Supplied By www.heating spares.co Tel. 0161 620 6677
ESS
Installation
& Servicing
Instructions
THESE INSTRUCTIONS
TO BE RETAINED
BY USER
Supplied By www.heating spares.co Tel. 0161 620 6677
Contents
Design principles & operating sequencePage
1.1Principle components2
1.2Mode of operation (at rest)2
1.3Heat request mode2
1.4Safety devices2
Technical dataPage
2.1Central heating3
2.2Gas pressure3
2.3Expansion vessel3
2.4Dimensions3
2.5Clearances3
2.6Connections3
2.7Electrical3
2.8Flue details3
2.9Efficiency3
2.10 Parameter defaults3
2.11 Emissions3
2.12 Pump duty4
General requirementsPage
3.1Related documents4
3.2Location of appliance4
3.3Gas supply5
3.4Flue system5
3.5Air supply5
3.6Water circulation5
3.7Electrical supply6
3.8Combustible surfaces6
3.9Timber framed buildings6
3.10 Condensate disposal6
3.11 Inhibitors6
InstallationPage
4.1Delivery7
4.2Contents7
4.3Unpacking7
4.4Preparation for mounting7
4.5Fitting the flue7
4.6Connecting the gas & water10
4.7Condensate outlet11
4.8Electrical connections11
Commissioning Page
5.1Gas supply installation12
5.2The heating system12
5.3Initial filling of the system12
5.4Initial flushing of the system12
5.5Pre-operation checks12
5.6Initial lighting12
5.7Final flushing of the system12
5.8Operating parameters13
5.9Functional parameters13
5.10 Range rating13
5.11 Setting the system design pressure13
5.12 Regulating the central heating system13
5.13 Final checks14
5.14 Instructing the user14
ServicingPage
6.1General14
6.2Routine annual servicing14
6.3Replacement of components14
6.4Component removal procedure14
6.5Pump head removal15
6.6Safety valve removal15
6.7Automatic air valve removal15
6.8Pressure gauge removal15
6.9Temperature sensor removal15
6.10 Main PCB removal15
6.11 Gas valve removal16
6.12 Fan removal16
6.13 Burner removal16
6.14 Electrode removal16
6.15 Injector removal16
6.16 Hydraulic manifold assembly17
6.17 Condense trap removal17
6.18 Condense pressure switch removal17
6.19 Combustion cover removal17
6.20 Expansion vessel removal18
6.21 Input & status PCB removal18
Checks, adjustments, and fault findingPage
7.1Checking appliance operation19
7.2Mode of operation19
7.3Checking/adjusting fan speeds19
7.4Adjusting the gas valve20
7.5Status code21
7.6Lockout faults codes21
7.7Diagnostic recall21
7.8Temperature sensor viewing mode22
7.9Checking the expansion vessel22
7.10 External faults (installation)22
7.11 Electrical checks22
7.12 Fault finding23
Wiring diagramsPage
8.1Important note26
8.2Installation of Vokera time clock26
8.3External controls26
Exploded diagramsPage
9.1Table 131
9.2Table 232
9.3Table 333
9.4Table 434
9.5Table 535
L.P.G. instructionsPage
10.1 Technical data36
10.2 Related documents36
10.3 Gas supply36
10.4 Gas supply installation36
10.5 Adjusting the gas valve36
10.6 Range rating37
Supplied By www.heating spares.co Tel. 0161 620 6677
INTRODUCTION
The Vokera Eclipse 216 ESS & 226 ESS are central
heating condensing boilers, which - by design incorporates full sequence electronic ignition, circulating
pump, expansion vessel, safety valve, pressure gauge
and automatic by-pass.
The Eclipse 216 & 226 ESS boilers are produced as room
sealed, category C1, C3, C6 appliances, suitable for wall
mounting applications only. The Eclipse is provided with
a fan powered flue outlet with an annular co-axial
combustion air intake that can be rotated – horizontally –
through 360 degrees for various horizontal or vertical
applications. The Eclipse can also be used with the
Vokera twin flue system.
These appliances are designed for use with sealed
systems only; consequently they are not intended for use
on open vented systems.
A range rating facility is incorporated in the appliance.
General layout
1Auto air vent
2Flue outlet & air intake
3Flue gas analysis test point
4Burner plate
5Spark/Sensing Electrode
6Fan assembly
7Pressure switch
8Electronic Control Board (PCB)
9Condense trap
12Gas connection
13Pressure gauge
14Time clock aperture
15Function key pad
16LED display
17Reset button
18Heating flow connection
19Safety valve
20Heating return connection
21Auto by-pass
22Hydraulic manifold
23Pump
24Return sensor (NTC2)
25Gas valve
26Flow sensor (NTC1)
Fig. 1
1
Supplied By www.heating spares.co Tel. 0161 620 6677
When there is no demand for heating or hot
water. And the appliance remains inactive for a
period of 24 hours, the pump will be energised for
a few moments to prevent it from seizing. Should
the flow temperature sensor fall below 7°C the
pump will be energised.
If the flow sensor temperature falls to below 3°C
the burner will be lit and the appliance will operate
at the minimum output until the temperature of
the flow sensor reaches 10°C, whereupon the
pump will continue to run in pump over-run mode.
1.4SAFETY DEVICES
When the appliance is in use, safe operation is
ensured by:
● a high limit thermostat that interrupts the
operation of the burner;
● a differential temperature protection circuit which
interrupts the burner if the temperature
differential is inverted;
● a fan speed sensor which checks the correct
operation of the fan, thereby allowing safe
operation of the burner;
● a safety valve which releases excess pressure
from the primary circuit.
● a condense pressure switch that will stop the
burner from operating should the condense
trap become blocked.
1
1.3MODE OF OPERATION (heating/hot water
request)
When there is a request for heat via the time clock
and/or external controls, the pump will start and
the fan will be activated via the flow temperature
sensor. When the fan is sensed to be operating
correctly, the ignition sequence commences. The
speed of the fan and therefore the output of the
boiler is determined by the temperature of the
water sensed by the flow & return temperature
sensors, consequently a high temperature at the
flow sensor results in a lower fan speed. As the
water temperature increases, the temperature
sensors – located on the flow & return pipes of the
boiler – reduce the fan speed via the electronic
circuitry. Depending on the load, either the water
temperature will continue to rise until the set point
is achieved or the water temperature will fall
whereby fan speed will increase relative to the
output required. When the boiler has reached the
set point, the burner will switch off. The built-in
anti-cycle device prevents the burner from relighting for an adjustable period of time (factory
default is 3 minutes). When the temperature of
the flow sensor falls below the set-point, the
burner will re-light.
Fig. 2
4
return flowgas
Main Heat
Exchanger
Expansion
vessel
2
Supplied By www.heating spares.co Tel. 0161 620 6677
SECTION 2TECHNICAL DATA
216226
2.1 Central heating
Heat input17,80 kW29,00 kW
Maximum heat output 60/80°C (return & flow temperature)15,40 kW25,30 kW
Maximum heat output 30/50°C (return & flow temperature)16,80 kW26,8 kW
Minimum heat output 60/80°C (return & flow temperature)4,40 kW7,3 kW
Minimum heat output 30/50°C (return & flow temperature)4,90 kW8,10 kW
Minimum working pressure0,45 bar0,45 bar
Maximum working pressure3 bar3 bar
Minimum flow rate350 l/h350 l/h
2.2 Gas pressure
Inlet pressure (G20)20,0 mbar20,0 mbar
Maximum gas rate1,69 m3/h2,76 m3/h
Minimum gas rate0,49 m3/h0,80 m3/h
Injector sizesingle injectors with six 3,1mm holessingle injectors with six 3,8mm holes
2.3 Expansion vessel
Capacity8 litres8 litres
Maximum system volume76 litres76 litres
Pre-charge pressure1,0 bar1,0 bar
2.4 Dimensions
Height790 mm790 mm
Width450 mm450 mm
Depth322 mm322 mm
Dry weight57 kg57 kg
2.5 Clearances
Sides25 mm25 mm
Top
Bottom150 mm150 mm
Front600 mm600 mm
2.6 Connections
Flow & return22 mm compression22 mm compression
Gas1/2 inch BSP1/2 inch BSP
Safety valve1/2 inch BSP1/2 inch BSP
2.7 Electrical
Voltage230V/~ 50hz230V/~ 50hz
Power consumption130 W130 W
Internal fuse2 A2 A
External fuse3 A3 A
2.8 Flue details
Maximum horizontal flue length (concentric)10 metres6,45 metres
Maximum vertical flue length (concentric)11 metres7,45 metres
Maximum twin flue length (horizontal or vertical)39 m + 39 m29 m + 29 m
2.9 Efficiency
SEBDUK ratingBand “A”Band “A”
2.10 Operating parameters (factory default shown)
Maximum fan speed4.000 RPM5.500 RPM
Minimum fan speed1.300 RPM1.700 RPM
Soft light setting100 (%)80 (%)
Anti-cycle delay (variable between 0 sec.-360 sec.)180 sec.180 sec.
Flow temperature (variable between 20°-90°)75°C75°C
Pump over-run (variable between 3-99 minutes)10 minutes10 minutes
2.11 Emissions
NOx at maximum output40 ppm30 ppm
NOx at minimum output20 ppm15 ppm
CO at maximum output50 ppm50 ppm
CO at minimum output50 ppm50 ppm
CO2 at maximum output (air chamber cover off)9,8 %9,8 %
CO2 at minimum output (air chamber cover off)9,8 %9,8 %
CO/CO
ratio0.0005 to 10.0005 to 1
2
150mm from casing or 25mm above150mm from casing or 25mm above
flue elbow (whichever is applicable)flue elbow (whichever is applicable)
Ref. Condition 15 °C , 1013,25 mbar, dry gas NOTE: L.P.G. data refer to section 10
3
Supplied By www.heating spares.co Tel. 0161 620 6677
2.12PUMP DUTY
Fig. 3 shows the flow rate available – after allowing
for pressure loss through the appliance – for
system requirements. When using this graph
apply only the pressure loss of the system. The
graph is based on 20°C temperature differential.
600
500
400
300
200
100
Water pressure (mbar)
0 100 200 300 400 500 600 700 800
Fig. 3
Litres Per Hour (x100)
900 1000
1100 1200 1300 1400
Terminal position for fan assisted boiler
(minimum distance) mm
A-Directly above or below an open window300
or other opening (e.g. air brick)
B-Below gutters, soil pipes or drain pipes25
C-Below eaves25
D-Below balconies or car port roof25
E-From vertical drain pipes and soil pipes75
F-From internal or external corners25
G-Above ground or below balcony level300
H-From a surface facing a terminal600
I-From a terminal facing a terminal1200
Fig. 4
SECTION 3GENERAL REQUIREMENTS
This appliance must be installed by a competent
person in accordance with the Gas Safety (Installation & Use) Regulations.
3.1RELATED DOCUMENTS
The installation of this boiler must be in accordance with the relevant requirements of the Gas
Safety (Installation & Use) Regulations, the local
building regulations, the current I.E.E. wiring
regulations, the bylaws of the local water
undertaking, the Building Standards (Scotland)
Regulation and Building Standards (Northern
Ireland) Regulations.
It should be in accordance also with any relevant
requirements of the local authority and the relevant
recommendations of the following British Standard
Codes of Practice.
J-From an opening in the car port (e.g. door
window) into dwelling.1200
K-Vertically from a terminal on the same wall1500
L-Horizontally from a terminal on the same wall300
M-Horizontally from a vertical terminal to a wall300
N –Horizontally from an opening, airbrick, openable
window, etc. 300
NOTE:The flue must be terminated in a place not likely to cause a
nuisance.
3.2LOCATION OF APPLIANCE
The appliance may be installed in any room or
internal space, although particular attention is
drawn to the requirements of the current I.E.E.
wiring regulations, and in Scotland, the electrical
provisions of the Building Regulations, with
respect to the installation of the appliance in a
room or internal space containing a bath or shower.
When an appliance is installed in a room or
internal space containing a bath or shower, the
appliance or any control pertaining to it must not
be within reach of a person using the bath or
shower.
The location chosen for the appliance must permit
the provision of a safe and satisfactory flue and
termination. The location must also permit an
adequate air supply for combustion purposes
4
Supplied By www.heating spares.co Tel. 0161 620 6677
BS 5440 PART 1FLUES
BS 5440 PART 2FLUES AND VENTILATION
BS 5449 PART 1FORCED CIRCULATION HOT WATER SYSTEMS
BS 6798INSTALLATION OF BOILERS OF RATED INPUT NOT EXCEEDING 60kW
BS 6891LOW PRESSURE INSTALLATION PIPES
BS 7074 PART 1APPLICATION, SELECTION, AND INSTALLATION OF EXPANSION VESSELS AND
ANCILLARY EQUIPMENT FOR SEALED WATER SYSTEMS
and an adequate space for servicing and air
circulation around the appliance.
Where the installation of the appliance will be in
an unusual location special procedures may be
necessary, BS 6798 gives detailed guidance on
this aspect.
A compartment used to enclose the appliance
must be designed and constructed specifically
for this purpose. An existing compartment/cupboard may be utilised provided that it is modified
to suit.
Details of essential features of compartment/
cupboard design, including airing cupboard installations, are given in BS 6798. This appliance
is not suitable for external installation.
3.3GAS SUPPLY
The gas meter – as supplied by the gas supplier
– must be checked to ensure that it is of adequate
size to deal with the maximum rated input of all
the appliances that it serves. Installation pipes
must be fitted in accordance with BS 6891.
Pipe-work from the meter to the appliance must be
of adequate size. Pipes of a smaller size than the
appliance gas inlet connection must not be used.
The installation must be tested for soundness in
accordance with BS 6891.
If the gas supply serves more than one appliance,
it must be ensured that an adequate supply is
maintained to each appliance when they are in
use at the same time.
3.4FLUE SYSTEM
The terminal should be located where the dispersal of combustion products is not impeded and
with due regard for the damage and discoloration
that may occur to building products located nearby.
The terminal must not be located in a place where
it is likely to cause a nuisance (see fig. 4).
Water vapour will condense on leaving the flue
terminal, the effect of such pluming must be
considered.
If installed less than 2m above a pavement or
platform to which people have access (including
balconies or flat roofs) the terminal must be
protected by a guard of durable material. The
guard must be fitted centrally over the terminal.
Refer to BS 5440 Part 1, when the terminal is 0,5
metres (or less) below plastic guttering or 1 metre
(or less) below painted eaves.
3.5AIR SUPPLY
The following notes are intended for general
guidance only.
This appliance is a room sealed, fan-flued boiler,
consequently it does not require a permanent air
vent for combustion air supply.
When installed in a cupboard or compartment,
ventilation for cooling purposes is also not required.
3.6WATER CIRCULATION
Detailed recommendations are given in BS 5449
Part 1 and BS 6798. The following notes are for
general guidance only.
3.6.1PIPEWORK
It is recommended that copper tubing to BS 2871
Part 1 is used in conjunction with soldered capillary joints.
Where possible pipes should have a gradient to
ensure air is carried naturally to air release points
and that water flows naturally to drain cocks.
Except where providing useful heat, pipes should
be insulated to avoid heat loss and in particular to
avoid the possibility of freezing. Particular attention should be paid to pipes passing through
ventilated areas such as under floors, loft-space,
and void areas.
3.6.2AUTOMATIC BY-PASS
The appliance has a built-in automatic by-pass,
consequently there is no requirement for an external by-pass, however the design of the system
should be such that it prevents boiler ‘cycling’.
3.6.3DRAIN COCKS
These must be located in accessible positions to
facilitate draining of the appliance and all water pipes
connected to the appliance. The drain cocks must be
manufactured in accordance with BS 2879.
3.6.4AIR RELEASE POINTS
These must be positioned at the highest points in
the system where air is likely to be trapped. They
should be used to expel trapped air and allow
complete filling of the system.
3.6.5EXPANSION VESSEL
The appliance has an integral expansion vessel
to accommodate the increased volume of water
when the system is heated. It can accept up to 8
5
Supplied By www.heating spares.co Tel. 0161 620 6677
litres of expansion from within the system, generally
this is sufficient, however if the system has an
unusually high water content, it may be necessary
to provide additional expansion capacity (see 6.19).
3.6.6FILLING POINT
A method for initial filling of the system and
replacing water lost during servicing etc. must be
provided. This method of filling must comply with
the local water authority regulations. Fig. 5 shows
a widely accepted method.
3.7ELECTRICAL SUPPLY
The appliance is supplied for operation on 230V
@ 50Hz electrical supply, it must be protected
with a 3-amp fuse. The method of connection to
the mains electricity supply must allow for
complete isolation from the supply. The preferred
method is by using a double-pole switch with a
contact separation of at least 3mm. The switch
must only supply the appliance and its
corresponding controls, i.e. time clock, room ther-
mostat, etc. Alternatively an un-switched shuttered
socket with a fused 3-pin plug both complying
with BS 1363 is acceptable.
3.8MOUNTING ON A COMBUSTIBLE SURFACE
If the appliance is to be fitted on a wall of combus-
tible material, a sheet of fireproof material must
protect the wall.
3.9TIMBER FRAMED BUILDINGS
If the appliance is to be fitted in a timber framed
building, it should be fitted in accordance with the
Institute of Gas Engineers publication (IGE/UP/7)
“Guide for Gas Installations in Timber Frame Buildings”.
Fig. 5
3.6.7LOW PRESSURE SEALED SYSTEM
An alternative method of filling the system would be
from an independent make-up vessel or tank
mounted in a position at least 1 metre above the
highest point in the system and at least 5 metres
above the boiler (see fig. 5 A). The cold feed from
the make-up vessel or tank must be fitted with an
approved non-return valve and stopcock for isolation purposes. The feed pipe should be connected
to the return pipe as close to the boiler as possible.
Make-up vessel
or tank
Automatic
air-vent
Non-return
valve
Stopcock
3.10CONDENSATE DISPOSAL
When choosing a location for the boiler,
consideration should be given to the disposal of
the condensate discharge into a suitable drain or
soil pipe. The condensate outlet pipe must be
connected to the drain in accordance with building
regulations or other rules in force.
3.11INHIBITORS
The system shall be flushed in accordance with
BS 7593. If an inhibitor is to be used, it shall be
from a reputable manufacturer and shall be
administered in strict accordance with the
manufacturers instructions.
5.0 metres minimum
Heating
Fig. 5 A
return
3.6.8FREQUENT FILLING
Frequent filling or venting of the system may be
indicative of a leak. Care should be taken during
the installation of the appliance to ensure all
aspects of the system are capable of withstanding pressures up to at least 3 bar.
Fig. 6
6
Supplied By www.heating spares.co Tel. 0161 620 6677
SECTION 4INSTALLATION
4.1DELIVERY
The appliance is delivered in a heavy-duty cardboard carton. Lay the carton on the floor with the
writing the correct way up.
4.2CONTENTS
Contained within the carton is:
● the boiler;
● the wall mounting bracket;
● template;
● an accessories pack containing the appliance
service valves and washers;
● the instruction pack containing the installation
& servicing instructions, user instructions,
Benchmark logbook, guarantee registration
card, and a 3amp fuse.
4.3UNPACKING
At the top of the carton pull both sides open – do
not use a knife – unfold the rest of the carton from
around the appliance, carefully remove all protective packaging from the appliance, and lay the
accessories etc. to one side.
4.4PREPARATION FOR MOUNTING THE
APPLIANCE
The appliance should be mounted on a smooth,
vertical, non-combustible surface, which must be
capable of supporting the full weight of the
appliance. Care should be exercised when
determining the position of the appliance with
respect to hidden obstructions such as pipes,
cables, etc.
When the position of the appliance has been
decided – using the template supplied – carefully
mark the position of the wall-mounting bracket
(see fig. 6) and flue-hole (if applicable).
Horizontal flue kit for use with
add. bends & extensions
350-500 T elescopic extension
0,5m extension
1,0m extension
2,0m extension
45° bend (pair)
90° bend
Wall bracket (5)
Using the template provided (see fig. 6), mark
and drill a 125mm hole for the passage of the
flue pipe. The hole should ha ve a 1° rise from the
boiler to outside.
The fixing holes for the wall-mounting bracket
should now be drilled and plugged, an
appropriate type and quantity of fixing should be
used to ensure that the bracket is mounted
securely. Once the br acket has been secured to
the wall, mount the appliance onto the brack et.
FITTING THE HORIZONTAL FLUE KIT
Black
gasket
Min-Max length
1000mm
350mm-500mm
500mm
1000mm
2000mm
N/A
N/A
N/A
Boiler top
adaptor
Flue outlet
4.5FITTING THE FLUE
The top flue outlet permits both horizontal and
vertical flue applications to be considered,
alternatively, the Vokera twin flue system can be
utilised if longer flue runs are required.
4.5.1CONCENTRIC HORIZONTAL FLUE
(For concentric vertical flue, see 4.5.2).
(For twin flue applications, see 4.5.3).
The appliance flue outlet elbow can be rotated
through 360° on its vertical axis. In addition the
flue may be extended from the outlet elbow in the
horizontal plane (see 2.8). A reduction must also
be made to the maximum length (see table below)
when additional bends are used.
Reduction for additional bends
Bend
45° bend
90° bend
Reduction in maximum flue length for each bend
0,5 metre
1,0 metre
Boiler
Fig. 7
Take the large black gasket - supplied with the
flue terminal kit - and stretch it over the appliance
flue outlet (fig. 7). Using a twisting motion, connect
the boiler top adaptor - supplied with the flue
terminal kit - to the appliance flue outlet ensuring
the male spigot of the adaptor is pushed fully into
the flue outlet spigot of the boiler (fig. 7). Carefully
measure the distance from the centre of the
appliance flue outlet to the edge of the finished
outside wall (dimension X). Add 45mm to
dimension X to give you Dimension Y (see fig
7A). Measure dimension Y from the terminal end
of the concentric flue pipe and cut off the excess.
Pass the concentric flue pipe through the
previously drilled hole. Fit the flue bend to the
boiler top adaptor and insert the concentric flue
pipe into the flue bend ensuring the correct seal
is made.
7
Supplied By www.heating spares.co Tel. 0161 620 6677
NOTE
You must ensure that the entire flue system is
properly supported and connected.
Seal the flue assembly to the wall using cement
or a suitable alternative that will provide
satisfactory weatherproofing. The interior and
exterior trim can now be fitted.
Seal the flue assembly to the wall using cement
or a suitable alternative that will provide
satisfactory weatherproofing. The interior and
exterior trim can now be fitted.
Push-fit connection
Extension pipe
Plain end
Fig. 7A
4.5.1.1 EXTENDING THE FLUE
Connect the bend – supplied with the terminal kit
– to the top of the boiler using the boiler top
adapter (supplied, see fig. 7). The additional
bends & extensions have push-fit connections,
care should be taken to ensure that the correct
seal is made when assembling the flue system.
Connect the required number of flue extensions
or bends (up to the maximum equivalent flue
length) to the flue terminal (see fig. 7B & 7C).
Push-fit
connection
Boiler top
adaptor
Extension
Boiler top adaptor
Boiler
Fig. 7C
4.5.2CONCENTRIC VERTICAL FLUE
The vertical flue terminal can be connected directly
to the appliance flue outlet.
Alternatively, an extension or bend can be
connected to the appliance flue outlet if desired
(see 2.8), however if additional bends are fitted,
a reduction must be made to the maximum flue
length (see table below).
Reduction for bends
Bend
45° bend
90° bend
Reduction in maximum flue length for each bend
0,5 metre
1,0 metre
Boiler
Part No.
Fig. 7B
NOTE
When cutting an extension to the required length,
you must ensure that the excess is cut from the
plain end of the extension (see fig. 7B & 7C).
Remove any burrs, and check that any seals are
located properly.
You must ensure that the entire flue system is
properly supported and connected.
Supplied By www.heating spares.co Tel. 0161 620 6677
Using the dimensions given in fig. 8 as a reference,
mark and cut a 105mm hole in the ceiling and/or roof.
IMPORTANT
You must ensure that the terminal is at least
300mm from any structure or surface (see fig. 8).
The vertical flue terminal is 1,0 metre in length
and cannot be cut; therefore it may be necessary
to adjust the height of the appliance to suit or use
a suitable extension.
Encure that any horizontal sections of the flue system
have a 1° fall back to the boiler (17mm per 1000mm).
Fit the appropriate flashing plate to the roof and
insert the vertical flue terminal through the flashing
plate from the outside, ensuring that the collar on
the flue terminal fits over the flashing.
The fixing holes for the wall-mounting bracket
should now be drilled and plugged, an appropriate
type and quantity of fixing should be used to
ensure that the bracket is mounted securely.
Once the bracket has been secured to the wall,
mount the appliance onto the bracket.
GUIDANCE NOTES ON TWIN FLUE
INSTALLATION
● The flue must hav e a f all back of 1° back to the
appliance to allow any condensate that forms
in the flue system to drain. Consideration must
also be given to the fact that there is the
possibility of a small amount of condensate
dripping from the terminal.
● Ensure that the entire flue system is adequately
supported, use at least one bracket for each
extension.
● As the exhaust outlet pipe can reach v ery high
temperatures it must be protected to prevent
persons touching the hot surface.
Reduction for bends
Bend
45° bend
90° bend
Reduction in maximum flue length for each bend
1,0 metre
1,0 metre
Twin flue accessories
300mm minimum
Fig. 8
NOTE
When cutting an extension to the required length,
you must ensure that the excess is cut from the
plain end of the extension.
Remove any b urrs, and check that an y seals are
located properly .
4.5.3TWIN FLUE SYSTEM
The Vokera twin flue system enables greater flue
distances to be achieved (see 2.8) than that of the
standard concentric flue system. It can be used f or
horizontal or vertical applications, howev er the twin
flue system must be converted to the dedicated
concentric flue kit for termination. It is essential that
the installation of the twin flue system be carried
out in strict accordance with these instructions.
The fixing holes for the wall-mounting bracket
should now be drilled and plugged, an
appropriate type and quantity of fixing should be
used to ensure that the bracket is mounted
securely. Once the br acket has been secured to
the wall, mount the appliance onto the bracket.
4.5.3.1 INSTALLATION OF TWIN ADAPTOR KIT (see
fig. 9)
● Discard the restrictor ring (supplied with the twin
adapter kit).
● Insert the exhaust connection manifold onto the
appliance flue outlet.
● Place the silicone seal (supplied with twin
adapter kit) over the rim of the exhaust
connection manifold.
● Remove one of the blanking plate (located to
the left & right of the appliance flue outlet) and
– using the same screws – install the air baffle.
9
Supplied By www.heating spares.co Tel. 0161 620 6677
Fig. 9
4.5.3.2 HORIZONTAL TERMINATION (see fig. 10)
The twin flue system must be converted to the
dedicated concentric flue kit for termination.
● The horizontal terminal is supplied with a built-
in converter box and cannot be shortened.
● A 130mm hole is required for the passage of
the concentric terminal through the wall.
Depending on site conditions it may be prefer able
to install the terminal assembly prior to fitting the
twin flue pipes.
Mark and drill a 130mm hole for the passage of
the horizontal flue terminal, ensuring that there
is a 1° fall back to the boiler (17mm per 1000mm).
Insert the terminal assembly into the flue hole.
Push-fit the twin flue pipes onto the concentric to
twin converter box ensuring that the exhaust pipe
connects to the exhaust connection on the
concentric to twin converter. If necessary cut the
plain ends (male) of the twin flue pipes to allow
connection to the concentric to twin converter.
NOTE
Before cutting twin flue pipes ensure allowances ha ve
been made for connection onto the previous piece
and onto the concentric to twin converter.
The last twin flue pipes must be pushed 50mm onto
the male spigots of the concentric to twin converter.
NOTE
You must ensure that the entire flue system is
properly supported and connected.
When cutting an extension to the required length,
you should ensure that the excess is cut from
the plain end of the extension. Remove an y burrs,
and check that both seals are located properly.
Seal the flue terminal assembly to the wall using
cement or a suitable alternative that will provide
satisfactory weatherproofing. The interior and
exterior trim can now be fitted.
4.5.3.3 VERTICAL TERMINATION (see fig. 11)
The twin flue system must be converted to the
dedicated concentric flue kit for termination.
● The vertical terminal is supplied with a built-in
converter box and cannot be shortened.
●A 130mm hole is required for the passage of
the concentric terminal through the ceiling and/or roof.
Depending on site conditions it may be pref erable
to install the terminal assembly prior to fitting the
twin flue pipes.
Fit the appropriate flashing plate to the roof and
insert the vertical flue terminal through the
flashing plate from the outside, ensuring that the
collar on the flue terminal fits over the flashing.
Push-fit the twin flue pipes onto the concentric to
twin converter ensuring that the exhaust pipe
connects to the exhaust connection on the
concentric to twin converter.
If necessary cut the plain ends (male) of the twin
flue pipes to allow connection to the concentric
to twin converter.
NOTE
● Before cutting twin flue pipes ensure
allowances have been made for connection
onto the previous piece and onto the concentric
to twin converter. The last twin flue pipes must
be pushed 50mm onto the male spigots of the
concentric to twin converter.
● You must ensure that the entire flue system is
properly supported and connected.
● Ensure that any horizontal sections of pipe hav e
a 1° fall towards the appliance (17mm per
1000mm).
● The convertor box on the vertical terminal will
have to be temporarily remo ved when inserting
the terminal through the flashing.
convertor box
Fig. 11
convertor box
4.6CONNECTING THE GAS AND WATER
Fig. 10
10
The appliance is supplied with an accessories pack
that contains sealing washers and service valves.
When connecting pipe work to the valves, tighten
the compression end first, then insert the sealing
washers before tightening the valve to the appliance.
Loading...
+ 28 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.