CONTEN | TS | ||||
---|---|---|---|---|---|
Section | Subject |
Page
No. |
Section | Subject | Page |
Section 1 | Introduction | - | 6.11 | Final check of operations | 14 |
General Layout
Schematic Diagram |
2 1 |
6.12
6.13 |
Concluding Operations
Refixing the front cover |
14
14 |
|
Section 2 | Design Principles and | Section 7 | Instructing the User | 14 | |
Operating Sequence | 000000000000000000000000000000000000000 | 3 | |||
2.2 | Central Heating 2.2.1-2.2.2 | 2 | Section 8 | Servicing Instructions | |
2.3 | Safety Devices | 2 | 8.1 | General | ರ |
8.2 | Important Notes | 5 | |||
Section 3 | lechnical Data | 8.3 | Recommended Houtine | ħ | |
3.1 | Units | မ | 84 | Servicing | ನೆ ರ |
а (З
2 С |
Dimensions and Contents | ິ | 8.5 | To remove/replace room sealed | ē |
5 C | Connection sizes | ະບ | 0.0 | chamber front cover | ธ |
ა.4
ი 4 |
Installation requirements | ى د | 8.6 | To remove/replace Electrode | ā |
ີ່ | Liectifical Details | ω c | & Main Burner | 17 | |
3.7 | Burner Details | ω | 8.7 | To remove Main Burner Injectors | 17 |
8.8
0 |
To Remove Main Heat Exchanger | ₫ | |||
Section 4 | General Requirements |
01.8
9.9 |
To Bemove Flue Fan | α | |
4.1 | Related Documents | 4 | Switch | 8 | |
4.2 | Coo Supply | - 1 | 8,11 | To Remove Combustion | |
4.4 | Flue System | 4 | Chamber and Insulation Panels | 19 | |
4.5 | Air Supply | თ | 8.12 | Control Valve Operator and | |
4.6 | Water Circulation | n U | Solenoid | 19 | |
4.7 | Electrical Supply | 7 0 | 8.13 | To Remove Gas Control Valve | 5 |
814 |
Complete
To Remove Pump |
25 | |||
o uonoec | Installation | 8.15 | To Remove Heating Manifold | 20 | |
5.1 | Delivery | 000 | 8.16 | Removal of Main Expansion | |
лU |
Unpacking
Branaring for Mounting |
α | • | Vessel | 20 |
л 0.0 | Fieparitig for Mounting | οα | 8.17 | Removal of Safety Valve | 21 |
5.5
5.4 |
Fitting the Flue | မပ | 8.18 | Components | 2 |
5.6 | Connecting the gas and water | 8.19 | Removal of Mechanical | ŗ | |
57 |
supplies
Electrical Connections |
= = | Instruments and Components | 22 | |
Section 6 | Commissioning and Testing | Section 9 | Operation Checks, Wiring | 3 | |
2 | 3 | ||||
6.2 | Gas Supply Installation | 75 75 | Fault finding Charts | 24 - 27 | |
6.3 | Central Heating System | 12 | Section 10 | Appendix | |
6.4 | Electrical Supply | 12 | Instructions for fitting Optional | ||
ດ.ບ | 5 7 | Time Clocks | 28 - 31 | ||
6.7
6.7 |
Checking the flue system | 5 5 | Exploded Diagrams | 32 - 36 | |
6.8 | Checking the Heating | 2 | Short Spare Parts List | 36 | |
Thermostat | 13 | Functional Flow Diagram | 37 | ||
6.9 | Regulating the Heating system | 13 |
General layout of winnig
Illustrated Wiring Diagram |
а
С |
|
6.10 | Final flushing of the heating | Q | 1 | ||
ayatelli | Ŧ | ||||
The Vokera 12-48 RSE Mynute is a central heating boiler which by design incorporates a circulating pump, expansion vessel, safety valve, temperature gauge, pressure gauge, automatic by-pass and electronic ignition.
applications only. It is provided with a fan powered flue outlet with an annular co-axial combustion air intake which can be rotated through 360 degrees. appliance suitable for wall mounting
12-48 Mynute
12-48 Mynute
is possible by the addition of an indirect cylinder with 'Y' or 'S' plan controls.
Fig.1
Pressure Differential Switch
18
Safety Valve Return Valve Flow Valve
20 Central Heating Manifold 21 Boiler Thermostat
26 Sens 27 Fan
Sensing Electrode
25 Gas Valve 24 Pump
23 Mode Selector Switch 22 ON/OFF Switch
principles described below. Fig 1 illustrates the general layout of components. Fig 2 illustrates the operating
SECTION 3
TECHNICAL DATA
: 360mm (14.2in) 345mm (13.6in
supplied with boiler Flue outlet: nom. dia. 100mm specially Gas Service Rc 1/2 (1/2in BSP int) Safety valve outlet: Rc 1/2 (1/2 BSP int)
but for each bend used the maximum length of straight flue is reduced by .75 metres. e.g. 1 extra bend plus 3.75 metres of straight extended to a maximum of 4.5 metres in a straight line. A maximum of two extra 90 degree bends may be used (Section 5.5.20
mains supply 240/250v ~ 50Hz Fused 3/ ower consumption: 190w
Min 9.2kW (31,400Btu/h) Nominal Heat Input Max. 17.6kW (60,000Btu/h)
Max. 14kW (48,000 Btu/h) Min. 6.7kW (22,860 Btu/h)
Max Pressure 10.6 mbar (4.3in wg
Maximum 1.5 bar/15m.wg/50ft w.g. Minimum 0.5 bar/5m.wg/16ft w.g Safety valve setting 3 bar/30m/102ft
appliance 350 litres/hour (1.28 gals/min) Minimum central heating flow rate through
Max. Gas Rate 1.68m3/h 59.4tt3/h Min. Gas Rate 0.92m3/h 32.5tt3/h
3.7
the appliance heating system after allowing
÷ 130
1 20
4.00 3.7 ្ពុខ្ល 2.9 2.6 2 8 : 8 5 ĝ
± 8 °, 28
2 0
gpm
gas safety (installation & use) Regulations This appliance must be installed by a
4.
the Gas Safety (Installation and Use) Regulations, the Local Building Regulations the current I.E.E. Wiring Regulations, the by cotland, in accordance with the Building aws of the local water undertaking, and in he installation of this boller must be in
and local authority and the relevant recommendations of the following British elevant requirements of the local gas region
cupboard installations are given in BS 6798:1987 and BS 5440 pt 2 1976. This compartment design including airing
4.3
checked, preferably by the gas region to ensure that the meter is adequate to deal by the local gas region or a local gas region contractor. An existing meter should be pe titted in accordance with BS 6891.
used. than the poller inlet connection should not be be of adequate size. Pipes of a smaller size
BS 6891 | 1988 | Low pressure installation pipes | |
BS 6798 | 1987 | Boilers of rated input not exceeding 60kW | |
BS 5449 | Part 1 | 1990 | Forced circulation hot water system |
BS 5440 | Part 1 | 1990 | Flues |
Part 2
1989
4.2
Regulations applicable in Scotland, with respect to the installation of the boiler in a internal space, although particular attention is drawn to the requirements of the current I.E.E. Wiring Regulations, and in Scotland, the electrical provisions of the Building The boiler may be installed in any room or om or internal space containing a bath c
electrical switch or appliance control a room containing a bath or shower, any where a room-sealed appliance is installed in
permit the provision of a satisfactory flue and termination. The location must also permit an necessary and BS 6798:1987 gives detailed nstallation of the boiler will be in an unusual
provided that it is modified for this purpose
soundness as described in the above code
other appliances ensure that an adequate supply is available both to the boiler and the N.B. If the gas supply for the boiler serves
4.
or discoloration that might occur to building
he effect of such steaming must be
a guard of durable material. (6.6tt) above a pavement or plattorm to which (2in) to any combustible material. For protection of combustibles, refer to BS
A suitable guard is manufactured by G.R. Claudio (Vokera) Ltd. Part No 018, (GC No 301 106). This guard must be fitted centrally
600 300
1500 1200
300
wali
The roomsealed fan flued boiler does not Intended for general guidance in BS5440;2;1989. The following notes are commendations for air supply are detailed
Where installed in a cuppoard of
minimum effective areas of such air vents
high
level |
OF
OF IR VENTS |
|
---|---|---|
159cm
2
(24.5in 2 ) |
AIR FROM
ROOM OR INTERNAL OUTSIDE |
AIR VENT |
80cm
2
(12.3in 2 ) |
AIR DIRECT
FROM OUTSIDE |
AREAS |
outside wall. the same room or space or be on the same i. Both vents must either communicate with
adjacent internal space, it is suggested that the space is adequately ventilated. . Where vents communicate with an
4.6 Detailed recommendations are given in BS 6798:1987 and BS 5449:1:1990 (for systems). The following notes are given for
compression fittings Copper tubing to BS 2871:1:1971 is recommended for water pipe. Jointing should
points and water flows naturally to drain taps Where possible, pipes should have a gradier
the appliance heat exchanger is not a natura
be paid to pipes passing through ventilated spaces in roofs and under floors. Except where providing useful heat,
boiler and systems should be designed to ensure that with only one radiator turned on a flow rate of at least 350 litres/hour (1.28 gals/ inv) in other of the boilty in the board the boilty of the b An automatic by-pass is incorporated in the
Section 10 appendix D gives wiring details
accordance with BS 2879:1980 positions to permit the draining of the whole systems. The taps must be least 15mm Inese must be located in accessible
80cm∠ (12.3in2)
i nese must be fitted at all high points where air will naturally collect, and must be sited to
4.6.7 heated, it can accept up to 6 litres increase of water volume when the system is connected to a system with an unusually
problem
area, contact the local authority for preferred this method is not suitable in a particular authority regulations. A method is shown in fig 7 using the Vokera filling loop which is acceptable in most areas. In the event that replacing water lost during servicing must be provided, and it must comply with local water A method for initially filling the system and
cause premature scaling of the main heat N.B. The installer should ensure that no leaks exist as frequent filling of the system could
The appliance is supplied for operation on 240/250V ~ 50Hz electricity supply. It should e protected with a 3-amp fuse. HIS APPLIANCE MUST BE EARTHED.
or at least 3mm I he preterred method is by using a tused double pole switch with a contact separation
ne switch must supply ONLY the appliance ogrammer/room thermostat)
complying with BS 1363 socket outlet with a fused 3- pin plug both
water supply
~ |
---|
C) |
- |
0 |
Z |
տ |
- |
z |
~~ |
~ |
⋗ |
- |
⊳ |
- |
_ |
~ |
0 |
~ |
arefully cut out and used prior to installation mark the locations for fixing holes for the
Fittings pack containing central heating alves (2) Installation Manual - Wall Bracket
Users Instructions
dimensions in tig 9.
dimensions for locating the hole. Where it is Herer to rig. 9 and rigs. 10-13 for relevant
п
Ъ
5.5.8 | Loosen the small maintenance clip and lift off the flue bend |
---|---|
5.5.9 |
Ensure inner and outer terminal tubes are
firmly fitted together with screw G (fig 12) Push the terminal tubes through the wall until the face of the outer tube protrudes 18mm from the face of the wall (fig 12) The terminal |
wall face. | |
5.5.10 | If extension pieces are used assemble these using the maintenance clips provided. |
5.5.11 | Make sure the entire length of the flue is truly horizontal and adequately supported. Use at |
least one bracket for each extension.
(Conventional adjustable strap supports suffice, Vokera stockist can supply if necessary. Part No 03 (GC No 301 105) |
|
5.5.12 |
Assemble the second small maintenance clip
on the end of the inner flue tube. |
5.5.13 |
Refit the flue elbow onto the boiler. Align the
flue elbow with the flue pipe and tighten the maintenance clip between the flue elbow and the boiler. |
5.5.14 | Draw the flue pipe towards the boiler and tighten the second clip over the joint between the inner flue pipe and the flue elbow. |
5.5.15 | There must now be a gap of approximately 15mm from the elbow to the end of the outer tube. |
5.5.16 | Check also that the outer end of the flue projects as indicated in fig 12. |
5.5.17 |
Referring to fig 10 fit the large maintenance
clips into position and secure the clip screws. |
5.5.18 | Check adjust and tighten all supports. |
5.5.19 |
Seal the peripheral gap around the outer tube
with cement or mastic and slip the cosmetic flexible plastic collar (fig 12) item C) into groove on the pipe. This operation can only be carried out with external access. |
N.B. Absence of the collar will not affect operation of the appliance. | |
5.5.20 |
INSTALLING ONE OR TWO ADDITIONAL
90° FLUE BENDS Part No 02 (GC No 301 104) |
5.5.21 |
Assemble the large and small maintenance
clips as show in fig 13A |
5.5.22 | Carry out steps 5.5.2-5.5.3 |
5.5.23 |
Ensure when siting the flue hole position that
the total length of the straight flue pipe used does not exceed the maximum permissable. 1 extra 90° bend and a maximum of 3.75 metres of straight flue. 2 extra 90° bends and |
metres of straight flue. 2 extra 90° bends and |
Connect a 15mm gas pipe to the gas service tap and tighten the union nut securing the
It has a threaded outlet (Rc 1/2" BSP Ini) to permit a discharge pipe to be connected. When connecting, ensure the discharge pip
when connecting, ensure the discharge pipe does not restrict access to or operation of the central heating valves. The discharge should terminate facing downwards exterior to the building in a position where discharging (possible boiling) water will not create danger or nuisance; but in an easily visible position.
The electricity supply must be as specified in clause 4.7. If controls external to the appliance are required design of the external electrical circuits should be undertaken by a competent person.
See section 10 for further electrical wiring details.
Factory fitted internal wiring must not be disturbed when wiring external controls N.B. IT IS ESSENTIAL THAT ALL EXTERNAL
Note these 2 screws and associated cup washers are not captive. Ensure they are not lost.
The panel is bottom hinged. Pull it forwards and downwards until it rests in an approximately horizontal position.
The terminal block is easily visible on the left hand side.
5.7.3 The electricity supply cable from the isolator and the Appliance terminal block must be 3 core flexible sized 0.75mm2 (24x0.2mm) to table 15-16 BS 6500.
Wiring to the Appliance should be rated for operation in contact with surfaces up to 90°C.
If required pass this cable through the same cord anchorage.
The conductors should be so connected that the conductor to terminal 2 becomes taut before those to 3 or Earth (+) should the cable be strained.
S |
---|
m |
0 |
Ľ. |
- |
0 |
ž |
- |
ົ |
0 |
× |
Q |
2 |
- |
~ |
~ |
~ |
S |
ō |
2 |
z |
= |
~ |
ഹ |
6.4.1 6.4
clean water (for at least five minutes). the entire system until the drain discharges return and a drain pipe to the flow and flush connect a temporary water supply to the
reconnect the flow and return pipes to the Drain the system by opening the drain taps at all low points. Close the drain taps and
6.5.7
6.5.1 6.5
mba
for soundness. Check all clamps and fixings
6.8.1 switches from 'on' to 'off' and vice versa (scale range covers approx. 45°C - 85°C) Allow the system to warm up and manipulate
system should be regulated to ensure a flow rate of at least 350 litres/hour (1.28 gals/min)
6.10 |
FINAL FLUSHING OF THE HEATING
SYSTEM |
6.11.4 |
Check the appearance of the gas flame to
assess adequacy of combustion air supply. |
---|---|---|---|
6.10.1 | After the system has been thoroughly heated to about 60°C (140°F) or above, and hot water | 6.11.5 |
Re-check the flue system for soundness and
adequacy of supports. |
has circulated to all parts any residual grease,
flux and other foreign material will have been dislodged. |
6.12 | CONCLUDING OPERATIONS | |
6.10.2 | Inspect the system for soundness. Turn the appliance off and turn off the on/off switch (fig 1 22). | 6.12.1 |
It external controls have been disconnected
and terminals 2 and 3 temporarily linked remove the link and reconnect the external control circuit, check the operation of the |
Open all drain taps and quickly drain the system whilst still hot to remove offending | external controls. | ||
substances. Refill as instructed in clause | |||
6.13 | REFIXING THE FRONT CASING. | ||
6.11 | FINAL CHECK FOR OPERATIONS | 6.13.1 | Offer up the front casing to the back frame in |
6.11.1 |
Disconnect pressure gauge, retighten screw.
Relight boiler. |
a near vertical attitude and locate the nooks
on the casing over the hooks on the frame. Slide the casing downwards to fully engage |
|
6.11.2 | Re-check for gas soundness. | the hooks and flex the bottom of the case | |
6.11.3 | Re examine heating and hot water systems and cold water supply for water soundness. | outwards and push nome to aligh the bottom fixing holes. Replace the four case retaining screws. |
71 Hand over the copy of the Users Instructions supplied together with this Installation book and explain how to operate the boiler correctly. Explain how to use the Timeclock and Boom Thermostat if fitted
7.5
7.6
To ensure efficient safe operation of the appliance it is necessary to carry out routin servicing at regular intervals.
The frequency of servicing will depend upon the particular installation conditions and the use to which the boiler is put; but, in general, once per year should be adequate. It is the law that any service work must be carried out by a competent person such as British Gas or other recognised companies.
The following instructions apply to the boiler and its controls, but it should be remembered that the central heating system will also require attention from time to time.
WARNING: Having carried out preliminary flame checks and before starting any servicing work, switch OFF the mains electricity supply and disconnect the plug at the main isolating switch and socket. (If a switch is used remove the fuse.)
Turn off gas supply at the gas service tap fitted to the appliance.
Always test for gas soundness after any service work and after exchanging any gas carrying component.
.3 RECOMMENDED ROUTINE SERVICING .3.1 ANNUAL SERVICING
The following procedures should be carrie out at least once per year.
The life of individual components varies and they will need servicing as and when faults develop. The fault finding sequence charts in section 9 will serve to locate which component is the cause of any malfunction, and instructions for removal, inspection and replacement of the individual parts are given in the following pages.
To remove components access to the interior is essential. Refer to figs 17 & 18
Fig
8.5
Fig. 18
Reassemble in reverse order. See fig 38 for
correct fitting of electrical connections. The air pipe must be reconnected to the upper nozzle on the pressure switch. |
8.10.6 | |
---|---|---|
Pull off tab connectors and ease pressure switch upwards, disconnecting air pressure pipe in the process. | 8.10.5 | |
Pull air tube from nozzle on inner flue bend. | 8.10.4 | |
Remove 3 screws holding pressure differential switch cover (fig 24) and remove cover. | 8.10.3 | |
Remove room-sealed front cover plate as 8.5.2 | 8.10.2 | |
Gain general access as 8.4 | 8.10.1 | |
FLUE PRESSURE DIFFERENTIAL SWITCH
Part No 5926 Refer to fig 24 |
8.10 | |
Reassemble in reverse order, replacing centre screw first. | 8.9.9 | |
Unscrew 3 screws retaining fan to flue hood
and remove fan. Transfer aluminium manifold (2 screws) to new fan. |
8.9.8 | |
Carefully slide flue hood forward
disconnecting electrical leads on fan in the process. |
8.9.7 | |
Remove 3 flue hood retaining screws (fig 24) | 8.9.6 | |
Remove silicone pipe from nozzle on inner flue bend. | 8.9.5 | |
Unscrew maintenance clip securing screws
and remove clip (fig 24) |
8.9.4 | |
Remove front of combustion chamber as 8.6.3 | 8.9.3 | |
Remove room-sealed front cover plate as 8.5.2 | 8.9.2 | |
Sei | Gain general access as 8.4 | 8.9.1 |
Тe |
FLUE FAN
Part No 5963 |
8.9 |
Reassemble in reverse order using new fibre washers on both unions. | 8.8.8 | |
Carefully slide out heat exchanger avoid spillage of water on boiler electric's. | 8.8.7 | |
Unscrew unions on both sides. | 8.8.6 | |
Place cloth under heat exchanger to catch
surplus water. |
8.8.5 | |
Close heating valves (1/4 turn until handle is horizontal). Turn safety valve 1/4 turn to drain primary circuit of boiler. | 8.8.4 | |
Remove front of combustion chamber as 8.6.3 | 8.8.3 | |
_ | Remove room-sealed front cover plate as 8.5.2 | 8,8,2 |
Gain general access as 8.4 | 8.8.1 | |
MAIN HEAT EXCHANGER
Part No 5388 Refer to fig 23 |
8.8 | |
Gain general access as 8.4
8.13.1
GAS CONTROL VALVE COMPLETE
8.13.5
Remove 2 screws securing gas valve bracket Remove 4 flange securing screws at lower
end. Undo union at top of supply to burner.
vaive to retain regulation settings.
Remove servo pressure regulato: Clause 8.12.5.
urn off gas supply. Disconnect 2 earth leads. Pull off all electrical connections
Check burner pressure (cl 6.6)
Fig. 25
lest all joints for gas soundness
Hegulator
Hegulato
8.14.7 Unscrew four Allen screws, withdraw head
electrical leads. Brown to L, Blue to N
Release cover retaining screws and ease of
Refer to tig 29 for location of components
vessel will require changing. Alternatively, a
8.16.11 expansion vessel in situ. follow steps 8.16.10 above of 343mm (13.5in) or more and with a N.B. If the boiler is installed with a clearance
Fig. 30
Reassemble in reverse order
spot)
Refer to figs 32 & 28
(3) lift vessel and pipe
heating expansion vessel behind combustio chamber
nect pipe at this enc
8.18.2
SECTION 9 | |
---|---|
OPERATIONAL ( | |
CHECKS, | |
WIRING DIAGRAMS & FAULT F | |
INDING |
а
Part No 4931
FAN OVER-RUN THERMOSTAT
8.20
9.1 remaking of electrical connections the checks Earth Continuity, polarity and
I he tollowing tlow diagrams suggest the logical sequence of steps for fault finding.
installer or service engineer.
role of each part is briefly described included for reference. As further help, the
provides an alternative suppy to the fan,
If the supply to P1 is broken (e.g. by a room
P1-1 breaks the boiler circuitry will go to rest
energised and the sparking will stop. To reset the boiler after lockout turn off the boiler on/ At which time the gas valve will be de
ignition attempt periou)
If a flame is not detected the boiler will go to
When tollowing this sequence, reter to tigs 36 & 38. It is assumed that the on/off switch
boiler to below 350 litres/hour (1.28 gpm) the boiler flow switch will open and de-energise the fan which in turn shuts down the boiler.
and safety thermostats will energise termina At the same time a supply through the boiler control thermostat (P1-1) via the high limit
and then in turn to the normally closed his supply is connected internally to termina
upply to terminal 10
remove the supply from the fan, allowing it to
energising it's normally open contact (pin 2 This supply is fed via the boiler flow switch to ressure differential switch to change over
gas valve being energised and the electrode I here will be a short delay, tollowed by the
attempt time (8-12 seconds) the sparking
12-48 Mynute
Temperatur
FAULT FINDING STEP 1 CHECK ELECTRICAL SUPPLIES, SWITCHES & CONNECTIONS
Proceed to Next Step
FAULT FINDING STEP 2 CHECKING C/H THERMOSTAT CIRCUIT
NOTE 1 Reduce number of radiators on to give quick response.
12-48 R.S.E. MYNUTE
FAULT FINDING STEP 3
18 Mynute
ğ (A) Fitting Vokera 24 Hour Time Switch (Part No. 032 GC No. 301 110) and Fitting Vokera Digital 7 Day Time Switch (Part No. 05 G.C. No. 301 109) (B) Wiring to external Time Switches, Room Thermostats and
rost inermos
(C) Wiring to 'Y' plan or 'S' plan installations
Remove the clock aperture blanking plate (1) (fig 1) by squeezing the two lugs on the rear of the plate together and push the plate out.
crews provided. (fig. 2). panel. Push the mounting bezel (2) through the
nect the other ends of the wires to the main inal block as detailed below. (fig. 3).
THILD I. d/White: Push on to spare spade connector on
Blue: Connect to terminal marked 'N'
Red / Black: Connect to spare terminal o
White: Connect to terminal 2 on main terminal block. (leave link 2-3 connected if no room thermostat is
Hemove the loop between terminals 2 & 3 on the boiler terminal block, if a room stat is also fitted.
12-48 Mynute
(i) 'Y' Plan
N ω
C. Wiring to 'Y' plan or 'S' plan installations
щ
12-48 Mynute
32
Fig. 35b Outer Casing
Fig. 35c Cover and Left-Right Sides
12-48 Mynute
3409 4250 4254
0598 0602
0557
493
Code
G.C. No
Description
- 5811 - 5143
Fig. 35m Front Panel
12-48 Mynute