VOKERA Eclipse ESC Installation & Servicing Instructions Manual

Supplied By www.heating spares.co Tel. 0161 620 6677
Installation & Servicing Instructions
THESE INSTRUCTIONS TO BE RETAINED BY USER
Supplied By www.heating spares.co Tel. 0161 620 6677
Contents
Design principles & operating sequence Page
1.1 Principle components 2
1.2 Mode of operation (at rest) 2
1.3 Domestic hot water mode 2
1.4 Central heating mode 2
1.5 Safety devices 2
Technical data Page
2.1 Central heating 3
2.2 Domestic hot water 3
2.3 Gas pressure 3
2.4 Expansion vessel 3
2.5 Dimensions 3
2.6 Clearances 3
2.7 Connections 3
2.8 Electrical 3
2.9 Flue details 3
2.10 Efficiency 3
2.11 Parameter defaults 4
2.12 Emissions 4
2.13 Pump duty 4
General requirements Page
3.1 Related documents 5
3.2 Location of appliance 5
3.3 Gas supply 5
3.4 Flue system 5
3.5 Air supply 6
3.6 Water circulation 6
3.7 Electrical supply 7
3.8 Showers 7
3.9 Mounting on a combustible surface 7
3.10 Timber framed buildings 7
3.11 Condensate disposal 7
3.12 Inhibitors 7
Installation Page
4.1 Delivery 7
4.2 Contents 7
4.3 Unpacking 7
4.4 Preparation for mounting the appliance 7
4.5 Fitting the flue 8
4.6 Connecting the gas & water 11
4.7 Condensate outlet 12
4.8 Electrical connections 12
Commissioning Page
5.1 Gas supply installation 14
5.2 The heating system 14
5.3 Initial filling of the system 14
5.4 Initial flushing of the system 14
5.5 Filling the hot water system 14
5.6 Pre-operation checks 14
5.7 Initial lighting 14
5.8 Final flushing of the heating system 14
5.9 Operating parameters 14
5.10 Functional parameters 15
5.11 Range rating 15
5.12 Setting the system design pressure 15
5.13 Regulating the central heating system 16
5.14 Final checks 16
5.15 Instructing the user 16
Servicing Page
6.1 General 17
6.2 Routine annual servicing 17
6.3 Replacement of components 17
6.4 Component removal procedure 17
6.5 Pump head removal 17
6.6 Safety valve removal 17
6.7 Automatic air valve removal 17
6.8 Pressure gauge removal 18
6.9 Temperature sensor removal 18
6.10 Main PCB removal 18
6.11 Gas valve removal 18
6.12 Fan removal 19
6.13 Burner removal 19
6.14 Electrode removal 19
6.15 Injector removal 19
6.16 DHW heat exchanger removal 20
6.17 Motorised valve actuator removal 20
6.18 Divertor valve assembly removal 20
6.19 Condense trap removal 20
6.20 Condense pressure switch removal 20
6.21 Combustion cover removal 20
6.22 Expansion vessel removal 21
6.23 Input & status PCB removal 21
Checks, adjustments, and fault finding Page
7.1 Checking appliance operation 22
7.2 Mode of operation 22
7.3 Checking/adjusting fan speeds 22
7.4 Adjusting the gas valve 23
7.5 Status code 24
7.6 Lockout faults codes 25
7.7 Diagnostic recall 25
7.8 Temperature sensor viewing mode 26
7.9 Checking the expansion vessel 26
7.10 External faults (installation) 26
7.11 Electrical checks 26
7.12 Fault finding 27
Wiring diagrams Page
8.1 Important note 31
8.2 Installation of Vokera time clock 31
8.3 External controls 31
Exploded diagrams Page
9.1 Table 1 35
9.2 Table 2 36
9.3 Table 3 37
9.4 Table 4 38
9.5 Table 5 39
9.6 Table 6 40
L.P.G. instructions Page
10.1 Technical data 41
10.2 Related documents 41
10.3 Gas supply 41
10.4 Gas supply installation 41
10.5 Adjusting the gas valve 41
10.6 Range rating 41
Supplied By www.heating spares.co Tel. 0161 620 6677
INTRODUCTION
The Vokera Eclipse ESC is a combined central heating and domestic hot water condensing boiler, which – by design – incorporates full sequence electronic ignition, circulating pump, expansion vessel, safety valve, pressure gauge, and automatic by-pass.
The Eclipse is produced as a room sealed, category C1, C3, C6 appliance, suitable for wall mounting applications only. The Eclipse is provided with a fan powered flue
outlet with an annular co-axial combustion air intake that can be rotated – horizontally – through 360 degrees for various horizontal or vertical applications. The Eclipse can also be used with the Vokera twin flue system. These appliances are designed for use with sealed systems only; consequently they are not intended for use on open vented systems.
A range rating facility is incorporated in the appliance.
General layout
1 Auto air vent 2 Flue outlet & air intake 3 Flue gas analysis test point 4 Burner plate 5 Spark/Sensing Electrode 6 Fan assembly 7 Pressure switch 8 Electronic Control Board (PCB) 9 Condense trap 10 Cold water inlet 11 Hot water outlet 12 Gas connection 13 Pressure gauge 14 Time clock aperture 15 Function key pad 16 LED display 17 Reset button 18 Heating flow connection 19 Safety valve 20 Heating return connection 21 Auto by-pass 22 Three port valve actuator 23 Pump 24 Return sensor (NTC2) 25 Gas valve 26 Flow sensor (NTC1)
Fig. 1
1
Supplied By www.heating spares.co Tel. 0161 620 6677
SECTION 1 DESIGN PRINCIPLES AND OPERATING SEQUENCE
1.1 PRINCIPLE COMPONENTS
A fully integrated electronic control board
featuring electronic temperature control, continuous air/gas modulation, anti-cycle control, pump over-run, self-diagnostic fault indicator, electronic ignition with flame supervision, & appliance frost protection.
Cast aluminium mono-block heat exchanger.
Low Nox burner with pre-mix.
Two-stage gas valve.
Pump.
Expansion vessel.
Pressure gauge.
Safety valve.
1.2 MODE OF OPERATION (at rest)
When there is no demand for heating or hot water, the boiler will periodically light to pre-heat the domestic hot water heat exchanger to approximately 55°C. This ensures that the appliance is at operating temperature when there is a request for domestic hot water. The parameter for the allowable temperature drop – between pre­heat operation – can be adjusted. If the appliance remains inactive for a period of 24 hours, the pump and motorised valve will be energised for a few moments to prevent these components from seizing. Should the flow temperature sensor fall below 7°C the pump will be energised. If the flow sensor temperature falls to below 3°C the burner will be lit and the appliance will operate at the minimum output until the temperature of the flow sensor reaches 10°C, whereupon the pump will continue to run in pump over-run mode.
1.3 DOMESTIC HOT WATER MODE
When the appliance is at rest, the motorised valve is energised to the hot water position, when a demand for hot water is made the cold water temperature sensor activates the pump and fan. When the fan is sensed to be operating correctly, the ignition sequence commences. The speed of the fan and therefore the output of the boiler is determined by the temperature of the water sensed by the return temperature sensor, consequently a high temperature at the return sensor results in a lower fan speed. As the water temperature increases, the temperature sensors – located on the flow and return pipes of the boiler – reduce the fan speed via the electronic circuitry. Depending on the load, either the water temperature will continue to rise until the set point is achieved or the water temperature will fall whereby fan speed will increase relative to the output required.
boiler is determined by the temperature of the water sensed by the flow & return temperature sensors, consequently a high temperature at the flow sensor results in a lower fan speed. As the water temperature increases, the temperature sensors – located on the flow and return pipes of the boiler – reduce the fan speed via the electronic circuitry. Depending on the load, either the water temperature will continue to rise until the set point is achieved or the water temperature will fall whereby fan speed will increase relative to the output required. When the boiler has reached the set point, the burner will switch off. The built-in anti-cycle device prevents the burner from re­lighting for an adjustable period of time (factory default is 3 minutes). When the temperature of the flow sensor falls below the set-point, the burner will re-light.
1.5 SAFETY DEVICES
When the appliance is in use, safe operation is ensured by:
a high limit thermostat that interrupts the
operation of the burner;
a differential temperature protection circuit which
interrupts the burner if the temperature differential is inverted;
a fan speed sensor which checks the correct
operation of the fan, thereby allowing safe operation of the burner;
a safety valve which releases excess pressure
from the primary circuit;
a condense pressure switch that will stop the
burner from operating should the condense trap become blocked.
4
NTC2 (return sensor)
Domestic Heat Exchanger
1
NTC1 (flow sensor)
Main Heat Exchanger
Expansion vessel
NTC 3 (inlet sensor)
1.4 CENTRAL HEATING MODE
When there is a request for heat via the time clock and/or external controls the motorised valve and pump will go through a self-test function this is to ensure correct operation and valve configuration. Once the self-test function is complete, the pump and fan will activated via the flow temperature sensor. When the fan is sensed to be operating correctly, the ignition sequence commences. The speed of the fan and therefore the output of the
Fig. 2
2
gas
return flow hw
outlet
cold inlet
Supplied By www.heating spares.co Tel. 0161 620 6677
SECTION 2 TECHNICAL DATA
2.1 Central heating
Heat input 29,00 kW Maximum heat output 60/80°C (return & flow temperature) 25,3 kW Maximum heat output 30/50°C (return & flow temperature) 26,8 kW Minimum heat output 60/80°C (return & flow temperature) 7,3 kW Minimum heat output 30/50°C (return & flow temperature) 8,10 kW Minimum working pressure 0,45 bar Maximum working pressure 3 bar Minimum flow rate 350 l/h
2.2 Domestic hot water
Maximum input 29,00 kW Maximum output 25,3 kW Minimum output 8,1 kW Flow rate (35°C rise) 10,4 l/min Maximum inlet pressure 6,0 bar Minimum inlet pressure to operate 0,15 bar Minimum flow rate to operate 2,5 l/min.
2.3 Gas pressure Maximum
Inlet pressure (G20) 20,0 mbar Maximum gas rate 2,76 m3/h Minimum gas rate 0,80 m3/h Injector size single injector with six 3,8 mm holes
2.4 Expansion vessel
Capacity 8 litres Maximum system volume 76 litres Pre-charge pressure 1,0 bar
2.5 Dimensions
Height 790 mm Width 450 mm Depth 322 mm Dry weight 57 kg
2.6 Clearances
Sides 25 mm Top Bottom 150 mm Front 600 mm
2.7 Connections
Flow & return 22 mm compression Hot & cold water 15 mm compression Gas 1/2 inch BSP Safety valve 1/2 inch BSP
2.8 Electrical
Voltage 230V/~ 50hz Power consumption 130 W Internal fuse 2 A External fuse 3 A
2.9 Flue details
Maximum horizontal flue length (concentric) 6,45 metres Maximum vertical flue length (concentric) 7,45 metres Maximum twin flue length (horizontal or vertical) 29 m + 29 m
2.10 Efficiency
SEBDUK rating Band “A”
150 mm from casing or 25mm above flue elbow (whichever is applicable)
Ref. Condition 15 °C , 1013,25 mbar, dry gas NOTE: L.P.G. data refer to section 10
3
Supplied By www.heating spares.co Tel. 0161 620 6677
2.11 Adjustable operating parameters PARAMETER MINIMUM MAXIMUM FACTORY SETTING
Maximum fan speed (HW mode) Fixed Fixed 5.500 RPM Maximum fan speed (CH mode) See fig. 32 See fig. 32 5.500 RPM Minimum fan speed Fixed Fixed 1.700 RPM Soft-light fan speed Fixed Fixed 4.400 RPM Pre-heat Fixed Fixed 55°C Pre-heat temperature drop 5°C30°C20°C Anti-cycle delay 0 seconds 306 seconds 92 seconds Central heating flow temperature 20°C90°C75°C Hot water outlet temperature 40°C65°C65°C Pump over-run 3 m 99 m 10 m
2.12 Emissions MIN. OUTPUT MAX. OUTPUT
NO
x
15 ppm 30 ppm CO 50 ppm 50 ppm CO
2
9,8% 9,8% CO/CO2 ratio 0.0005 to 1 0.0005 to 1
2.13 PUMP DUTY
Fig. 3 shows the flow rate available – after allowing for pressure loss through the appliance – for system requirements. When using this graph apply only the pressure loss of the system. The graph is based on 20°C temperature differential.
600
500
400
300
200
100
Water pressure (mbar)
0 100 200 300 400 500 600 700 800
Fig. 3
Litres Per Hour (x100)
900 1000
1100 1200 1300 1400
Terminal position for fan assisted boiler
(minimum distance) mm A - Directly above or below an open window 300
J - From an opening in the car port (e.g. door
or other opening (e.g. air brick) B - Below gutters, soil pipes or drain pipes 25 C - Below eaves 25 D - Below balconies or car port roof 25 E - From vertical drain pipes and soil pipes 75
K - Vertically from a terminal on the same wall 1500 L - Horizontally from a terminal on the same wall 300 M - Horizontally from a vertical terminal to a wall 300
N – Horizontally from an opening, airbric k,
F - From internal or external corners 25 G - Above ground or below balcony level 300 H - From a surface facing a terminal 600 I - From a terminal facing a terminal 1200
NOTE:The flue must be terminated in a place not likely to cause a nuisance.
Fig. 4
4
window) into dwelling. 1200
openable window, etc. 300
Supplied By www.heating spares.co Tel. 0161 620 6677
SECTION 3 GENERAL REQUIREMENTS
This appliance must be installed by a competent person in accordance with the Gas Safety (Instal­lation & Use) Regulations.
3.1 RELATED DOCUMENTS
The installation of this boiler must be in accord­ance with the relevant requirements of the Gas Safety (Installation & Use) Regulations, the local building regulations, the current I.E.E. wiring regulations, the bylaws of the local water undertaking, the Building Standards (Scotland) Regulation and Building Standards (Northern Ireland) Regulations.
It should be in accordance also with any relevant requirements of the local authority and the relevant recommendations of the following British Standard Codes of Practice.
3.2 LOCATION OF APPLIANCE
The appliance may be installed in any room or internal space, although particular attention is drawn to the requirements of the current I.E.E. wiring regulations, and in Scotland, the electrical provisions of the Building Regulations, with respect to the installation of the appliance in a room or internal space containing a bath or shower.
for this purpose. An existing compartment/cup­board may be utilised provided that it is modified to suit.
Details of essential features of compartment/ cupboard design, including airing cupboard in­stallations, are given in BS 6798. This appliance is not suitable for external installation.
3.3 GAS SUPPLY
The gas meter – as supplied by the gas supplier – must be checked to ensure that it is of adequate size to deal with the maximum rated input of all the appliances that it serves. Installation pipes must be fitted in accordance with BS 6891. Pipe-work from the meter to the appliance must be of adequate size. Pipes of a smaller size than the appliance gas inlet connection must not be used. The installation must be tested for soundness in accordance with BS 6891.
If the gas supply serves more than one appliance, it must be ensured that an adequate supply is maintained to each appliance when they are in use at the same time.
BS 5440 PART 1 FLUES BS 5440 PART 2 FLUES AND VENTILATION BS 5449 PART 1 FORCED CIRCULATION HOT WATER SYSTEMS BS 5546 INSTALLATION OF GAS HOT WATER SUPPLIES FOR DOMESTIC PURPOSES
(2ND FAMILY GASES) BS 6798 BOILERS OF RATED INPUT NOT EXCEEDING 60kW BS 6891 LOW PRESSURE INSTALLATION PIPES BS 7074 PART 1 APPLICATION, SELECTION, AND INSTALLATION OF EXPANSION VESSELS AND
ANCILLARY EQUIPMENT FOR SEALED WATER SYSTEMS
When an appliance is installed in a room or internal space containing a bath or shower, the appliance or any control pertaining to it must not be within reach of a person using the bath or shower.
The location chosen for the appliance must permit the provision of a safe and satisfactory flue and termination. The location must also permit an adequate air supply for combustion purposes and an adequate space for servicing and air circulation around the appliance. Where the installation of the appliance will be in an unusual location special procedures may be necessary, BS 6798 gives detailed guidance on this aspect.
A compartment used to enclose the appliance must be designed and constructed specifically
3.4 FLUE SYSTEM
The terminal should be located where the disper­sal of combustion products is not impeded and with due regard for the damage and discoloration that may occur to building products located nearby. The terminal must not be located in a place where it is likely to cause a nuisance (see fig. 4).
Water vapour will condense on leaving the flue terminal, the effect of such pluming must be considered.
5
Supplied By www.heating spares.co Tel. 0161 620 6677
If installed less than 2m above a pavement or platform to which people have access (including balconies or flat roofs) the terminal must be protected by a guard of durable material. The guard must be fitted centrally over the terminal. Refer to BS 5440 Part 1, when the terminal is 0,5 metres (or less) below plastic guttering or 1 metre (or less) below painted eaves.
3.5 AIR SUPPLY
The following notes are intended for general guidance only.
This appliance is a room sealed, fan-flued boiler, consequently it does not require a permanent air vent for combustion air supply.
When installed in a cupboard or compartment, venti­lation for cooling purposes is also not required.
3.6 WATER CIRCULATION
Detailed recommendations are given in BS 5449 Part 1 and BS 6798. The following notes are for general guidance only.
3.6.1 PIPEWORK
It is recommended that copper tubing to BS 2871 Part 1 is used in conjunction with soldered capillary joints.
Where possible pipes should have a gradient to ensure air is carried naturally to air release points and that water flows naturally to drain cocks.
Except where providing useful heat, pipes should be insulated to avoid heat loss and in particular to avoid the possibility of freezing. Particular atten­tion should be paid to pipes passing through ventilated areas such as under floors, loft-space, and void areas.
3.6.2 AUTOMATIC BY-PASS
The appliance has a built-in automatic by-pass, consequently there is no requirement for an ex­ternal by-pass, however the design of the system should be such that it prevents boiler ‘cycling’.
3.6.6 FILLING POINT
A method for initial filling of the system and replacing water lost during servicing etc. must be provided. This method of filling must comply with the local water authority regulations. Fig. 5 shows a widely accepted method.
Fig. 5
3.6.7 LOW PRESSURE SEALED SYSTEM
An alternative method of filling the system would be from an independent make-up vessel or tank mounted in a position at least 1 metre above the highest point in the system and at least 5 metres above the boiler (see fig. 5 A). The cold feed from the make-up vessel or tank must be fitted with an approved non-return valve and stopcock for iso­lation purposes. The feed pipe should be con­nected to the return pipe as close to the boiler as possible.
Make-up vessel or tank
Automatic air-vent
3.6.3 DRAIN COCKS
These must be located in accessible positions to facilitate draining of the appliance and all water pipes connected to the appliance. The drain cocks must be manufactured in accordance with BS 2879.
3.6.4 AIR RELEASE POINTS
These must be positioned at the highest points in the system where air is likely to be trapped. They should be used to expel trapped air and allow complete filling of the system.
3.6.5 EXPANSION VESSEL
The appliance has an integral expansion vessel to accommodate the increased volume of water when
Fig. 5 A
3.6.8 FREQUENT FILLING
the system is heated. It can accept up to 8 litres of expansion from within the system, generally this is sufficient, however if the system has an unusually high water content, it may be necessary to provide additional expansion capacity (see 6.19).
6
Non-return
valve
Stopcock
5.0 metres minimum
Heating return
Frequent filling or venting of the system may be indicative of a leak. Care should be taken during the installation of the appliance to ensure all aspects of the system are capable of withstand­ing pressures up to at least 3 bar.
Supplied By www.heating spares.co Tel. 0161 620 6677
3.7 ELECTRICAL SUPPLY
The appliance is supplied for operation on 230V @ 50Hz electrical supply, it must be protected with a 3-amp fuse. The method of connection to the mains electricity supply must allow for complete isolation from the supply. The preferred method is by using a double-pole switch with a contact separation of at least 3mm. The switch must only supply the appliance and its corresponding controls, i.e. time clock, room ther­mostat, etc. Alternatively an un-switched shuttered socket with a fused 3-pin plug both complying with BS 1363 is acceptable.
3.8 SHOWERS
If the appliance is intended for use with a shower, the shower must be thermostatically controlled and be suitable for use with a combination boiler.
3.9 MOUNTING ON A COMBUSTIBLE SURFACE
If the appliance is to be fitted on a wall of combus­tible material, a sheet of fireproof material must protect the wall.
3.10 TIMBER FRAMED BUILDINGS
If the appliance is to be fitted in a timber framed building, it should be fitted in accordance with the Institute of Gas Engineers publication (IGE/UP/
7) “Guide for Gas Installations in Timber Frame Buildings”.
3.11 CONDENSATE DISPOSAL
When choosing a location for the boiler, consideration should be given to the disposal of the condensate discharge into a suitable drain or soil pipe. The condensate outlet pipe must be connected to the drain in accordance with building regulations or other rules in force.
SECTION 4 INSTALLATION
4.1 DELIVERY
The appliance is delivered in a heavy-duty card­board carton. Lay the carton on the floor with the writing the correct way up.
4.2 CONTENTS
Contained within the carton is:
the boiler;
the wall mounting bracket;
template;
an accessories pack containing the appliance
service valves and washers;
the instruction pack containing the installation
& servicing instructions, user instructions, Benchmark logbook, guarantee registration card, and a 3amp fuse.
4.3 UNPACKING
At the top of the carton pull both sides open – do not use a knife – unfold the rest of the carton from
Fig. 6
3.12 INHIBITORS
The system shall be flushed in accordance with BS 7593. If an inhibitor is to be used, it shall be from a reputable manufacturer and shall be administered in strict accordance with the manufacturers instructions.
around the appliance, carefully remove all pro­tective packaging from the appliance, and lay the accessories etc. to one side.
4.4 PREPARATION FOR MOUNTING THE APPLIANCE
The appliance should be mounted on a smooth, vertical, non-combustible surface, which must be capable of supporting the full weight of the appliance. Care should be exercised when determining the position of the appliance with respect to hidden obstructions such as pipes, cables, etc.
When the position of the appliance has been decided – using the template supplied – carefully mark the position of the wall-mounting bracket (see fig. 6) and flue-hole (if applicable).
7
Supplied By www.heating spares.co Tel. 0161 620 6677
4.5 FITTING THE FLUE
The top flue outlet permits both horizontal and vertical flue applications to be considered, alternatively, the Vokera twin flue system can be utilised if longer flue runs are required.
4.5.1 CONCENTRIC HORIZONTAL FLUE
(For concentric vertical flue, see 4.5.2). (For twin flue applications, see 4.5.3). The appliance flue outlet elbow can be rotated through 360° on its vertical axis. In addition the flue may be extended from the outlet elbow in the horizontal plane (see 2.9). A reduction must also be made to the maximum length (see table below) when additional bends are used.
Reduction for additional bends
Bend
Reduction in maximum flue length for each bend
Take the large black gasket - supplied with the flue terminal kit - and stretch it over the appliance flue outlet (fig. 7). Using a twisting motion, connect the boiler top adaptor - supplied with the flue terminal kit - to the appliance flue outlet ensuring the male spigot of the adaptor is pushed fully into the flue outlet spigot of the boiler (fig. 7). Carefully measure the distance from the centre of the appliance flue outlet to the edge of the finished outside wall (dimension X). Add 45mm to dimension X to give you Dimension Y (see fig 7A). Measure dimension Y from the terminal end of the concentric flue pipe and cut off the excess. Pass the concentric flue pipe through the previously drilled hole. Fit the flue bend to the boiler top adaptor and insert the concentric flue pipe into the flue bend ensuring the correct seal is made.
45° bend 90° bend
Part No. 0225720
0225755 0225740 0225745 0225750 0225730 0225735 0225760
0,5 metre 1,0 metre
Horizontal flue terminals and accessories
Description
Horizontal flue kit for use with add. bends & extensions
350-500 T elescopic extension 0,5m extension 1,0m extension 2,0m extension 45° bend (pair) 90° bend Wall bracket (5)
Min-Max length 1000mm
350mm-500mm 500mm 1000mm 2000mm N/A N/A N/A
Using the template provided (see fig. 6), mark and drill a 125mm hole for the passage of the flue pipe. The hole should ha ve a 1° rise from the boiler to outside.
Fig. 7A
NOTE
You must ensure that the entire flue system is properly supported and connected.
Seal the flue assembly to the wall using cement or a suitable alternative that will provide satisfactory weatherproofing. The interior and exterior trim can now be fitted.
The fixing holes for the wall-mounting bracket should now be drilled and plugged, an appropriate type and quantity of fixing should be used to ensure that the bracket is mounted securely. Once the bracket has been secured to the wall, mount the appliance onto the brack et.
FITTING THE HORIZONTAL FLUE KIT
Boiler top
Black
adaptor
gasket
Flue outlet
Boiler
Fig. 7
8
Fig. 7B
Boiler
Push-fit connection
Boiler top adaptor
Extension
Supplied By www.heating spares.co Tel. 0161 620 6677
4.5.1.1 EXTENDING THE FLUE
Connect the bend – supplied with the terminal kit – to the top of the boiler using the boiler top adapter (supplied, see fig. 7). The additional bends & extensions have push-fit connections, care should be taken to ensure that the correct seal is made when assembling the flue system. Connect the required number of flue extensions or bends (up to the maximum equivalent flue length) to the flue terminal (see fig. 7B & 7C).
NOTE
When cutting an extension to the required length, you must ensure that the excess is cut from the plain end of the extension (see fig. 7B & 7C). Remove any burrs, and check that any seals are located properly. You must ensure that the entire flue system is properly supported and connected.
Push-fit connection
Plain end
Extension pipe
Boiler top adaptor
Vertical flue terminal and accessories
Part No. 0225725
0225770 0225765 0225755 0225740 0225745 0225750 0225730 0225735 0225760
Description Vertical flue terminal
Pitched roof flashing plate Flat roof flashing plate 350-500 telescopic extension 0,5m extension 1,0m extension 2,0m extension 45° bend (pair) 90° bend Wall bracket (4)
Min-Max length 1000 mm
N/A N/A 350mm-500mm 500mm 1000mm 2000mm N/A N/A N/A
Using the dimensions given in fig. 8 as a reference, mark and cut a 105mm hole in the ceiling and/or roof.
IMPORTANT
You must ensure that the terminal is at least 300mm from any structure or surface (see fig. 8). The vertical flue terminal is 1,0 metre in length and cannot be cut; therefore it may be necessary to adjust the height of the appliance to suit or use a suitable extension. Encure that any horizontal sections of the flue system have a 1° fall back to the boiler (17mm per 1000mm).
Fit the appropriate flashing plate to the roof and insert the vertical flue terminal through the flashing plate from the outside, ensuring that the collar on the flue terminal fits over the flashing.
The fixing holes for the wall-mounting bracket should now be drilled and plugged, an appropriate type and quantity of fixing should be used to ensure that the bracket is mounted securely. Once the bracket has been secured to the wall, mount the appliance onto the bracket.
300mm minimum
Boiler
Fig. 7C
4.5.2 CONCENTRIC VERTICAL FLUE
The vertical flue terminal can be connected directly to the appliance flue outlet. Alternatively, an extension or bend can be connected to the appliance flue outlet if desired (see 2.9), however if additional bends are fitted, a reduction must be made to the maximum flue length (see table below).
Reduction for bends
Bend 45° bend
90° bend
Reduction in maximum flue length for each bend 0,5 metre
1,0 metre
Fig. 8
520mm
139mm
9
Supplied By www.heating spares.co Tel. 0161 620 6677
NOTE
When cutting an extension to the required length, you must ensure that the excess is cut from the plain end of the extension. Remove any b urrs, and check that an y seals are located properly .
4.5.3 TWIN FLUE SYSTEM
The Vokera twin flue system enables greater flue distances to be achieved (see 2.9) than that of the standard concentric flue system. It can be used f or horizontal or vertical applications, howev er the twin flue system must be converted to the dedicated concentric flue kit for termination. It is essential that the installation of the twin flue system be carried out in strict accordance with these instructions.
GUIDANCE NOTES ON TWIN FLUE INSTALLATION
The flue must hav e a f all back of 1° back to the
appliance to allow any condensate that forms in the flue system to drain. Consideration must also be given to the fact that there is the possibility of a small amount of condensate dripping from the terminal.
Ensure that the entire flue system is adequately
supported, use at least one bracket for each extension.
As the exhaust outlet pipe can reach v ery high
temperatures it must be protected to prevent persons touching the hot surface.
Reduction for bends
Bend 45° bend 90° bend
Reduction in maximum flue length for each bend 1,0 metre
1,0 metre
Twin flue accessories
Part No. Description 0225805
0225810 359 0225770 0225765 0225815 0225820 0225825 0225830 0225835 0225840 0225845 0225850 0225855
Horizontal flue terminal Vertical flue terminal Twin adapter kit Pitched roof flashing plate Flat roof flashing plate Condensate drain kit 0,25m extension (pair) 0,5m extension (pair) 1,0m extension (pair) 2,0m extension (pair) 45° bend (pair) 90° bend (pair) Twin bracket (5) Single bracket (5)
MOUNTING THE BOILER
The fixing holes for the wall-mounting bracket should now be drilled and plugged, an appropriate type and quantity of fixing should be used to ensure that the bracket is mounted securely. Once the bracket has been secured to the wall, mount the appliance onto the bracket.
Length 1000 mm
1000 mm N/A N/A N/A N/A 250mm 500mm 1000mm 2000mm N/A N/A N/A N/A
4.5.3.1 INSTALLATION OF TWIN ADAPTOR KIT (see fig. 9)
Discard the restrictor ring (supplied with the twin
adapter kit).
Insert the exhaust connection manifold onto the
appliance flue outlet.
Place the silicone seal (supplied with twin
adapter kit) over the rim of the exhaust connection manifold.
Remove one of the blanking plate (located to
the left & right of the appliance flue outlet) and – using the same screws – install the air baffle.
Fig. 9
4.5.3.2 HORIZONTAL TERMINATION (see fig. 10)
The twin flue system must be converted to the dedicated concentric flue kit for termination.
The horizontal terminal is supplied with a built-
in converter box and cannot be shortened.
A 130mm hole is required for the passage of
the concentric terminal through the wall.
Depending on site conditions it may be pref erable to install the terminal assembly prior to fitting the twin flue pipes.
Mark and drill a 130mm hole for the passage of the horizontal flue terminal, ensuring that there is a 1° fall back to the boiler (17mm per 1000mm). Insert the terminal assembly into the flue hole.
Push-fit the twin flue pipes onto the concentric to twin converter box ensuring that the exhaust pipe connects to the exhaust connection on the concentric to twin converter. If necessary cut the plain ends (male) of the twin flue pipes to allow connection to the concentric to twin converter.
NOTE
Before cutting twin flue pipes ensure allowances have been made f or connection onto the previous piece and onto the concentric to twin converter. The last twin flue pipes must be pushed 50mm onto the male spigots of the concentric to twin converter.
NOTE
You must ensure that the entire flue system is properly supported and connected. When cutting an extension to the required length, you should ensure that the excess is cut from
10
Supplied By www.heating spares.co Tel. 0161 620 6677
the plain end of the extension. Remove an y burrs, and check that both seals are located properly.
Seal the flue terminal assembly to the wall using cement or a suitable alternative that will provide satisfactory weatherproofing. The interior and exterior trim can now be fitted.
convertor box
Fig. 10
Push-fit the twin flue pipes onto the concentric to twin converter ensuring that the exhaust pipe connects to the exhaust connection on the concentric to twin converter. If necessary cut the plain ends (male) of the twin flue pipes to allow connection to the concentric to twin converter.
NOTE
Before cutting twin flue pipes ensure
allowances have been made for connection onto the previous piece and onto the concentric to twin converter. The last twin flue pipes must be pushed 50mm onto the male spigots of the concentric to twin converter.
You must ensure that the entire flue system is
properly supported and connected.
Ensure that any horizontal sections of pipe hav e
a 1° fall towards the appliance (17mm per 1000mm).
The convertor box on the vertical terminal will
have to be temporarily remo ved when inserting the terminal through the flashing.
4.5.3.3 VERTICAL TERMINATION (see fig. 11)
The twin flue system must be converted to the dedicated concentric flue kit for termination.
The vertical terminal is supplied with a built-in
converter box and cannot be shortened.
A 130mm hole is required for the passage of
the concentric terminal through the ceiling and/ or roof.
Depending on site conditions it may be prefer able to install the terminal assembly prior to fitting the twin flue pipes.
Fit the appropriate flashing plate to the roof and insert the vertical flue terminal through the flashing plate from the outside, ensuring that the collar on the flue terminal fits over the flashing.
convertor box
4.6 CONNECTING THE GAS AND WATER
The appliance is supplied with an accessories pack that contains sealing washers and service valves. When connecting pipe work to the valves, tighten the compression end first, then insert the sealing washers before tightening the valve or connection to the appliance.
NOTE
It will be necessary to hold the valve with one spanner whilst tightening with another.
4.6.1 GAS (see fig. 12)
The appliance is supplied with a 1/2 inch BSP service valve, connect the supply pipe to the inlet of the valve and tighten the connecting nut.
NOTE
It will be necessary to calculate the diameter of the gas pipe to ensure the appliance has an adequate supply of gas.
4.6.2 FLOW & RETURN (see fig. 12)
The appliance is supplied with 22mm service valves for the flow and return connections, connect a 22mm pipe to the inlet of each valve and tighten both nuts.
4.6.3 SAFETY VALVE (see fig. 12)
Fig. 11
Connect a suitable coupling and 15mm pipe to the safety valve outlet and tighten.The discharge pipe must have a continuous fall away from the appliance to outside and allow any water to drain away thereby eliminating the possibility of freezing. The discharge pipe must terminate in a position where any water - possibly boiling - discharges safely without causing damage or injury, but is still visible.
11
Supplied By www.heating spares.co Tel. 0161 620 6677
4.6.4 COLD WATER INLET (see fig. 12)
The appliance is supplied with a 15mm service valve, connect a 15mm pipe to the inlet of the valve and tighten both nuts.
4.6.5 HOT WATER OUTLET (see fig. 12)
The appliance is supplied with a 15mm male connector. Using a suitable coupling, connect a 15mm pipe to the supplied connector and tighten the nut.
4.7 CONDENSATE OUTLET (see fig. 12)
During normal operation the boiler produces condensate which is collected in a trap located in the lower part of the boiler. A flexible pipe (condensate outlet pipe) is connected to the outlet of the trap. The flexible pipe must be connected to a plastic waste pipe only. The plastic waste pipe must have a minimum of a 3° fall towards the drain. Any external run of pipe should be insulated to prevent the risk of freezing.
CONNECTING THE CONDENSATE OUTLET
Gently pull the condensate outlet pipe down from its location inside the boiler until approximately 250mm protrudes from the underside of the boiler. Connect a suitable pipe (no less than 20mm diameter) to the outlet pipe and ensure it discharges in accordance with building regulations or other rules in force.
4.8.1 CASING REMOVAL
To gain access to the appliance electrical con­nections you must first remove the casing, pro­ceed as follows:
locate and remove the 2 screws that secure the
controls fascia to the appliance casing (see fig. 13).
locate and remove the 2 screws that secure the
casing to the back frame of the boiler (see fig. 13).
gently pull one side of the casing then the other
to disengage it from the retaining clips.
lift the casing upward to disengage it from the
top locating hooks and then remove.
store the casing and screws safely until required.
Re-fit in the reverse order.
Fig.13
Safety valve
outlet
Condensate
outlet pipe
Fig. 12
Return Gas
Flow
Cold water
inlet
4.8 ELECTRICAL CONNECTIONS
The electrical supply must be as specified in 3.7. A qualified electrician should connect the electri­cal supply to the appliance. If controls - external to the appliance - are required, a competent person must undertake the design of any external electrical circuits, please refer to section 8 for detailed instructions. ANY EXTERNAL CONTROL OR WIRING MUST BE SERVED FROM THE SAME ISOLATOR AS THAT OF THE APPLIANCE. The supply cable from the isolator to the appliance must be 3-core flexible sized 0,75mm to BS 6500. Wiring to the appliance must be rated for opera­tion in contact with surfaces up to 90°C.
4.8.2 ELECTRICAL INPUT BOARD
The appliance electrical input board is located behind the control fascia (see fig.14). Locate and remove the 4 screws securing the input board cover.
NOTE
The appliance comes with a factory fitted link to allow basic operation of the boiler via the keypad. If it is anticipated that external controls will be required please refer to the wiring diagrams in section 8 for more detailed information.
Cable
entries
Hot water
outlet
Fig.14
12
Loading...
+ 30 hidden pages