VOKERA Eclipse 216 ESS, Eclipse 226 ESS Installation & Servicing Instructions Manual

Supplied By www.heating spares.co Tel. 0161 620 6677
Installation & Servicing Instructions
THESE INSTRUCTIONS TO BE RETAINED BY USER
Supplied By www.heating spares.co Tel. 0161 620 6677
Contents
Design principles & operating sequence Page
1.1 Principle components 2
1.2 Mode of operation (at rest) 2
1.3 Heat request mode 2
1.4 Safety devices 2
Technical data Page
2.1 Central heating 3
2.2 Gas pressure 3
2.3 Expansion vessel 3
2.4 Dimensions 3
2.5 Clearances 3
2.6 Connections 3
2.7 Electrical 3
2.8 Flue details 3
2.9 Efficiency 3
2.10 Parameter defaults 3
2.11 Emissions 3
2.12 Pump duty 4
General requirements Page
3.1 Related documents 4
3.2 Location of appliance 4
3.3 Gas supply 5
3.4 Flue system 5
3.5 Air supply 5
3.6 Water circulation 5
3.7 Electrical supply 6
3.8 Combustible surfaces 6
3.9 Timber framed buildings 6
3.10 Condensate disposal 6
3.11 Inhibitors 6
Installation Page
4.1 Delivery 7
4.2 Contents 7
4.3 Unpacking 7
4.4 Preparation for mounting 7
4.5 Fitting the flue 7
4.6 Connecting the gas & water 10
4.7 Condensate outlet 11
4.8 Electrical connections 11
Commissioning Page
5.1 Gas supply installation 12
5.2 The heating system 12
5.3 Initial filling of the system 12
5.4 Initial flushing of the system 12
5.5 Pre-operation checks 12
5.6 Initial lighting 12
5.7 Final flushing of the system 12
5.8 Operating parameters 13
5.9 Functional parameters 13
5.10 Range rating 13
5.11 Setting the system design pressure 13
5.12 Regulating the central heating system 13
5.13 Final checks 14
5.14 Instructing the user 14
Servicing Page
6.1 General 14
6.2 Routine annual servicing 14
6.3 Replacement of components 14
6.4 Component removal procedure 14
6.5 Pump head removal 15
6.6 Safety valve removal 15
6.7 Automatic air valve removal 15
6.8 Pressure gauge removal 15
6.9 Temperature sensor removal 15
6.10 Main PCB removal 15
6.11 Gas valve removal 16
6.12 Fan removal 16
6.13 Burner removal 16
6.14 Electrode removal 16
6.15 Injector removal 16
6.16 Hydraulic manifold assembly 17
6.17 Condense trap removal 17
6.18 Condense pressure switch removal 17
6.19 Combustion cover removal 17
6.20 Expansion vessel removal 18
6.21 Input & status PCB removal 18
Checks, adjustments, and fault finding Page
7.1 Checking appliance operation 19
7.2 Mode of operation 19
7.3 Checking/adjusting fan speeds 19
7.4 Adjusting the gas valve 20
7.5 Status code 21
7.6 Lockout faults codes 21
7.7 Diagnostic recall 21
7.8 Temperature sensor viewing mode 22
7.9 Checking the expansion vessel 22
7.10 External faults (installation) 22
7.11 Electrical checks 22
7.12 Fault finding 23
Wiring diagrams Page
8.1 Important note 26
8.2 Installation of Vokera time clock 26
8.3 External controls 26
Exploded diagrams Page
9.1 Table 1 31
9.2 Table 2 32
9.3 Table 3 33
9.4 Table 4 34
9.5 Table 5 35
L.P.G. instructions Page
10.1 Technical data 36
10.2 Related documents 36
10.3 Gas supply 36
10.4 Gas supply installation 36
10.5 Adjusting the gas valve 36
10.6 Range rating 37
Supplied By www.heating spares.co Tel. 0161 620 6677
INTRODUCTION
The Vokera Eclipse 216 ESS & 226 ESS are central heating condensing boilers, which - by design ­incorporates full sequence electronic ignition, circulating pump, expansion vessel, safety valve, pressure gauge and automatic by-pass.
The Eclipse 216 & 226 ESS boilers are produced as room sealed, category C1, C3, C6 appliances, suitable for wall mounting applications only. The Eclipse is provided with a fan powered flue outlet with an annular co-axial
combustion air intake that can be rotated – horizontally – through 360 degrees for various horizontal or vertical applications. The Eclipse can also be used with the Vokera twin flue system.
These appliances are designed for use with sealed systems only; consequently they are not intended for use on open vented systems.
A range rating facility is incorporated in the appliance.
General layout
1 Auto air vent 2 Flue outlet & air intake 3 Flue gas analysis test point 4 Burner plate 5 Spark/Sensing Electrode 6 Fan assembly 7 Pressure switch 8 Electronic Control Board (PCB) 9 Condense trap 12 Gas connection 13 Pressure gauge 14 Time clock aperture 15 Function key pad 16 LED display 17 Reset button 18 Heating flow connection 19 Safety valve 20 Heating return connection 21 Auto by-pass 22 Hydraulic manifold 23 Pump 24 Return sensor (NTC2) 25 Gas valve 26 Flow sensor (NTC1)
Fig. 1
1
Supplied By www.heating spares.co Tel. 0161 620 6677
SECTION 1 DESIGN PRINCIPLES AND OPERATING SEQUENCE
1.1 PRINCIPLE COMPONENTS
A fully integrated electronic control board
featuring electronic temperature control, continuous air/gas modulation, anti-cycle control, pump over-run, self-diagnostic fault indicator, electronic ignition with flame supervision, & appliance frost protection.
Cast aluminium mono-block heat exchanger.
Low Nox burner with pre-mix.
Two-stage gas valve.
Pump.
Expansion vessel.
Pressure gauge.
Safety valve.
1.2 MODE OF OPERATION (at rest)
When there is no demand for heating or hot water. And the appliance remains inactive for a period of 24 hours, the pump will be energised for a few moments to prevent it from seizing. Should the flow temperature sensor fall below 7°C the pump will be energised. If the flow sensor temperature falls to below 3°C the burner will be lit and the appliance will operate at the minimum output until the temperature of the flow sensor reaches 10°C, whereupon the pump will continue to run in pump over-run mode.
1.4 SAFETY DEVICES
When the appliance is in use, safe operation is ensured by:
a high limit thermostat that interrupts the
operation of the burner;
a differential temperature protection circuit which
interrupts the burner if the temperature differential is inverted;
a fan speed sensor which checks the correct
operation of the fan, thereby allowing safe operation of the burner;
a safety valve which releases excess pressure
from the primary circuit.
a condense pressure switch that will stop the
burner from operating should the condense trap become blocked.
1
1.3 MODE OF OPERATION (heating/hot water request)
When there is a request for heat via the time clock and/or external controls, the pump will start and the fan will be activated via the flow temperature sensor. When the fan is sensed to be operating correctly, the ignition sequence commences. The speed of the fan and therefore the output of the boiler is determined by the temperature of the water sensed by the flow & return temperature sensors, consequently a high temperature at the flow sensor results in a lower fan speed. As the water temperature increases, the temperature sensors – located on the flow & return pipes of the boiler – reduce the fan speed via the electronic circuitry. Depending on the load, either the water temperature will continue to rise until the set point is achieved or the water temperature will fall whereby fan speed will increase relative to the output required. When the boiler has reached the set point, the burner will switch off. The built-in anti-cycle device prevents the burner from re­lighting for an adjustable period of time (factory default is 3 minutes). When the temperature of the flow sensor falls below the set-point, the burner will re-light.
Fig. 2
4
return flowgas
Main Heat Exchanger
Expansion vessel
2
Supplied By www.heating spares.co Tel. 0161 620 6677
SECTION 2 TECHNICAL DATA
216 226
2.1 Central heating
Heat input 17,80 kW 29,00 kW Maximum heat output 60/80°C (return & flow temperature) 15,40 kW 25,30 kW Maximum heat output 30/50°C (return & flow temperature) 16,80 kW 26,8 kW Minimum heat output 60/80°C (return & flow temperature) 4,40 kW 7,3 kW Minimum heat output 30/50°C (return & flow temperature) 4,90 kW 8,10 kW Minimum working pressure 0,45 bar 0,45 bar Maximum working pressure 3 bar 3 bar Minimum flow rate 350 l/h 350 l/h
2.2 Gas pressure
Inlet pressure (G20) 20,0 mbar 20,0 mbar Maximum gas rate 1,69 m3/h 2,76 m3/h Minimum gas rate 0,49 m3/h 0,80 m3/h Injector size single injectors with six 3,1mm holes single injectors with six 3,8mm holes
2.3 Expansion vessel
Capacity 8 litres 8 litres Maximum system volume 76 litres 76 litres Pre-charge pressure 1,0 bar 1,0 bar
2.4 Dimensions
Height 790 mm 790 mm Width 450 mm 450 mm Depth 322 mm 322 mm Dry weight 57 kg 57 kg
2.5 Clearances
Sides 25 mm 25 mm Top
Bottom 150 mm 150 mm Front 600 mm 600 mm
2.6 Connections
Flow & return 22 mm compression 22 mm compression Gas 1/2 inch BSP 1/2 inch BSP Safety valve 1/2 inch BSP 1/2 inch BSP
2.7 Electrical
Voltage 230V/~ 50hz 230V/~ 50hz Power consumption 130 W 130 W Internal fuse 2 A 2 A External fuse 3 A 3 A
2.8 Flue details
Maximum horizontal flue length (concentric) 10 metres 6,45 metres Maximum vertical flue length (concentric) 11 metres 7,45 metres Maximum twin flue length (horizontal or vertical) 39 m + 39 m 29 m + 29 m
2.9 Efficiency
SEBDUK rating Band “A” Band “A”
2.10 Operating parameters (factory default shown)
Maximum fan speed 4.000 RPM 5.500 RPM Minimum fan speed 1.300 RPM 1.700 RPM Soft light setting 100 (%) 80 (%) Anti-cycle delay (variable between 0 sec.-360 sec.) 180 sec. 180 sec. Flow temperature (variable between 20°-90°)75°C75°C Pump over-run (variable between 3-99 minutes) 10 minutes 10 minutes
2.11 Emissions
NOx at maximum output 40 ppm 30 ppm NOx at minimum output 20 ppm 15 ppm CO at maximum output 50 ppm 50 ppm CO at minimum output 50 ppm 50 ppm CO2 at maximum output (air chamber cover off) 9,8 % 9,8 % CO2 at minimum output (air chamber cover off) 9,8 % 9,8 % CO/CO
ratio 0.0005 to 1 0.0005 to 1
2
150mm from casing or 25mm above 150mm from casing or 25mm above flue elbow (whichever is applicable) flue elbow (whichever is applicable)
Ref. Condition 15 °C , 1013,25 mbar, dry gas NOTE: L.P.G. data refer to section 10
3
Supplied By www.heating spares.co Tel. 0161 620 6677
2.12 PUMP DUTY
Fig. 3 shows the flow rate available – after allowing for pressure loss through the appliance – for system requirements. When using this graph apply only the pressure loss of the system. The graph is based on 20°C temperature differential.
600
500
400
300
200
100
Water pressure (mbar)
0 100 200 300 400 500 600 700 800
Fig. 3
Litres Per Hour (x100)
900 1000
1100 1200 1300 1400
Terminal position for fan assisted boiler
(minimum distance) mm A - Directly above or below an open window 300
or other opening (e.g. air brick) B - Below gutters, soil pipes or drain pipes 25 C - Below eaves 25 D - Below balconies or car port roof 25 E - From vertical drain pipes and soil pipes 75 F - From internal or external corners 25 G - Above ground or below balcony level 300 H - From a surface facing a terminal 600 I - From a terminal facing a terminal 1200
Fig. 4
SECTION 3 GENERAL REQUIREMENTS
This appliance must be installed by a competent person in accordance with the Gas Safety (Instal­lation & Use) Regulations.
3.1 RELATED DOCUMENTS
The installation of this boiler must be in accord­ance with the relevant requirements of the Gas Safety (Installation & Use) Regulations, the local building regulations, the current I.E.E. wiring regulations, the bylaws of the local water undertaking, the Building Standards (Scotland) Regulation and Building Standards (Northern Ireland) Regulations.
It should be in accordance also with any relevant requirements of the local authority and the relevant recommendations of the following British Standard Codes of Practice.
J - From an opening in the car port (e.g. door
window) into dwelling. 1200 K - Vertically from a terminal on the same wall 1500 L - Horizontally from a terminal on the same wall 300 M - Horizontally from a vertical terminal to a wall 300
N – Horizontally from an opening, airbrick, openable
window, etc. 300
NOTE:The flue must be terminated in a place not likely to cause a nuisance.
3.2 LOCATION OF APPLIANCE
The appliance may be installed in any room or
internal space, although particular attention is
drawn to the requirements of the current I.E.E.
wiring regulations, and in Scotland, the electrical
provisions of the Building Regulations, with
respect to the installation of the appliance in a
room or internal space containing a bath or shower.
When an appliance is installed in a room or
internal space containing a bath or shower, the
appliance or any control pertaining to it must not
be within reach of a person using the bath or
shower.
The location chosen for the appliance must permit
the provision of a safe and satisfactory flue and
termination. The location must also permit an
adequate air supply for combustion purposes
4
Supplied By www.heating spares.co Tel. 0161 620 6677
BS 5440 PART 1 FLUES BS 5440 PART 2 FLUES AND VENTILATION BS 5449 PART 1 FORCED CIRCULATION HOT WATER SYSTEMS BS 6798 INSTALLATION OF BOILERS OF RATED INPUT NOT EXCEEDING 60kW BS 6891 LOW PRESSURE INSTALLATION PIPES BS 7074 PART 1 APPLICATION, SELECTION, AND INSTALLATION OF EXPANSION VESSELS AND
ANCILLARY EQUIPMENT FOR SEALED WATER SYSTEMS
and an adequate space for servicing and air circulation around the appliance. Where the installation of the appliance will be in an unusual location special procedures may be necessary, BS 6798 gives detailed guidance on this aspect.
A compartment used to enclose the appliance must be designed and constructed specifically for this purpose. An existing compartment/cup­board may be utilised provided that it is modified to suit.
Details of essential features of compartment/ cupboard design, including airing cupboard in­stallations, are given in BS 6798. This appliance is not suitable for external installation.
3.3 GAS SUPPLY
The gas meter – as supplied by the gas supplier – must be checked to ensure that it is of adequate size to deal with the maximum rated input of all the appliances that it serves. Installation pipes must be fitted in accordance with BS 6891. Pipe-work from the meter to the appliance must be of adequate size. Pipes of a smaller size than the appliance gas inlet connection must not be used. The installation must be tested for soundness in accordance with BS 6891.
If the gas supply serves more than one appliance, it must be ensured that an adequate supply is maintained to each appliance when they are in use at the same time.
3.4 FLUE SYSTEM
The terminal should be located where the disper­sal of combustion products is not impeded and with due regard for the damage and discoloration that may occur to building products located nearby. The terminal must not be located in a place where it is likely to cause a nuisance (see fig. 4).
Water vapour will condense on leaving the flue terminal, the effect of such pluming must be considered.
If installed less than 2m above a pavement or platform to which people have access (including balconies or flat roofs) the terminal must be protected by a guard of durable material. The guard must be fitted centrally over the terminal. Refer to BS 5440 Part 1, when the terminal is 0,5 metres (or less) below plastic guttering or 1 metre (or less) below painted eaves.
3.5 AIR SUPPLY
The following notes are intended for general guidance only.
This appliance is a room sealed, fan-flued boiler, consequently it does not require a permanent air vent for combustion air supply.
When installed in a cupboard or compartment, ventilation for cooling purposes is also not required.
3.6 WATER CIRCULATION
Detailed recommendations are given in BS 5449 Part 1 and BS 6798. The following notes are for general guidance only.
3.6.1 PIPEWORK
It is recommended that copper tubing to BS 2871 Part 1 is used in conjunction with soldered capil­lary joints.
Where possible pipes should have a gradient to ensure air is carried naturally to air release points and that water flows naturally to drain cocks.
Except where providing useful heat, pipes should be insulated to avoid heat loss and in particular to avoid the possibility of freezing. Particular atten­tion should be paid to pipes passing through ventilated areas such as under floors, loft-space, and void areas.
3.6.2 AUTOMATIC BY-PASS
The appliance has a built-in automatic by-pass, consequently there is no requirement for an ex­ternal by-pass, however the design of the system should be such that it prevents boiler ‘cycling’.
3.6.3 DRAIN COCKS
These must be located in accessible positions to facilitate draining of the appliance and all water pipes connected to the appliance. The drain cocks must be manufactured in accordance with BS 2879.
3.6.4 AIR RELEASE POINTS
These must be positioned at the highest points in the system where air is likely to be trapped. They should be used to expel trapped air and allow complete filling of the system.
3.6.5 EXPANSION VESSEL
The appliance has an integral expansion vessel to accommodate the increased volume of water when the system is heated. It can accept up to 8
5
Supplied By www.heating spares.co Tel. 0161 620 6677
litres of expansion from within the system, generally this is sufficient, however if the system has an unusually high water content, it may be necessary to provide additional expansion capacity (see 6.19).
3.6.6 FILLING POINT
A method for initial filling of the system and replacing water lost during servicing etc. must be provided. This method of filling must comply with the local water authority regulations. Fig. 5 shows a widely accepted method.
3.7 ELECTRICAL SUPPLY
The appliance is supplied for operation on 230V
@ 50Hz electrical supply, it must be protected
with a 3-amp fuse. The method of connection to
the mains electricity supply must allow for
complete isolation from the supply. The preferred
method is by using a double-pole switch with a
contact separation of at least 3mm. The switch
must only supply the appliance and its
corresponding controls, i.e. time clock, room ther-
mostat, etc. Alternatively an un-switched shuttered
socket with a fused 3-pin plug both complying
with BS 1363 is acceptable.
3.8 MOUNTING ON A COMBUSTIBLE SURFACE
If the appliance is to be fitted on a wall of combus-
tible material, a sheet of fireproof material must
protect the wall.
3.9 TIMBER FRAMED BUILDINGS
If the appliance is to be fitted in a timber framed
building, it should be fitted in accordance with the
Institute of Gas Engineers publication (IGE/UP/7)
“Guide for Gas Installations in Timber Frame Buildings”.
Fig. 5
3.6.7 LOW PRESSURE SEALED SYSTEM
An alternative method of filling the system would be from an independent make-up vessel or tank mounted in a position at least 1 metre above the highest point in the system and at least 5 metres above the boiler (see fig. 5 A). The cold feed from the make-up vessel or tank must be fitted with an approved non-return valve and stopcock for isola­tion purposes. The feed pipe should be connected to the return pipe as close to the boiler as possible.
Make-up vessel or tank
Automatic air-vent
Non-return
valve
Stopcock
3.10 CONDENSATE DISPOSAL
When choosing a location for the boiler,
consideration should be given to the disposal of
the condensate discharge into a suitable drain or
soil pipe. The condensate outlet pipe must be
connected to the drain in accordance with building
regulations or other rules in force.
3.11 INHIBITORS
The system shall be flushed in accordance with
BS 7593. If an inhibitor is to be used, it shall be
from a reputable manufacturer and shall be
administered in strict accordance with the
manufacturers instructions.
5.0 metres minimum
Heating
Fig. 5 A
return
3.6.8 FREQUENT FILLING
Frequent filling or venting of the system may be indicative of a leak. Care should be taken during the installation of the appliance to ensure all aspects of the system are capable of withstand­ing pressures up to at least 3 bar.
Fig. 6
6
Supplied By www.heating spares.co Tel. 0161 620 6677
SECTION 4 INSTALLATION
4.1 DELIVERY
The appliance is delivered in a heavy-duty card­board carton. Lay the carton on the floor with the writing the correct way up.
4.2 CONTENTS
Contained within the carton is:
the boiler;
the wall mounting bracket;
template;
an accessories pack containing the appliance
service valves and washers;
the instruction pack containing the installation
& servicing instructions, user instructions, Benchmark logbook, guarantee registration card, and a 3amp fuse.
4.3 UNPACKING
At the top of the carton pull both sides open – do not use a knife – unfold the rest of the carton from around the appliance, carefully remove all pro­tective packaging from the appliance, and lay the accessories etc. to one side.
4.4 PREPARATION FOR MOUNTING THE APPLIANCE
The appliance should be mounted on a smooth, vertical, non-combustible surface, which must be capable of supporting the full weight of the appliance. Care should be exercised when determining the position of the appliance with respect to hidden obstructions such as pipes, cables, etc.
When the position of the appliance has been decided – using the template supplied – carefully mark the position of the wall-mounting bracket (see fig. 6) and flue-hole (if applicable).
Horizontal flue terminals and accessories
Part No.
0225720
0225755 0225740 0225745 0225750 0225730 0225735 0225760
Description
Horizontal flue kit for use with add. bends & extensions
350-500 T elescopic extension 0,5m extension 1,0m extension 2,0m extension 45° bend (pair) 90° bend Wall bracket (5)
Using the template provided (see fig. 6), mark and drill a 125mm hole for the passage of the flue pipe. The hole should ha ve a 1° rise from the boiler to outside.
The fixing holes for the wall-mounting bracket should now be drilled and plugged, an appropriate type and quantity of fixing should be used to ensure that the bracket is mounted securely. Once the br acket has been secured to the wall, mount the appliance onto the brack et.
FITTING THE HORIZONTAL FLUE KIT
Black
gasket
Min-Max length 1000mm
350mm-500mm 500mm 1000mm 2000mm N/A N/A N/A
Boiler top
adaptor
Flue outlet
4.5 FITTING THE FLUE
The top flue outlet permits both horizontal and vertical flue applications to be considered, alternatively, the Vokera twin flue system can be utilised if longer flue runs are required.
4.5.1 CONCENTRIC HORIZONTAL FLUE
(For concentric vertical flue, see 4.5.2). (For twin flue applications, see 4.5.3). The appliance flue outlet elbow can be rotated through 360° on its vertical axis. In addition the flue may be extended from the outlet elbow in the horizontal plane (see 2.8). A reduction must also be made to the maximum length (see table below) when additional bends are used.
Reduction for additional bends Bend 45° bend 90° bend
Reduction in maximum flue length for each bend 0,5 metre
1,0 metre
Boiler
Fig. 7
Take the large black gasket - supplied with the flue terminal kit - and stretch it over the appliance flue outlet (fig. 7). Using a twisting motion, connect the boiler top adaptor - supplied with the flue terminal kit - to the appliance flue outlet ensuring the male spigot of the adaptor is pushed fully into the flue outlet spigot of the boiler (fig. 7). Carefully measure the distance from the centre of the appliance flue outlet to the edge of the finished outside wall (dimension X). Add 45mm to dimension X to give you Dimension Y (see fig 7A). Measure dimension Y from the terminal end of the concentric flue pipe and cut off the excess. Pass the concentric flue pipe through the previously drilled hole. Fit the flue bend to the boiler top adaptor and insert the concentric flue pipe into the flue bend ensuring the correct seal is made.
7
Supplied By www.heating spares.co Tel. 0161 620 6677
NOTE
You must ensure that the entire flue system is properly supported and connected.
Seal the flue assembly to the wall using cement or a suitable alternative that will provide satisfactory weatherproofing. The interior and exterior trim can now be fitted.
Seal the flue assembly to the wall using cement or a suitable alternative that will provide satisfactory weatherproofing. The interior and exterior trim can now be fitted.
Push-fit connection
Extension pipe
Plain end
Fig. 7A
4.5.1.1 EXTENDING THE FLUE
Connect the bend – supplied with the terminal kit – to the top of the boiler using the boiler top adapter (supplied, see fig. 7). The additional bends & extensions have push-fit connections, care should be taken to ensure that the correct seal is made when assembling the flue system. Connect the required number of flue extensions or bends (up to the maximum equivalent flue length) to the flue terminal (see fig. 7B & 7C).
Push-fit connection
Boiler top adaptor
Extension
Boiler top adaptor
Boiler
Fig. 7C
4.5.2 CONCENTRIC VERTICAL FLUE
The vertical flue terminal can be connected directly to the appliance flue outlet. Alternatively, an extension or bend can be connected to the appliance flue outlet if desired (see 2.8), however if additional bends are fitted, a reduction must be made to the maximum flue length (see table below).
Reduction for bends
Bend 45° bend 90° bend
Reduction in maximum flue length for each bend 0,5 metre
1,0 metre
Boiler
Part No.
Fig. 7B
NOTE
When cutting an extension to the required length, you must ensure that the excess is cut from the plain end of the extension (see fig. 7B & 7C). Remove any burrs, and check that any seals are located properly. You must ensure that the entire flue system is properly supported and connected.
0225725 0225770 0225765 0225755 0225740 0225745 0225750 0225730 0225735 0225760
8
Vertical flue terminal and accessories
Description Vertical flue terminal
Pitched roof flashing plate Flat roof flashing plate 350-500 telescopic extension 0,5m extension 1,0m extension 2,0m extension 45° bend (pair) 90° bend Wall bracket (4)
Min-Max length 1000 mm
N/A N/A 350mm-500mm 500mm 1000mm 2000mm N/A N/A N/A
Supplied By www.heating spares.co Tel. 0161 620 6677
Using the dimensions given in fig. 8 as a reference, mark and cut a 105mm hole in the ceiling and/or roof.
IMPORTANT
You must ensure that the terminal is at least 300mm from any structure or surface (see fig. 8). The vertical flue terminal is 1,0 metre in length and cannot be cut; therefore it may be necessary to adjust the height of the appliance to suit or use a suitable extension. Encure that any horizontal sections of the flue system have a 1° fall back to the boiler (17mm per 1000mm).
Fit the appropriate flashing plate to the roof and insert the vertical flue terminal through the flashing plate from the outside, ensuring that the collar on the flue terminal fits over the flashing.
The fixing holes for the wall-mounting bracket should now be drilled and plugged, an appropriate type and quantity of fixing should be used to ensure that the bracket is mounted securely. Once the bracket has been secured to the wall, mount the appliance onto the bracket.
GUIDANCE NOTES ON TWIN FLUE INSTALLATION
The flue must hav e a f all back of 1° back to the
appliance to allow any condensate that forms in the flue system to drain. Consideration must also be given to the fact that there is the possibility of a small amount of condensate dripping from the terminal.
Ensure that the entire flue system is adequately
supported, use at least one bracket for each extension.
As the exhaust outlet pipe can reach v ery high
temperatures it must be protected to prevent persons touching the hot surface.
Reduction for bends
Bend 45° bend
90° bend
Reduction in maximum flue length for each bend 1,0 metre
1,0 metre
Twin flue accessories
300mm minimum
Fig. 8
NOTE
When cutting an extension to the required length, you must ensure that the excess is cut from the plain end of the extension. Remove any b urrs, and check that an y seals are located properly .
4.5.3 TWIN FLUE SYSTEM
The Vokera twin flue system enables greater flue distances to be achieved (see 2.8) than that of the standard concentric flue system. It can be used f or horizontal or vertical applications, howev er the twin flue system must be converted to the dedicated concentric flue kit for termination. It is essential that the installation of the twin flue system be carried out in strict accordance with these instructions.
520mm
520mm
Part No.
0225805 0225810 359 0225770 0225765 0225815 0225820 0225825 0225830 0225835 0225840 0225845 0225850 0225855
Description Horizontal flue terminal
Vertical flue terminal Twin adapter kit Pitched roof flashing plate Flat roof flashing plate Condensate drain kit 0,25m extension (pair) 0,5m extension (pair) 1,0m extension (pair) 2,0m extension (pair) 45° bend (pair) 90° bend (pair) Twin bracket (5) Single bracket (5)
Length 1000 mm
1000 mm N/A N/A N/A N/A 250mm 500mm 1000mm 2000mm N/A N/A N/A N/A
MOUNTING THE BOILER
The fixing holes for the wall-mounting bracket should now be drilled and plugged, an appropriate type and quantity of fixing should be used to ensure that the bracket is mounted securely. Once the br acket has been secured to the wall, mount the appliance onto the bracket.
4.5.3.1 INSTALLATION OF TWIN ADAPTOR KIT (see fig. 9)
Discard the restrictor ring (supplied with the twin
adapter kit).
Insert the exhaust connection manifold onto the
appliance flue outlet.
Place the silicone seal (supplied with twin
adapter kit) over the rim of the exhaust connection manifold.
Remove one of the blanking plate (located to
the left & right of the appliance flue outlet) and – using the same screws – install the air baffle.
9
Supplied By www.heating spares.co Tel. 0161 620 6677
Fig. 9
4.5.3.2 HORIZONTAL TERMINATION (see fig. 10)
The twin flue system must be converted to the dedicated concentric flue kit for termination.
The horizontal terminal is supplied with a built-
in converter box and cannot be shortened.
A 130mm hole is required for the passage of
the concentric terminal through the wall.
Depending on site conditions it may be prefer able to install the terminal assembly prior to fitting the twin flue pipes.
Mark and drill a 130mm hole for the passage of the horizontal flue terminal, ensuring that there is a 1° fall back to the boiler (17mm per 1000mm). Insert the terminal assembly into the flue hole.
Push-fit the twin flue pipes onto the concentric to twin converter box ensuring that the exhaust pipe connects to the exhaust connection on the concentric to twin converter. If necessary cut the plain ends (male) of the twin flue pipes to allow connection to the concentric to twin converter.
NOTE
Before cutting twin flue pipes ensure allowances ha ve been made for connection onto the previous piece and onto the concentric to twin converter. The last twin flue pipes must be pushed 50mm onto the male spigots of the concentric to twin converter.
NOTE
You must ensure that the entire flue system is properly supported and connected. When cutting an extension to the required length, you should ensure that the excess is cut from the plain end of the extension. Remove an y burrs, and check that both seals are located properly.
Seal the flue terminal assembly to the wall using cement or a suitable alternative that will provide satisfactory weatherproofing. The interior and exterior trim can now be fitted.
4.5.3.3 VERTICAL TERMINATION (see fig. 11)
The twin flue system must be converted to the dedicated concentric flue kit for termination.
The vertical terminal is supplied with a built-in
converter box and cannot be shortened.
A 130mm hole is required for the passage of
the concentric terminal through the ceiling and/or roof. Depending on site conditions it may be pref erable
to install the terminal assembly prior to fitting the twin flue pipes. Fit the appropriate flashing plate to the roof and insert the vertical flue terminal through the flashing plate from the outside, ensuring that the collar on the flue terminal fits over the flashing. Push-fit the twin flue pipes onto the concentric to twin converter ensuring that the exhaust pipe connects to the exhaust connection on the concentric to twin converter. If necessary cut the plain ends (male) of the twin flue pipes to allow connection to the concentric to twin converter.
NOTE
Before cutting twin flue pipes ensure
allowances have been made for connection onto the previous piece and onto the concentric to twin converter. The last twin flue pipes must be pushed 50mm onto the male spigots of the concentric to twin converter.
You must ensure that the entire flue system is
properly supported and connected.
Ensure that any horizontal sections of pipe hav e
a 1° fall towards the appliance (17mm per 1000mm).
The convertor box on the vertical terminal will
have to be temporarily remo ved when inserting the terminal through the flashing.
convertor box
Fig. 11
convertor box
4.6 CONNECTING THE GAS AND WATER
Fig. 10
10
The appliance is supplied with an accessories pack that contains sealing washers and service valves. When connecting pipe work to the valves, tighten the compression end first, then insert the sealing washers before tightening the valve to the appliance.
Loading...
+ 28 hidden pages