Supplied By www.heating spares.co Tel. 0161 620 6677
Compact HE
High efficiency combi boiler
Installation
& Servicing
Instructions
THESE INSTRUCTIONS
TO BE RETAINED
BY USER
Vokèra is a licensed member of the Benchmark scheme
which aims to improve the standards of installation and
commissioning of domestic hot water systems in the UK.
Supplied By www.heating spares.co Tel. 0161 620 6677
7.2.2Selector switch in the hot water only position24
7.2.3Selector switch in the heating & hot water position24
7.2.4Appliance functions24
7.2.5DHW mode24
7.2.6Heating mode25
7.3Checking & adjusting burner pressure2 6
7.3.1Setting the maximum burner pressure26
7.3.2Setting the minimum burner pressure26
7.3.3Setting the minimum CH output26
7.4Combustion analysis test26
7.5Checking the expansion vessel27
7.6External faults27
7.6.1Installation faults27
7.7Electrical checks27
7.7.1Earth continuity test27
7.7.2Short circuit check27
7.7.3Polarity check27
7.7.4Reversed polarity or supply fault28
7.7.5Resistance to earth check28
7.8Fault finding28
7.8.1Replacing the main PCB28
7.9Fault codes28
7.10Fault finding29-34
Wiring diagramsPage
8.1External wiring35
8.2Typical control applications35
8.3Vokera remote control35
8.4Room thermostat35
8.5Other controls35
Functional diagram36
Exploded diagramsPage
Table 1-537-41
L.P.G. instructionsPage
10.1Related documents42
10.2Technical data4 2
10.3Converting the appliance gas supply42
10.4Gas supply4 2
10.5Gas supply installation42
10.6Checking & adjusting burner pressure4 2
10.6.1 Setting the maximum burner pressure42
10.6.2 Setting the minimum burner pressure42
45
Supplied By www.heating spares.co Tel. 0161 620 6677
INTRODUCTION
The Compact HE range of appliances is comprised of 2
models of high-efficiency combination boiler with inputs
to heating & DHW of 25, 29 & 35kW respectively. Each
appliance - by design - incorporates electronic ignition,
circulating pump, expansion vessel, safety valve, pressure gauge, and automatic by-pass.
The Compact HE range is produced as room sealed,
category II2H3P appliances, suitable for internal wall
mounting applications only. They are provided with a fan
powered flue outlet with an annular coaxial combustion
air intake that can be rotated - horizontally - through 360
degrees for various horizontal or vertical applications.
The Compact HE range can also be used with the Vokera
twin flue system.
The Compact HE range is approved for use with C12 &
C32 type flue applications.
These appliances are designed for use with a sealed
system only; consequently they are not intended for use
on open vented systems
Fig.1 General Layout
1Diverter valve motor
2Discharge valve
3Domestic hot water heat exchanger
4Safety valve
5Pump
6Pressure switch
7Auto air vent (AAV)
8Electrode
9Main burner
10 Main heat exchanger
11 Latent heat collector
12 Flue gas analysis test point
13 Flue outlet
14 Air intake
15 Differential pressure switch
16 Silicone pressure tube (-)
17 Silicone pressure tube (+)
18 Fan assembly
19 CH NTC sensor
20 Combustion chamber
21 High limit thermostat
22 Expansion vessel
23 Condensate pressure switch
24 Ignition transformer
25 Condense trap
26 Modulator coil
27 Gas valve
28 DHW flow switch
Fig. 1
293031323334
29 Pressure gauge
30 DHW temperature selector
31 Mode selector switch
32 Status fault/indicator led
33 CH temperature selector
34 Timeclock
1
Supplied By www.heating spares.co Tel. 0161 620 6677
SECTION 1DESIGN PRINCIPLES AND OPERATING SEQUENCE
1.1PRINCIPLE COMPONENTS
● A fully integrated electronic control board fea-
turing electronic temperature control, anti-cycle control, pump over-run, LED fault indicator,
full gas modulation.
● Low-water-content, copper heat exchanger.
● Electronic ignition with flame supervision.
● Integral high-head pump.
● Fan.
● Air pressure switch.
● Expansion vessel.
● Water pressure switch.
● Two-stage gas valve.
● Pressure gauge.
● Safety valve.
● Condense switch.
1.2MODE OF OPERATION (at rest)
When the appliance is at rest and there are no
requests for heating or DHW, the following functions are active:
● Frost-protection system - the frost-protection
system protects the appliance against the risk
of frost damage. Should the temperature of the
appliance fall to 5 °C, the boiler will function in
the heating mode at minimum power until it
reaches 35 °C.
● Anti-block function - the anti-block function
enables the pump and divertor valve actuator,
to be energised for short periods, when the
appliance has been inactive for more than 19hours.
expansion
vessel
AAV
valve motor
safety valve
Fig. 2
pump
diverter
automatic
by-pass
latent heat
collector
CH
return
CH
flow
flue
outlet
DHW heat
exchanger
intake
gas valve
DHW
outlet
air
pressure
switch
main heat
exchanger
CH NTC
sensor
main
burner
DHW tempera-
ture sensor
DHW non
return valve
flow switch
Domestic cold
water inlet
water
pressure
switch
DHW
1.3MODE OF OPERATION (Heating)
When there is a request for heat via the time clock
and/or any external control, the pump and fan are
started, the fan will then prove the air pressure
switch. At this point an ignition sequence is
enabled.
Ignition is sensed by the electronic circuitry to
ensure flame stability at the burner. Once successful ignition has been achieved, the electronic
circuitry increases the gas rate to 75% for a
period of 15 minutes. Thereafter, the boiler’s
output will either be increase to maximum or
modulate to suit the set requirement.
When the appliance reaches the desired temperature the burner will shut down and the boiler
will perform a three-minute anti-cycle (timer delay).
When the request for heat has been satisfied the
appliance pump and fan may continue to operate
to dissipate any residual heat within the appliance.
1.4MODE OF OPERATION (DHW)
When there is a request for DHW via a hot water
outlet or tap, the pump and fan are started, the fan
will then prove the air pressure switch. At this
point an ignition sequence is enabled.
Ignition is sensed by the electronic circuitry to
ensure flame stability at the burner. Once successful ignition has been achieved, the electronic
circuitry increases the gas rate to maximum or
will modulate output to stabilise the temperature.
In the event of the appliance exceeding the
desired temperature the burner will shut down
until the temperature drops.
When the request for DHW has been satisfied the
appliance pump and fan may continue to operate
to dissipate any residual heat within the appliance.
1.5SAFETY DEVICES
When the appliance is in use, safe operation is
ensured by:
● A water pressure switch that monitors system
water pressure and will de-activate the pump,
fan and burner should the system water pressure drop below the rated tolerance.
● A high limit thermostat that over-rides the tem-
perature control circuit to prevent or interrupt
the operation of the burner.
● An air pressure switch that requires the fan to
prove operation before the gas valve is energised.
● A pressure switch that interrupts the operation
of the appliance if the condense pipe becomes
blocked.
● A safety valve which releases excess pressure
from the primary circuit.
2
Supplied By www.heating spares.co Tel. 0161 620 6677
SECTION 2TECHNICAL DATA
2529
2.1 Central heating
Heat input (kW)25.029.034.8
Maximum heat output@ 80/60 °C (kW)24.328.133.8
Minimum heat output@ 80/60 °C (kW)14.214.213.9
Maximum heat output@ 50/30 °C (kW)25.930.236.1
Minimum heat output@ 50/30 °C (kW)14.914.814.4
Minimum working pressure0.5 bar0.5 bar0.5 bar
Maximum working pressure3.0 bar3.0 bar3.0 bar
Minimum flow rate350 l/h350 l/h350 l/h
2.2 Domestic hot water
Maximum output (kW)25.029.034.8
Minimum output (kW)9.59.99.9
Flow rate (35 °C rise)10.2 l/min11.9 l/min14.3 l/min
Maximum inlet pressure6.0 bar6.0 bar6.0 bar
Minimum inlet working pressure0.15 bar0.15 bar0.15 bar
Minimum flow rate2 l/min.2 l/min.2 l/min.
2.3 Gas pressures
Inlet pressure G2020.0 mbar20.0 mbar20.0 mbar
Maximum burner pressure9.40 mbar9.20 mbar10.1 mbar
Minimum burner pressure (central heating)3.50 mbar2.70 mbar2.10 mbar
Minimum burner pressure (domestic hot water)1.50 mbar1.20 mbar1.00 mbar
Gross rate (central haeting, max - min)2.64 - 1.59 m3/h3.07 - 1.59 m3/h3.68 - 1.59 m3/h
Injectors size12 x 1.35 mm14 x 1.35 mm16 x 1.35 mm
2.4 Expansion vessel
Capacity8 litres10 litres10 litres
Maximum system volume76 litres76 litres76 litres
Pre-charge pressure1.0 bar1.0 bar1.0 bar
2.5 Dimensions
Height780 mm780 mm780 mm
Width400 mm450 mm500 mm
Depth332 mm332 mm332 mm
Dry weight40 kg44 kg48 kg
2.6 Clearances
Sides12 mm12 mm12 mm
Top 150 mm from casing or 25 mm above flue elbow, whichever is applicable
Bottom150 mm150 mm150 mm
Front600 mm600 mm600 mm
2.7 Connections
Flow & return22 mm22 mm22 mm
Hot & cold water connections15 mm15 mm15 mm
Gas15 mm15 mm15 mm
Safety valve15 mm15 mm15 mm
Condense21 mm21 mm21 mm
2.8 Electrical
Voltage230V/~ 50Hz230V/~ 50Hz230V/~ 50Hz
Power consumption153 W153 W153 W
Internal fuse2 A2 A2 A
External fuse3 A3 A3 A
2.9 Flue details (concentric)
Maximum horizontal flue length (60/100mm)4.5 m4.0 m1.85 m
Maximum vertical flue length (60/100mm)5.5 m5.0 m2.85 m
Maximum horizontal flue length (80/125mm)11.0 m9.0 m6.8 m
Maximum vertical flue length (80/125mm)12.0 m10.0 m7.8 m
2.9 Flue details (twin pipe)
Maximum horizontal flue length (80mm + 80mm)20 m + 20 m12 m + 12 m10 m + 10 m
Maximum vertical flue length (80mm + 80mm)20 m + 20 m12 m + 12 m10 m + 10 m
2.10 Efficiency
SEDBUK86.9 Band “B”87.1 Band “B”86.65 Band “B”
35
Ref. Condition 15 °C , 1013,25 mbar, dry gas
NOTE: L.P.G. data refer to section 10
3
Supplied By www.heating spares.co Tel. 0161 620 6677
2.11PUMP DUTY
Fig. 3 shows the flow rate available - after allowing for pressure loss through the appliance - for system
requirements. When using this graph, apply only the pressure loss of the system. The graph is based on a
20 ºC temperature differential.
NOx98 ppm - 172 mg/kWh81 ppm - 142 mg/kWh85 ppm - 149 mg/kWh
CO (max-min)80 ppm - 80 ppm100 ppm - 60 ppm100 ppm - 120 ppm
CO2 (max-min)6.75 - 3.90 %7.05 - 3.40 %6.8 - 2.7 %
CO/CO2 ratio (max)0.001 to 10.001 to 10.001 to 1
CO/CO
ratio (min)0.002 to 10.001 to 10.004 to 1
2
SECTION 3GENERAL REQUIREMENTS (UK)
Fig. 4
KeyLocationMinimum distance
ABelow an opening (window, air-brick, etc.)300 mm
BAbove an opening (window, air-brick, etc.)300 mm
CTo the side of an opening (window, air-brick, etc.)300 mm
DBelow gutter, drain-pipe, etc.75 mm
EBelow eaves200 mm
FBelow balcony, car-port roof, etc.1200 mm
GTo the side of a soil/drain-pipe, etc.150 mm
HFrom internal/external corner or boundary300 mm
IAbove ground, roof, or balcony level300 mm
JFrom a surface or boundary facing the terminal1200 mm
KFrom a terminal facing a terminal1200 mm
LFrom an opening in the car-port into the building1200 mm
MVertically from a terminal on the same wall1500 mm
NHorizontally from a terminal on the same wall300 mm
PFrom a structure to the side of the vertical terminal500 mm
QFrom the top of the vertical terminal to the roof flashingAs determined by the fixed collar
of the vertical terminal
4
Supplied By www.heating spares.co Tel. 0161 620 6677
This appliance must be installed by a competent
person in accordance with the Gas Safety (Installation & Use) Regulations.
3.1RELATED DOCUMENTS
The installation of this boiler must be in accordance with the relevant requirements of the Gas
Safety (Installation & Use) Regulations, the local
building regulations, the current I.E.E. wiring
regulations, the bylaws of the local water undertaking, the Building Standards (Scotland) Regulation and Building Standards (Northern Ireland)
Regulations.
It should be in accordance also with any relevant
requirements of the local authority and the relevant recommendations of the following British
Standard Codes of Practice.
3.2LOCATION OF APPLIANCE
The appliance may be installed in any room or
internal space, although particular attention is
drawn to the requirements of the current I.E.E.
wiring regulations, and in Scotland, the electrical
provisions of the Building Regulations, with respect to the installation of the appliance in a room
or internal space containing a bath or shower.
3.3GAS SUPPLY
The gas meter – as supplied by the gas supplier
– must be checked to ensure that it is of adequate
size to deal with the maximum rated input of all
the appliances that it serves. Installation pipes
must be fitted in accordance with BS 6891.
Pipe work from the meter to the appliance must
be of adequate size. Pipes of a smaller size than
the appliance gas inlet connection must not be
used. The installation must be tested for soundness in accordance with BS6891.
If the gas supply serves more than one appliance,
it must be ensured that an adequate supply is
maintained to each appliance when they are in
use at the same time.
3.4FLUE SYSTEM
The terminal should be located where the dispersal of combustion products is not impeded and
with due regard for the damage and discoloration
that may occur to building products located nearby.
The terminal must not be located in a place where
it is likely to cause a nuisance (see fig. 4).
Water vapour will condense on leaving the terminal and the effect of such pluming must be
considered.
BS 5440PART 1FLUES
BS 5440PART 2FLUES & VENTILATION
BS 5449PART 1FORCED CIRCULATION HOT WATER SYSTEMS
BS 5546INSTALLATION OF GAS HOT WATER SUPPLIES FOR DOMESTIC PURPOSES
(2ND FAMILY GASES)
BS 6798INSTALLATION OF BOILERS OF RATED INPUT NOT EXCEEDING 60kW
BS 6891LOW PRESSURE INSTALLATION PIPES
BS 7074PART 1APPLICATION, SELECTION AND INSTALLATION OF EXPANSION VESSELS AND
ANCILLARY EQUIPMENT FOR SEALED WATER SYSTEMS
When an appliance is installed in a room or
internal space containing a bath or shower, the
appliance or any control pertaining to it must not
be within reach of a person using the bath or
shower.
The location chosen for the appliance must permit the provision of a safe and satisfactory flue
and termination. The location must also permit an
adequate air supply for combustion purposes
and an adequate space for servicing and air
circulation around the appliance. Where the installation of the appliance will be in an unusual
location special procedures may be necessary,
BS 6798 gives detailed guidance on this aspect.
A compartment used to enclose the appliance
must be designed and constructed specifically
for this purpose. An existing compartment/cupboard may be utilised provided that it is modified
to suit.
Details of essential features of compartment/
cupboard design including airing cupboard installations are given in BS 6798. This appliance is not
suitable for external installation.
3.5AIR SUPPLY
3.6WATER CIRCULATION
If installed less than 2m above a pavement or
platform to which people have access (including
balconies or flat roofs) the terminal must be
protected by a guard of durable material. The
guard must be fitted centrally over the terminal.
Refer to BS 5440 Part 1, when a terminal is sited
less than 1m below a plastic gutter, or less than
500mm below a painted surface, a suitable one
metre long heat shield should be fitted.
The following notes are intended for general
guidance only.
This appliance is a room-sealed, fan-flued boiler,
consequently it does not require a permanent air
vent for combustion air supply.
When installed in a cupboard or compartment,
ventilation for cooling purposes is also not required.
Detailed recommendations are given in BS 5449
Part 1 and BS 6798. The following notes are for
general guidance only.
5
Supplied By www.heating spares.co Tel. 0161 620 6677
3.6.1PIPEWORK
It is recommended that copper tubing to BS 2871
Part 1 is used in conjunction with soldered capillary joints.
Where possible pipes should have a gradient to
ensure air is carried naturally to air release points
and that water flows naturally to drain cocks.
Except where providing useful heat, pipes should
be insulated to avoid heat loss and in particular to
avoid the possibility of freezing. Particular attention should be paid to pipes passing through
ventilated areas such as under floors, loft space,
and void areas.
3.6.2AUTOMATIC BY-PASS
The appliance has a built-in automatic by-pass.
However it may be necessary to fit an external
bypass should the design of the heating system
require such. In any case, the design of the
system should be such that it prevents boiler
‘cycling’.
3.6.3DRAIN COCKS
These must be located in accessible positions to
facilitate draining of the appliance and all water
pipes connected to the appliance. The drain
cocks must be manufactured in accordance with
BS 2879.
3.6.7LOW PRESSURE SEALED SYSTEM
An alternative method of filling the system would
be from an independent make-up vessel or tank
mounted in a position at least 1 metre above the
highest point in the system and at least 5 metres
above the boiler (see fig. 5a).
The cold feed from the make-up vessel or tank
must be fitted with an approved non-return valve
and stopcock for isolation purposes. The feed
pipe should be connected to the return pipe as
close to the boiler as possible.
Make-up vessel
or tank
Automatic
air-vent
Non-return
valve
Stopcock
5.0 metres minimum
3.6.4AIR RELEASE POINTS
These must be positioned at the highest points in
the system where air is likely to be trapped. They
should be used to expel trapped air and allow
complete filling of the system.
3.6.5EXPANSION VESSEL
The appliance has an integral expansion vessel
to accommodate the increased volume of water
when the system is heated. It can accept up to 8
litres (25kW) or 10 litres (29 & 35kW) of expansion from within the system, generally this is
sufficient, however if the system has an unusually high water content, it may be necessary to
provide additional expansion capacity (see 6.19).
3.6.6FILLING POINT
An approved method for initial filling of the system
and replacing water lost during servicing etc. is
required (see fig. 5). This method of filling must
comply with the current Water Supply (Water
Fittings) Regulations 1999 and Water Bylaws
2000 (Scotland).
control valve
temporary
connection
control valve
Fig. 5a
Heating
return
3.6.8FREQUENT FILLING
Frequent filling or venting of the system may be
indicative of a leak. Care should be taken during
the installation of the appliance to ensure all
aspects of the system are capable of withstanding pressures up to at least 3 bar.
3.7ELECTRICAL SUPPLY
The appliance is supplied for operation on 230V
@ 50Hz electrical supply; it must be protected
with a 3-amp fuse. The method of connection to
the mains electricity supply must allow for complete isolation from the supply. The preferred
method is by using a double-pole switch with a
contact separation of at least 3mm. The switch
must only supply the appliance and its corresponding controls, i.e. time clock, room thermostat, etc. Alternatively an un-switched shuttered
socket with a fused 3-pin plug both complying
with BS 1363 is acceptable.
flow/return
pipe
Fig. 5
6
double check
valve
supply pipe
3.8SHOWERS
If the appliance is intended for use with a shower,
the shower must be thermostatically controlled
and be suitable for use with a combination boiler.
Supplied By www.heating spares.co Tel. 0161 620 6677
3.9MOUNTING ON A COMBUSTIBLE SURFACE
If the appliance is to be fitted on a wall of
combustible material, a sheet of fireproof material must protect the wall.
3.10TIMBER FRAMED BUILDING
If the appliance is to be fitted in a timber framed
building, it should be fitted in accordance with the
Institute of Gas Engineers publication (IGE/UP/
7) ‘Guide for Gas Installations in Timber Frame
Buildings’.
3.11INHIBITORS
Vokera recommend that an inhibitor - suitable for
use with copper and aluminium heat exchangers
- is used to protect the boiler and system from the
effects of corrosion and/or electrolytic action.
The inhibitor must be administered in strict accordance with the manufacturers instructions*.
*Water treatment of the complete heating system
- including the boiler - should be carried out in
accordance with BS 7593 and the Domestic
Water Treatment Association’s (DWTA) code of
practice.
Fig. 6a
30kW
25kW
35kW
Fig. 6
7
Supplied By www.heating spares.co Tel. 0161 620 6677
SECTION 3AGENERAL REQUIREMENTS (EIRE)
This appliance must be installed by a competent
person in accordance with and defined by, the
Standard Specification (Domestic Gas Installations) Declaration (I.S. 813).
3A.1RELATED DOCUMENTS
The installation of this boiler must be in accordance with the relevant requirements of the local
building regulations, the current ETCI National
Rules for Electrical Installations, and the bylaws
of the local water undertaking.
It should be in accordance also with any relevant
requirements of the local and/or district authority.
3A.2LOCATION OF APPLIANCE
The appliance may be installed in any room or
internal space, although particular attention is
drawn to the requirements of the current ETCI
National Rules for Electrical Installations, and
I.S. 813, Annex K.
When an appliance is installed in a room or
internal space containing a bath or shower, the
appliance or any control pertaining to it must not
be within reach of a person using the bath or
shower.
The location chosen for the appliance must permit the provision of a safe and satisfactory flue
and termination. The location must also permit an
adequate air supply for combustion purposes
and an adequate space for servicing and air
circulation around the appliance. Where the installation of the appliance will be in an unusual
location special procedures may be necessary,
refer to I.S. 813 for detailed guidance on this
aspect. A compartment used to enclose the
appliance must be designed and constructed
specifically for this purpose. An existing compartment/cupboard may be utilised provided that it is
modified to suit.
This appliance is not suitable for external installation.
3A.3GAS SUPPLY
The gas meter - as supplied by the gas supplier
- must be checked to ensure that it is of adequate
size to deal with the maximum rated input of all
the appliances that it serves. Installation pipes
must be fitted in accordance with I.S. 813.
Pipe work from the meter to the appliance must
be of adequate size. Pipes of a smaller size than
the appliance gas inlet connection must not be
used. The installation must be tested for soundness in accordance with I.S. 813.
If the gas supply serves more than one appliance,
it must be ensured that an adequate supply is
maintained to each appliance when they are in
use at the same time.
3A.4FLUE SYSTEM
The terminal should be located where the dispersal of combustion products is not impeded and
with due regard for the damage and discoloration
that may occur to building products located nearby.
The terminal must not be located in a place where
it is likely to cause a nuisance (refer to I.S. 813 for
guidance on permitted locations and minimum
distances of flue terminals).
Water vapour will condense on leaving the terminal; the effect of such pluming must be considered.
If installed less than 2m above a pavement or
platform to which people have access (including
balconies or flat roofs) the terminal must be
protected by a guard of durable material. The
guard must be fitted centrally over the terminal.
Refer to I.S. 813, when the terminal is 0.5 metres
(or less) below plastic guttering or 1 metre (or
less) below painted eaves.
3A.5AIR SUPPLY
The following notes are intended for general
guidance only. This appliance is a room-sealed,
fan-flued boiler, consequently it does not require
a permanent air vent for combustion air supply.
When installed in a cupboard or compartment,
ventilation for cooling purposes is also not required.
3A.6WATER CIRCULATION
Specific recommendations are given in I.S. 813.
The following notes are for general guidance only.
3A.6.1 PIPEWORK
It is recommended that copper tubing be used in
conjunction with soldered capillary joints.
Where possible pipes should have a gradient to
ensure air is carried naturally to air release points
and that water flows naturally to drain cocks.
Except where providing useful heat, pipes should
be insulated to avoid heat loss and in particular to
avoid the possibility of freezing. Particular attention should be paid to pipes passing through
ventilated areas such as under floors, loft space,
and void areas.
3A.6.2 AUTOMATIC BY-PASS
The appliance has a built-in automatic by-pass.
However it may be necessary to fit an external
bypass should the design of the heating system
require such. In any case, the design of the
system should be such that it prevents boiler
‘cycling’.
3A.6.3 DRAIN COCKS
These must be located in accessible positions to
facilitate draining of the appliance and all water
pipes connected to the appliance.
3A.6.4 AIR RELEASE POINTS
These must be positioned at the highest points in
the system where air is likely to be trapped. They
should be used to expel trapped air and allow
complete filling of the system.
3A.6.5 EXPANSION VESSEL
The appliance has an integral expansion vessel
to accommodate the increased volume of water
8
Supplied By www.heating spares.co Tel. 0161 620 6677
when the system is heated. It can accept up to 8
litres (25kW) or 10 litres (29 & 35kW) of expansion from within the system, generally this is
sufficient, however if the system has an unusually high water content, it may be necessary to
provide additional expansion capacity (see 6.19).
3A.6.6 FILLING POINT
A suitable method for initial filling of the system
and replacing water lost during servicing etc. is
required (see fig. 5). You should ensure this
method of filling complies with the local water
authority regulations.
3A.6.7 LOW PRESSURE SEALED SYSTEM
An alternative method of filling the system would
be from an independent make-up vessel or tank
mounted in a position at least 1 metre above the
highest point in the system and at least 5 metres
above the boiler (see fig. 5A).
The cold feed from the make-up vessel or tank
must be fitted with an approved non-return valve
and stopcock for isolation purposes. The feed
pipe should be connected to the return pipe as
close to the boiler as possible.
effects of corrosion and/or electrolytic action.
The inhibitor must be administered in strict accordance with the manufacturers’ instructions*.
*Water treatment of the complete heating system
- including the boiler - should be carried out in
accordance with I.S. 813 and the Domestic Water Treatment Association’s (DWTA) code of
practice.
3A.12 DECLARATION OF CONFORMITY
A Declaration of Conformity (as defined in I.S.
813) must be provided on completion of the installation.
A copy of the declaration must be given to the
responsible person and also to the gas supplier if
required.
3A.6.8 FREQUENT FILLING
Frequent filling or venting of the system may be
indicative of a leak. Care should be taken during
the installation of the appliance to ensure all
aspects of the system are capable of withstanding pressures up to at least 3 bar.
3A.7ELECTRICAL SUPPLY
The appliance is supplied for operation on 230V
@ 50Hz electrical supply; it must be protected
with a 3-amp fuse. The method of connection to
the mains electricity supply must allow for complete isolation from the supply. The preferred
method is by using a double-pole switch with a
contact separation of at least 3mm. The switch
must only supply the appliance and its corresponding controls, i.e. time clock, room thermostat, etc.
3A.8SHOWERS
If the appliance is intended for use with a shower,
the shower must be thermostatically controlled
and be suitable for use with a combination boiler.
3A.9MOUNTING ON A COMBUSTIBLESURFACE
If the appliance is to be fitted on a wall of
combustible material, a sheet of fireproof material must protect the wall.
3A.10 TIMBER FRAMED BUILDINGS
If the appliance is to be fitted in a timber framed
building, it should be fitted in accordance with I.S.
813 and local Building Regulations.
The Institute of Gas Engineers publication (IGE/
UP/7) ‘Guide for Gas Installations in Timber
Frame Buildings’ gives specific advice on this
type of installation.
3A.11 INHIBITORS
Vokera recommend that an inhibitor - suitable for
use with copper and aluminium heat exchangers
- is used to protect the boiler and system from the
9
Supplied By www.heating spares.co Tel. 0161 620 6677
SECTION 4INSTALLATION
4.1DELIVERY
Due to the weight of the appliance it may be
necessary for two people to lift and attach the
appliance to its mounting. The appliance is contained within a heavy-duty cardboard carton. Lay
the carton on the floor with the writing the correct
way up.
4.2CONTENTS
Contained within the carton is:
● the boiler
● the wall bracket
● appliance template
● an accessories pack containing appliance serv-
ice connections and washers
● the instruction pack containing the installation
& servicing instructions, user instructions,
Benchmark logbook, guarantee registration card
and a 3-amp fuse.
4.3UNPACKING
At the top of the carton pull both sides open - do
not use a knife - unfold the rest of the carton from
around the appliance, carefully remove all protective packaging from the appliance, and lay the
accessories etc. to one side. Protective gloves
should be used to lift the appliance, the appliance
back-frame should be used for lifting points.
Reduction for additional bends
BendReduction in maximum flue length for each bend
45º bend0.5 metre
90º bend1.0 metre
Horizontal flue terminals and accessories
Part No.DescriptionMin-Max Length
0225720Horizontal flue kit for use with 1000 mm
add. bends & extensions
0225755Telescopic extension350 mm – 500 mm
02257400.5m extension500 mm
02257451.0m extension1000 mm
02257502.0m extension2000 mm
022573045º bend (pair)N/A
022573590º bendN/A
0225760Wall bracket (5)N/A
Using the template provided, mark and drill a
115mm hole for the passage of the flue pipe. The
hole should be drilled level to ensure any condense fluid that forms will drain back to the boiler.
The fixing holes for the wall-mounting bracket
should now be drilled and plugged, an appropriate type and quantity of fixing should be used to
ensure that the bracket is mounted securely.
Once the bracket has been secured to the wall,
mount the appliance onto the bracket.
4.4PREPARATION FOR MOUNTING THE APPLIANCE
The appliance should be mounted on a smooth,
vertical, non-combustible surface, which must be
capable of supporting the full weight of the appliance. Care should be exercised when determining the position of the appliance with respect to
hidden obstructions such as pipes, cables, etc.
When the position of the appliance has been
decided - using the template supplied - carefully
mark the position of the wall- mounting bracket
(see fig. 6) and flue-hole (if applicable).
4.5FITTING THE FLUE
The top flue outlet permits both horizontal and
vertical flue applications to be considered, alternatively, the Vokera twin flue system can be
utilised if longer flue runs are required.
4.5.1CONCENTRIC HORIZONTAL FLUE
(For concentric vertical flue, see section 4.5.2).
(For twin flue applications, see section 4.5.3).
The appliance can be used with either the Vokera
condensing 60/100mm concentric flue system or
the optional 80/125mm concentric flue system.
NOTE
These instructions relate only to the Vokera condensing 60/100mm concentric flue system. For
specific details on the installation of the 80/125mm
concentric flue system please refer to the instructions supplied with the 80/125mm terminal.
The appliance flue outlet elbow can be rotated
through 360º on its vertical axis. In addition the
flue may be extended from the outlet elbow in the
horizontal plane (see 2.9). A reduction must also
be made to the maximum length (see table
below) when additional bends are used.
Push-fit connection
Terminal or
extension
outer
clamp
Fig. 7
Boiler
FITTING THE HORIZONTAL FLUE KIT
Carefully measure the distance from the centre of
the appliance flue outlet to the edge of the finished outside wall (dimension X). Add 45mm to
dimension X to give you Dimension Y (see fig 7A).
Measure dimension Y from the terminal end of
the concentric flue pipe and cut off the excess
ensuring any burrs are removed. Pass the concentric flue pipe through the previously drilled
hole. Fit the flue bend to the boiler flue outlet and
insert the concentric flue pipe into the flue bend
ensuring the correct seal is made.
Using the clamp, gasket, and screws supplied,
secure the flue bend to the appliance flue spigot.
The 60mm M & F adaptor (supplied with the flue
kit) should be discarded.
NOTE
Fit the internal (White) trim to the flue assembly
prior to connecting the flue pipe to the bend.
You must ensure that the entire flue system is
properly supported and connected.
Seal the flue assembly to the wall using cement
or a suitable alternative that will provide satisfactory weatherproofing. The exterior trim (Black)
can now be fitted.
10
Supplied By www.heating spares.co Tel. 0161 620 6677
Fig. 7a
“X” + 45 mm = “Y”
FLUE RESTRICTOR RING (horizontal flue)
To ensure maximum efficiency of the appliance,
it may be necessary to fit one of the supplied
flue restrictor rings to the appliance flue outlet
(see tables below).
25
Total flue lengthRestrictor required
Less than 1.2 metre82.5mm diameter
Less than 3.0 metres88mm diameter
Less than 4.5 metresnot required
29
Total flue lengthRestrictor required
Less than 2.0 metres84mm diameter
Less than 4.0 metresnot required
35
Total flue lengthRestrictor required
Less than 1.85 metres not required
4.5.1.1 EXTENDING THE FLUE
Connect the bend - supplied with the terminal kit
- to the top of the boiler using clamp (supplied)
see fig. 7. The additional bends & extensions have
push-fit connections, care should be taken to
ensure that the correct seal is made when assembling the flue system. Connect the required
number of flue extensions or bends (up to the
maximum equivalent flue length) to the flue terminal (see fig. 7 & 8).
The flue pipe should have a minimum 1-degree
rise from the boiler (17mm every 1.0 metre) to
ensure that any condense fluid drains back to the
appliance.
NOTE
When cutting an extension to the required length,
you must ensure that the excess is cut from the
plain end of the extension (see fig. 7 & 8). Remove any burrs, and check that all seals are located properly.
125 mm
You must ensure that the entire flue system is
properly supported and connected.
Seal the flue assembly to the wall using cement
or a suitable alternative that will provide satisf actory weatherproofing.
4.5.2CONCENTRIC VERTICAL FLUE
The appliance can be used with either the Vokera
condensing 60/100mm concentric flue system or
the optional 80/125mm concentric flue system.
NOTE
These instructions relate only to the Vokera condensing 60/100mm concentric flue system. For
specific details on the installation of the 80/125mm
concentric flue system please refer to the instructions supplied with the 80/125mm terminal.
The vertical flue terminal can be connected directly to the appliance flue outlet. Alternatively,
an extension or bend can be connected to the
appliance flue outlet if desired (see 4.4.2), however if additional bends are fitted, a reduction
must be made to the maximum flue length (see
table below).
Reduction for bends
BendReduction in maximum flue length for each bend
0225755350-500 telescopic extension 350 mm – 500 mm
02257400.5m extension500 mm
02257451.0m extension1000 mm
02257502.0m extension2000 mm
022573045º bend (pair)N/A
022573590º bendN/A
0225760Wall bracket (4)N/A
Using the dimensions given in fig. 9 as a reference, mark and cut a 107mm hole in the ceiling
and/or roof.
Fig. 9
Fig. 8
145
11
Supplied By www.heating spares.co Tel. 0161 620 6677
Fit the appropriate flashing plate to the roof and
insert the vertical flue terminal through the flashing plate from the outside, ensuring that the collar
on the flue terminal fits over the flashing.
The fixing holes for the wall-mounting bracket
should now be drilled and plugged, an appropriate type and quantity of fixing should be used to
ensure that the bracket is mounted securely.
Once the bracket has been secured to the wall,
mount the appliance onto the bracket.
IMPORTANT
The vertical flue terminal is 1.0 metre in length
and cannot be cut; therefore it may be necessary
to adjust the height of the appliance to suit or use
a suitable extension.
Connect the vertical flue assembly to the boiler flue
spigot using the 60mm & 100mm clips, gaskets &
screws (supplied), ensuring the correct seal is
made. The flue support bracket (supplied with the
vertical flue kit) can now be fitted.
If the vertical flue requires extension/s or additional bend/s, connect the required number of
flue extensions or bends (up to the maximum
equivalent flue length) between the boiler and
vertical flue assembly (see fig. 8).
Ensure that any horizontal sections of the flue
system have a minimum 1º fall back to the boiler
(17mm per 1000mm).
NOTE
When cutting an extension to the required length,
you must ensure that the excess is cut from the
plain end of the extension (see fig. 8). Remove
any burrs, and check that any seals are located
properly.
You must ensure that the entire flue system is
properly supported and connected.
FLUE RESTRICTOR RING (vertical flue)
To ensure maximum efficiency of the appliance,
it may be necessary to fit one of the supplied
flue restrictor rings to the appliance flue outlet
(see tables below).
25
Total flue lengthRestrictor required
Less than 2.0 metre82.5mm diameter
Less than 4.0 metres88mm diameter
Less than 5.5 metresnot required
29
Total flue lengthRestrictor required
Less than 2.8 metres84mm diameter
Less than 5.0 metresnot required
35
Total flue lengthRestrictor required
Less than 2.7 metresnot required
4.5.3TWIN FLUE SYSTEM
The Vokera twin flue system enables greater flue
distances to be achieved (see 4.4.2) than that of
a concentric flue system. It can be used for
horizontal or vertical applications, however the
twin flue system must be converted to the dedicated concentric flue kit for termination. It is
essential that the installation of the twin flue
system be carried out in strict accordance with
these instructions.
GUIDANCE NOTES ON TWIN FLUE INSTALLATION
● The flue must have a fall back of 1º back to the
appliance to allow any condensate that may form
in the flue system to drain via the condensate
drain. Consideration must also be given to the
fact that there is the possibility of a small amount
of condensate dripping from the terminal.
● Ensure that the entire flue system is adequately
supported, use at least one bracket for each
extension.
● The entire flue system must be adequately
insulated to maintain heat within the flue system thereby reducing the possibility of condensate production.
● As the exhaust outlet pipe can reach very high
temperatures it must be protected to prevent
persons touching the hot surface.
● The condensate drainpipe must be connected
in accordance with local building regulations
that are in force.
Reduction for bends
BendReduction in maximum flue length for each bend
45º bend1.0 metre
90º bend1.0 metre
Twin flue accessories
Part No.DescriptionMin-Max Length
0225805Horizontal flue terminal1.0 metre
0225810Vertical flue terminal1.0 metre
430T win adapter kitN/A
0225770Pitched roof flashing plateN/A
0225765Flat roof flashing plateN/A
0225815Condensate drain kitN/A
02258200.25 m extension (pair)250 mm
02258250.5 m extension (pair)500 mm
02258301.0 m extension (pair)1000 mm
02258352.0 m extension (pair)2000 mm
022584045º bend (pair)N/A
022584590º bend (pair)N/A
0225850Twin br acket (5)N/A
0225855Single bracket (5)N/A
MOUNTING THE BOILER
The fixing holes for the wall-mounting bracket
should now be drilled and plugged, an appropriate type and quantity of fixing should be used to
ensure that the bracket is mounted securely.
Once the bracket has been secured to the wall,
mount the appliance onto the bracket.
FLUE RESTRICTOR RING (vertical flue)
To ensure maximum efficiency of the appliance,
it may be necessary to fit one of the flue restrictor
rings (supplied with the twin adaptor kit) to the
appliance flue outlet (see tables below).
25
Total flue lengthRestrictor required
Less than 7.0 metre40mm diameter
Less than 13.5 metres 45mm diameter
Less than 19.5 metres not required
29
Total flue lengthRestrictor required
Less than 5.0 metres45mm diameter
Less than 12.0 metres not required
12
Supplied By www.heating spares.co Tel. 0161 620 6677
35
Total flue lengthRestrictor required
Less than 5.0 metres50mm diameter
Less than 10.0 metres not required
4.5.3.1 INSTALLATION OF TWIN ADAPTOR KIT (fig.
10 & 11)
● Insert the exhaust connection manifold (A)
onto the appliance flue outlet.
● Remove the blanking plate (located to the right
of the appliance flue outlet) and – using the
same screws – install the air inlet plate (B).
● Using the hole in the exhaust connection mani-
fold as a guide, drill a 3mm hole in the appliance
flue spigot and secure the exhaust manifold
connection to the flue spigot using the screw
provided (C).
● Using the two holes in the air inlet plate as a
guide, drill a 3mm hole in each and secure the
air inlet pipe/bend using the screws provided.
● The twin flue pipes extensions and accessories
can now be installed by pushing together (the
plain end of each extension or bend should be
pushed approximately 50mm into the female
socket of the previous piece).
Fig. 12
Fig. 10
A
Fig. 11
C
B
4.5.3.2 HORIZONTAL TERMINATION (see fig. 12)
The twin flue system must be converted to the
dedicated concentric flue kit for termination.
● The horizontal terminal is supplied with a built-
in converter box and cannot be shortened.
● A 130mm hole is required for the passage of
the concentric terminal through the wall.
Depending on site conditions it may be preferable to install the terminal assembly prior to fitting the twin flue pipes.
Mark and drill a 130mm hole for the passage of the
horizontal flue terminal, ensuring that there is a minimum 1º fall back to the boiler (17mm per 1000mm).
Insert the terminal assembly into the flue hole.
Push-fit the twin flue pipes onto the concentric
to twin converter box ensuring that the exhaust
pipe connects to the exhaust connection on the
concentric to twin converter.
If necessary cut the plain ends (male) of the twin
flue pipes to allow connection to the concentric to
twin converter.
Fig. 13
NOTE
Before cutting twin flue pipes ensure allowances
have been made for connection onto the previous
piece and onto the concentric to twin converter.
The last twin flue pipes must be pushed 50mm onto
the male spigots of the concentric to twin converter.
NOTE
You must ensure that the entire flue system is
properly supported and connected.
Seal the flue terminal assembly to the wall using
cement or a suitable alternative that will provide
satisfactory weatherproofing. The interior and
exterior trim can now be fitted.
4.5.3.3 VERTICAL TERMINATION (see fig. 13)
The twin flue system must be converted to the
dedicated concentric flue kit for termination.
● The vertical terminal is supplied with a built-in
converter box and cannot be shortened.
● A 130mm hole is required for the passage of
the concentric terminal through the ceiling and/
or roof.
13
Loading...
+ 33 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.