Domestic hot water 3
2.3 Gas pressure 3
2.4 Expansion vessel 3
2.5 Dimensions 3
2.6 Clearances 3
2.7 Connections 3
2.8 Electrical 3
2.9 Flue details 3
2.10 Efficiency 3
2.11 Parameter defaults 4
2.12 Emissions 4
2.13 Pump duty 4
General requirements Page
3.1 Related documents 5
3.2 Location of appliance 5
3.3 Gas supply 5
3.4 Flue system 5
3.5 Air supply 6
3.6 Water circulation 6
3.7 Electrical supply 7
3.8 Showers 7
3.9 Mounting on a combustible surface 7
3.10 Timber framed buildings 7
3.11 Condensate disposal 7
3.12 Inhibitors 7
Installation Page
4.1 Delivery 7
4.2 Contents 7
4.3 Unpacking 7
4.4 Preparation for mounting the appliance 7
4.5 Fitting the flue 8
4.6 Connecting the gas & water 11
4.7 Condensate outlet 12
4.8 Electrical connections 12
Commissioning Page
5.1 Gas supply installation 14
5.2 The heating system 14
5.3 Initial filling of the system 14
5.4 Initial flushing of the system 14
5.5 Filling the hot water system 14
5.6 Pre-operation checks 14
5.7 Initial lighting 14
5.8 Final flushing of the heating system 14
5.9 Operating parameters 14
5.10 Functional parameters 15
5.11 Range rating 15
5.12 Setting the system design pressure 15
5.13 Regulating the central heating system 16
5.14 Final checks 16
5.15 Instructing the user 16
Servicing Page
6.1 General 17
6.2 Routine annual servicing 17
6.3 Replacement of components 17
6.4 Component removal procedure 17
6.5 Pump head removal 17
6.6 Safety valve removal 17
6.7 Automatic air valve removal 17
6.8 Pressure gauge removal 18
6.9 Temperature sensor removal 18
6.10 Main PCB removal 18
6.11 Gas valve removal 18
6.12 Fan removal 19
6.13 Burner removal 19
6.14 Electrode removal 19
6.15 Injector removal 19
6.16 DHW heat exchanger removal 20
6.17 Motorised valve actuator removal 20
6.18 Divertor valve assembly removal 20
6.19 Condense trap removal 20
6.20 Condense pressure switch removal 20
6.21 Combustion cover removal 20
6.22 Expansion vessel removal 21
6.23 Input & status PCB removal 21
Checks, adjustments, and fault finding Page
7.1 Checking appliance operation 22
7.2 Mode of operation 22
7.3 Checking/adjusting fan speeds 22
7.4 Adjusting the gas valve 23
7.5 Status code 24
7.6 Lockout faults codes 25
7.7 Diagnostic recall 25
7.8 Temperature sensor viewing mode 26
7.9 Checking the expansion vessel 26
7.10 External faults (installation) 26
7.11 Electrical checks 26
7.12 Fault finding 27
Wiring diagrams Page
8.1 Important note 31
8.2 Installation of Vokera time clock 31
8.3 External controls 31
Exploded diagrams Page
9.1 Table 1 35
9.2 Table 2 36
9.3 Table 3 37
9.4 Table 4 38
9.5 Table 5 39
9.6 Table 6 40
L.P.G. instructions Page
10.1 Technical data 41
10.2 Related documents 41
10.3 Gas supply 41
10.4 Gas supply installation 41
10.5 Adjusting the gas valve 41
10.6 Range rating 41
Page 3
Supplied By www.heating spares.co Tel. 0161 620 6677
INTRODUCTION
The Vokera Eclipse ESC is a combined central heating and domestic hot water condensing boiler, which – by design – incorporates full sequence electronic ignition, circulating pump, expansion vessel, safety valve, pressure gauge, and automatic by-pass.
The Eclipse is produced as a room sealed, category C1, C3, C6 appliance, suitable for wall mounting applications only. The Eclipse is provided with a fan powered flue
outlet with an annular co-axial combustion air intake that can be rotated – horizontally – through 360 degrees for various horizontal or vertical applications. The Eclipse can also be used with the Vokera twin flue system. These appliances are designed for use with sealed systems only; consequently they are not intended for use on open vented systems.
A range rating facility is incorporated in the appliance.
General layout
1 Auto air vent 2 Flue outlet & air intake 3 Flue gas analysis test point 4 Burner plate 5 Spark/Sensing Electrode 6 Fan assembly 7 Pressure switch 8 Electronic Control Board (PCB) 9 Condense trap 10 Cold water inlet 11 Hot water outlet 12 Gas connection 13 Pressure gauge 14 Time clock aperture 15 Function key pad 16 LED display 17 Reset button 18 Heating flow connection 19 Safety valve 20 Heating return connection 21 Auto by-pass 22 Three port valve actuator 23 Pump 24 Return sensor (NTC2) 25 Gas valve 26 Flow sensor (NTC1)
Fig. 1
1
Page 4
Supplied By www.heating spares.co Tel. 0161 620 6677
SECTION 1 DESIGN PRINCIPLES AND OPERATING SEQUENCE
1.1 PRINCIPLE COMPONENTS
A fully integrated electronic control board
featuring electronic temperature control, continuous air/gas modulation, anti-cycle control, pump over-run, self-diagnostic fault indicator, electronic ignition with flame supervision, & appliance frost protection.
Cast aluminium mono-block heat exchanger.
Low Nox burner with pre-mix.
Two-stage gas valve.
Pump.
Expansion vessel.
Pressure gauge.
Safety valve.
1.2 MODE OF OPERATION (at rest)
When there is no demand for heating or hot water, the boiler will periodically light to pre-heat the domestic hot water heat exchanger to approximately 55°C. This ensures that the appliance is at operating temperature when there is a request for domestic hot water. The parameter for the allowable temperature drop – between pre­heat operation – can be adjusted. If the appliance remains inactive for a period of 24 hours, the pump and motorised valve will be energised for a few moments to prevent these components from seizing. Should the flow temperature sensor fall below 7°C the pump will be energised. If the flow sensor temperature falls to below 3°C the burner will be lit and the appliance will operate at the minimum output until the temperature of the flow sensor reaches 10°C, whereupon the pump will continue to run in pump over-run mode.
1.3 DOMESTIC HOT WATER MODE
When the appliance is at rest, the motorised valve is energised to the hot water position, when a demand for hot water is made the cold water temperature sensor activates the pump and fan. When the fan is sensed to be operating correctly, the ignition sequence commences. The speed of the fan and therefore the output of the boiler is determined by the temperature of the water sensed by the return temperature sensor, consequently a high temperature at the return sensor results in a lower fan speed. As the water temperature increases, the temperature sensors – located on the flow and return pipes of the boiler – reduce the fan speed via the electronic circuitry. Depending on the load, either the water temperature will continue to rise until the set point is achieved or the water temperature will fall whereby fan speed will increase relative to the output required.
boiler is determined by the temperature of the water sensed by the flow & return temperature sensors, consequently a high temperature at the flow sensor results in a lower fan speed. As the water temperature increases, the temperature sensors – located on the flow and return pipes of the boiler – reduce the fan speed via the electronic circuitry. Depending on the load, either the water temperature will continue to rise until the set point is achieved or the water temperature will fall whereby fan speed will increase relative to the output required. When the boiler has reached the set point, the burner will switch off. The built-in anti-cycle device prevents the burner from re­lighting for an adjustable period of time (factory default is 3 minutes). When the temperature of the flow sensor falls below the set-point, the burner will re-light.
1.5 SAFETY DEVICES
When the appliance is in use, safe operation is ensured by:
a high limit thermostat that interrupts the
operation of the burner;
a differential temperature protection circuit which
interrupts the burner if the temperature differential is inverted;
a fan speed sensor which checks the correct
operation of the fan, thereby allowing safe operation of the burner;
a safety valve which releases excess pressure
from the primary circuit;
a condense pressure switch that will stop the
burner from operating should the condense trap become blocked.
4
NTC2 (return sensor)
Domestic Heat Exchanger
1
NTC1 (flow sensor)
Main Heat Exchanger
Expansion vessel
NTC 3 (inlet sensor)
1.4 CENTRAL HEATING MODE
When there is a request for heat via the time clock and/or external controls the motorised valve and pump will go through a self-test function this is to ensure correct operation and valve configuration. Once the self-test function is complete, the pump and fan will activated via the flow temperature sensor. When the fan is sensed to be operating correctly, the ignition sequence commences. The speed of the fan and therefore the output of the
Fig. 2
2
gas
return flow hw
outlet
cold inlet
Page 5
Supplied By www.heating spares.co Tel. 0161 620 6677
SECTION 2 TECHNICAL DATA
2.1 Central heating
Heat input 29,00 kW Maximum heat output 60/80°C (return & flow temperature) 25,3 kW Maximum heat output 30/50°C (return & flow temperature) 26,8 kW Minimum heat output 60/80°C (return & flow temperature) 7,3 kW Minimum heat output 30/50°C (return & flow temperature) 8,10 kW Minimum working pressure 0,45 bar Maximum working pressure 3 bar Minimum flow rate 350 l/h
2.2 Domestic hot water
Maximum input 29,00 kW Maximum output 25,3 kW Minimum output 8,1 kW Flow rate (35°C rise) 10,4 l/min Maximum inlet pressure 6,0 bar Minimum inlet pressure to operate 0,15 bar Minimum flow rate to operate 2,5 l/min.
2.3 Gas pressure Maximum
Inlet pressure (G20) 20,0 mbar Maximum gas rate 2,76 m3/h Minimum gas rate 0,80 m3/h Injector size single injector with six 3,8 mm holes
2.4 Expansion vessel
Capacity 8 litres Maximum system volume 76 litres Pre-charge pressure 1,0 bar
2.5 Dimensions
Height 790 mm Width 450 mm Depth 322 mm Dry weight 57 kg
2.6 Clearances
Sides 25 mm Top Bottom 150 mm Front 600 mm
2.7 Connections
Flow & return 22 mm compression Hot & cold water 15 mm compression Gas 1/2 inch BSP Safety valve 1/2 inch BSP
2.8 Electrical
Voltage 230V/~ 50hz Power consumption 130 W Internal fuse 2 A External fuse 3 A
2.9 Flue details
Maximum horizontal flue length (concentric) 6,45 metres Maximum vertical flue length (concentric) 7,45 metres Maximum twin flue length (horizontal or vertical) 29 m + 29 m
2.10 Efficiency
SEBDUK rating Band “A”
150 mm from casing or 25mm above flue elbow (whichever is applicable)
Ref. Condition 15 °C , 1013,25 mbar, dry gas NOTE: L.P.G. data refer to section 10
3
Page 6
Supplied By www.heating spares.co Tel. 0161 620 6677
2.11 Adjustable operating parameters PARAMETER MINIMUM MAXIMUM FACTORY SETTING
Maximum fan speed (HW mode) Fixed Fixed 5.500 RPM Maximum fan speed (CH mode) See fig. 32 See fig. 32 5.500 RPM Minimum fan speed Fixed Fixed 1.700 RPM Soft-light fan speed Fixed Fixed 4.400 RPM Pre-heat Fixed Fixed 55°C Pre-heat temperature drop 5°C30°C20°C Anti-cycle delay 0 seconds 306 seconds 92 seconds Central heating flow temperature 20°C90°C75°C Hot water outlet temperature 40°C65°C65°C Pump over-run 3 m 99 m 10 m
2.12 Emissions MIN. OUTPUT MAX. OUTPUT
NO
x
15 ppm 30 ppm CO 50 ppm 50 ppm CO
2
9,8% 9,8% CO/CO2 ratio 0.0005 to 1 0.0005 to 1
2.13 PUMP DUTY
Fig. 3 shows the flow rate available – after allowing for pressure loss through the appliance – for system requirements. When using this graph apply only the pressure loss of the system. The graph is based on 20°C temperature differential.
600
500
400
300
200
100
Water pressure (mbar)
0 100 200 300 400 500 600 700 800
Fig. 3
Litres Per Hour (x100)
900 1000
1100 1200 1300 1400
Terminal position for fan assisted boiler
(minimum distance) mm A - Directly above or below an open window 300
J - From an opening in the car port (e.g. door
or other opening (e.g. air brick) B - Below gutters, soil pipes or drain pipes 25 C - Below eaves 25 D - Below balconies or car port roof 25 E - From vertical drain pipes and soil pipes 75
K - Vertically from a terminal on the same wall 1500 L - Horizontally from a terminal on the same wall 300 M - Horizontally from a vertical terminal to a wall 300
N – Horizontally from an opening, airbric k,
F - From internal or external corners 25 G - Above ground or below balcony level 300 H - From a surface facing a terminal 600 I - From a terminal facing a terminal 1200
NOTE:The flue must be terminated in a place not likely to cause a nuisance.
Fig. 4
4
window) into dwelling. 1200
openable window, etc. 300
Page 7
Supplied By www.heating spares.co Tel. 0161 620 6677
SECTION 3 GENERAL REQUIREMENTS
This appliance must be installed by a competent person in accordance with the Gas Safety (Instal­lation & Use) Regulations.
3.1 RELATED DOCUMENTS
The installation of this boiler must be in accord­ance with the relevant requirements of the Gas Safety (Installation & Use) Regulations, the local building regulations, the current I.E.E. wiring regulations, the bylaws of the local water undertaking, the Building Standards (Scotland) Regulation and Building Standards (Northern Ireland) Regulations.
It should be in accordance also with any relevant requirements of the local authority and the relevant recommendations of the following British Standard Codes of Practice.
3.2 LOCATION OF APPLIANCE
The appliance may be installed in any room or internal space, although particular attention is drawn to the requirements of the current I.E.E. wiring regulations, and in Scotland, the electrical provisions of the Building Regulations, with respect to the installation of the appliance in a room or internal space containing a bath or shower.
for this purpose. An existing compartment/cup­board may be utilised provided that it is modified to suit.
Details of essential features of compartment/ cupboard design, including airing cupboard in­stallations, are given in BS 6798. This appliance is not suitable for external installation.
3.3 GAS SUPPLY
The gas meter – as supplied by the gas supplier – must be checked to ensure that it is of adequate size to deal with the maximum rated input of all the appliances that it serves. Installation pipes must be fitted in accordance with BS 6891. Pipe-work from the meter to the appliance must be of adequate size. Pipes of a smaller size than the appliance gas inlet connection must not be used. The installation must be tested for soundness in accordance with BS 6891.
If the gas supply serves more than one appliance, it must be ensured that an adequate supply is maintained to each appliance when they are in use at the same time.
BS 5440 PART 1 FLUES BS 5440 PART 2 FLUES AND VENTILATION BS 5449 PART 1 FORCED CIRCULATION HOT WATER SYSTEMS BS 5546 INSTALLATION OF GAS HOT WATER SUPPLIES FOR DOMESTIC PURPOSES
(2ND FAMILY GASES) BS 6798 BOILERS OF RATED INPUT NOT EXCEEDING 60kW BS 6891 LOW PRESSURE INSTALLATION PIPES BS 7074 PART 1 APPLICATION, SELECTION, AND INSTALLATION OF EXPANSION VESSELS AND
ANCILLARY EQUIPMENT FOR SEALED WATER SYSTEMS
When an appliance is installed in a room or internal space containing a bath or shower, the appliance or any control pertaining to it must not be within reach of a person using the bath or shower.
The location chosen for the appliance must permit the provision of a safe and satisfactory flue and termination. The location must also permit an adequate air supply for combustion purposes and an adequate space for servicing and air circulation around the appliance. Where the installation of the appliance will be in an unusual location special procedures may be necessary, BS 6798 gives detailed guidance on this aspect.
A compartment used to enclose the appliance must be designed and constructed specifically
3.4 FLUE SYSTEM
The terminal should be located where the disper­sal of combustion products is not impeded and with due regard for the damage and discoloration that may occur to building products located nearby. The terminal must not be located in a place where it is likely to cause a nuisance (see fig. 4).
Water vapour will condense on leaving the flue terminal, the effect of such pluming must be considered.
5
Page 8
Supplied By www.heating spares.co Tel. 0161 620 6677
If installed less than 2m above a pavement or platform to which people have access (including balconies or flat roofs) the terminal must be protected by a guard of durable material. The guard must be fitted centrally over the terminal. Refer to BS 5440 Part 1, when the terminal is 0,5 metres (or less) below plastic guttering or 1 metre (or less) below painted eaves.
3.5 AIR SUPPLY
The following notes are intended for general guidance only.
This appliance is a room sealed, fan-flued boiler, consequently it does not require a permanent air vent for combustion air supply.
When installed in a cupboard or compartment, venti­lation for cooling purposes is also not required.
3.6 WATER CIRCULATION
Detailed recommendations are given in BS 5449 Part 1 and BS 6798. The following notes are for general guidance only.
3.6.1 PIPEWORK
It is recommended that copper tubing to BS 2871 Part 1 is used in conjunction with soldered capillary joints.
Where possible pipes should have a gradient to ensure air is carried naturally to air release points and that water flows naturally to drain cocks.
Except where providing useful heat, pipes should be insulated to avoid heat loss and in particular to avoid the possibility of freezing. Particular atten­tion should be paid to pipes passing through ventilated areas such as under floors, loft-space, and void areas.
3.6.2 AUTOMATIC BY-PASS
The appliance has a built-in automatic by-pass, consequently there is no requirement for an ex­ternal by-pass, however the design of the system should be such that it prevents boiler ‘cycling’.
3.6.6 FILLING POINT
A method for initial filling of the system and replacing water lost during servicing etc. must be provided. This method of filling must comply with the local water authority regulations. Fig. 5 shows a widely accepted method.
Fig. 5
3.6.7 LOW PRESSURE SEALED SYSTEM
An alternative method of filling the system would be from an independent make-up vessel or tank mounted in a position at least 1 metre above the highest point in the system and at least 5 metres above the boiler (see fig. 5 A). The cold feed from the make-up vessel or tank must be fitted with an approved non-return valve and stopcock for iso­lation purposes. The feed pipe should be con­nected to the return pipe as close to the boiler as possible.
Make-up vessel or tank
Automatic air-vent
3.6.3 DRAIN COCKS
These must be located in accessible positions to facilitate draining of the appliance and all water pipes connected to the appliance. The drain cocks must be manufactured in accordance with BS 2879.
3.6.4 AIR RELEASE POINTS
These must be positioned at the highest points in the system where air is likely to be trapped. They should be used to expel trapped air and allow complete filling of the system.
3.6.5 EXPANSION VESSEL
The appliance has an integral expansion vessel to accommodate the increased volume of water when
Fig. 5 A
3.6.8 FREQUENT FILLING
the system is heated. It can accept up to 8 litres of expansion from within the system, generally this is sufficient, however if the system has an unusually high water content, it may be necessary to provide additional expansion capacity (see 6.19).
6
Non-return
valve
Stopcock
5.0 metres minimum
Heating return
Frequent filling or venting of the system may be indicative of a leak. Care should be taken during the installation of the appliance to ensure all aspects of the system are capable of withstand­ing pressures up to at least 3 bar.
Page 9
Supplied By www.heating spares.co Tel. 0161 620 6677
3.7 ELECTRICAL SUPPLY
The appliance is supplied for operation on 230V @ 50Hz electrical supply, it must be protected with a 3-amp fuse. The method of connection to the mains electricity supply must allow for complete isolation from the supply. The preferred method is by using a double-pole switch with a contact separation of at least 3mm. The switch must only supply the appliance and its corresponding controls, i.e. time clock, room ther­mostat, etc. Alternatively an un-switched shuttered socket with a fused 3-pin plug both complying with BS 1363 is acceptable.
3.8 SHOWERS
If the appliance is intended for use with a shower, the shower must be thermostatically controlled and be suitable for use with a combination boiler.
3.9 MOUNTING ON A COMBUSTIBLE SURFACE
If the appliance is to be fitted on a wall of combus­tible material, a sheet of fireproof material must protect the wall.
3.10 TIMBER FRAMED BUILDINGS
If the appliance is to be fitted in a timber framed building, it should be fitted in accordance with the Institute of Gas Engineers publication (IGE/UP/
7) “Guide for Gas Installations in Timber Frame Buildings”.
3.11 CONDENSATE DISPOSAL
When choosing a location for the boiler, consideration should be given to the disposal of the condensate discharge into a suitable drain or soil pipe. The condensate outlet pipe must be connected to the drain in accordance with building regulations or other rules in force.
SECTION 4 INSTALLATION
4.1 DELIVERY
The appliance is delivered in a heavy-duty card­board carton. Lay the carton on the floor with the writing the correct way up.
4.2 CONTENTS
Contained within the carton is:
the boiler;
the wall mounting bracket;
template;
an accessories pack containing the appliance
service valves and washers;
the instruction pack containing the installation
& servicing instructions, user instructions, Benchmark logbook, guarantee registration card, and a 3amp fuse.
4.3 UNPACKING
At the top of the carton pull both sides open – do not use a knife – unfold the rest of the carton from
Fig. 6
3.12 INHIBITORS
The system shall be flushed in accordance with BS 7593. If an inhibitor is to be used, it shall be from a reputable manufacturer and shall be administered in strict accordance with the manufacturers instructions.
around the appliance, carefully remove all pro­tective packaging from the appliance, and lay the accessories etc. to one side.
4.4 PREPARATION FOR MOUNTING THE APPLIANCE
The appliance should be mounted on a smooth, vertical, non-combustible surface, which must be capable of supporting the full weight of the appliance. Care should be exercised when determining the position of the appliance with respect to hidden obstructions such as pipes, cables, etc.
When the position of the appliance has been decided – using the template supplied – carefully mark the position of the wall-mounting bracket (see fig. 6) and flue-hole (if applicable).
7
Page 10
Supplied By www.heating spares.co Tel. 0161 620 6677
4.5 FITTING THE FLUE
The top flue outlet permits both horizontal and vertical flue applications to be considered, alternatively, the Vokera twin flue system can be utilised if longer flue runs are required.
4.5.1 CONCENTRIC HORIZONTAL FLUE
(For concentric vertical flue, see 4.5.2). (For twin flue applications, see 4.5.3). The appliance flue outlet elbow can be rotated through 360° on its vertical axis. In addition the flue may be extended from the outlet elbow in the horizontal plane (see 2.9). A reduction must also be made to the maximum length (see table below) when additional bends are used.
Reduction for additional bends
Bend
Reduction in maximum flue length for each bend
Take the large black gasket - supplied with the flue terminal kit - and stretch it over the appliance flue outlet (fig. 7). Using a twisting motion, connect the boiler top adaptor - supplied with the flue terminal kit - to the appliance flue outlet ensuring the male spigot of the adaptor is pushed fully into the flue outlet spigot of the boiler (fig. 7). Carefully measure the distance from the centre of the appliance flue outlet to the edge of the finished outside wall (dimension X). Add 45mm to dimension X to give you Dimension Y (see fig 7A). Measure dimension Y from the terminal end of the concentric flue pipe and cut off the excess. Pass the concentric flue pipe through the previously drilled hole. Fit the flue bend to the boiler top adaptor and insert the concentric flue pipe into the flue bend ensuring the correct seal is made.
45° bend 90° bend
Part No. 0225720
0225755 0225740 0225745 0225750 0225730 0225735 0225760
0,5 metre 1,0 metre
Horizontal flue terminals and accessories
Description
Horizontal flue kit for use with add. bends & extensions
350-500 T elescopic extension 0,5m extension 1,0m extension 2,0m extension 45° bend (pair) 90° bend Wall bracket (5)
Min-Max length 1000mm
350mm-500mm 500mm 1000mm 2000mm N/A N/A N/A
Using the template provided (see fig. 6), mark and drill a 125mm hole for the passage of the flue pipe. The hole should ha ve a 1° rise from the boiler to outside.
Fig. 7A
NOTE
You must ensure that the entire flue system is properly supported and connected.
Seal the flue assembly to the wall using cement or a suitable alternative that will provide satisfactory weatherproofing. The interior and exterior trim can now be fitted.
The fixing holes for the wall-mounting bracket should now be drilled and plugged, an appropriate type and quantity of fixing should be used to ensure that the bracket is mounted securely. Once the bracket has been secured to the wall, mount the appliance onto the brack et.
FITTING THE HORIZONTAL FLUE KIT
Boiler top
Black
adaptor
gasket
Flue outlet
Boiler
Fig. 7
8
Fig. 7B
Boiler
Push-fit connection
Boiler top adaptor
Extension
Page 11
Supplied By www.heating spares.co Tel. 0161 620 6677
4.5.1.1 EXTENDING THE FLUE
Connect the bend – supplied with the terminal kit – to the top of the boiler using the boiler top adapter (supplied, see fig. 7). The additional bends & extensions have push-fit connections, care should be taken to ensure that the correct seal is made when assembling the flue system. Connect the required number of flue extensions or bends (up to the maximum equivalent flue length) to the flue terminal (see fig. 7B & 7C).
NOTE
When cutting an extension to the required length, you must ensure that the excess is cut from the plain end of the extension (see fig. 7B & 7C). Remove any burrs, and check that any seals are located properly. You must ensure that the entire flue system is properly supported and connected.
Push-fit connection
Plain end
Extension pipe
Boiler top adaptor
Vertical flue terminal and accessories
Part No. 0225725
0225770 0225765 0225755 0225740 0225745 0225750 0225730 0225735 0225760
Description Vertical flue terminal
Pitched roof flashing plate Flat roof flashing plate 350-500 telescopic extension 0,5m extension 1,0m extension 2,0m extension 45° bend (pair) 90° bend Wall bracket (4)
Min-Max length 1000 mm
N/A N/A 350mm-500mm 500mm 1000mm 2000mm N/A N/A N/A
Using the dimensions given in fig. 8 as a reference, mark and cut a 105mm hole in the ceiling and/or roof.
IMPORTANT
You must ensure that the terminal is at least 300mm from any structure or surface (see fig. 8). The vertical flue terminal is 1,0 metre in length and cannot be cut; therefore it may be necessary to adjust the height of the appliance to suit or use a suitable extension. Encure that any horizontal sections of the flue system have a 1° fall back to the boiler (17mm per 1000mm).
Fit the appropriate flashing plate to the roof and insert the vertical flue terminal through the flashing plate from the outside, ensuring that the collar on the flue terminal fits over the flashing.
The fixing holes for the wall-mounting bracket should now be drilled and plugged, an appropriate type and quantity of fixing should be used to ensure that the bracket is mounted securely. Once the bracket has been secured to the wall, mount the appliance onto the bracket.
300mm minimum
Boiler
Fig. 7C
4.5.2 CONCENTRIC VERTICAL FLUE
The vertical flue terminal can be connected directly to the appliance flue outlet. Alternatively, an extension or bend can be connected to the appliance flue outlet if desired (see 2.9), however if additional bends are fitted, a reduction must be made to the maximum flue length (see table below).
Reduction for bends
Bend 45° bend
90° bend
Reduction in maximum flue length for each bend 0,5 metre
1,0 metre
Fig. 8
520mm
139mm
9
Page 12
Supplied By www.heating spares.co Tel. 0161 620 6677
NOTE
When cutting an extension to the required length, you must ensure that the excess is cut from the plain end of the extension. Remove any b urrs, and check that an y seals are located properly .
4.5.3 TWIN FLUE SYSTEM
The Vokera twin flue system enables greater flue distances to be achieved (see 2.9) than that of the standard concentric flue system. It can be used f or horizontal or vertical applications, howev er the twin flue system must be converted to the dedicated concentric flue kit for termination. It is essential that the installation of the twin flue system be carried out in strict accordance with these instructions.
GUIDANCE NOTES ON TWIN FLUE INSTALLATION
The flue must hav e a f all back of 1° back to the
appliance to allow any condensate that forms in the flue system to drain. Consideration must also be given to the fact that there is the possibility of a small amount of condensate dripping from the terminal.
Ensure that the entire flue system is adequately
supported, use at least one bracket for each extension.
As the exhaust outlet pipe can reach v ery high
temperatures it must be protected to prevent persons touching the hot surface.
Reduction for bends
Bend 45° bend 90° bend
Reduction in maximum flue length for each bend 1,0 metre
1,0 metre
Twin flue accessories
Part No. Description 0225805
0225810 359 0225770 0225765 0225815 0225820 0225825 0225830 0225835 0225840 0225845 0225850 0225855
Horizontal flue terminal Vertical flue terminal Twin adapter kit Pitched roof flashing plate Flat roof flashing plate Condensate drain kit 0,25m extension (pair) 0,5m extension (pair) 1,0m extension (pair) 2,0m extension (pair) 45° bend (pair) 90° bend (pair) Twin bracket (5) Single bracket (5)
MOUNTING THE BOILER
The fixing holes for the wall-mounting bracket should now be drilled and plugged, an appropriate type and quantity of fixing should be used to ensure that the bracket is mounted securely. Once the bracket has been secured to the wall, mount the appliance onto the bracket.
Length 1000 mm
1000 mm N/A N/A N/A N/A 250mm 500mm 1000mm 2000mm N/A N/A N/A N/A
4.5.3.1 INSTALLATION OF TWIN ADAPTOR KIT (see fig. 9)
Discard the restrictor ring (supplied with the twin
adapter kit).
Insert the exhaust connection manifold onto the
appliance flue outlet.
Place the silicone seal (supplied with twin
adapter kit) over the rim of the exhaust connection manifold.
Remove one of the blanking plate (located to
the left & right of the appliance flue outlet) and – using the same screws – install the air baffle.
Fig. 9
4.5.3.2 HORIZONTAL TERMINATION (see fig. 10)
The twin flue system must be converted to the dedicated concentric flue kit for termination.
The horizontal terminal is supplied with a built-
in converter box and cannot be shortened.
A 130mm hole is required for the passage of
the concentric terminal through the wall.
Depending on site conditions it may be pref erable to install the terminal assembly prior to fitting the twin flue pipes.
Mark and drill a 130mm hole for the passage of the horizontal flue terminal, ensuring that there is a 1° fall back to the boiler (17mm per 1000mm). Insert the terminal assembly into the flue hole.
Push-fit the twin flue pipes onto the concentric to twin converter box ensuring that the exhaust pipe connects to the exhaust connection on the concentric to twin converter. If necessary cut the plain ends (male) of the twin flue pipes to allow connection to the concentric to twin converter.
NOTE
Before cutting twin flue pipes ensure allowances have been made f or connection onto the previous piece and onto the concentric to twin converter. The last twin flue pipes must be pushed 50mm onto the male spigots of the concentric to twin converter.
NOTE
You must ensure that the entire flue system is properly supported and connected. When cutting an extension to the required length, you should ensure that the excess is cut from
10
Page 13
Supplied By www.heating spares.co Tel. 0161 620 6677
the plain end of the extension. Remove an y burrs, and check that both seals are located properly.
Seal the flue terminal assembly to the wall using cement or a suitable alternative that will provide satisfactory weatherproofing. The interior and exterior trim can now be fitted.
convertor box
Fig. 10
Push-fit the twin flue pipes onto the concentric to twin converter ensuring that the exhaust pipe connects to the exhaust connection on the concentric to twin converter. If necessary cut the plain ends (male) of the twin flue pipes to allow connection to the concentric to twin converter.
NOTE
Before cutting twin flue pipes ensure
allowances have been made for connection onto the previous piece and onto the concentric to twin converter. The last twin flue pipes must be pushed 50mm onto the male spigots of the concentric to twin converter.
You must ensure that the entire flue system is
properly supported and connected.
Ensure that any horizontal sections of pipe hav e
a 1° fall towards the appliance (17mm per 1000mm).
The convertor box on the vertical terminal will
have to be temporarily remo ved when inserting the terminal through the flashing.
4.5.3.3 VERTICAL TERMINATION (see fig. 11)
The twin flue system must be converted to the dedicated concentric flue kit for termination.
The vertical terminal is supplied with a built-in
converter box and cannot be shortened.
A 130mm hole is required for the passage of
the concentric terminal through the ceiling and/ or roof.
Depending on site conditions it may be prefer able to install the terminal assembly prior to fitting the twin flue pipes.
Fit the appropriate flashing plate to the roof and insert the vertical flue terminal through the flashing plate from the outside, ensuring that the collar on the flue terminal fits over the flashing.
convertor box
4.6 CONNECTING THE GAS AND WATER
The appliance is supplied with an accessories pack that contains sealing washers and service valves. When connecting pipe work to the valves, tighten the compression end first, then insert the sealing washers before tightening the valve or connection to the appliance.
NOTE
It will be necessary to hold the valve with one spanner whilst tightening with another.
4.6.1 GAS (see fig. 12)
The appliance is supplied with a 1/2 inch BSP service valve, connect the supply pipe to the inlet of the valve and tighten the connecting nut.
NOTE
It will be necessary to calculate the diameter of the gas pipe to ensure the appliance has an adequate supply of gas.
4.6.2 FLOW & RETURN (see fig. 12)
The appliance is supplied with 22mm service valves for the flow and return connections, connect a 22mm pipe to the inlet of each valve and tighten both nuts.
4.6.3 SAFETY VALVE (see fig. 12)
Fig. 11
Connect a suitable coupling and 15mm pipe to the safety valve outlet and tighten.The discharge pipe must have a continuous fall away from the appliance to outside and allow any water to drain away thereby eliminating the possibility of freezing. The discharge pipe must terminate in a position where any water - possibly boiling - discharges safely without causing damage or injury, but is still visible.
11
Page 14
Supplied By www.heating spares.co Tel. 0161 620 6677
4.6.4 COLD WATER INLET (see fig. 12)
The appliance is supplied with a 15mm service valve, connect a 15mm pipe to the inlet of the valve and tighten both nuts.
4.6.5 HOT WATER OUTLET (see fig. 12)
The appliance is supplied with a 15mm male connector. Using a suitable coupling, connect a 15mm pipe to the supplied connector and tighten the nut.
4.7 CONDENSATE OUTLET (see fig. 12)
During normal operation the boiler produces condensate which is collected in a trap located in the lower part of the boiler. A flexible pipe (condensate outlet pipe) is connected to the outlet of the trap. The flexible pipe must be connected to a plastic waste pipe only. The plastic waste pipe must have a minimum of a 3° fall towards the drain. Any external run of pipe should be insulated to prevent the risk of freezing.
CONNECTING THE CONDENSATE OUTLET
Gently pull the condensate outlet pipe down from its location inside the boiler until approximately 250mm protrudes from the underside of the boiler. Connect a suitable pipe (no less than 20mm diameter) to the outlet pipe and ensure it discharges in accordance with building regulations or other rules in force.
4.8.1 CASING REMOVAL
To gain access to the appliance electrical con­nections you must first remove the casing, pro­ceed as follows:
locate and remove the 2 screws that secure the
controls fascia to the appliance casing (see fig. 13).
locate and remove the 2 screws that secure the
casing to the back frame of the boiler (see fig. 13).
gently pull one side of the casing then the other
to disengage it from the retaining clips.
lift the casing upward to disengage it from the
top locating hooks and then remove.
store the casing and screws safely until required.
Re-fit in the reverse order.
Fig.13
Safety valve
outlet
Condensate
outlet pipe
Fig. 12
Return Gas
Flow
Cold water
inlet
4.8 ELECTRICAL CONNECTIONS
The electrical supply must be as specified in 3.7. A qualified electrician should connect the electri­cal supply to the appliance. If controls - external to the appliance - are required, a competent person must undertake the design of any external electrical circuits, please refer to section 8 for detailed instructions. ANY EXTERNAL CONTROL OR WIRING MUST BE SERVED FROM THE SAME ISOLATOR AS THAT OF THE APPLIANCE. The supply cable from the isolator to the appliance must be 3-core flexible sized 0,75mm to BS 6500. Wiring to the appliance must be rated for opera­tion in contact with surfaces up to 90°C.
4.8.2 ELECTRICAL INPUT BOARD
The appliance electrical input board is located behind the control fascia (see fig.14). Locate and remove the 4 screws securing the input board cover.
NOTE
The appliance comes with a factory fitted link to allow basic operation of the boiler via the keypad. If it is anticipated that external controls will be required please refer to the wiring diagrams in section 8 for more detailed information.
Cable
entries
Hot water
outlet
Fig.14
12
Page 15
Supplied By www.heating spares.co Tel. 0161 620 6677
4.8.3 CONNECTING THE MAINS (230V) INPUT (see fig. 15)
Remove the electrical input board cover as described in 4.8.2. Pass the cable through the cable anchorage (see fig. 6). Connect the supply cable wires (earth, live, & neutral) to their corresponding terminals on the electrical input board. Ensure that the EARTH wire is left slightly longer than the others, this will prevent strain on the Earth wire should the cable become taut. Do not remove the 24V link wire (between terminals 2 & 3 on plug M4) unless additional external controls are to be fitted (see section 8). Re-fit the electrical input board cover. The securing screw on the cable anchorage should now be tightened. This must be done before the control fascia is re-fitted in the upright position. The appliance casing and screws can
now be re-fitted.
Fig. 15
13
Page 16
Supplied By www.heating spares.co Tel. 0161 620 6677
SECTION 5 COMMISSIONING
5.1 GAS SUPPLY INSTALLATION
Inspect the entire installation including the gas meter, test for soundness and purge. Refer to BS 6891 for specific instruction.
5.2 THE HEATING SYSTEM
The appliance contains components that may become damaged or rendered inoperable by oils and/or debris that are residual from the installa­tion of the system, consequently it is essential that the system be flushed in accordance with the following instructions.
5.3 INITIAL FILLING OF THE SYSTEM
Ensure both flow and return service valves are open, remove appliance casing as described in
4.8.1, identify the automatic air release valve and loosen the dust cap by turning cap anti-clockwise one full turn. IMPORTANT, THERE ARE NO MANUAL AIR RELEASE VALVES LOCATED ON THE APPLIANCE. Ensure all manual air release valves located on the heating system are closed. Using the method of filling as described in fig. 5, slowly proceed to fill the system. As water enters the system the pressure gauge will begin to rise. Once the gauge has reached 1 bar close the filling valve and begin venting all manual air release valves, starting at the lowest first. It may be necessary to go back and top-up the pressure until the entire system has been filled. Inspect the system for water soundness, rectifying any leaks.
5.4 INITIAL FLUSHING OF THE SYSTEM
The whole of the heating system must be flushed both cold and hot as detailed in 5.8. Open all radiator or heating valves and the appliance flow & return service valves. Drain the boiler and system from the lowest points. Open the drain valve full bore to remove any installation debris from the boiler prior to lighting. Refill the boiler and heating system as described in 5.3.
5.5 FILLING THE HOT WATER SYSTEM
Close all hot water outlets, turn appliance stop­cock on (anti-clockwise), slowly open each outlet until all air has been expelled and clear water is discharged. Check pipe-work etc. for water soundness.
ensure the system has been filled, vented, and
the pressure set to 1 bar;
ensure the flue system has been fitted properly
and in accordance with the instructions;
ensure all appliance service valves are open.
5.7 INITIAL LIGHTING
Ensure the electrical supply to the appliance is switched on. Switch the time clock or programmer to an ‘on’ position and ensure all external controls are also calling for heat.
The appliance will now operate in the pre-heat mode as described in 1.2. Once the pre-heat function has been completed, the appliance will operate in the central heating mode as described in 1.4. Should the appliance fail to ignite, refer to
5.6 and/or section 7 (fault finding).
5.8 FINAL FLUSHING OF THE HEATING SYSTEM
The system shall be flushed in accordance with BS 7593. If a cleanser is to be used, it shall be from a reputable manufacturer* and shall be administered in strict accordance with the manufacturers instructions.
*Both Sentinel and Fernox manufacture products that have proved suitable for use with Vokera appliances. Vokera Ltd. cannot comment on the suitability of any other such product with our appliances.
5.8.1 INHIBITORS
See 3.12
5.9 OPERATING PARAMETERS
The Eclipse boiler is supplied with built-in parameter defaults (see 2.11), the following procedure can be used if any parameters require to be adjusted or changed.
Press the MODE button until a FIXED decimal
point appears in LED 1 (see fig. 16).
Press the STEP button until the desired
parameter is shown in LED 1.
Using the +/- buttons, change the parameter
value (shown in LED 2).
Press the STORE button to save the new value.
Press the MODE button until no decimal point
is shown.
5.6 PRE-OPERATION CHECKS
Before attempting to initial lighting of the appli­ance, the following checks must be carried out:
ensure all gas service valves from the meter to
the appliance are open and the supply pipe has been properly purged;
ensure the proper electrical checks have been
carried out, (see 7.7) particularly continuity, polarity and resistance to earth;
ensure the 3 amp fuse – supplied with the
appliance – has been fitted;
Fig. 16
14
Page 17
Supplied By www.heating spares.co Tel. 0161 620 6677
STEP
1 2
3
4
OPERATING PARAMETER
Hot water outlet temperature Pre-heat temperature drop
Central heating mode
Central heating flow temperature
5.10 FUNCTIONAL PARAMETERS
These parameters should only be changed or adjusted by the commissioning engineer or service technician. To change or adjust the functional parameters, it is necessary to access the appliance engineer mode.
Press and hold the MODE and STEP buttons
simultaneously, LED 1 should now show “C” (see fig. 17).
Whilst continuing to hold down the MODE and
STEP buttons, using the +/- buttons, adjust LED 2 until it shows “33”.
Press STORE.
LED 2 will now flash twice, the MODE and
STEP buttons can now be released.
Press the MODE button until it shows a FIXED
decimal point (see fig. 16).
Press the STEP button until it shows the desired
parameter (LED 1).
Adjust the value (LED 2) using the +/- buttons
Press STORE to save the new setting.
Press the RESET button to exit the appliance
engineer mode.
IMPORTANT
Under no circumstances should any parameters
- other than those shown above - be changed or adjusted. Please refer to section 7 before making any adjustments to the fan speed parameters of the boiler.
5.11 RANGE RATING
The output of the boiler is automatically adjusted by a continuous air/gas modulation system. The system is controlled by the NTC thermistors (flow
VALUE
Variable between 40°-65°C
DEFAULT SETTING
60°C
02 = 5°C 03 = 10°C 04 = 20°C
04 = 20°C
05 = 30°C 00 = off
01 = on
01 = on Variable between 20° 90°C
75°C
Fig. 17
& return temperature sensors) which ensures stability of temperature irrespective of load conditions. However the appliance also has a range rating facility which can be used to limit the maximum output - to central heating - if required. Please refer to section 7 for more details.
5.12 SETTING THE SYSTEM DESIGN PRESSURE
The design pressure should be a minimum of 1 bar and a maximum of 1,5 bar.
The actual reading should ideally be 1 bar plus equivalent height in metres (0,1 bar = 1 metre) to the highest point in the system above the base of the appliance (up to the maximum of 1,5 bar total). N.B. The safety valve is set to lift at 3 bar/30 metres/45 psig.
To lower the system pressure to the required value, pull lever on head of safety valve to release water until the required figure registers on the pressure gauge (see fig. 1).
STEP
A
OPERATING PARAMETER
Anty-cycle
VALUE DEFAULT SETTING
Variable between 0-30 (where 1=10,2 seconds)
b
Pump over-run
Variable between 3-99 (where 1=1 minute)
I
CH delay after HW request
Variable between 0-30 (where 1=10,2 seconds)
J
CH fan speed (maximum)
Variable between 17-55
(where 1=100 RPM) L n
DHW fan speed (maximum) Minimum fan speed (CH & DHW)
Fixed
Variable between 16-55
(where 1=100 RPM) o
Soft-light fan speed
Variable between 1-100
(where 1=1%)
9 (91,8 seconds) 10 (10 minutes) 3 (30,6 seconds) 55 (5500 RPM) 55 (5500 RPM)
17 (1700 RPM) 80 (%)
15
Page 18
Supplied By www.heating spares.co Tel. 0161 620 6677
5.13 REGULATING THE CENTRAL HEATING SYSTEM
Fully open all radiator and circuit valves and run the appliance for both heating and hot water until heated water is circulating. If conditions are warm remove any thermostatic heads. Adjust radiator return valves and any branch circuit return valves until the individual return temperatures are correct and are approximately equal.
5.14 FINAL CHECKS
ENSURE ALL TEST NIPPLES ON THE AP-
PLIANCE GAS VALVE ARE TIGHT AND HAVE BEEN CHECKED FOR SOUNDNESS.
ENSURE THE APPLIANCE FLUE SYSTEM IS
FITTED CORRECTLY AND IS PROPERLY SECURED.
ENSURE ALL PIPE WORK IS RE-CHECKED
FOR SOUNDNESS.
RE-FIT APPLIANCE CASING.
COMPLETE APPLIANCE LOGBOOK.
Complete details of the boiler, controls, installa­tion and commissioning in the logbook supplied with the boiler. This is an important document, which must be correctly completed and handed to the user. Failure to install and commission the appliance to the manufacturers instructions may invalidate the warranty.
5.15 INSTRUCTING THE USER
Hand over all documentation supplied with this appliance – including these instructions – and explain the importance of keeping them in a safe place.
Explain to the user how to isolate the appliance from the gas, water, and electricity supplies, and the locations of all drain points.
Show the user how to operate the appliance and its associated controls correctly.
Show the user the location of the filling valve and how to top-up the system pressure correctly, and show the location of all manual air release points.
Explain to the user how to turn off the appliance for both long and short periods, and advise on the necessary precautions to prevent frost damage.
16
Page 19
Supplied By www.heating spares.co Tel. 0161 620 6677
SECTION 6 SERVICING INSTRUCTIONS
6.1 GENERAL
To ensure the continued safe and efficient opera­tion of the appliance, it is recommended that it is checked and serviced at regular intervals.
The frequency of servicing will depend upon the particular installation conditions, but in general, once per year should be adequate.
It is the law that any servicing work is carried out by a competent person such as a Vokera engineer, an approved service agent, British Gas, or other CORGI registered personnel.
The following instructions apply to the appliance and its controls, but it should be remembered that the central heating system will also require attention from time to time.
6.2 ROUTINE ANNUAL SERVICING
Check the operation of the appliance and ensure
it functions as described in section 7.
Compare the performance of the appliance
with its design specification. The cause of any noticeable deterioration should be identified and rectified without delay.
Thoroughly inspect the appliance for signs of
damage or deterioration especially the flue system and the electrical apparatus.
Check and adjust – if necessary – the system
design pressure (see 5.12).
Ensure both the burner and heat exchanger are
clean and free from any debris or obstruction.
Carry out an analysis of the flue gases (see
7.4), and visually check the condition of the entire flue assembly.
Compare the results with the appliance design
specification. Any deterioration in performance must be identified and rectified without delay.
Inspect all joints for signs of leakage and repair
if necessary.
Refer to the commissioning section and/or re-
placement of parts section for detailed instruction if required.
6.3 REPLACEMENT OF COMPONENTS
Although it is anticipated that this appliance will give years of reliable, trouble free service, the life span of components will be determined by factors such as operating conditions and usage. Should the appliance develop a fault, the fault finding section will assist in determining which component is malfunctioning.
some water absorbent cloths are available to catch any residual water that may drip from the appliance or removed component. Undertake a complete commissioning check as detailed in section 5, after replacing any component.
ALWAYS TEST FOR GAS SOUNDNESS IF ANY GAS CARRYING COMPONENTS HAVE BEEN REMOVED OR DISTURBED.
6.5 PUMP HEAD (see fig. 18)
Carry out component removal procedure as de­scribed in 6.4. Using a 4mm Allen key or ‘T’ bar, unscrew and remove the four Allen screws that hold the pump in position, pull firmly on the pump head to release it from the base. Disconnect the electrical leads. Replace in the reverse order.
Pump head
Fig. 18
6.6 SAFETY VALVE (see fig. 19)
Carry out component removal procedure as de­scribed in 6.4. Disconnect the outlet pipe from the safety valve. Remove safety valve locking screw from the underside of the appliance manifold. Replace in the reverse order.
6.7 AUTOMATIC AIR RELEASE VALVE (AAV)
Carry out component removal procedure as de­scribed in 6.4. Using a suitable pair of pump pliers, unscrew the AAV from its position. Replace in the reverse order.
6.4 COMPONENT REMOVAL PROCEDURE
To remove a component, access to the interior of the appliance is essential. Isolate the appliance from the electrical supply and remove the fuse. And when necessary, close all service valves on the appliance, remove the appliance casing as described in section 4.8.1. Drain the water content from the appliance via the safety valve. Ensure
Fig. 19
Safety valve
Locking screw
17
Page 20
Supplied By www.heating spares.co Tel. 0161 620 6677
6.8 PRESSURE GAUGE (see fig. 20)
Carry out component removal procedure as de­scribed in 6.4. Remove pressure gauge locking screw, located on manifold, and withdraw the pressure gauge pipe, locate the spring tabs on the pressure gauge body, push and hold tabs in, to enable extraction of the gauge from its location. Replace in the reverse order.
Manifold
Pressure gauge connection
Locking screw
Fig. 20
6.9 NTC THERMISTORS (temperature sensors)
Carry out component removal procedure as de­scribed in 6.4.
Cold water inlet sensor (see fig. 21)
Disconnet thermistor electrical plug. Using a 13mm spanner slacken and remove the thermistor and sealing washer. Replace in the reverse order.
Screw
Screw
Fig. 22
6.10 PRINTED CIRCUIT BOARD (PCB) (see fig. 23)
Carry out component removal procedure as de­scribed in 6.4.
Locate and remove the 4 screws that secure
the PCB housing cover, then remove cover.
After carefully taking note of all wiring
connections, disconnect all wiring from the PCB.
Locate and remove the PCB housing securing
screws, remove PCB housing.
Remove the 4 screws that secure the
transformer to the PCB housing.
Locate and remove the 3 screws that secure
the PCB to the housing.
Replace in the reverse order.
Housing
P.C.B.
Cover
Actuator
locking pin
Actuator
Fig. 21
Cold water
inlet sensor
Flow & return sensors (see fig. 1 & 22)
Pull back protective boot and remove the 2 spade connectors. Slacken and remove the 2 securing screws. Replace in the reverse order.
Fig. 23
6.11 GAS VALVE (see fig. 24)
Carry out component removal procedure as de­scribed in 6.4. The gas valve must be changed as complete unit. Unclip and remove the air chamber cover. Disconnect the electrical plug from the gas valve. Disconnect silicone tube from gas valve regulator. Slacken and unscrew gas valve inlet and outlet connections. Please note, the sealing washers must be discarded and replaced with new sealing washers. The gas valve can now be removed. Replace in the reverse order. Refer to section seven for detailed instructions on how to set-up the gas valve. WARNING, A GAS SOUNDNESS
CHECK MUST BE CARRIED OUT.
18
Page 21
Supplied By www.heating spares.co Tel. 0161 620 6677
6.12 FAN (see fig. 24)
Carry out component removal procedure as de­scribed in 6.4. Unclip and remove the air chamber cover. Disconnect the electrical plug from the fan. Locate and remove the 4 bolts that secure the fan to the pre-mix manifold. Replace in reverse order.
Silicone tube
Outlet
All dimensions in mm.
Pre-mix manifold
Gas valve
Inlet
Fig. 24
Fan securing bolts
6.13 BURNER (see fig. 25)
Carry out component removal procedure as de­scribed in 6.4. Unclip and remove the air chamber cover. Locate and remove the 8 nuts (10mm) securing the pre-mix manifold/burner assembly. Disconnect the gas valve outlet pipe at its connection to the pre-mix manifold. Disconnect the silicone pipe from the pre-mix manifold. Gently pull away the fan/pre-mix manifold assembly from the heat exchanger. Remove the earth wire from the burner earth tab and gently lift the burner from its location. Replace in the reverse order. Please note, ensure all seals are in good condition, taking care to ensure they are replaced correctly.
Fan
Fig. 26
6.14 ELECTRODE (see fig. 25 & 26)
Carry out component removal procedure as de­scribed in 6.4. Unclip and remove the air chamber cover. Remove the electrode lead. Remove the 2 screws that secure the electrode to the combustion cover, and gently withdraw the electrode. Replace in the reverse order, ensuring that the electrode seal is in good condition and that the combustion cover insulation board is undisturbed.
6.15 INJECTOR (see fig. 27)
Carry out component removal procedure as de­scribed in 6.4. Unclip and remove the air chamber cover. Remove the fan as detailed in 6.12 using a 17mm socket, locate and unscrew the injector. Replace in the reverse order.
Securing nuts
Spark
electrode
Fig. 27
Fig. 25
Gas valve outlet
connection
Burner plate
Injector
Fan
19
Page 22
Supplied By www.heating spares.co Tel. 0161 620 6677
6.16 DOMESTIC HOT WATER HEAT EXCHANGER (see fig. 31)
Carry out component removal procedure as de­scribed in 6.4. Remove motorised valve actuator as described in 6.17. Disconnect condense outlet pipe from the condense trap. Remove the insulation cover from the DHW heat exchanger. Locate and remove both inlet and outlet securing screws. Gently ease the heat exchanger from its location. Replace in the reverse order, ensuring the rubber O’ ring seals are in good condition and are correctly located.
6.20 CONDENSE PRESSURE SWITCH (see fig. 29)
Carry out component removal procedure as described in 6.4. Unclip and remove the air chamber cover. Disconnect the electrical wiring and pressure tube from the pressure switch. Remove the retaining screws and/or clip. Replace in the reverse order.
6.17 MOTORISED VALVE ACTUATOR (see fig. 31)
Carry out component removal procedure as de­scribed in 6.4. Disconnect the electrical plug from the actuator. Remove the locking pin from the divertor valve cover. Withdraw the actuator. Replace in the reverse order.
6.18 DIVERTOR VALVE ASSEMBLY (see fig. 31)
Carry out component removal procedure as de­scribed in 6.4. Remove motorised valve actuator as described in 6.17. Remove the divertor valve cover by unscrewing the 4 retaining screws. The divertor valve assembly is held in place by an O’ ring seal, the components are spring loaded. Care should be taken when removing the valve cover or when levering the sealing plate from its position. Replace in the reverse order, ensuring that the divertor valve spring and bobbin are seated properly.
NOTE
It may be prudent to replace the O’ ring seals and valve cover gasket whenever the divertor valve assembly is disturbed.
6.19 CONDENSE TRAP (see fig. 28)
Carry out component removal procedure as described in 6.4. Remove the PCB housing as described in 6.10. Disconnect the pressure switch tube from the condense trap. Disconnect both the inlet and outlet connections from the trap. Carefully withdraw the trap, keeping it upright to a v oid spillage. Replace in the reverse order.
Condense pressure switch
Fig. 29
6.21 COMBUSTION COVER (see fig. 31)
Carry out component removal procedure as described in 6.4. Unclip and remove the air chamber cover. Remove the gas valve as described in 6.11. Remove the condense pressure switch as described in 6.20. Disconnect the electrical connection from the fan, disconnect the spark electrode lead and earth wire from the spark electrode. Locate and remove the twelve 10mm securing nuts. Carefully remove the combustion cover from the locating studs. Remove the combustion cover from the air chamber, withdrawing it at a slight angle from the right hand side. Replace in the reverse order, ensuring that all seals and insulation panels are undamaged and in good condition.
Fig. 28
Fig. 30
20
Page 23
Supplied By www.heating spares.co Tel. 0161 620 6677
6.22 EXPANSION VESSEL (see fig. 1)
Due to the compact design of this appliance, removal and/or replacement of the expansion vessel may require the appliance to be removed from the wall, if this is deemed impractical, an external expansion vessel may be fitted to the return pipe as close to the appliance as possible.
6.22.1 EXPANSION VESSEL (removal)
Carry out component removal procedure as described in 6.4. Disconnect the flue from the appliance. Disconnect the expansion pipe from the hydraulic manifold. Locate and remove the 2 screws that secure the vessel to the rear frame. The expansion vessel can now be removed. Replace in the reverse order. Ensure all seals are in good condition, taking care to ensure they are replaced correctly.
DHW heat exchanger
6.23 INPUT PCB & STATUS PCB (see fig. 14)
Carry out component removal procedure as described in 6.4.
Refer to 4.8.2 for details on how to remove the PCB cover. Carefully note the positions of all connections relative to the PCB that is to be removed. Remove the wiring and plugs from the PCB. Locate and remove the securing screws. Remove PCB.
Replace in the reverse order, ensuring correct configuration of wiring.
Flow-rate restrictor
Manifold
Divertor valve assembly
Outlet securing screw
Non-return valve
Cold water inlet sensor
Auto-bypass assembly
Inlet securing screw
Locking pin
Fig. 31
Motorised valve actuator
21
Page 24
Supplied By www.heating spares.co Tel. 0161 620 6677
SECTION 7 CHECKS, ADJUSTMENTS, AND FAULT FINDING
7.1 CHECKING APPLIANCE OPERATION
When carrying out any repairs or servicing to the appliance, the relevant commissioning and/or set-up procedure must be undertaken to ensure the continued safe operation of the appliance. Particular attention should be made to ensure gas soundness, water soundness, and the electrical integrity of the appliance.
7.2 APPLIANCE MODE OF OPERATION
7.2.1 START-UP
When power is first supplied to the appliance it will go through a self-purge procedure whereby the pump, fan, and motorised valve will be momentarily energised. The boiler will then operate in either one of the following modes:
DHW pre-heat
Central Heating
DHW operation
NOTE
A DHW request has priority over the other modes of operation.
7.2.2 PRE-HEAT
When there is no demand for heating or hot water, the boiler will periodically light to pre-heat the domestic hot water heat exchanger to approximately 55°C (measured via the cold water inlet sensor). This ensures that the appliance is at operating temperature when there is a request for domestic hot water. The parameter for the allowable temperature drop – between pre-heat operation – can be adjusted. If the appliance remains inactive for a period of 24 hours, the pump and motorised valve will be energised for a few moments to prevent these components from seizing. Should the flow temperature sensor fall below 7°C the pump will be energised. If the flow sensor temperature falls to below 3°C the burner will be lit and the appliance will operate at the minimum output until the temperature of the flow sensor reaches 10°C, whereupon the pump will continue to run in pump over-run mode.
7.2.3 DOMESTIC HOT WATER MODE
When the appliance is at rest, the motorised valve is energised to the hot water position, when a demand for hot water is made the cold water temperature sensor activates the pump and fan. When the fan is sensed to be operating correctly, the ignition sequence commences. The speed of the fan and therefore the output of the boiler is determined by the temperature of the water sensed by the return temperature sensor, consequently a high temperature at the return sensor results in a lower fan speed.
7.2.4 DHW TEMPERATURE ADJUSTEMENT
The temperature of the hot water outlet can be adjusted via the operating parameters (see 5.9). The boiler is also fitted with a flow-rate restrictor (see fig. 28) that limits the actual flow of hot water
to the taps or outlets. This is to ensure that the boiler maintains a reasonable outlet temperature even if the tap or outlet is fully open.
However if the incoming mains pressure is unusually high, it may possible for the flow-rate to exceed the desired limit, if this situation occurs the following procedure should be followed:
set the hot water outlet temperature to maximum
(see 5.9);
open the hot water outlet (preferably the bath
tap) fully;
use the adjustable stopcock (fitted on the cold
water inlet) to reduce the flow of water through the boiler until a reasonable temperature is achieved.
7.2.5 CENTRAL HEATING MODE
When there is a request for heat via the time clock and/or external controls the motorised valve and pump will go through a self-test function this is to ensure correct operation and valve configuration. Once the self-test function is complete, the pump and fan will be activated via the flow temperature sensor. When the fan is sensed to be operating correctly, the ignition sequence commences. The speed of the fan and therefore the output of the boiler is determined by the temperature of the water sensed by the flow & return temperature sensors, consequently a high temperature at the flow sensor results in a lower fan speed. As the water temperature increases, the temperature sensors – located on the flow and return pipes of the boiler – reduce the fan speed via the electronic circuitry. Depending on the load, either the water temperature will continue to rise until the set point is achieved or the water temperature will fall whereby fan speed will increase relative to the output required. When the boiler has reached the set point, the burner will switch off. The built-in anti-cycle device prevents the burner from re­lighting for an adjustable period of time (factory default is 3 minutes). When the temperature of the flow sensor falls below the set-point, the burner will re-light.
7.3 CHECKING/ADJUSTING FAN SPEEDS
To check the fan speeds, you must first access the engineer mode. Before entering the appliance engineer mode, allow the boiler to purge and preheat the DHW heat exchanger. The fan speed should only be changed or adjusted by the commissioning engineer or service technician (see 5.10). To access the appliance engineer mode:
press and hold the MODE and STEP buttons
simultaneously, LED 1 should now show ‘C’ (see fig. 17);
whilst continuing to hold down the MODE and
STEP buttons, using the +/- buttons, adjust LED 2 until it shows ‘33’;
22
Page 25
Supplied By www.heating spares.co Tel. 0161 620 6677
press STORE;
LED 2 will now flash once, the MODE and
STEP buttons can now be released;
press the MODE button until it shows a FIXED
decimal point (see fig. 16).
7.3.1 MAXIMUM FAN SPEED (central heating)
Press the STEP button until it shows the
letter ‘J’ (LED 1).
Adjust the value (LED 2) using the +/- buttons
(see fig. 33)
Press STORE to save the new setting.
7.3.2 MAXIMUM FAN SPEED (DHW)
Press the STEP button until it shows the letter
‘L’ (LED 1).
Adjust the value (LED 2) using the +/- buttons
until it shows ‘55’
Press STORE to save the new setting.
7.3.3 MINIMUM FAN SPEED (DHW & CH)
Press the STEP button until it shows the letter
‘N’ (LED 1).
Adjust the value (LED 2) using the +/- buttons
until it shows ‘17’
Press STORE to save the new setting.
7.3.4 SOFT-LIGHT FAN SPEED
Press the STEP button until it shows the letter
‘O’ (LED 1).
Adjust the value (LED 2) using the +/- buttons
until it shows ‘80’
Press STORE to save the new setting.
7.3.5 FAN SPEED CONFIRMATION
To verify that the new fan speed has been accepted into the memory:
press and hold the MODE and ‘+’ buttons for 3
Seconds;
allow the boiler to purge (approx. 10 seconds);
when ‘H’ is displayed in LED 1, press the
MODE button until LED 1 shows an alternating cursor (see fig. 33);
when the digit is to the left, LED 2 shows the first
two digits of the maximum fan speed;
when the digit is to the right, LED 2 shows the
last two digits of the maximum fan speed;
press the MODE button until a fixed decimal is
shown in LED 1;
press and hold the MODE and ‘-–‘ buttons until
‘L’ appears in LED 1;
press the MODE button until LED 1 shows an
alternating cursor (see fig. 33);
when the digit is to the left, LED 2 shows the first
two digits of the minimum fan speed;
when the digit is to the right, LED 2 shows the
last two digits of the minimum fan speed.
NOTE
The actual fan speed displayed may not exactly match what has been programmed. However, providing the displayed speed is within 200 RPM (+/-) of the programmed speed, this is acceptable.
7.3.6 EXIT ENGINEER MODE
Press the RESET button to exit the appliance engineer mode.
Output BTU/H
102,360
85,300
68,240
51,180
34,120 17,060
0
30
25
20
15
kW
10
5
0 1500 2000 2500 3000 3500 4000 4500 5000 5500
Fig. 32
50°C flow & 30°C return temperature
Fan speed in RPM
Digit to the left
LED 2 showing first two digits of actual fan speed
80°C flow & 60°C return temperature
7.4 ADJUSTING THE GAS VALVE THE GAS VALVE MUST BE SET-UP OR
ADJUSTED WITH THE AID OF A PROPERLY CALIBRATED FLUE GAS ANALYSER.
Remove the appliance casing as detailed in 4.8.1. Unclip and remove the air chamber cover. Set the flue gas analyser to read CO2 and insert the probe into the flue analysis test point (see fig. 1). Using the procedure as detailed in 7.3 & 7.3.5 respectively, enter the appliance engineer mode and set the fan speed to minimum.
Digit to the right
LED 2 showing the last two digits of the actual fan speed
Fig. 33
Fan speed shown is 4198 RPM
23
Page 26
Supplied By www.heating spares.co Tel. 0161 620 6677
7.4.1 MINIMUM SETTING
With the boiler operating at minimum output the CO2 reading should be 8.6% (+/- 0.2%). If the CO reading is correct, proceed to 7.4.2. If the CO reading is incorrect, the minimum gas pressure must be adjusted as follows:
Remove the cover, then using a suitable
screwdriver, very slowly turn the minimum adjustment screw (see fig. 34) – clockwise to increase, counter clockwise to decrease – until the correct value is displayed on the CO analyser (allow time for the analyser to stabilise).
Using the procedure detailed in 7.3.5, change
the fan speed momentarily from minimum to maximum, then back to minimum.
Check that the correct value is still being
obtained. If not, repeat the above procedure.
NOTE
You should ensure that all radiators or heat
2 2
emitters are fully open during the above procedures. This will ensure that the fan speed (output) of the boiler is not compromised due to a high flow temperature.
7.5 LED 1 STATUS CODES
When the boiler is operating normally (without fault), LED 1 displays the current status of the
2
boiler whilst LED 2 will normally display the relevant outlet temperature.
Status
Standby
Purge
LED 1
0 1
LED 2
CH inlet temp.
Flow/return temp.
7.4.2 MAXIMUM SETTING
The maximum setting must only be checked and/ or adjusted after the correct minimum setting has been verified. Using the procedure detailed in
7.3.5, change the fan speed from minimum to maximum.
With the boiler operating at maximum output the CO2 reading should be 8.6% (+/- 0.2%). If the CO reading is correct, press the RESET button to exit the appliance engineer mode. If the CO2 reading is incorrect, the maximum gas pressure must be adjusted as follows:
Using a suitable screwdriver, very slowly turn
the maximum adjustment screw (see fig. 34) – clockwise to increase, counter clockwise to decrease – until the correct value is displayed on the CO2 analyser (allow time for the analyser to stabilise).
Using the procedure detailed in 7.3.5, change
the fan speed momentarily from maximum to minimum, then back to maximum.
Check that the correct value is still being
obtained. If not, repeat the above procedure.
Press the RESET button to exit the appliance
engineer mode.
Remove the analyser test probe from the analysis test point and refit cap. Refit the air chamber cover. Refit appliance casing.
Ignition
CH mode
DHW mode
Fan-speed low
Built-in delay
CH over-run
2
DHW over-run
High temperature
LED 1
E E E E E
E
2 3 4 5 6 7 8 9
Flow/return temp. Flow/return temp.
Return temperature
Flow/return temp. Flow/return temp. Flow/return temp.
DHW over-run
Return temperature
In addition to the above operating status codes, the boiler may also display intermittent anomaly codes as featured below.
LED 2
18 19 24
Temperature differential exceeded
Reason for lockout
Flow sensor above 95°C
Return sensor above 95°C
26 30
Return sensor 35°C higher than flow
sensor
65
Insufficient fan speed
Maximum screw
Minimum screw
Fig. 34
24
Page 27
Supplied By www.heating spares.co Tel. 0161 620 6677
7.6 LOCKOUT FAULT CODES
The built-in fault diagnostic system automatically displays a unique fault code that can be used to determine why the boiler has locked out.
LED 1
LED 2
0 1 2 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 24 26 30
Reason for lockout
False flame
24V short circuit
No flame detected
Internal fault (PCB)
Lockout then power off
Internal fault (PCB) Internal fault (PCB) Internal fault (PCB) Internal fault (PCB) Internal fault (PCB) Internal fault (PCB) Internal fault (PCB) Internal fault (PCB) Internal fault (PCB) Internal fault (PCB) Internal fault (PCB) Internal fault (PCB) Internal fault (PCB)
Flow/return sensors reversed
Internal fault (PCB)
Difference between flow & return
temperature too high 4 4 4 4 4 4 4 4 4 4 5 5 5 5 9 9 9 9
31 32 33 36 37 38 41 42 44 60 28 29 61 65 12 18 19 25
Short circuit on flow sensor
Short circuit on return sensor
Short circuit on inlet sensor Open circuit on flow sensor
Open circuit on return sensor
Open circuit on inlet sensor
Internal fault (PCB) Internal fault (PCB) Internal fault (PCB) Internal fault (PCB)
No signal from fan Internal fault (PCB) Internal fault (PCB)
Insufficient fan speed
Condense trap blocked
Flow temperature too high
Return temperature too high
Rapid temperature increase
7.7 DIAGNOSTIC RECALL
In addition to displaying a fault code, the appliance memorises the operating conditions at the time of lockout, this information can be recalled and displayed using the following procedure:
Access the appliance engineer mode as detailed
in 5.10.
Press the MODE button until a flashing ‘1’
appears in LED 1.
Press the STEP button to recall the information
as detailed below.
Press the RESET button to exit the appliance engineer mode.
LED 2 shows
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 24 26 30 31 32 33 36 37 38 41 42 44 60 28 29 61 65 12 18 19 25
LED 2 shows
0 1 2 3 4 5 6 7 8 9
LED 2 shows °C
LED 1 shows 1
Reason
False flame
24V short circuit
No flame detected
Internal fault (PCB)
Lockout then power off
Internal fault (PCB) Internal fault (PCB) Internal fault (PCB) Internal fault (PCB) Internal fault (PCB) Internal fault (PCB) Internal fault (PCB) Internal fault (PCB) Internal fault (PCB) Internal fault (PCB) Internal fault (PCB) Internal fault (PCB) Internal fault (PCB)
Flow/return sensors reversed
Insufficient gas pressure
Internal fault (PCB)
Short circuit on flow sensor
Short circuit on return sensor
Short circuit on inlet sensor Open circuit on flow sensor
Open circuit on return sensor
Open circuit on inlet sensor
Internal fault (PCB) Internal fault (PCB) Internal fault (PCB) Internal fault (PCB)
No signal from fan No signal from fan
Internal fault (PCB)
Insufficient fan speed
Condense trap blocked
Flow temperature too high
Return temperature too high
Rapid temperature increase
LED 1 shows 2
Reason
Standby
Purge
Ignition
CH mode
DHW mode
Fan-speed low
Built-in delay
CH over-run
DHW over-run
High temperature
LED 1 shows 3
Temperature of flow sensor at time
of lockout
25
Page 28
Supplied By www.heating spares.co Tel. 0161 620 6677
LED 1 shows 4
LED 2 shows °C
Temperature of return sensor at
time of lockout
LED 1 shows 5
LED 2 shows °C Temperature of cold water inlet
sensor at time of lockout
7.8 TEMPERATURE SENSOR VIEWING MODE
The current temperature of the three temperature sensors can be viewed individually via the LED display, in addition the set-point of the flow or return sensor can also be viewed (depending on mode of operation). To access the viewing mode:
Press the MODE button until a flashing decimal
point is displayed in LED 1.
Press the STEP button to display the relevant
information in LED 2 (see below).
LED 1 SHOWS
1 2 3 4 5 6 7 8
Set-point (dependant on mode)
Temperature rise per second
LED 2 SHOWS
Flow sensor temperature
Return sensor temperature
Cold water inlet temperature
N/A N/A
Return rise per 8 seconds
9
7.9 CHECKING THE EXPANSION VESSEL
Carry out the component removal procedure as described in 6.4. You must ensure that the boiler is completely drained of water. Using a suitable pressure gauge, remove dust cap on expansion vessel and check the charge pressure. The correct charge pressure should be
1.0 bar ± 0.1 bar. If the charge pressure is less, use a suitable pump to increase the charge.
Please note, you must ensure the safety valve is in the open position whilst re-charging takes place. Replace the dust cap and carry out the relevant commissioning procedure.
7.10 EXTERNAL FAULTS
Before carrying out any fault-finding or component replacement, ensure the fault is not attributable to any aspect of the installation. For example, external wiring fault, service valves closed, gas supply turned off, etc. The table below may assist in identifying some common installation faults.
Fault code Displayed
Possible cause
Gas turned off
202
Air in gas pipe
Insufficient gas
Pump seized
918 436
Flow/return service valve
Flow sensor cable
disconnected
437
Return sensor cable
disconnected
438
Cold water inlet sensor cable
disconnected
7.11 ELECTRICAL CHECKS
Any electrical checks must be carried out by a suitably qualified person.
7.11.1 EARTH CONTINUITY TEST
Isolate the appliance from the electrical supply, and using a suitable multi-meter carry out a resistance test. Connect test leads between an appliance earth point and the earth wire of the appliance supply cable. The resistance should be less than 1 ohm. If the resistance is greater than 1 ohm check all earth wires and connectors for continuity and integrity.
7.11.2 SHORT CIRCUIT CHECK
Isolate the appliance from the electrical supply, and using a suitable multi-meter, carry out a short circuit test between the Live & Neutral connections at the appliance input board (see fig.15). Repeat above test on the Live & Earth connections at the appliance input board (see fig.15).
NOTE
Should it be found that a fuse has failed but no fault is indicated, a detailed continuity. Check will be required to trace the fault. A visual inspection of components may also assist in locating the fault.
7.11.3 POLARITY CHECK
With the appliance connected to the electrical supply and using a suitable Multi-meter, carry out the following voltage tests:
connect test leads between the Live & Neutral
connections at the appliance input board (see fig.15). The meter should read approximately 230V ac. If so proceed to next stage. If not, see 7.11.4.
connect test leads between the Live & Earth
connections at the appliance input board (see fig.15). The meter should read approximately 230V ac. If so proceed to next stage. If not, see 7.11.4.
connect test leads between the Neutral & Earth
connections at the appliance input board (see fig.15). The meter should read approximately 0 – 15Vac. If so polarity is correct. If not, see 7.11.4.
closed
26
Page 29
Supplied By www.heating spares.co Tel. 0161 620 6677
7.11.4 REVERSED POLARITY OR SUPPLY FAULT
Repeat the above tests at the appliance isolator, if testing reveals correct polarity and/or supply at the isolator, re-check wiring and connections between the isolator and the appliance. If tests on the isolator also reveal reversed polarity or a supply fault, consult the local electricity supplier for advice.
7.11.5 RESISTANCE TO EARTH CHECK
Isolate the appliance from the electrical supply, and using a suitable multi-meter carry out a resistance test. Connect test leads between the Live & Earth connections at the appliance input board (see fig.15). If the meter reads other than infinity there is a fault that must be isolated, carry out a detailed continuity check to identify the location of the fault.
IMPORTANT
These series of checks must be carried out before attempting any fault-finding procedures on the appliance. On completion of any task that required the disconnection and re-connection of any electrical wiring or component, these checks must be repeated.
FAULT
No display, boiler
inactive
No display, valve
actuator working
(press reset to test)
No display, pump
running
No display, pump
running, fan speed
alternating
No display, boiler
working okay
Pump failure
Fan fault
Ignition fault
7.12.2 WIRING DIAGRAMS
Figures 36 & 37 indicate the positions of all plugs, fuses and internal wiring configuration.
GO TO
Test 1
Test 1A
Test 1A
Test 1A
Test 1A
Test 2 Test 3 Test 4
7.11.6 FUSES
The appliance is equipped with spare fuses. These fuses are located on the covers of the input board and main PCB respectively. If a fuse has blown it is usually indicative of an external wiring fault or a faulty component such as the pump, fan, valve actuator, etc. Under no circumstances should a blown fuse be replaced with one of a higher rating.
7.12 FAULT FINDING BEFORE ATTEMPTING ANY FAULT
DIAGNOSIS OR REPAIR THE FOLLOWING PROCEDURE SHOULD BE CARRIED OUT:
carry out the relevant electrical checks as
detailed in 7.11;
disconnect any external wiring from plug M4
(terminals 2 & 3) and replace with a solid link wire,
ensure the appliance is protected – externally –
by a 3 amp fuse.
IMPORTANT The Eclipse boiler utilises 24V switching. Any
external controls that are directly connected to the boiler must be suitable for 24V applications and shall be voltage free. Under no circumstances should a 230V supply be connected to plug M4.
7.12.1 FAULT FINDING TESTS
If a lockout code is displayed on LED’s 1 & 2, please refer to 7.6 for the cause of the lockout.
27
Page 30
Supplied By www.heating spares.co Tel. 0161 620 6677
7.12.3 FAULT FINDING TEST ‘1’
YES
IS THERE
230V AT
YES
PLUG X1 (L & N)
YES
IS THERE
230V AT
PLUG M6 ON INPUT
BOARD?
NO
TEST1
SWITCH ON ELECTRICAL
SUPPL Y T O BOILER
IS THERE
230V AT
PLUG M5 ON INPUT
BOARD?
NO
CHECK
FUSE ON
INPUT BOARD
NO
CHECK
INCOMING
SUPPLY
END OF
TEST
7.12.4 FAULT FINDING TEST ‘1A’
CHECK CONTINUITY
NO
BETWEEN
INPUT PCB &
MAIN PCB
YES
IS THERE 10-14 Vdc
A T TERMINALS
1 & 7 OF
PLUG X7
TEST 1A
IS THERE
230V AT
PLUG X1
(L & N)
YES
NO
GO TO
TEST 1
IS FUSE
F1 OK?
NO
REPLACE
FUSE
NO
REPLACE
PCB
NO
YES
REPLACE
PCB
YES
ARE FUSES F2 & F3
OK?
YES
24Vac
A T TERMINALS
6 & 7 OF
PLUG X10
NO
REPLACE
FUSE/S
YES
230V AT
TERMINALS
1 & 3 OF
PLUG X10
REPLACE
TRANSFORMER
28
YES
REPLACE
DISPLAY PCB
IS THERE 10-14 Vdc
A T TERMINALS
1 & 7 OF PLUG X7a
OF DISPLAY PCB
NO
CHECK
CONTINUITY OF
RIBBON CABLE
Page 31
Supplied By www.heating spares.co Tel. 0161 620 6677
7.12.5 FAULT FINDING TEST ‘2’
YES
TEST 2
PUMP FAULT
230V ON
TERMINALS P & N
OF PLUG X1
NO
230V AT
L & N OF PUMP
YES
REPLACE
PUMP
7.12.6 FAULT FINDING TEST ‘3’
NO
CHECK
CONTINUITY
YES
REPLACE
YES
PCB
F1 FUSE ON
MAIN PCB OK
TEST 3
FAN
FAULT
IS "5"
DISPLAYED
AT LED 1
NO
REPLACE
FUSE
NO
NO
REPLACE
PCB
NO
NO
IS THERE 4-9 Vdc
A T TERMINALS
1 & 2 ON
PLUG X2
YES
CHECK
CONTINUITY
YES
IS THERE 4-9 Vdc
AT GREY & PINK
WIRE OF FAN
NO
REPLACE
FAN
YES
REPLACE
PCB
YES
FAN IS
OK?
YES
IS THERE
4-9 Vdc
A T TERMINALS
1 & 2 ON
PLUG X2
DOES
FAN RUN
YES
REPLACE
YES
IS THERE 1,8-2 Vdc
AT GREY & BLUE
WIRE OF FAN
NO
CHECK
CONTINUITY
FAN
NO
REPLACE
FAN
NO
IS THERE 30-35 Vdc
AT RED & GREY
WIRE OF FAN
YES
CHECK
CONTINUITY
PRESS RESET ENSURE HEAT
REQUEST
NO
IS THERE 30-35 Vdc
A T TERMINALS
2 & 3 OF
PLUG X2
NO
REPLACE
PCB
29
Page 32
Supplied By www.heating spares.co Tel. 0161 620 6677
7.12.7 FAULT FINDING TEST ‘4’
YES
TEST 4
IGNITION
FAULT
SPARK
AT ELECTRODE
NO
NO
CHECK:
SPARK GAP,
ELECTRODE & LEAD,
EARTH
CONNECTION
YES
OK?
NO
IS IONISATION
VOLTAGE
ABOVE 2,0 Vdc
NO
YES
DOES BURNER STAY LIT
YES
REPLACE
PCB
YES
FINISH
SILICONE PIPE &
YES
REPLACE
GAS VALVE
DOES
BURNER
LIGHT
YES
CHECK: GAS
SUPPLY,
NOZZLE, VALVE
REGULATOR
OK?
REST ART TEST
NO
24 VA C
AT GAS VALVE
NO
RECTIFY &
YES
REPLACE
PCB
YES
CHECK
CONTINUITY
ARE
ELECTRODE
& LEAD OK
NO
24 VA C
A T TERMINALS
11 & 12 OF PLUG X2
NO
REPLACE &
REST ART TEST
NO
REPLACE
PCB
REPLACE
PCB
RECTIFY &
REST ART TEST
IONISATION CHECK: Terminal 5 on plug X2 to Earth
30
Page 33
Supplied By www.heating spares.co Tel. 0161 620 6677
SECTION 8 WIRING DIAGRAMS
8.1 IMPORTANT The Eclipse boiler utilises 24V switching. Any
external controls that are directly connected to the boiler must be suitable for 24V applications and shall be voltage free. Under no circumstances should a 230V supply be connected to plug M4.
8.2 INSTALLATION OF VOKERA TIMECLOCK (part no. 201 or 202)
Isolate the appliance from the electrical supply
and remove the casing as described in 4.8.1.
Gain access to the electrical input board as
detailed in 4.8.2.
Remove the square blanking plate from the
clock aperture of the control panel.
Insert the clock bezel (supplied with boiler) into
the aperture and secure in place with the 2 locking tabs.
Connect the wires to the clock as shown in
fig.35.
Mount the clock to the clock bezel using the
screws provided.
Remove the factory fitted link between terminals
2 & 3 on plug M4.
Connect the clock wires to the electrical input
board as shown in fig. 35.
Replace the input board cover and appliance
casing once the clock installation has been completed.
Fig. 35
red/white
blue
Electrical input board
white
red/black
12 345
clock
24V room thermostat
8.3 EXTERNAL CONTROLS IMPORTANT (see 8.1)
If additional or alternative controls are required, they must be connected to the boiler as shown in figure 35A or 35C.
NOTE
Guidance on the recommended practice for the installation of external controls, can be found in CHeSS – HC1/HC2 (www.energy-efficiency.gov.uk).
Fig. 35A
Fig. 35C
31
Page 34
Supplied By www.heating spares.co Tel. 0161 620 6677
FUNCTIONAL DIAGRAM
NOTE. L-N-E CONNECTION MUST NOT BE INTERCHANGED
Fig. 36
Key
R.T. Room thermostat F Fan P Pump S1 Flow thermistor (NTC) S2 Return thermistor (NTC) S3 D.H.W. thermistor (NTC) L1 Led OK (green)
L2 Led alarm (blink red) F1 Fusibile 2 AF F.se/I.E. Spark/sense electrode OPE Gas valve solenoids 3W 3 way valve RL3V 3 way relay P.S. Pressure switch (NC)
32
Page 35
Supplied By www.heating spares.co Tel. 0161 620 6677
FUNCTIONAL DIAGRAM
NOTE. L-N-E CONNECTION MUST NOT BE INTERCHANGED
CONTROL SWITCHING OF TIME CLOCK AND ROOM THERMOSTAT IS 24 vdc.
Fig. 37
33
Page 36
Supplied By www.heating spares.co Tel. 0161 620 6677
PCB
Input PCB Input PCB Input PCB Input PCB Input PCB Input PCB Input PCB Input PCB
PLUG or CONNECTION
M1 M4 M5 M6 M7 M8 M9
F1
DESIGNATION
3-port valve actuator
Low voltage connector
Incoming 230V supply
230V supply to main PCB
Low voltage connector
230V connector (unused)
230V clock supply
2AF fuse
PCB
Main PCB Main PCB
Main PCB Main PCB Main PCB Main PCB Main PCB Main PCB Main PCB
PCB
display PCB display PCB display PCB
PLUG or CONNECTION
X1 X2
X3 X7 X8
X10
F1 F2 F3
PLUG or CONNECTION
X7A
X9
X20
DESIGNATION
Incoming 230V supply & pump connection
Fan connection, condense pressure switch
connection, gas valve connection
Sensor connections
Display board connection
Unused
External transformer connection
2AF fuse 2AF fuse 4AT fuse
DESIGNATION
Connection from main PCB
Unused
Status LED connection
PCB
Gas valve
Fan
Condense pressure switch
Flow sensor
Return sensor
Pump
External transformer
Cold water inlet sensor
External sensor (if fitted)
Actuator
24V connection for time clock or
room thermostat
Relay for actuator
Status LED
PLUG or CONNECTION
OPE
F
P.S.
S1 S2
P
S3 S4
3W (M)
R.T.
RL3V L1 L2
DESIGNATION
Plug X2 on main PCB Plug X2 on main PCB Plug X2 on main PCB Plug X3 on main PCB Plug X3 on main PCB Plug X1 on main PCB
Plug X10 on main PCB
Plug M4 on input PCB Plug M4 on input PCB
Plug M1on input PCB
Plug M4 on input PCB (terminals 2 & 3)
Input PCB
Plug X20 on display PCB
34
Page 37
Supplied By www.heating spares.co Tel. 0161 620 6677
SECTION 9 EXPLODED DIAGRAMS
1
8
27
29
12
6
10
9
13
141516
11
17 18
19
23
22
21
Pos Description Code
1 FRAME ASSEMBLY 8344 6 GUARD 9814 9 GREEN-RED LED 8921 10 2A INLINE FUSE (5 pcs.) 8968 11 DISPLAY BOARD 8918 12 INSTRUMENTAL PANEL 8346 13 QUICK PRIMER PRESSURE GAUGE 8968 14 HOLE COVER 9709 15 ADHESIVE FILM FOR INSTRUMENTAL PANEL 8349 16 PLASTIC TRADE MARK LABEL 1748
17 PLASTIC TRADE MARK LABEL BRACKET 2138 18 DOOR PANEL 6168 19 DOOR PANEL 5254 20 FLANGE 5304 21 MOUNTING SPINDLE 5301 22 PIN 5303 23 SPRING FOR PANEL 5275 27 O-RING 9289 29 SCREW (20 pcs.) 5080
35
Page 38
Supplied By www.heating spares.co Tel. 0161 620 6677
8 18
11
23
9
14
15
12
13
18
6
4
1
Pos Description Code
1 CASE 01005170 4 3A FUSE 3478 6 CASE CLIP (10 pcs.) 5588 8 WIRED TRANSFORMER 1048 9 PRESSURE GAUGE 1037 11 PRINTED CIRCUIT BOARD MTN SETTING 10022685 11 PRINTED CIRCUIT BOARD LPG SETTING 10022688 12 3,15A INLET FUSE 8969 13 2A INLET FUSE (5 pcs.) 8968 14 PRINTED CIRCUIT FRONT SEMI-BOX 8862 15 BLACK VELCRO 1041 18 SCREW (20 pcs.) 5080 23 EDGE CLIP (20 pcs.) 5128
23
36
Page 39
Supplied By www.heating spares.co Tel. 0161 620 6677
1
36
42 41
35
43
40
43
2
3
9
34
10
40
8
11
33
4
38
5
6
7
44
46
14
15
16
38
50
17
13
23
49
31
18
19
20
29
21
22
24
25
26
38
27
Pos Description Code
1 EXPANSION VESSEL 7204 2 DOMESTIC WATER HEAT EXCHANGER 1957 3 O-RING (10 pcs.) 7999 4 CONNECTION 8952 5 NTC SENSOR 8855 6 EXPANSION VESSEL PIPE 7207 7 HEATING MANIFOLD 2916 8 HEATING BY-PASS BACK PLUG 2911 9 CONNECTION 8432 10 NON RETURN VALVE 2908 11 BLANKING PLUG 4611 12 FLOW MANIFOLD FRONT PLATE 6853 13 SAFETY VALVE 1806 14 HEATING BY-PASS VALVE 1734 15 RUBBER DIAPHRAGM 6872 16 FLOW MANIFOLD FRONT PLATE 6853 17 BRASS CAP 8866 18 3 PORT VALVE SPRING 6862 19 O-RING (5 pcs.) 6895 20 SHUTTER FOR 3 WAY 2910 21 WASHER (5 pcs.) 2913 22 PUSH ROD 6887
28
30
23 O-RING (10 pcs.) 8444 24 SEATING PLATE 7134 25 MOTORIZED VALVE FIXING FORK WRENCH 2906 26 3 WA Y VALVE COVER 2904 27 OR UNION ASSEMBLY BRAKET 6919 28 MOTORIZED V ALVE 2905 29 CONNECTIONS COVER 7216 30 FIXING KNOB 7172 31 HEATING WA TER COCK 7100 33 WATER SUPPLY STOP COCK 7099 34 CONNECTION 8958 35 PIPE 8956 36 PIPE 8957 38 WASHER (10 pcs.) 5041 40 WASHER (10 pcs.) 5071 41 BLUE FLOW GOVERNOR 8009 42 O-RING 8959 43 WASHER (10 pcs.) 5026 44 SCREW 6903 46 WASHER (10 pcs.) 5042 49 WASHER (10 pcs.) 5023 50 WIRING HARNESS 10022483
37
Page 40
Supplied By www.heating spares.co Tel. 0161 620 6677
3
4
5
2
6
15 14
4
13
5
13
7 8
4 16 3
17
9
10
12
18
11
17
19
20 21
Pos Description Code
2 PIPE 1011 3 NTC SENSOR 1194 4 WASHER (10 pcs.) 5023 5 CONNECTIONS 8873 6 PIPE 1013 7 CONNECTION 9730 8 WASHER (10 pcs.) 9732 9 PIPE 9731 10 CONNECTION 10022570 11 PIPE 1192
38
12 SIPHON 1191 13 SILICONE TUBE 1457 14 PRESSURE SWITCH 10022556 15 BLACK VELCRO 1041 16 PUMP PIPE 8868 17 RUBBER RING 6897 18 PUMP 8876 19 WIRING HARNESS 1045 20 BRASS NUT 10022444 21 O-RING 6898
Page 41
Supplied By www.heating spares.co Tel. 0161 620 6677
5
6
1
27
2
3
7
4
9
10
11
12
26
13
14
15
38
33 3517
Pos Description Code
1 AIR VENT BOTTLE 9849 2 NON RETURN VALVE 8910 3 CONNECTION FOR NON RETURN VALVE 8911 4 UPPER PANEL FOR AIR BOX 8881 5 CLAMP 8675 6 WASHER CLAMP (10 pcs.) 5920 7 AIR BOX HOLE CAP 8084 9 WASHER (10 pcs.) 5905 10 CONNECTION 8908 11 WASHER 8912 12 HEAT EXCHANGER 8884 13 WASHER 9287 14 EXCHANGER LOWER INSULATING PANEL 1193 15 COVER FOR HEAT EXCHANGER 1033
18 19
16
22
20 21
23
24
25
16 EXCHANGER UPPER INSULATING PANEL 1016 17 ROOMSEALED CHAMBER 10022672 18 WASHER 8903 19 GLASS 8900 20 WASHER 8902 21 GLASS SUPPORT COVER 8901 22 WASHER 8896 23 SPARK-SENSING ELECTRODE 9288 24 GASKET 8904 25 SP ARK ELECTRODE CABLE 1044 26 FRONT PANEL FOR AIR BOX 1035 27 PLUG 8909 33 WASHER 1033 35 SCREW R5216 38 CLIP (10 pcs.) 10021115
39
Page 42
Supplied By www.heating spares.co Tel. 0161 620 6677
3
2
3
5
31
24
18
24 21
17
24
25
24 19
16
6 7 8
14
13
15
9
10
7
11
12
Pos Description Code
2 MAIN BURNER 1196 3 WASHER 9285 5 AIR CONVEYOR 8886 6 PRESSURE CONNECTION 8916 7 SILICONE TUBE 1457 8 SPRING 9296 9 FUN GASKET (5 pcs.) 8893 10 FAN 1018 11 SCREW 1006 12 SCREW 9292 13 PRESSURE CONNECTION 8915 14 WASHER 9299
23
22
15 MAIN BURNER JET (MTN) 8970 15 MAIN BURNER JET (LPG) 9295 16 MAIN BURNER JET SUPPORT 1195 17 GAS PIPE 10022442 18 GAS VALVE 10022441 19 GAS PIPE 10022443 21 PIPE 9772 22 GAS COCK 7098 23 SCREW (20 pcs.) 5176 24 WASHER (10 pcs.) 5023 25 SCREW 1006 31 WIRING HARNESS 10022355
40
Page 43
Supplied By www.heating spares.co Tel. 0161 620 6677
SECTION 10 L.P.G. INSTRUCTIONS
For details of converting boilers to LPG please refer to the instructions supplied with the relevant conversion kit.
10.1 TECHNICAL DATA
Inlet pressure
Gas rate
Injector size
CO2 level (cover off)
Fan speed (RPM)
Soft-light
NOx
CO
CO
CO/CO2 ratio
2
10.2 RELATED DOCUMENTS
BS 6798 BS 5449 BS 5546 BS 5440 BS 5482
PART 1
PART 1 PART 1
INSTALLATION OF BOILERS OF RATED INPUT NOT EXCEEDING 60 kW FORCED CIRCULATION HOT WATER SYSTEMS INSTALLATION OF GAS HOT WATER SUPPLIES FOR DOMESTIC PURPOSES FLUES DOMESTIC BUTANE & PROPANE GAS BURNERS IN PERMAMENT DWELLINGS
Maximum
37 mbar
4,08 l/per hr.
Single injector with six 2.3mm holes
9,80%
5.500
3.025 30 ppm 50 ppm
10% (cover on)
0.0005 to 1
Single injector with six 2.3mm holes
Minimum
37 mbar
1,19 l/per hr.
9,80%
1.700
3.025 20 ppm 20 ppm
10% (cover on)
0.0005 to 1
10.3 GAS SUPPLY
The gas supply must be connected to the appliance by a competent LPG installer and must be of sufficient size to supply the appliance at its maximum output.
An existing supply must be checked to ensure that it is of adequate size to deal with the maximum rated input of this and any other appliances that it serves.
10.4 GAS SUPPLY INSTALLATION
The entire installation including the meter, must be purged and checked for gas soundness.
10.5 ADJUSTING THE GAS VALVE The gas valve must be set-up or adjusted with the aid of a properly calibrated flue gas analyser.
Remove the appliance casing as detailed in 4.8.1. Unclip and remove the air chamber cover. Set the flue gas analyser to read CO2 and insert the probe into the flue analysis test point (see fig.1). Using the procedure as detailed in 7.3 & 7.3.5 respectively, enter the appliance engineer mode and set the fan speed to minimum.
10.5.1 MINIMUM SETTING
With the boiler operating at minimum output the CO2 reading should be 9.8% (+/- 0.2%). If the CO reading is correct, proceed to 10.5.2. If the CO reading is incorrect, the minimum gas pressure must be adjusted as follows:
Using a suitable screwdriver, very slowly turn the
minimum adjustment screw (see fig. 34) – clockwise to increase, counter clockwise to decrease – until the correct value is displayed on the CO2 analyser (allow time for the analyser to stabilise).
Using the procedure detailed in 7.3.5, change
the fan speed momentarily from minimum to maximum, then back to minimum.
Check that the correct value is still being
obtained. If not, repeat the above procedure.
10.5.2 MAXIMUM SETTING
The maximum setting must only be checked and/or adjusted after the correct minimum setting has been verified. Using the procedure detailed in 7.3.5, change the fan speed from minimum to maximum.
With the boiler operating at maximum output the CO2 reading should be 9.8% (+/- 0.2%). If the CO reading is correct, press the RESET button to exit
the appliance engineer mode. If the CO2 reading is incorrect, the maximum gas pressure must be adjusted as follows:
Using a suitable screwdriver, very slowly turn the
maximum adjustment screw (see fig. 34) – clockwise to increase, counter clockwise to decrease – until the correct value is displayed on the CO2 analyser (allow time for the analyser to stabilise).
Using the procedure detailed in 7.3.5, change
the fan speed momentarily from maximum to minimum, then back to maximum.
Check that the correct value is still being
obtained. If not, repeat the above procedure.
Press the RESET button to exit the appliance
engineer mode.
Remove the analyser test probe from the analysis test point and refit cap. Refit the air chamber cover. Refit appliance casing.
NOTE
You should ensure that all radiators or heat emitters are fully open during the above procedures. This will ensure that the fan speed (output) of the boiler
2 2
10.6 RANGE RATING
is not compromised due to a high flow temperature.
The output of the boiler is automatically adjusted by a continuous air/gas modulation system. The system is controlled by the NTC thermistors (flow & return temperature sensors) which ensures stability of temperature irrespective of load conditions. However the appliance also has a range rating facility which can be used to limit the max. output - to central heating - if required. Please refer to 7.3.1 & fig. 37 for more details.
Output BTU/H
2
102,360 85,300
68,240 51,180
34,120 17,060
0
Fig. 37
30
25
20
15
kW
10
5
0 1500 2000 2500 3000 3500 4000 4500 5000 5500
50°C flow & 30°C return temperature
80°C flow & 60°C return temperature
Fan speed in RPM
41
Page 44
Supplied By www.heating spares.co Tel. 0161 620 6677
energizing home heating
Vokèra Ltd.
4th Floor, Catherine House, Boundary Way, Hemel Hempstead, Herts, HP2 7RP
Cod. 10022484 - Ed. 2 - 16/02
Email: enquiries@vokera.co.uk Web: www.vokera.co.uk
General Enquiries - Tel: 01442 281400 Fax: 01442 281460
Technical Advice - Tel: 0141 945 6810
Spare Parts - Tel: 0141 945 6820
After Sales Service - Tel: 0870 333 0220
Vokèra Ireland
West Court, Callan, Co Kilkenny
Tel: 056 55057 Fax: 056 55060
Vokèra Ltd. reserve the right to change the specifications without prior notice. Consumers’ statutory rights are not affected.
A Riello Group Company
COLLECTIVE MARK
“Vokèra”
supports Benchmark
Loading...