Vokèra is a licensed member of the Benchmark scheme
which aims to improve the standards of installation and
commissioning of domestic hot water systems in the UK.
Contents
Design principles and operating sequencePage
1.1Principle components2
1.2Central heating mode2
1.3Hot water mode2
1.4Safety devices2
1.5Frost protection2
Technical dataPage
2.1Central heating3
2.2Domestic hot water3
2.3Gas pressure3
2.4Expansion vessel3
2.5Dimensions3
2.6Clearances3
2.7Connections3
2.8Electrical3
2.9Flue details3
2.10Efficiency3
2.11Pump duty4
General requirements (UK)Page
3.1Related documents5
3.2Location of appliance5
3.3Gas supply5
3.4Flue system5
3.5Air supply5
3.6Water circulation5
3.6.1Pipework6
3.6.2Automatic by-pass6
3.6.3Drain cocks6
3.6.4Air release points6
3.6.5Expansion vessel6
3.6.6Filling point6
3.6.7Low pressure sealed system6
3.6.8Frequent filling6
3.7Electrical supply6
3.8Showers6
3.9Mounting on a combustible surface7
3.10Timber framed building7
3.11Inhibitors7
General requirements (EIRE)Page
3.A1Related documents7
3.A2Location of appliance7
3.A3Gas supply7
3.A4Flue system7
3.A5Air supply8
3.A6Water circulation8
3.A6.1 Pipework8
3.A6.2 Automatic by-pass8
3.A6.3 Drain cocks8
3.A6.4 Air release points8
3.A6.5 Expansion vessel8
3.A6.6 Filling point8
3.A6.7 Low pressure sealed system8
3.A6.8 Frequent filling8
3.A7Electrical supply8
3.A8Showers8
3.A9Mounting on a combustible surface8
3.A10 Timber framed building8
3.A11 Inhibitors8
3.A12 Declaration of conformity8
InstallationPage
4.1Delivery9
4.2Contents9
4.3Unpacking9
4.4Preparation for mounting the appliance9
4.4.1Important9
4.4.2Flue restrictor ring9
4.5Fitting the flue9
4.5.1Concentric horizontal flue9
4.5.2Concentric vertical flue11
4.5.3Twin flue system11
4.6Connecting the gas and water13
4.6.1Gas13
4.6.2Flow and return14
4.6.3Safety valve14
4.6.4Cold water inlet14
4.6.5Hot water outlet14
4.7Electrical connections14
4.7.1Casing removal14
4.7.2Electrical connection14
4.7.3Connecting the mains (230V) input15
Commissioning Page
5.1Gas supply installation16
5.2The heating system16
5.3Initial filling of the system16
5.4Initial flushing16
5.5Filling the hot water system16
5.6Pre-operation checks16
5.7Initial lighting16
5.8Checking burner pressures16
5.9Final flushing of the heating system17
5.9.1Inhibtors17
5.10Setting the flow temperature17
5.11Setting the system design pressure17
5.12Regulating the central heating system17
5.13Regulating the domestic hot water17
5.14Final checks17
5.15Instructing the user17
Servicing instructionsPage
6.1General18
6.2Routine annual servicing18
6.3Replacement of components18
6.4De-scaling main heat exchanger18
6.5Component removal procedure18
6.6Pump head18
6.7Safety valve18
6.8Automatic air release valve19
6.9Water pressure switch19
6.10Domestic water flow switch19
6.11Pressure gauge19
6.12Primary and secondary thermistors19
6.13High limit thermostat19
6.14PCB20
6.15Integral time switch20
6.16Gas valve20
6.17Burner, injectors and spark/sense electrode20
6.18Flue fan21
6.19Heat exchanger21
6.20Air pressure switch21
6.21Expansion vessel21
6.22Expansion vessel (removal)21
Checks, adjustments and fault findingpage
7.1Checking appliance operation22
7.2At rest mode22
7.3Hot water mode22
7.4Heating mode22
7.5Frost protection mode22
7.6Burner pressure settings22
7.6.1Setting the maximum DHW gas pressure23
7.6.2Setting the minimum DHW gas pressure23
7.6.3Setting the max & min CH burner pressures23
7.7Combustion analysis test23
7.8Checking the expansion vessel23
7.9Electro-mechanical faults23
7.10Possible installation faults24
7.11Electrical checks24
7.11.1 Earth continuity test24
7.11.2 Short circuit test24
7.11.3 Polarity check24
7.11.4 Reversed polarity or supply fault24
7.11.5 Resistance to earth check24
7.11.6 Fuses24
7.12Fault finding24-31
Wiring diagramsPage
8.1Connection of a room thermostat32
8.2Connection of an external time clock32
Functional flow diagram33-34
Exploded diagramsPage
Table 135
Table 236
Table 337
Table 438
Table 539
L.P.G. instructionsPage
10.1Technical data40
10.2Related documents40
10.3Gas supply40
10.4Gas supply installation40
10.5Burner pressures40
10.5.1 Setting the maximum DHW gas pressure40
10.5.2 Setting the minimum DHW gas pressure40
10.5.3 Setting the max & min CH burner pressures40
REAR FLUEPage
11.1Fitting the flue41
INTRODUCTION
The Vokera Compact range of appliances are combined
central heating and domestic hot water boilers, which –
by design – incorporates full sequence electronic ignition,
circulating pump, expansion vessel, safety valve,
pressure gauge, automatic by-pass, and mechanical time
clock.
Compact is produced as a room sealed appliance, suitable
for wall mounting applications only. Compact is provided
1
2
25
24
23
22
21
20
19
18
150
85
35
95
150
3
4
5
6
7
8
9
10
11
with a fan powered flue outlet with an annular co-axial
combustion air intake that can be rotated – horizontally –
through 360 degrees for various horizontal or vertical
applications, and can also be converted for use with a
rear flue outlet. Compact can also be used with the
Vokera twin flue system.
This appliance is designed primarily for use with sealed
systems; consequently it is not intended for use on an
open vented system.
Fig.1 General Layout
1Flue Analysis Test Point
2Pressure Tube Negative
3Fan Assembly
4Heat Exchanger
5Secondary thermistor
6Combustion chamber
7Burner
8Expansion vessel
9Water pressure switch
10 Domestic Hot Water Flow Switch
11 Gas Valve
12 Timeclock
13 CH position
14 Fault indicator led
15 Mode selector switch
16 DHW position
17 Pressure gauge
18 Safety valve
19 Pump
20 Auto air vent
21 Electrode
22 High limit thermistor
23 Primary thermistor
24 Air chamber (with cover removed)
25 Air pressure switch
26 Auto by pass (fig. 2)
27 Water flow restrictor (fig. 2)
Fig. 1
Compact
1
SECTION 1DESIGN PRINCIPLES AND OPERATING SEQUENCE
1.1PRINCIPLE COMPONENTS
● A fully integrated, electronic control board fea-
turing mode selection switch, full sequenceelectronic ignition, temperature control system,
and appliance status indicator.
● A BI-thermal gas to water heat exchanger.
● A multi-functional gas valve.
● Two-stage, primary water pressure switch.
Integral pump, expansion vessel, pressure relief valve, pressure gauge, domestic water flow
switch, fan, differential air pressure switch, and
time clock.
MODES OF OPERATION
1.2CENTRAL HEATING MODE
When there is a request for central heating via the
time-clock and/or any external controls, the pump
and fan are started, the fan proves the differential
air pressure switch which in-turn, allows an ignition
sequence to begin.
Ignition is sensed by the electronic circuitry to
ensure flame stability at the burner. Once successful ignition has been achieved the appliance
operates al 75% of maximum for a fifteen-minute
period, and thereafter the appliance operates on
maximum output until the desired temperature
setting is reached.
4
23
8
1.3HOT WATER MODE
1.4SAFETY DEVICES
27
5
Once the desired temperature is reached, the
burner will modulate to maintain that temperature, however should the temperature within the
appliance continue to rise, the burner will shut
down and the boiler will perform a three-minute
anti-cycle (timer delay).
When there is a demand for domestic hot water
the domestic hot water flow switch is proved by
the flow of water through the appliance, this
allows the fan to run, the fan proves the differential air pressure switch which in-turn, allows an
ignition sequence to begin.
Ignition is sensed by the electronic circuitry to
ensure flame stability at the burner. Once
successful ignition has been achieved the appliance will modulate burner gas pressure to maintain the desired water temperature, should the
temperature of the domestic hot water exceed
the temperature setting by 5 ºC the burner will
shut down until the water temperature drops
below the required setting.
In both central heating and domestic hot water
modes, safe operation is ensured by.
● A water pressure switch that monitors the sys-
tem pressure and will deactivate the pump and
prevent burner ignition should the pressure or
primary flow rate fall below the rated tolerance.
● Differential air pressure switch that checks the
correct operation of the fan and flue thereby
preventing or interrupting burner operation.
● A high limit thermostat that overrides the con-
trol circuit to prevent or interrupt burner ignition.
● A safety valve which releases excess pressure
from the primary circuit.
20
19
18
26
10
1.5FROST PROTECTION
9
The appliance has built-in frost protection that
allows the pump to operate if the appliance temperature drops to 7 ºC, should the temperature
continue to drop the burner will light until the
primary circuit temperature exceeds 30 ºC.
hw
returnflow
outlet
Fig. 2
2
cold
inlet
Compact
SECTION 2TECHNICAL DATA
Compact 24Compact 28
2.1 Central heating
Heat input (kW)26.331.0
Heat output (maximum) kW24.028.0
Heat output (minimum) kW9.410.5
Minimum working pressure0,5 bar0,5 bar
Maximum working pressure3.0 bar3.0 bar
Minimum flow rate350 l/h350 l/h
2.2 Domestic hot water
Heat input (kW)26.331.0
Heat output (maximum) kW24.028.0
Heat output (minimum) kW8.28.7
Flow rate (35 °C rise)9.8 l/min11.5 l/min
Maximum inlet pressure6.0 bar6.0 bar
Minimum inlet working pressure0.15 bar0.15 bar
Minimum flow rate2 l/min.2 l/min.
2.3 Gas pressures
Inlet pressure G2020.0 mbar20.0 mbar
Maximum burner pressure10.1 mbar10.2 mbar
Minimum burner pressure (central heating)1.9 mbar1.9 mbar
Minimum burner pressure (domestic hot water)1.5 mbar1.3 mbar
Gross rate (maximum)2.78 m3/h3.28 m3/h
Injectors size12 x 1.35 mm14 x 1.35 mm
2.4 Expansion vessel
Capacity8 litres8 litres
Maximum system volume76 litres76 litres
Pre-charge pressure1.0 bar1.0 bar
2.5 Dimensions
Height740 mm740 mm
Width400 mm450 mm
Depth328 mm328 mm
Dry weight32 kg34 kg
2.6 Clearances
Left side50 mm50 mm
Right side12 mm12 mm
Top150 mm from casing or 25 mm above flue elbow, whichever is applicable
Bottom150 mm150 mm
Front600 mm600 mm
2.7 Connections
Flow & return22 mm22 mm
Hot & cold water connections15 mm15 mm
Gas15 mm15 mm
Safety valve15 mm15 mm
2.8 Electrical
Voltage230V/~ 50hz230V/~ 50hz
Power consumption125 W125 W
Internal fuse2 A2 A
PCB fuse2 AF2 AF
External fuse3 A3 A
2.9 Flue details
Maximum horizontal flue length (concentric)4.25 m3.4 m
Maximum vertical flue length (concentric)5 m4.2 m
Maximum twin flue length (horizontal or vertical)14 m + 14 m14 m + 14 m
Maximum rear flue length (see section 11)1.0 m1.0 m
2.10 Efficiency
SEDBUKBand “D”Band “D”
Ref. Condition 15 °C , 1013,25 mbar, dry gas
NOTE: L.P .G. data refer to section 10
Compact
3
2.11PUMP DUTY
Fig. 3 shows the flow rate available – after
allowing for pressure loss through the
appliance – against system pressure loss.
When using this graph apply only the
pressure loss of the system. The graph is
based on a 20 ºC temperature differential.
BAbove an opening (window, air-brik, etc.)300 mm
CTo the side of an opening (window, air-brik, etc.)300 mm
DBelow gutter, drain-pipe, etc.75 mm
EBelow eaves200 mm
FBelow balcony, car-port roof, etc.200 mm
GTo the side of a soil/drain-pipe, etc.150 mm
HFrom internal/external corner or boundary300 mm
IAbove ground, roof, or balcony level300 mm
JFrom a surface or boundary facing the terminal600 mm
KFrom a terminal facing a terminal1200 mm
LFrom an opening in the car-port into the building1200 mm
MVertically from a terminal on the same wall1500 mm
NHorizontally from a terminal on the same wall300 mm
PFrom a structure to the side of the vertical terminal300 mm
QFrom the top of the vertical terminal to the roof flashingAs determined by the fixed collar
Fig. 4
4
of the vertical terminal
Compact
This appliance must be installed by a competent
person in accordance with the Gas Safety
(Installation & Use) Regulations.
3.1RELATED DOCUMENTS
The installation of this boiler must be in accordance
with the relevant requirements of the Gas Safety
(Installation & Use) Regulations, the local building
regulations, the current I.E.E. wiring regulations,
the bylaws of the local water undertaking, the
Building Standards (Scotland) Regulation, and
Building Standards (Northern Ireland)
Regulations.
It should be in accordance also with any relevant
requirements of the local authority and the relevant
recommendations of the following British Standard
Codes of Practice.
3.2LOCATION OF APPLIANCE
The appliance may be installed in any room or
internal space, although particular attention is
drawn to the requirements of the current I.E.E.
wiring regulations, and in Scotland, the electrical
provisions of the Building Regulations, with
respect to the installation of the appliance in a
room or internal space containing a bath or shower.
3.3GAS SUPPLY
The gas meter – as supplied by the gas supplier
– must be checked to ensure that it is of adequate
size to deal with the maximum rated input of all
the appliances that it serves. Installation pipes
must be fitted in accordance with BS 6891.
Pipe work from the meter to the appliance must
be of adequate size. Pipes of a smaller size than
the appliance gas inlet connection must not be
used. The installation must be tested for
soundness in accordance with BS6891.
If the gas supply serves more than one appliance,
it must be ensured that an adequate supply is
maintained to each appliance when they are in
use at the same time.
3.4FLUE SYSTEM
The terminal should be located where the dispersal
of combustion products is not impeded and with
due regard for the damage and discoloration that
may occur to building products located nearby.
The terminal must not be located in a place where
it is likely to cause a nuisance (fig. 4).
In cold and/or humid weather, water vapour may
condense on leaving the terminal; the effect of
such pluming must be considered.
BS 5440PART 1FLUES
BS 5440PART 2FLUES AND VENTILATION
BS 5449PART 1FORCED CIRCULATION HOT WATER SYSTEMS
BS5546INSTALLATION OF GAS HOT WATER SUPPLIES FOR DOMESTIC PURPOSES
(2ND FAMILY GASES)
BS 6798BOILERS OF RATED INPUT NOT EXCEEDING 60kW
BS 6891LOW PRESSURE INSTALLATION PIPES
BS 7074PART 1APPLICATION, SELECTION, AND INSTALLATION OF EXPANSION VESSELS AND
ANCILLARY EQUIPMENT FOR SEALED WATER SYSTEMS
When an appliance is installed in a room or
internal space containing a bath or shower, the
appliance or any control pertaining to it must not
be within reach of a person using the bath or
shower.
The location chosen for the appliance must permit
the provision of a safe and satisfactory flue and
termination. The location must also permit an
adequate air supply for combustion purposes
and an adequate space for servicing and air
circulation around the appliance. Where the
installation of the appliance will be in an unusual
location special procedures may be necessary,
BS 6798 gives detailed guidance on this aspect.
A compartment used to enclose the appliance
must be designed and constructed specifically
for this purpose. An existing compartment/
cupboard may be utilised provided that it is
modified to suit.
Details of essential features of compartment/
cupboard design including airing cupboard
installations are given in BS 6798. This appliance
is not suitable for external installation.
3.5AIR SUPPLY
3.6WATER CIRCULATION
If installed less than 2 m above a pavement or
platform to which people have access (including
balconies or flat roofs) the terminal must be
protected by a guard of durable material. The
guard must be fitted centrally over the terminal.
Refer to BS 5440 Part 1, when the terminal is 0.5
metres (or less) below plastic guttering or 1 metre
(or less) below painted eaves.
The following notes are intended for general
guidance only.
This appliance is a room-sealed, fan-flued boiler,
consequently it does not require a permanent air
vent for combustion air supply.
When installed in a cupboard or compartment,
ventilation for cooling purposes is also not
required.
Detailed recommendations are given in BS 5449
Part 1 and BS 6798. The following notes are for
general guidance only.
Compact
5
3.6.1PIPEWORK
It is recommended that copper tubing to BS 2871
Part 1 is used in conjunction with soldered capillary
joints.
Where possible pipes should have a gradient to
ensure air is carried naturally to air release points
and that water flows naturally to drain cocks.
Except where providing useful heat, pipes should
be insulated to avoid heat loss and in particular to
avoid the possibility of freezing. Particular attention
should be paid to pipes passing through ventilated
areas such as under floors, loft space, and void
areas.
3.6.2AUTOMATIC BY-PASS
The appliance has a built-in automatic by-pass,
consequently there is no requirement for an
external by-pass, however the design of the
system should be such that it prevents boiler
‘cycling’.
3.6.7LOW PRESSURE SEALED SYSTEM
An alternative method of filling the system would
be from an independent make-up vessel or tank
mounted in a position at least 1 metre above the
highest point in the system and at least 5 metres
above the boiler (fig. 5a).
The cold feed from the make-up vessel or tank
must be fitted with an approved non-return valve
and stopcock for isolation purposes. The feed
pipe should be connected to the return pipe as
close to the boiler as possible.
Make-up vessel
or tank
Automatic
air-vent
3.6.3DRAIN COCKS
These must be located in accessible positions to
facilitate draining of the appliance and all water
pipes connected to the appliance. The drain
cocks must be manufactured in accordance with
BS 2879.
3.6.4AIR RELEASE POINTS
These must be positioned at the highest points in
the system where air is likely to be trapped. They
should be used to expel trapped air and allow
complete filling of the system.
3.6.5EXPANSION VESSEL
The appliance has an integral expansion vessel
to accommodate the increased volume of water
when the system is heated. It can accept up to 8
litres of expansion from within the system,
generally this is sufficient, however if the system
has an unusually high water content, it may be
necessary to provide additional expansion
capacity (see section 6.19).
3.6.6FILLING POINT
A method for initial filling of the system and
replacing water lost during servicing etc. must be
provided. This method of filling must comply with
the current Water Supply (Water Fittings)
Regulations 1999 and Water Bylaws 2000
(Scotland). Fig. 5 shows an accepted method.
control valve
temporary
connection
control valve
Stopcock
Fig. 5a
Non-return
valve
Heating
return
3.6.8FREQUENT FILLING
Frequent filling or venting of the system may be
indicative of a leak. Care should be taken during
the installation of the appliance to ensure all
aspects of the system are capable of withstanding
pressures up to at least 3 bar.
3.7ELECTRICAL SUPPLY
The appliance is supplied for operation on 230V
@ 50Hz electrical supply; it must be protected
with a 3-amp fuse. The method of connection to
the mains electricity supply must allow for
complete isolation from the supply. The preferred
method is by using a double-pole switch with a
contact separation of at least 3 mm. The switch
must only supply the appliance and its
corresponding controls, i.e. time clock, room
thermostat, etc. Alternatively an un-switched
shuttered socket with a fused 3-pin plug both
complying with BS 1363 is acceptable.
5.0 metres minimum
Fig. 5
6
flow/return
pipe
double check
valve
supply pipe
3.8SHOWERS
If the appliance is intended for use with a shower,
the shower must be thermostatically controlled
and be suitable for use with a combination boiler.
Compact
3.9MOUNTING ON A COMBUSTIBLE SURFACE
If the appliance is to be fitted on a wall of
combustible material, a sheet of fireproof material
must protect the wall.
3.10TIMBER FRAMED BUILDING
If the appliance is to be fitted in a timber framed
building, it should be fitted in accordance with the
Institute of Gas Engineers publication (IGE/UP/
7) ‘Guide for Gas Installations in Timber Frame
Buildings’.
3.11INHIBITORS
Vokera recommend that a neutral inhibitor is
used to protect the heating system from the
effects of corrosion and/or electrolytic action.
The inhibitor must be administered in strict
accordance with the manufacturers* instructions.
*Fernox and Sentinel manufacture products that
have proved suitable for use with Vokera
appliances. Vokera Ltd. cannot comment on the
suitability of any other such product with our
appliances.
Fig. 6
85
150
35
95
150
SECTION 3AGENERAL REQUIREMENTS (EIRE)
This appliance must be installed by a competent
person in accordance with and defined by, the
Standard Specification (Domestic Gas
Installations) Declaration (I.S. 813).
3A.1RELATED DOCUMENTS
The installation of this boiler must be in accordance
with the relevant requirements of the local building
regulations, the current ETCI National Rules for
Electrical Installations, and the bylaws of the
local water undertaking.
It should be in accordance also with any relevant
requirements of the local and/or district authority.
3A.2LOCATION OF APPLIANCE
The appliance may be installed in any room or
internal space, although particular attention is
drawn to the requirements of the current ETCI
National Rules for Electrical Installations, and
I.S. 813, Annex K.
When an appliance is installed in a room or internal
space containing a bath or shower, the appliance
or any control pertaining to it must not be within
reach of a person using the bath or shower.
The location chosen for the appliance must permit
the provision of a safe and satisfactory flue and
termination. The location must also permit an
adequate air supply for combustion purposes
and an adequate space for servicing and air
circulation around the appliance. Where the
installation of the appliance will be in an unusual
location special procedures may be necessary,
refer to I.S. 813 for detailed guidance on this
aspect. A compartment used to enclose the
appliance must be designed and constructed
specifically for this purpose. An existing
compartment/cupboard may be utilised provided
that it is modified to suit.
3A.3GAS SUPPLY
3A.4FLUE SYSTEM
This appliance is not suitable for external
installation.
The gas meter – as supplied by the gas supplier
– must be checked to ensure that it is of adequate
size to deal with the maximum rated input of all
the appliances that it serves. Installation pipes
must be fitted in accordance with I.S. 813.
Pipe work from the meter to the appliance must
be of adequate size. Pipes of a smaller size than
the appliance gas inlet connection must not be
used. The installation must be tested for
soundness in accordance with I.S. 813.
If the gas supply serves more than one appliance,
it must be ensured that an adequate supply is
maintained to each appliance when they are in
use at the same time.
The terminal should be located where the dispersal
of combustion products is not impeded and with
due regard for the damage and discoloration that
may occur to building products located nearby.
The terminal must not be located in a place where
it is likely to cause a nuisance (see I.S. 813).
In cold and/or humid weather, water vapour may
condense on leaving the terminal; the effect of
such pluming must be considered.
If installed less than 2 m above a pavement or
platform to which people have access (including
balconies or flat roofs) the terminal must be
protected by a guard of durable material. The
guard must be fitted centrally over the terminal.
Refer to I.S. 813, when the terminal is 0.5 metres
(or less) below plastic guttering or 1 metre (or
less) below painted eaves.
Compact
7
3A.5AIR SUPPLY
The following notes are intended for general
guidance only. This appliance is a room-sealed,
fan-flued boiler, consequently it does not require
a permanent air vent for combustion air supply.
When installed in a cupboard or compartment,
ventilation for cooling purposes is also not
required.
3A.6WATER CIRCULATION
Specific recommendations are given in I.S. 813.
The following notes are for general guidance
only.
3A.6.1 PIPEWORK
It is recommended that copper tubing be used in
conjunction with soldered capillary joints.
Where possible pipes should have a gradient to
ensure air is carried naturally to air release points
and that water flows naturally to drain cocks.
Except where providing useful heat, pipes should
be insulated to avoid heat loss and in particular to
avoid the possibility of freezing. Particular attention
should be paid to pipes passing through ventilated
areas such as under floors, loft space, and void
areas.
3A.6.2 AUTOMATIC BY-PASS
The appliance has a built-in automatic by-pass,
consequently there is no requirement for an
external by-pass, however the design of the
system should be such that it prevents boiler
‘cycling’.
3A.6.3 DRAIN COCKS
These must be located in accessible positions to
facilitate draining of the appliance and all water
pipes connected to the appliance.
3A.6.4 AIR RELEASE POINTS
These must be positioned at the highest points in
the system where air is likely to be trapped. They
should be used to expel trapped air and allow
complete filling of the system.
3A.6.5 EXPANSION VESSEL
The appliance has an integral expansion vessel
to accommodate the increased volume of water
when the system is heated. It can accept up to 8
litres of expansion from within the system,
generally this is sufficient, however if the system
has an unusually high water content, it may be
necessary to provide additional expansion
capacity (see section 6.19).
3A.6.6 FILLING POINT
A method for initial filling of the system and
replacing water lost during servicing etc. has
been provided. You should ensure this method of
filling complies with the local water authority
regulations.
3A.6.7 LOW PRESSURE SEALED SYSTEM
An alternative method of filling the system would
be from an independent make-up vessel or tank
mounted in a position at least 1 metre above the
highest point in the system and at least 5 metres
above the boiler (fig. 5).
The cold feed from the make-up vessel or tank
must be fitted with an approved non-return valve
and stopcock for isolation purposes. The feed
pipe should be connected to the return pipe as
close to the boiler as possible.
3A.6.8 FREQUENT FILLING
Frequent filling or venting of the system may be
indicative of a leak. Care should be taken during
the installation of the appliance to ensure all
aspects of the system are capable of withstanding
pressures up to at least 3 bar.
3A.7ELECTRICAL SUPPLY
The appliance is supplied for operation on 230V
@ 50Hz electrical supply; it must be protected
with a 3-amp fuse. The method of connection to
the mains electricity supply must allow for
complete isolation from the supply. The preferred
method is by using a double-pole switch with a
contact separation of at least 3 mm. The switch
must only supply the appliance and its
corresponding controls, i.e. time clock, room
thermostat, etc.
3A.8SHOWERS
If the appliance is intended for use with a shower,
the shower must be thermostatically controlled
and be suitable for use with a combination boiler.
3A.9MOUNTING ON A COMBUSTIBLESURFACE
If the appliance is to be fitted on a wall of
combustible material, a sheet of fireproof material
must protect the wall.
3A.10 TIMBER FRAMED BUILDINGS
If the appliance is to be fitted in a timber framed
building, it should be fitted in accordance with I.S.
813 and local Building Regulations.
The Institute of Gas Engineers publication (IGE/
UP/7) ‘Guide for Gas Installations in Timber Frame
Buildings’ gives specific advice on this type of
installation.
3A.11 INHIBITORS
Vokera recommend that a neutral inhibitor is
used to protect the heating system from the
effects of corrosion and/or electrolytic action.The
inhibitor must be administered in strict accordance
with the manufacturers* instructions.
*Fernox and Sentinel manufacture products that
have proved suitable for use with Vokera
appliances. Vokera Ltd. cannot comment on the
suitability of any other such product with our
appliances.
3A.12 DECLARATION OF CONFORMITY
A Declaration of Conformity (as defined in I.S.
813) must be provided on completion of the
installation.
A copy of the declaration must be given to the
responsible person and also to the gas supplier if
required.
8
Compact
SECTION 4INSTALLATION
4.1DELIVERY
The appliance is delivered in a heavy-duty cardboard carton. Lay the carton on the floor with the
writing the correct way up.
4.2CONTENTS
Contained within the carton is:
● the boiler
● the wall mounting bracket
● an accessories pack containing service valves
and sealing washers
● the instructions pack containing installation &
servicing instructions, appliance logbook, user
instructions, guarantee registration card, 3 amp
fuse and flue restrictor ring.
4.3UNPACKING
At the top of the carton pull both sides open – do
not use a knife – unfold the rest of the carton from
around the appliance, carefully remove all
protective packaging from the appliance, and lay
the accessories etc. to one side. Protective gloves
should be used to lift the appliance, the appliance
back-frame should be used for lifting points.
4.4PREPARATION FOR MOUNTING THE
APPLIANCE
The appliance should be mounted on a smooth,
non-combustible, vertical surface, which must be
capable of supporting the full weight of the
appliance. Care should be exercised when
determining the position of the appliance with
respect to hidden obstructions such as pipes,
cables, etc.
When the position of the appliance has been
decided – using the template supplied – carefully
mark the position of the wall bracket (fig. 7) and
flue-hole (if applicable).
4.4.1IMPORTANT
There are three hole types set out on the
appliance template:
● type 1 should be used in conjunction with
the telescopic flue kits (part no. 0225705 &
0225710)
● type 2 should be used in conjunction with
standard horizontal flue kit (part no.
2359029)
● type 3 should be used in conjunction with
the telescopic rear flue kits (part no.
0225905 & 0225910).
4.4.2FLUE RESTRICTOR RING
To ensure maximum efficiency of the appliance,
it may be necessary to fit one of the supplied flue
restrictor rings to the appliance flue outlet.
4.5FITTING THE FLUE
The top flue outlet permits both horizontal and
vertical flue applications to be considered,
alternatively, the Vokera twin flue system can be
utilised if longer flue runs are required.
4.5.1CONCENTRIC HORIZONTAL FLUE
(For concentric vertical flue, see section 4.5.2).
(For twin flue applications, see section 4.5.3).
Compact 24
Total flue lengthRestrictor required
Less than 0.85 metre
Less than 2 metre
Less than 3 metre
Less than 4.25 metre
42 mm diameter
44 mm diameter
46 mm diameter
Not installed
Compact 28
Total flue lengthRestrictor required
Less than 0.85 metre
Less than 1.70 metre
Less than 2.70 metre
Less than 3.40 metre
45 mm diameter
47 mm diameter
49 mm diameter
Not installed
The appliance flue outlet elbow can be rotated
through 360º on its vertical axis. In addition the
flue may be extended from the outlet elbow in the
horizontal plane (see section 4.4.2), however if
the flue is to be extended or additional bends are
to be fitted, the standard horizontal flue kit (part
no. 2359029) must be used. A reduction must
also be made to the maximum length (see table)
when additional bends are used.
BendReduction in maximum flue length for each bend
45º bend0.5 metre
90º bend0.85 metre
Horizontal flue terminals and accessories
Part No.DescriptionMin-Max Length
0225705Standard telescopic flue380 mm – 600 mm
(Dimension ‘X’)
0225710Extended telescopic flue600 mm – 920 mm
(Dimension ‘X’)
2359029Horizontal flue kit
For use with add. Bends833 mm
& extensions(dimension ‘X’)
2359069750 mm extension750 mm
23590791500 mm extension1500 mm
235904945º bend (pair)N/A
235905990º bendN/A
0225760Wall bracket (5)N/A
Using the template provided (see section 4.4.1),
mark and drill a 125 mm hole for the passage of
the flue pipe. The hole should have a 1º drop
from the boiler to outside, to eliminate the
possibility of rainwater entering the appliance via
the flue.
The fixing holes for the wall-mounting bracket
should now be drilled and plugged, an appropriate
type and quantity of fixing should be used to
ensure that the bracket is mounted securely.
Once the bracket has been secured to the wall,
mount the appliance onto the bracket.
Compact
9
2
1
3
type 1= centre of rear flue hole
using only 0225705 or
0225710 flue
type 2= centre of rear flue hole
for use with 2359029
type 3= for rear flue only
Fig. 7
FITTING THE TELESCOPIC FLUE KIT
(0225705 & 0225710)
Total flue lengthRestrictor required
Compact24Compact28
Less than 1 metre
40 mm diameter 42 mm diameter
Carefully measure the distance from the centre of
the appliance flue outlet to the face of the outside
wall (dimension ‘X’, fig. 8). Add 50 mm to
dimension ‘X’ to give the overall flue length
(dimension ‘Y’). Using the complete telescopic
flue assembly adjust the length to suit dimension
‘Y’. Once the telescopic flue terminal has been
adjusted to the correct length, secure the flue
assembly with the screw supplied.
Insert the flue restrictor ring (supplied in the
instruction pack) into the appliance flue gas outlet.
Slide the flue assembly into the previously drilled
flue hole and locate the flue bend over the
appliance flue outlet. Push the flue bend down
over the appliance flue outlet and ensure the
correct seal is made. Pull the flue assembly
towards and over the flue bend – using a twisting
action – ensuring the correct seal is made. Check
that the terminal protrudes past the finished
outside wall by the correct length (115 mm).
115 mm
FITTING THE STANDARD (2359029)
HORIZONTAL FLUE KIT (see section 4.4.1)
Carefully measure the distance from the centre
of the appliance flue outlet to the face of the
outside wall (dimension ‘X’, fig. 8A). Ensure the
inner (60 mm) pipe is fully inserted into the outer
(100 mm) pipe (when the inner pipe is fully
inserted, it stands proud of the outer pipe by 7.5
mm). Add 32 mm to dimension ‘X’ to give the
overall flue length (dimension ‘Y’). The standard
horizontal flue kit (part no. 2359029) is suitable
for a distance (dimension ‘Y’) of up to 865 mm.
NOTE
Dimension ‘Y’ is measured from the end of the
terminal to the end of the outer (100 mm) pipe.
The internal trim should be fitted to the flue pipe
before connection of the 90º bend.
Insert the flue restrictor ring (supplied with
instruction pack) into the appliance flue gas outlet
if the total flue length is less than 1.0 metre.
If the horizontal flue kit (2359029) requires to be
cut to the correct size (dimension ‘Y’), you must
ensure that the inner (60 mm) pipe stands proud
of the outer (100 mm) pipe by 7.5 mm (fig. 8B).
Ensure any burrs are filed or removed and that
any seals are located properly before assembly.
Connect the inner (60 mm) pipe of the terminal
assembly to the push-fit end of the 90º bend
(supplied) using a twisting action. Insert the
assembled flue into the previously drilled hole.
Using the clips & screws supplied, connect the
flue assembly to the boiler, ensuring that the
terminal protrudes past the finished outside wall
by the correct length (135 mm).
You must ensure that the entire flue system is
properly supported and connected.
Seal the flue assembly to the wall using cement
or a suitable alternative that will provide
satisfactory weatherproofing. The exterior trim
can now be fitted.
Dimension “Y”
110
7,5
Max 833 mm
Dimension “X”
135 mm
Fig. 8A
10
“X” + 50 mm = “Y”
Fig. 8
NOTE
You must ensure that the entire flue system is
properly supported and connected. Seal the flue
assembly to the wall using cement or a suitable
alternative that will provide satisfactory
weatherproofing. The interior and exterior trim
can now be fitted.
EXTENDING THE HORIZONTAL FLUE
If the horizontal flue requires extension/s or
additional bend/s, the standard horizontal flue
terminal (2359029) must be used. Connect the
bend – supplied with the terminal kit – to the top
of the boiler using the clips, screws & gaskets
supplied. The additional bends & extensions have
an internal push-fit connection, care should be
taken to ensure that the correct seal is made
when assembling the flue system. Connect the
required number of flue extensions or bends (up
to the maximum equivalent flue length) to the flue
terminal using the clips, screws & gaskets supplied
(fig. 8A & 8B).
Compact
NOTE
When cutting the horizontal flue terminal or an
extension to the required length, you must ensure
that the excess is cut from the plain end of the
terminal or extension, and that the inner (60 mm)
pipe is 7.5 mm longer than outer (100 mm) pipe
(fig. 8A & 8B). Remove any burrs, and check that
any seals are located properly.
You must ensure that the entire flue system is
properly supported and connected.
Seal the flue assembly to the wall using cement
or a suitable alternative that will provide
satisfactory weatherproofing. The interior and
exterior trim can now be fitted.
Push-fit connection
Extension
7,5 mm
Boiler
4.5.2CONCENTRIC VERTICAL FLUE
The vertical flue terminal can be connected directly
to the appliance flue outlet. Alternatively, an
extension or bend can be connected to the
appliance flue outlet if desired (see section 4.4.2),
however if additional bends are fitted, a reduction
must be made to the maximum flue length (see
table below).
Compact 24
Total flue lengthRestrictor required
Less than 1.5 metre
Less than 2.5 metre
Less than 3.5 metre
Less than 5 metre
42 mm diameter
44 mm diameter
46 mm diameter
Not installed
Fig. 8B
Fit the appropriate flashing plate to the roof and
insert the vertical flue terminal through the flashing
plate from the outside, ensuring that the collar on
the flue terminal fits over the flashing.
The fixing holes for the wall-mounting bracket
should now be drilled and plugged, an appropriate
type and quantity of fixing should be used to
ensure that the bracket is mounted securely.
Once the bracket has been secured to the wall,
mount the appliance onto the bracket.
IMPORTANT
The vertical flue terminal is 1.0 metre in length
and cannot be cut; therefore it may be necessary
to adjust the height of the appliance to suit or use
a suitable extension.
Insert the flue restrictor ring into the appliance flue
outlet, in accordance with the table in section 4.4.2.
Connect the vertical flue assembly to the boiler
flue spigot using the 60 mm & 100 mm clips,
gaskets, & screws (supplied), ensuring the correct
seal is made. The flue support bracket (supplied
with the vertical flue kit) can now be fitted.
If the vertical flue requires extension/s or additional
bend/s, connect the required number of flue
extensions or bends (up to the maximum
equivalent flue length) between the boiler and
vertical flue assembly (fig. 8B).
NOTE
When cutting an extension to the required length,
you must ensure that the excess is cut from the
plain end of the extension and that the inner (60
mm) pipe is 7.5 mm longer than outer (100 mm)
pipe (fig. 8B). Remove any burrs, and check that
any seals are located properly.
You must ensure that the entire flue system is
properly supported and connected.
300 mm
min.
465 mm
Compact 28
Total flue lengthRestrictor required
Less than 1.5 metre
Less than 2.4 metre
Less than 3.4 metre
Less than 4.2 metre
BendReduction in maximum flue length for each bend
45º bend 0.5 metre
90º bend 0.85 metre
Vertical flue terminal and accessories
Part No.DescriptionLength
2359039Vertical flue terminal1.0 metre
0225770Pitched roof flashing plateN/A
0225765Flat roof flashing plateN/A
2359069750 mm extension750 mm
23590791500 mm extension1500 mm
235904945º bend (pair)N/A
235905990º bendN/A
0225760Wall bracket (5)N/A
45 mm diameter
47 mm diameter
49 mm diameter
Not installed
Using the dimensions given in fig. 9 as a reference,
mark and cut a 105 mm hole in the ceiling and/or roof.
Fig. 9
150 mm
4.5.3TWIN FLUE SYSTEM
Compact 24
Total flue length (air = fumes)Restrictor required
Less than 4.5 + 4.5
Less than 10.5 + 10.5
Less than 14 + 14
42 mm diameter
44 mm diameter
46 mm diameter
Compact
11
Compact 28
Total flue lengthRestrictor required
Less than 4 + 4
Less than 8 + 8
Less than 12.5 + 12.5
Less than 14 + 14
45 mm diameter
47 mm diameter
49 mm diameter
Not required
Compact 24
restrictor ring
The Vokera twin flue system enables greater flue
distances to be achieved (see section 2.8) than
that of the standard concentric flue system. It can
be used for horizontal or vertical applications,
however the twin flue system must be converted
to the dedicated concentric flue kit for termination.
It is essential that the installation of the twin flue
system be carried out in strict accordance with
these instructions.
GUIDANCE NOTES ON TWIN FLUE
INSTALLATION
● The flue must have a fall back of 1º back to the
appliance to allow any condensate that forms
in the flue system to drain. Consideration must
also be given to the fact that there is the
possibility of a small amount of condensate
dripping from the terminal.
● Ensure that the entire flue system is adequately
supported, use at least one bracket for each
extension.
● Extreme care must be taken to ensure that no
debris is allowed to enter the flue system at
any time.
● As the exhaust outlet pipe can reach very high
temperatures it must be protected to prevent
persons touching the hot surface.
Twin flue accessories
Part No.DescriptionLength
0225805Horizontal flue terminal1.0 metre
0225810Vertical flue terminal1.0 metre
300Twin adapter kit for Compact 24N/A
2359249Twin adapter kit for Compact 28N/A
0225770Pitched roof flashing plateN/A
0225765Flat roof flashing plateN/A
0225815Condensate drain kitN/A
02258200.25 m extension (pair)250 mm
02258250.5 m extension (pair)500 mm
02258301.0 m extension (pair)1000 mm
02258352.0 m extension (pair)2000 mm
022584045º bend (pair)N/A
022584590º bend (pair)N/A
0225850Twin bracket (5)N/A
0225855Single bracket (5)N/A
MOUNTING THE BOILER
The fixing holes for the wall-mounting bracket
should now be drilled and plugged, an
appropriate type and quantity of fixing should be
used to ensure that the bracket is mounted
securely . Once the bracket has been secured to
the wall, mount the appliance onto the bracket.
4.5.3.1 INSTALLATION OF TWIN ADAPTOR KIT (fig. 10 &
10A)
● Insert the exhaust connection manifold (B) onto
the appliance flue outlet and secure to the flue
spigot using the screws provided.
● Insert the silicone seal into the exhaust outlet.
● Remove the blanking plates (located to the left
of the appliance flue outlet) and – using the
same screws – install the air baffle (A).
flue outlet
air inlet
Fig. 10
Compact 28
restrictor ring
flue outlet
air inlet
Fig. 10A
4.5.3.2 INST ALLA TION OF CONDENSA TE DRAIN KIT
(fig. 10B)
The condensate drain kit must be fitted within 1 metre
of the appliance flue outlet. It is recommended that
the condensate drain kit should be fitted in the vertical
plane, however it can be fitted horizontally with care.
● Fit the first bend to the condensate drain kit or
exhaust connection manifold by firmly pushing
in to position.
● Using the two holes in the exhaust connection
manifold as a guide, drill a 3 mm hole in each
and secure using the screws provided.
● Connect the air inlet pipe to the air baffle as above.
● The twin flue pipes extensions and accessories
can now be installed by pushing together (the
plain end of each extension or bend should be
pushed approximately 50 mm into the female
socket of the previous piece).
The condensate drain trap must be connected
to the drain in accordance with building
Regulations or other rules in force.
Condensate drain kit
Fig. 10B
12
Compact
Loading...
+ 30 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.